Division 21: FIRE SUPRESSION WET-PIPE SPRINKLER PROTECTION SYSTEM. The Academy Sept Table of Contents 1 Division 21

Similar documents
DIVISION 21: FIRE SUPPRESSION WATER BASED FIRE SUPRESSION SYSTEMS

FIRE SUPPRESSION SPRINKLER SYSTEM

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University.

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements.

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

Mercury Plastics New Building February TABLE OF CONTENTS

Lucy s Pizza 100% CD Specification 06/22/2018

ADDENDUM NO. 3 March 19, 2018

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

DIVISION 21: FIRE SUPPRESSION

DIVISION 21 - FIRE SUPPRESSION

TABLE OF CONTENTS

West District Library Section Campeau Drive, Ottawa SPRINKLER SYSTEMS City of Ottawa Project No. CR Page 1 of 8

DIVISION 21 - FIRE SUPPRESSION

DIVISION 21: FIRE SUPPRESSION

Design & Construction Standards, Revised January

New Rigby Elementary School February TABLE OF CONTENTS

SECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM

Kenworth Sales Co. - North Las Vegas, Nevada November TABLE OF CONTENTS

SECTION FIRE PROTECTION. A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section

Port of St Helens SIA Aircraft Hanger Scappoose, OR

D. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following:

UC Santa Cruz Campus Design Guide. Includes the following sections: None DESIGN REQUIREMENTS

THE JAMES RUSHTON EARLY LEARNING AND FAMILY SUCCESS CENTER #2616 ISSUE FOR CONSTRUCTION

WET AUTOMATIC FIRE SPRINKLER SYSTEMS

SECTION FIRE-SUPPRESSION STANDPIPES

SECTION WET AUTOMATIC FIRE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS

Western Michigan University Facilities Management Engineering Division

SECTION ELECTRIC-DRIVEN, FIRE PUMPS

2. Welding Materials and Procedures shall conform to the ASME Code.

DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES

SECTION DRY-PIPE SPRINKLER SYSTEMS

SECTION (13900) - FIRE SUPPRESSION SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE

SECTION WATER BASED FIRE SUPPRESSION SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION DRY-PIPE SPRINKLER SYSTEMS

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE

A. This section includes design and performance information for fire protection and suppression systems.

APPENDIX H (DESIGN SUBMISSION CRITERIA)

Environmental Health & Safety

ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1. The Curators of the University of Missouri

SECTION WET-PIPE SPRINKLER SYSTEMS

FIRE & LIFE SAFTEY STANDARD

SECTION FIRE PROTECTION

SECTION WET-PIPE FIRE SUPPRESSION SPRINKLERS

CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau

Gas Station & C Store SECTION CWM Job No

TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION WATER BASED FIRE PROTECTION SYSTEMS... 5

A. Section includes wet-pipe sprinkler system, system design, installation, and certification.

Fire Sprinkler Submittal Requirements and Acceptance Testing

DIVISION 21 FIRE SUPPRESSION FIRE SUPRESSION

SECTION : FIRE PROTECTION SYSTEMS

DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES

DIVISION 21 FIRE SUPPRESSION SECTION FIRE PROTECTION SPECIALTIES

MLA Architects Pierz Public Schools ISD #484 Healy High School Multi-Purpose & Choir Additions Pioneer Elementary School Class Room Addition Pierz, MN

B. Section Identification for Fire Suppression Piping and Equipment.

Public School Facilities Authority State of New Mexico 2019 Galisteo, Suite B Santa Fe, New Mexico 87505

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM

Design & Construction Standards, Revised January

UBC Technical Guidelines Section Edition Fire Protection General Requirements Page 1 of 6

UMC El Paso Far East Clinic and Neighborhood Healthcare Center West Issue for Construction Page Project No and April 13, 2015

B. Galvanized-Steel-Sheet Sleeves: inch minimum thickness; round tube closed with welded longitudinal joint.

SECTION WET FIRE SPRINKLER SYSTEMS

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

SECTION ADDENDUM NO. 1 FIRE SPRINKLER SYSTEM

DESIGN & CONSTRUCTION GUIDELINES

1.2 CODES AND REGULATIONS A. Sprinkler system design, equipment, materials, devices, and installation shall conform to the following:

AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations)

CITY OF PASADENA FIRE DEPARTMENT

Sprinkler Permit Applications

DIVISION 21: FIRE SUPPRESSION SYSTEMS SECTION Fire Protection Systems Protecting Cold Storage and Unheated Warehouses

SECTION Fire Pumps

DIVISION 21 FIRE SUPPRESSION

SECTION SPRINKLER SYSTEMS

SPRINKLERS TABLE OF CONTENTS

B. The sprinkler system shall be designed to meet the more stringent of the requirements of NFPA 13 and FM Global requirements.

D. Reference Standards (Utilize latest editions available):

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

SECTION DRY-PIPE SPRINKLER SYSTEMS

Oxnard Fire Department 360 W. Second Street Oxnard, CA (805) Fax (805)

Wayne State University WSU Project No Chatsworth Tower Apts. Misc. Bldg. Upgrades DSD Project No

DIVISION 21 FIRE SUPPRESSION FIRE SUPPRESSION GENERAL PROVISIONS .1 PREPARATION OF CONTRACT DOCUMENTS

SECTION INSPECTION AND TESTING OF WORK

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

FIRE SPRINKLER SYSTEMS POLICY

SECTION SPRINKLER SYSTEMS

AUTOMATIC FIRE SPRINKLER SYSTEMS

New Construction Fire Inspection Process

B. Related Sections: The following Sections contain requirements that relate to this Section.

SECTION AUTOMATIC SPRINKLER PIPING

SECTION REGULATORY REQUIREMENTS. A. Relationship between Code, Ordinances, Standards and Contract Documents

Transcription:

Division 21: FIRE SUPRESSION 21 1313 WET-PIPE SPRINKLER PROTECTION SYSTEM Table of Contents 1 Division 21

SECTION 21 1313 WET-PIPE SPRINKLER PROTECTION SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings, General Provisions of Contract, including General and Supplementary Conditions apply to this Section. 1.2 SUMMARY A. Furnish and install a wet-pipe automatic fire sprinkler protection system as described in Contract Documents. 1. System shall be installed beginning with connection to the new building service main or city supply main located as shown and work shall include but not necessarily be limited to the following areas: a. New construction 2. Provide double check valve on fire sprinkler line. 1.3 APPLICABLE CODES AND ORDINANCES A. The following form a part of this specification: 1. National Fire Protection Association Pamphlets: Standards of the National Fire Protection Association for the Installation of Sprinkler and Fire Protection Equipment. a. Pamphlet No. 13, 13D, 13R, 14, and applicable standards. b. Pamphlet No. 231, 231C and applicable standards. c. And as approved over this geographical area 2. International Building Code 3. International Fire Code 4. Underwriter's Laboratories, Inc. Publications: List of Inspected Fire Protection Equipment and Materials. 5. Applicable state and local codes and ordinances pertaining to fire protection systems and equipment. 6. Requirements of State Fire Marshal. 7. Requirements of Local Fire Marshal. 8. Safety Code for Elevators and Escalators. 9. Life Safety Code. B. Work in Idaho must be done by an Idaho licensed sprinkler contractor and plans submitted to and approved by the office of the Idaho State Fire Marshal. C. The contractor shall notify the Idaho State Fire Marshall and the Local Fire Department to witness the test of the fire sprinkler system. 1.4 VERIFICATIONS AND REQUIREMENTS A. Fire Sprinkler Contractor shall verify adequacy of the water service to the building. B. Fire Sprinkler Contractor shall also check with the Local City Fire Marshal, the State Fire Marshal and the Fire Rating Bureau to determine requirements for the following: 1. Fire hydrants 2. Fire department connections 3. Test connections 4. Exterior and interior piping 5. Water storage and supply 6. Spacing of heads 7. Need for pumps 8. Secondary power source 9. Need for dry pipe system Wet-Pipe Sprinkler Protection System 21 1313-2

