A36D/TPSD Modbus RTU (Serial) SCADA INTERFACE INSTRUCTIONS

Similar documents
A36D/TPSD Modbus TCP SCADA INTERFACE INSTRUCTIONS

Setup Instructions. This manual is only valid for A36D/TPSD Chargers. equipped with a 341S control card with P341S0012 or P341S0013 software

A77 SNMPv1 SCADA INTERFACE INSTRUCTIONS

A77 SNMPv3 SCADA INTERFACE INSTRUCTIONS

La Marche Manufacturing Company Option 46 Series. Digital Combined Accessory Package. Installation and Operation Manual

La Marche Manufacturing Company Option 16 Series. Digital Combined Accessory Package. Installation and Operation Manual

TPSD. Installation and Operation Manual. Filtered Battery Charger Power Supply / Battery Eliminator

EOS INTERFACE GUIDE AND POINTS LIST For EOS BTCII Firmware Version J1239D-570 and newer

CTT8 TEMPERATURE MONITOR DEVICE

Modbus RTU RS485 Manual

La Marche Manufacturing Company A36D. Battery Charger / Power Supply. Installation and Operation Manual

MO n : 12JMC rév A

Carbon Monoxide Transmitter

Q-SMART MODBUS KIT. Modbus Protocol & Parameters. Cod EN rev.a ed.08/2018. Q-SMART Software Version AE17

MODEL P531, P532 AND P532UI FLAME MONITOR OPERATING MANUAL

TEMON 4-C. Doc. N MO-0368-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 4-C OPERATION MANUAL. Microener- Copyright 2010 FW 2.1 Date Rev.

SM3000 Videographic Recorder. User Guide. Modbus (RTU) Communications Option

RS485 MODBUS Module 8AI

A77 Series. Microprocessor Controlled SCR Filtered/Battery Eliminator Filtered Charger. Installation and Operation Manual

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

Temperature Controllers

PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS

End To End Optical Beam Smoke Detector. Additional Information

How to use the BTRM in Remote Enclosures

Process & TeMPerATUre UniversAl input DigiTAl MeTers

DIGITAL TEMPERATURE RELAY TR-100

DC VOLTMETER DCV-10 / 10A / 10C / 10S / 10CS / 11 / 11A / 11C / 11S / 11CS. A4741 / Rev.1

P2267 NETWORK INTERFACE

ACCURATE ELECTRONICS INC

Adaptive CyCLO Technical and HMI User Guide. CyCLO User Guide. Version th December 2017 REV

02/11/2015

Multiple Battery Cabinets Dual-Lite TRN. External Maintenance Switch Configuration Options. External Maintenance Switch Options

PTE0705 Electric Fence Monitor

HRX Technical Manual. Version 1.2

INSTRUCTION MANUAL and DETAILED PRODUCT SPECIFICATION TRIPLEX PUMP CONTROL SYSTEM MODEL NUMBER CPC-3. M336 Rev F. November 21, 2000.

DPR-145 TEMPERATURE PROTECTION RELAY. DPR-145 User Manual V-2.0 ( ) PT100 INPUTS: 4 RELAY OUTPUTS: 4 RS-485 MODBUS PORT VDC SUPPLY -1-

Metasys Integrator Airflow Application

Refrigerated air dryers

MAIN MENU/HOME SCREEN OVERVIEW

System 57. An advanced World of intelligent gas detection system management

Toxic and Explosive Smart Gas Monitor PN / Installation and User Manual

SERVICE INSTRUCTIONS FOR. Fire Alarm System MINI-2000

MYRIAD TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL

Endura AZ40 Oxygen and carbon monoxide equivalent (COe) analyzer

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

21-light Remote Annunciator. Owner s Manual

System 57. An advanced world of intelligent gas detection system management

Pump-Up Controller MODEL 4062

ibox Modbus Server Gateway for the integration of Notifier ID3000 / ID3002 / ID60 / ID50 fire panels in Modbus enabled monitoring and control systems

M2000 Engine Controller

CLEANROOM MONITOR CR3A Network - Installation Instructions

4800 Gas Controller User Guide

Lift Station Level Controller

Pump-Down Controller MODEL 4052

Dryer Master DM510 Commissioning Guide

Multi-Gas-Controller MGC2

LCF Touch Modbus Datasheet Application Security Advice Caution

LC150 VIEW-AT-A-GLANCE PUMP CONTROL-TELEMETRY UNIT

FlameGard 5 MSIR HART

725B Configuration Software Manual

NGC-UIT2 MODBUS PROTOCOL INTERFACE MAPPING FOR NGC-30 SYSTEMS. Firmware versions up to V2.0.X

