SECTION WET AUTOMATIC FIRE SPRINKLER SYSTEMS

Similar documents
WET AUTOMATIC FIRE SPRINKLER SYSTEMS

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University.

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements.

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

SECTION AUTOMATIC SPRINKLER PIPING

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

A. Section includes wet-pipe sprinkler system, system design, installation, and certification.

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE

B. Section Identification for Fire Suppression Piping and Equipment.

SECTION FIRE PROTECTION. A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section

Gas Station & C Store SECTION CWM Job No

THE JAMES RUSHTON EARLY LEARNING AND FAMILY SUCCESS CENTER #2616 ISSUE FOR CONSTRUCTION

B. Galvanized-Steel-Sheet Sleeves: inch minimum thickness; round tube closed with welded longitudinal joint.

DIVISION 21 FIRE SUPPRESSION SECTION FIRE PROTECTION SPECIALTIES

SECTION SPRINKLER SYSTEMS

SECTION FIRE-SUPPRESSION STANDPIPES

FIRE SUPPRESSION SPRINKLER SYSTEM

SECTION WET-PIPE SPRINKLER SYSTEMS

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

B. Related Sections: The following Sections contain requirements that relate to this Section.

SPRINKLERS TABLE OF CONTENTS

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

2. Welding Materials and Procedures shall conform to the ASME Code.

D. NEMA Compliance: Provide electric motors and components which comply with NEMA standards.

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

MLA Architects Pierz Public Schools ISD #484 Healy High School Multi-Purpose & Choir Additions Pioneer Elementary School Class Room Addition Pierz, MN

A. ASME Compliance: Fabricate and install hydronic piping in accordance with ASME B31.9 "Building Services Piping.

A. Standard-Pressure Piping System Component: Listed for 175-psig minimum working pressure.

SECTION DRY-PIPE SPRINKLER SYSTEMS

SECTION DRY-PIPE SPRINKLER SYSTEMS

Division 21: FIRE SUPRESSION WET-PIPE SPRINKLER PROTECTION SYSTEM. The Academy Sept Table of Contents 1 Division 21

Wayne State University WSU Project No Chatsworth Tower Apts. Misc. Bldg. Upgrades DSD Project No

TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION WATER BASED FIRE PROTECTION SYSTEMS... 5

SECTION WET-PIPE SPRINKLER SYSTEMS

West District Library Section Campeau Drive, Ottawa SPRINKLER SYSTEMS City of Ottawa Project No. CR Page 1 of 8

B. The sprinkler system shall be designed to meet the more stringent of the requirements of NFPA 13 and FM Global requirements.

B. HI Compliance: Design, manufacture, and install pumps in accordance with HI "Hydraulic Institute Standards."

SECTION WATER BASED FIRE SUPPRESSION SYSTEMS

DIVISION 21 - FIRE SUPPRESSION

SECTION WET FIRE SPRINKLER SYSTEMS

SECTION SPRINKLER SYSTEMS

DIVISION 21 - FIRE SUPPRESSION

ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1. The Curators of the University of Missouri

DARTMOUTH COLLEGE DESIGN November 15, 2007 & CONSTRUCTION GUIDELINES

SECTION ELECTRIC-DRIVEN, FIRE PUMPS

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION FIRE PUMP AND CONTROLS

DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES

North Hanover Township School District North Hanover Township, New Jersey

A. This section includes design and performance information for fire protection and suppression systems.

2016 CDM Smith All Rights Reserved July 2016 SECTION FIRE PROTECTION - SPRINKLER AND STANDPIPE SYSTEMS

SECTION FIRE PROTECTION

SECTION FIRE PROTECTION

SECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

1.2 CODES AND REGULATIONS A. Sprinkler system design, equipment, materials, devices, and installation shall conform to the following:

ADDENDUM NO. 3 March 19, 2018

DIVISION 21 FIRE PROTECTION ISSUE DATE REVISION

DIVISION 21: FIRE SUPPRESSION WATER BASED FIRE SUPRESSION SYSTEMS

SECTION WET-PIPE FIRE SUPPRESSION SPRINKLERS

SECTION WET-PIPE SPRINKLER SYSTEMS

UC Santa Cruz Campus Design Guide. Includes the following sections: None DESIGN REQUIREMENTS

Mercury Plastics New Building February TABLE OF CONTENTS

A. All Fire Suppression System design and installation shall comply with the most current and adopted version of NFPA 13.