10. Rating of building 1.5 FEES AND PERMITS A. Fees or permits required to furnish and install the fire protection system shall be included as part of this Section of the Contract Documents. 1.6 PIPE SIZING A. Fire Sprinkler Contractor shall be required to size all piping for this project in accordance with requirements of Chapter 7 of National Fire Protection Association Pamphlet No. 13 for Hydraulically Designed Sprinkler Systems. 1.7 SHOP DRAWINGS A. Shop drawings shall be submitted as required by the Mechanical General Conditions. B. Fire Sprinkler Contractor shall submit complete layouts to underwriters having jurisdiction and the State Fire Marshal for approval prior to submission to Architect. 1. Particular attention shall be paid in layout to coordination of sprinkler piping and structural system of beams. Notations shall be made on shop drawings where pipes are required to pass thru beams. 2. Wall sprinkler shall be used in ramp areas where headroom is at a minimum and shall be arranged so as not to conflict with egress and door swings. 3. Careful coordination shall be given to avoid changing ceiling lighting systems as shown on drawings. 4. Sprinklers must be spaced equally with lights and ceiling diffusers. 5. No fabrication of piping shall be done until piping drawings are accepted by Mechanical Engineer and State Fire Marshal. C. The Fire Protection Sprinkler Contractor shall submit drawings that have been prepared and overseen by a NICET Certified Engineering Technician in fire protection with a minimum, Level 3 rating, or by a Professional Engineer in fire protection. This person shall be employed and be a staff member of the Fire Protection Contractor and shall be required to certify that the drawings are in accordance with the specifications and all regulatory requirements. All drawings shall be signed by the CET or stamped and signed by the Professional Engineer. PART 2 - PRODUCTS 2.1 MATERIALS AND COMPONENTS A. Sprinkler Heads: 1. Sprinkler head orifice sizes shall be in accordance with National Fire Protection Association. 2. Any change in spacing must be in straight rows with lights and walls. 3. Sprinkler heads shall be automatic and conventional (spray) type approved by a nationally recognized testing laboratory. 4. Each head shall have an orifice of nominal 1/2" diameter. 5. Sprinkler heads shall be pendant type where installed above a hung ceiling. 6. Any sprinkler heads in non-conditioned areas or exterior areas shall be protected with antifreeze loop or freeze proof sprinkler heads as required. 7. Heads in jail cell areas or other designated security areas shall be security type heads especially designed for that use. B. Protective Guards: 1. Heavy wire protective guard shall be provided for sprinkler heads located in heavy use areas where damage may result including, but not limited to: a. Gyms b. Locker rooms c. Multi-purpose rooms d. Shops e. Equipment rooms Wet-Pipe Sprinkler Protection System 21 1313-3