02/11/2015

4/8/12/16 Channel Temperature Scanner with FREE Data Logging PC Software RS485

PowerWizard. Level 1.0 & Level 2.0 Control Systems Training

SEQUENCE OF OPERATIONS

ENGINE MONITOR VOTT MODEL: YEAR WARRANTY

UNC100 Integra Manual

Two-Channel Gas Controller

Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts

M1000 Alarm Annunciator

Metasys Integrator Vilter Application

READ AND SAVE THESE INSTRUCTIONS

MF-PFA ver 3.x. Micaflex PFA ver 3. Pressure- and Flow transmitter with alarmfunction. Installation- & Operation manual [Dok. id: mi-303gb_180528]

Carbon Monoxide Transmitter

OWNERS MANUAL YEAR LIMITED WARRANTY READ ALL INSTRUCTIONS BEFORE PROCEEDING. Store this booklet for future reference

Installation Manual Tracker 221

Danfoss gas detection units

INSTALLATION INSTRUCTIONS

Table of Contents SECTION PAGE SECTION 1 INTRODUCTION Description Features Models... SECTION 2 RS-232 COMMUNICATIONS...

TECHNICAL MANUAL CVM 20 C 5005 CV/04-99 GB

DAP III Zone Master User s Guide

Metasys Integrator Liebert Application

Gas Controller Module GC-06

NELSON CM HEAT TRACE CONTROLLER Installation and Operating Instructions

REMOTE CONTROL FOR CHILLER MYCHILLER

Variable Frequency Drive SERIES MP800 VFD

DiMM Unit. LST Digital Interface Monitor Module (LST-DiMM) MAN3109

1600 Gas Controller. User s Manual. Industrial Scientific Corporation. Version 3.2 September 1, 2006

General Routing Interface

INSTALLATION INSTRUCTIONS

OWNER S OPERATION MANUAL

ModBus DE-1 INSTALLATION AND USER MANUAL

Application, Installation, Operation & Maintenance Manual

NGC-40 Bridge. Modbus Overview. Raychem-AR-H58862-NGC40BridgeModbusOV-EN-1805 nvent.com 1

P/N f. HomeWorks QS Palladiom Thermostat Configuration Guide

Model OI-6000K Sensor Assembly

FIRERAY 5000 range USER GUIDE

Bacnet Room Setpoint & Temp Display. Descriptions. Specifications

OPERATION AND MAINTENANCE MANUAL

ACCURATE ELECTRONICS INC PO BOX SW HALL BLVD BEAVERTON OR USA FAX

Transcription:

SCADA INTERFACE INSTRUCTIONS - OPTION 21S - FOR A36D/TPSD SYSTEMS with option 500 and 550. A36D/TPSD Modbus RTU (Serial) SCADA INTERFACE OPTION 21S INSTRUCTIONS This manual is valid for A36D/TPSD Chargers equipped with 341S control cards with software P341S0012 or P341S0013 and 388S Communications Board CPN 135485 21183-7 11/17 21183-2 12/16 ECN/DATE ISSUE DATE: ECN 21183-7 11/2017 106 BRADROCK DRIVE DES PLAINES, IL. 60018-1967 (847) 299-1188 FAX: (847) 299-3061 INSTRUCTION DRAWING NUMBER: P25-LOPT21S-A36D-TPSD-1-341S

Default Settings The LaMarche Communications Card is shipped with the following default settings; Protocol: Modbus RTU Modbus Address: 1 Modbus Port: RS485 Modbus Baud Rate: 9600 Modbus Parity: Data Bits: Fixed at 8 Stop Bits: Fixed at 1 Setting the Modbus Type, Address, Baud Rate, Parity & Read Only Mode To change the Address, Baud Rate and Parity you need to enter the customer calibration mode where you can choose the following; Modbus Type: Serial Modbus Address: 1 through 247 Modbus Baud Rate (Serial Only): 1200, 2400, 4800, 9600, 19200, 38400 Modbus Parity Type (Serial Only): NONE, ODD, EVEN Read Only Mode: This mode does not allow any settings to be modified remotely. Page 2 of 10

Board Configuration CHARGER PORT (LAMARCHE USE ONLY) POWER SUPPLY BIAS RESISTOR JUMPER SELECT RS232 RS485 PORT SELECTION JUMPERS RS232 PORT (DTE) D+ GND D- RS485 PORT TERMINATION RESISTOR JUMPER SELECT For RS232 (WIRED AS DTE CONNECTION): The shorting jumpers must be on positions JP14 and JP16. For RS485 The shorting jumpers must be on positions JP13 and JP15. In addition for RS485 applications the following should also be set as required; Shorting jumper on JP5 Termination resistor is OUT of circuit. Shorting jumper on JP6 Termination resistor is IN circuit. Shorting jumper on JP1 D+ bias resistor is OUT of circuit. Shorting jumper on JP2 D+ bias resistor is IN circuit. Shorting jumper on JP3 D- bias resistor is OUT of circuit. Shorting jumper on JP4 D- bias resistor is IN circuit. Page 3 of 10