UBC Technical Guidelines Section Edition Fire Protection General Requirements Page 1 of 6

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION

WET-PIPE SPRINKLER SYSTEMS

TABLE OF CONTENTS

Addendum No. 2 to the Contract Documents

CITY OF PASADENA FIRE DEPARTMENT

DIVISION 21: FIRE SUPPRESSION

Lucy s Pizza 100% CD Specification 06/22/2018

SECTION BASIC MATERIALS AND METHODS

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

Environmental Health & Safety

SECTION PREACTION SPRINKLER SYSTEMS

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING. A. This Section includes the following sanitary drainage piping specialties:

DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES

SECTION SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING

TECHNICAL SPECIFICATIONS SECTION DRY PIPE SPRINKLER SYSTEM PLAISTOW PUBLIC LIBRARY 85 MAIN STREET PLAISTOW, NEW HAMPSHIRE 100%CD.

AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations)

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 21 FIRE SUPPRESSION

PHYSICAL FACILITIES. 1 General. 2 Related Requirements. 5 Quality Assurance. 3 Wiring. 4 Submittals

Mercy Hospital of Buffalo Catholic Health System 2 nd Floor Patient Holding Center 3 rd Floor Locker Rooms Shaflucas Architects, PC Project No.

Design and Construction Standards SECTION FIRE SUPPRESSION

New Rigby Elementary School February TABLE OF CONTENTS

SECTION FIRE-SUPPRESSION SYSTEMS

A. This Section includes the following fire-suppression piping inside the building:

SECTION FIRE SUPRESSION

SECTION DRY-PIPE FIRE-SUPPRESSION SPRINKLERS

DESIGN & CONSTRUCTION GUIDELINES

Transcription:

SECTION 15501 WET AUTOMATIC FIRE SPRINKLER SYSTEMS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Wet automatic fire sprinkler systems including fire pump, fire pump controller, alarms, safety devices, piping, sprinklers and related accessories, sized and spaced for light hazard occupancy and ordinary hazard occupancy. B. Related Sections: 1. 2. 15047 - Identification. 15330 - Automatic Sprinkler Piping. 3. 15410 - Piping (Plumbing). 1.02 SUBMITTALS A. Submit properly identified manufacturer's data and Shop Drawings for acceptance before starting work. 1. Available water flow, pressure calculations, and Shop Drawings. 1.03 DRAWINGS A. The intent of the drawings is to provide the fire sprinkler installer a framework for pricing and hydraulic calculations. 1.04 FINAL SIZING A. After final sizing is accepted by A/E and other authorities having jurisdiction, contract price will be adjusted due to over sizing or under sizing of original engineering drawings. PART 2 PRODUCTS 2.01 MANUFACTURERS A. Sprinkler Heads: Concealed, quick response. 1. Central Sprinkler Corp. 2. Grinnel. Project No. SPECIFICATION GUIDELINES 15501-1

3. Viking. B. Horizontal Fire Pump: Peerless Model 6AF13 or accepted equivalent. C. Jockey Pump: Peerless Model JG5E or approved equivalent. 2.02 EQUIPMENT A. Piping: 1. Provide piping and fittings of correct weight, size, and type according to National Fire Protection Association (NFPA) 13, 14, and 15. a. Use American Standard fittings for pressure involved, but with not less than 175 lbs. WOG nonstick working pressure. 2. Hanger and Supports: a. Provide adjustable hangers as required for proper support of pipe lines according to requirements of NFPA 13, Fed.Spec.WW-H-171E, and is UL listed. Hangers shall allow for expansion and contraction of pipe lines and be wrought iron clevis type. Wire type hangers are not allowed. b. Piping Supported from Concrete Slabs: Use hangers attached to galvanized rods suspended from concrete inserts. Powder actuated fasteners and devices are not allowed. "Redhead" self-drilling concrete expansion anchors are acceptable. c. Single Pipe Runs: Support with adjustable swivel ring hangers. Wire type hangers are not acceptable. d. Piping Supported from Walls or Columns: Use welded steel brackets and adjustable swivel ring hanger. e. Standpipes Supported from Walls with Wrought Strap: Grinnell Fig.262. B. Sleeves: Per NFPA regulations. C. Valves: 1. Control Valves: a. Accepted O.S.& Y. gate valves suitable for 175 lbs., minimum working pressure. b. Size: 1-1/2" and larger shall be flanged type. Project No. SPECIFICATION GUIDELINES 15501-2