C. Control Valves: 1. Approved by a nationally recognized testing laboratory. 2. Necessary appurtenances shall be provided at each control valve. D. Backflow Valves: 1. Furnish and install in each fire sprinkler system, a line size double check valve backflow prevention device to meet the performance specifications of AWWA, UL, ASSE, Land IAMPO. 2. Installation shall include valves and test ports. E. Each control valve and alarm check shall have alarm contacts wired to fire alarm panel. Conduit and wire for this function are specified under the electrical division of Contract Documents. Provide water flow alarm on exterior of building close to control valve location. F. Interior Piping, Valves and Fittings: 1. Sprinkler and stand pipe shall meet the requirements of NFPA 13, and have a corrosion resistant ratio greater than one (1). No threadable thinwall pipe is acceptable. 2. Fittings shall be cast iron, black, screwed, except where flange fittings are required. 3. Flanged fittings shall be 150 pound class American Standard. 4. Exposed sprinkler piping shall be thoroughly cleaned and given one shop coat of prime coat paint by Fire Sprinkler Contractor. 5. Alarm check valves, OS&Y gate valves, indicator gate valves, ordinary check valves, ball drips, vacuum breakers, pressure relief valves, pressure gauges, angle valves and all other miscellaneous appurtenances required shall be provided and shall be approved for sprinkler service by a nationally recognized testing laboratory. 6. All pipe hangers and hanger spacings shall be in strict accordance with National Fire Protection Association. G. Valve Signs: 1. Properly lettered approved metal signs shall be attached to each control valve. H. Sleeves and Floor, Wall and Ceiling Escutcheon Plates: 1. Provide approved type one-piece or split-type escutcheon plates for sprinkler and standpipe piping passing thru floors, walls, and ceilings. Plates shall be securely anchored in place with set screws or other approved positive means. I. Areas Subject to Freezing Temperatures: 1. Branches serving these areas may contain a cold weather valve and ordinary pipe sprinkler heads. 2. If an air compressor is used this contractor is responsible for the compressor and all related piping and electrical conduit, wire and electrical devices to power the compressor. PART 3 - EXECUTION 3.1 INSTALLATION A. Work shall be executed and inspected in accord with laws, ordinances, rules and regulations of local authorities having jurisdiction over such work. Should any change in the drawings or specifications be required to conform to these ordinances, Fire Sprinkler Contractor shall notify the Architect-Engineer at time of submitting his bid. After entering into the contract, Fire Sprinkler Contractor shall be held to complete all necessary work to meet local requirements without expense to Owner. B. Sprinkler system shall be installed such that spacing of sprinkler heads in relation to ceiling shall not exceed that permitted for type of ceiling construction involved. C. General Contractor is required under contract stipulations to leave chases and openings in walls, floors, ceilings, partitions and beams, etc., provided Fire Sprinkler Contractor shall furnish to General Contractor full information as to locations, dimensions, etc., of such chases and openings including the provision and proper setting of all sleeves and other equipment in advance of construction of work so as to cause no delay in work. Wet-Pipe Sprinkler Protection System 21 1313-4

D. Should any cutting of walls, floors, ceilings, partitions, etc., be required for proper installation of the work or apparatus of Fire Sprinkler Contractor due to his failure in giving the General Contractor proper information at time required, such cutting shall be done at his own expense and in a manner acceptable to Architect- Engineer. All drilling and patching for anchor bolts, hangers, and other supports shall be subject to approval of Architect-Engineer. E. Siamese connections and watermains to sprinkler room shall be provided by Fire Sprinkler Contractor and connections to sprinkler system shall be by Fire Sprinkler Contractor. F. Conduits and wiring for alarm contacts, power wiring from starter to motor, and starter shall be provided and wired complete by Electrical Contractor for testing by Fire Sprinkler Contractor. Control wiring from starter to control and safety devices shall be provided and wired by Fire Sprinkler Contractor. 3.2 FIELD TESTING A. All portions of the system shall be hydrostatically tested. B. Flushing of underground piping shall be done in accord with National Fire Protection Association. C. On completion of the work, system shall be tested by full flow. 1. Each control valve for each sprinkler system shall be tested by use of an inspector's test valve or the application of heat to sprinkler head most remote from the valve. 2. All alarms and other devices shall be tested. 3. All appliances and equipment for testing shall be furnished by Fire Sprinkler Contractor. 4. Expenses, except for water and electricity used in connection with the tests, shall be defrayed by Fire Sprinkler Contractor. 5. On completion of tests by Fire Sprinkler Contractor, any defects detected shall be corrected by Fire Sprinkler Contractor at his own expense and additional tests made until systems are proved satisfactory. 6. Fire Sprinkler Contractor shall submit to Architect-Engineer a certificate covering materials and tests, similar to that specified by National Fire Protection Association, with a request for formal inspection at least two working days prior to date of inspection. The State and Local Fire Marshalls shall also be notified to witness this test. At such inspection any or all of required tests shall be repeated as directed by the Architect-Engineer. D. Final Inspection: The Sprinkler Contractor CET or PE responsible for overseeing this project shall make a complete and final inspection of the installation, checking out all alarms, valves, piping, seismic bracing, hangers, etc., conduct a final main drain test on the system, and provide documentation of this final inspection. END OF SECTION END OF DIVISION Wet-Pipe Sprinkler Protection System 21 1313-5