Supported Modbus Types RTU TCP Supported Modbus Function Codes 01 Read Coil Status (0X) 02 Read Discrete Input Registers (1X) 03 Read Holding Registers (4X) 04 Read Input Registers (3X) 05 Write Single Coil 06 Write Single Register 10 Write Multiple Coils 0F Write Multiple Registers 01 - Coils LaMarche Modbus Implementation Address Name/Description 00000 Float/EQ Mode Indicator (FLOAT=0, EQUALIZE=1) 00001 Temperature Compensation Enable (ENABLED=1). 00002 LCD Backlight Timeout Enable (ENABLED=1) This has no effect on Chargers equipped with VFD Displays. 00003 Include Low Current Alarm in Summary Alarm (INCLUDED=1) 00004 Include AC Alarm in Summary Alarm (INCLUDED=1) 00005 Include Ground Detection Alarms in Summary Alarm (INCLUDED=1). TPSD ONLY. 00006 Include Over Temperature Alarm in Summary (INCLUDED=1) 00007 Latch Summary Alarm (YES=1) 00008 Latch AC Fail Alarm (YES=1) 00009 Latch Low Voltage Alarm (YES=1) 00010 Latch High Voltage Alarm (YES=1) 00011 Latch High Voltage Shutdown Alarm (YES=1) 00012 Latch Positive Ground Alarm (YES=1). TPSD ONLY. 00013 Latch Negative Ground Alarm (YES=1). TPSD ONLY. 00014 Latch Overload Alarm (YES=1) 00015 Latch End of Discharge Alarm (YES=1) Reset Alarms (YES=1) 00016 Write a 1 to reset alarms. After alarms are reset software in the controller sets this point to 0. 00017 Ground Detection Alarm Enable. (ENABLED=1, DISABLED=0) TPSD ONLY. 00018 Test All Alarm Contacts (BEGIN TEST=1, END TEST=0). Note the HVSD alarm contacts are not tested remotely. 00019 Test Negative Ground Contacts (BEGIN TEST=1, END TEST=0). TPSD ONLY. Page 4 of 10

01 - Coils Address Name/Description 00020 Test High Voltage Alarm Contacts (BEGIN TEST=1, END TEST=0). 00021 Test Low Voltage Alarm Contacts (BEGIN TEST=1, END TEST=0). 00022 Test Positive Ground Contacts (BEGIN TEST=1, END TEST=0). TPSD ONLY. 00023 Test AC Alarm Contacts (BEGIN TEST=1, END TEST=0). 00024 Test Summary Alarm Contacts (BEGIN TEST=1, END TEST=0). 00025 Test Low Current Alarm Contacts (BEGIN TEST=1, END TEST=0). 00026 Test Open DC Protection Alarm Contacts (BEGIN TEST=1, END TEST=0). A36D ONLY. 02 - Discrete Inputs Address Name/Description 10000 AC Alarm Indicator (FAILURE=1) 10001 High Voltage Alarm Indicator (FAILURE=1) 10002 High Voltage Shutdown Alarm Indicator (FAILURE=1) 10003 Low Current Alarm Indicator (FAILURE=1) 10004 Open DC Protection Alarm Indicator (FAILURE=1) A36D ONLY. For TPSD this point will always read 0. 10005 Positive Ground Alarm Indicator (FAILURE=1). TPSD ONLY. For A36D this point will always read 0. 10006 Negative Ground Alarm Indicator (FAILURE=1). TPSD ONLY. For A36D this point will always read 0. 10007 Summary Alarm Indicator (FAILURE=1) 10008 End of Discharge Alarm Indicator (FAILURE=1). 10009 Overload Alarm Indicator (FAILURE=1) 10010 Over Temperature Alarm Enable (ENABLED=1) 10011 Over Temperature Alarm Status (FAILURE=1) Charger in Settings Menu (Set to 1 when charger is manually put into the settings menu 10012 through the front panel) Remote setting changes are disabled when this is set to 1 until the local operator exits the Settings Menu. 10013 SCADA Read Only Mode (ENABLED=1). Setting changes are not allowed when the charger is in the settings menu or when the SCADA Read Only Mode has been selected. 10014 Negative Ground Alarm Relay Contacts (CLOSED=1, OPEN=0). TPSD ONLY. 10015 High Voltage Alarm Relay Contacts (CLOSED=1, OPEN=0). 10016 Low Voltage Alarm Relay Contacts (CLOSED=1, OPEN=0). 10017 Positive Ground Alarm Relay Contacts (CLOSED=1, OPEN=0). TPSD ONLY. 10018 AC Fail Alarm Relay Contacts (CLOSED=1, OPEN=0). 10019 Summary Alarm Relay Contacts (CLOSED=1, OPEN=0). 10020 Low Current Alarm Relay Contacts (CLOSED=1, OPEN=0). 10021 Open DC Protection Alarm Relay Contacts (CLOSED=1, OPEN=0). Page 5 of 10