2. Valve Directory: Plastic laminated on solid backing, giving number, location, and function of each valve. a. Where it is necessary to operate more than 1 valve to control a section of piping, note this fact and show the number of second valve on directory. 3. Inspector's Test Connections: One test pipe and valve connection of not less than 1 inch diameter, terminating in a smooth bore, 1/2" brass outlet, discharging through a suitable air gap connection to sanitary collection system. D. Sprinkler Heads: 1. High temperature automatic type with fusible elements and low velocity, wide angle "water spray" discharge. 2. Provide accepted heads as follows: a. Unfinished Areas: Pendent sprinklers with standard finish and polished brass escutcheon plates. b. Finished Suspended Ceiling Areas: Chrome plated, flush type, sprinkler heads. c. Wall mounted sprinkler heads. 3. Metal Cabinet: E. Pumps: a. Provide with 12 extra automatic sprinkler heads, in proportionate quantity of each temperature range and type installed. b. Provide 2 sprinkler wrenches and water flow stoppers suitable for interrupting sprinkler head discharge. c. Provide 1 water flow stopper of the short type and other with long handle. 1. Fire Pumps and Controller: a. UL listed, FM approved, horizontal fire pump, 60 HP, 480/3/60 electric service, 1760 rpm with a capacity of 1000 gmp against a total dynamic head of 162 TDH with an estimated minimum city suction pressure of 80 TDH. b. Automatic electric motor controller, floor mounted, UL listed, FM approved, specifically built for fire pump service and designed for primary resistor reduced voltage start with a minimum interrupting capacity rating of 50,000 amps. Project No. SPECIFICATION GUIDELINES 15501-3

2. Jockey Pump: a. 3460 rpm, 480/3/60 electric service, with a capacity of 10 gpm against a total dynamic head of 200 TDH. b. Provide 1 jockey pump controller with running period timer. PART 3 EXECUTION 3.01 INSTALLATION A. Install system according to NFPA 13 "Standards for the Installation of Sprinkler Systems". 1. Place main piping with minimum 12 inch clearance between other mechanical and electrical services. 2. Branch piping shall clear light fixtures by at least 6 inches. 3. Where automatic sprinkler protection is indicated for suspended ceiling, install piping above ceiling with sprinkler heads installed below ceiling in pendant position. B. Flush fire mains with clean water in the presence of A/E until clean and accepted. 1. Maintain a flow of 7 feet per second velocity for a period of time consistent with length of pipe to accomplish flushing. C. Sleeves: 1. Provide square ends projecting 2 inches above floor for sleeves through floors. 2. Make sleeves passing through walls or beams flush with adjacent sides. 3. Provide flashing for sleeves passing through roof. 4. Make sleeves watertight (where required) by caulking space between pipe and sleeve. D. All work shall be done by experienced mechanics. E. Provide escutcheons on both side of piping in partitions, ceilings, and floors. F. Install piping to allow freedom of movement during expansion and contraction operations, without causing Project No. SPECIFICATION GUIDELINES 15501-4

warping, by using expansion joints and pipe loops. G. Offset piping as necessary to avoid interference with other work and to maintain headroom. 1. Provide proper drain and drip where necessary. H. Run pipe in the most direct, straight mechanical manner and properly graded. I. Identification: Identify piping, valves, and specialties as specified under Section 15047. J. Caps and Plugs: Keep openings closed during construction with cast-iron or malleable caps, plugs, or blind flanges. K. Pipe Anchors: Provide anchors to support risers, to maintain pipes in position, and to properly regulate expansion. L. Valves: 1. Control Valves: a. Place valves in readily accessible locations or with suitable means of access. b. Seal gate valves in open position with riveted straps or wire and lead seals designed for this purpose. 2. Alarm Valves, Variable Pressure: a. Provide in each main automatic sprinkler system riser, where indicated, an accepted variable pressure alarm valve complete with trim. 1) Circuit Closer Switch: Designed for 100 volts AC with two pairs of reversible contacts for connection to and suitable for operation of the alarm system. M. Inspector's Test Connections: 1. Extend from highest point of automatic sprinkler system to a point where discharge can be readily observed. 2. Locate test valve at an accessible point, not over 7 feet from the floor. N. Fire Pumps and Controller: Install according to NFPA 20. Project No. SPECIFICATION GUIDELINES 15501-5

3.02 FIELD QUALITY CONTROL A. Upon completion of the work, notify any local authorities having jurisdiction, proper insurance authorities, and A/E and arrange to have their authorized inspectors present when final job inspection and tests are conducted. B. Test all parts of system hydrostatically at 200 psi for a minimum 2 hour period according to NFPA 13 and 24. 1. Repair all defects and retest. END OF SECTION Project No. SPECIFICATION GUIDELINES 15501-6