03 - Holding Registers Address Description, Units, Valid Settings/Range Scale Factor 40000 Equalize Timer Mode (0,1 2,3,4) 40001 Equalize Timer Setting (0 to 144) 40002 Low Voltage Alarm Threshold, Volts, (0 to MAXAV) 0.1 40003 High Voltage Alarm Threshold, Volts, (0 to MAXAV) 0.1 40004 High Voltage Shutdown Alarm Threshold, Volts, (0 to MAXAV) 0.1 40005 Low DC Current Alarm Threshold, Amps, (0 to MAXAI) 0.1 40006 Low DC Current Alarm Recovery Threshold, Amps (Low DC Current Alarm Threshold to MAXAI) 0.1 40007 Low Voltage Alarm Recovery Threshold, Percent (0 to 20) 40008 Low Voltage Alarm Delay, Seconds, (1 to 300) 40009 Equalize Timer Mode 4 (Auto Equalize on LV Alarm Recovery) Delay, Seconds (1 to 300) 40010 High Voltage Alarm Delay, Seconds, (1 to 300) 40011 High Voltage Alarm Recovery Threshold, Percent (0 to 20) 40012 High Voltage Shutdown Alarm Delay, Seconds, (1 to 300) 40013 Low Current Alarm Delay, Seconds, (1 to 300) 40014 End of Discharge Alarm Threshold, Volts, (0 to MAXAV) 0.1 40015 End of Discharge Alarm Recovery Threshold, Percent (0 to 20) 40016 Overload Alarm Threshold, Amps, (0 to MAXAI) 0.1 40017 Overload Alarm Recovery Threshold, Percent (0 to 20) 40018 AC Alarm Delay, Seconds, (1 to 300) 40019 Ground Detection Alarm Delay, Seconds, (1-300) TPSD ONLY. For A36D this point will always read 0 and writes to are prohibited. 40020 End of Discharge Alarm Delay, Seconds (1-300) 40021 Overload Alarm Delay, Seconds (1-300) 04 - Input Registers Address Description, Units Scale Factor 30000 Heartbeat This register increases once per second and may be used to determine if communications are still occurring. 30001 Board Number. Will read 205 for 205T card. 30002 Software Version, Version of software on 205T card. 30003 Voltage, Volts 0.1 30004 Current, Amps 0.1 30005 Equalize Cycle Time Hours Remaining, Hours, Minutes Note: The last two digits are the minutes. 30006 Auto Equalize Timer, Days 30007 Auto Equalize Timer, Hours, Minutes Note: The last two digits are the minutes. 30008 Low DC Current Alarm Low Limit, Amps. Setting the Low DC Current Alarm below this will result in disabling the Low DC Current Alarm Status Indicator. 0.1 Page 6 of 10

04 - Input Registers Address Description, Units Scale Factor 30009 Local Temperature Probe Reading, Degrees C Note: A shorted probe will give a reading of 273 and an open probe will give a reading of+273 30010 Temperature Probe Status OK=0,SHORTED=1,OPEN=2,HARDWARE FAILURE=3 30011 Maximum Settable Alarm Voltage, MAXAV, Volts 0.1 30012 Maximum Settable Alarm Current, MAXAI, Amps 0.1 30013 Over Temperature Probe Reading, Degrees C Note: A shorted probe will give a reading of 273 and an open probe will give a reading of+273 30014 Over Temperature Probe Status OK=0,SHORTED=1,OPEN=2,HARDWARE FAILURE=3 30015 Charger Series. (0=TPSD,1=A36D) 30016 Battery Voltage, Volts Note: This point should only be monitored when DI 10015=1 0.1 NOT AVAILABLE= 30000, FAILED = 30001 30017 Aux Temperature Probe #1, C Note: NOT AVAILABLE=30000, SHORTED=30001, OPEN=30002, FAILED=30003 30018 Aux Temperature Probe #2, C Note: NOT AVAILABLE=30000, SHORTED=30001, OPEN=30002, FAILED=30003 30019 Low Voltage Alarm Status (0=NO ALARM,1=LOW VOLTAGE ALARM,2=LOW BATTERY VOLTAGE ALARM) 30020 P60-407S Board Failure Alarm (0=N/A,1=NO ALARM,2=ALARM) Page 7 of 10