TS93 EMR WITH SMOKE DETECTOR

Similar documents
8600 EMR SERIES. INSPK NO Rev.06/ INS NO. GENERAL DESCRIPTION

TS93 EMF SERIES. INSPK NO Rev.03/10

MODEL /4" Conduit. (By others) Terminal Strips Companion unit (without electronics) not shown. Approximate Preload

Wiring Instructions for the 2900 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector

Wiring Instructions. Single Doors 99 Checkmate Series Use one or Master Unit each door or one or Support unit each door

Single Doors FIREGUARD Series Use one Master Unit each door or one 2409 Support unit each door. Pairs of Doors

Wiring Instructions (01-09)

DETECTOR TEST LOG. Detector Identification Information DHX-501 INTELLIGENT AIR DUCT SMOKE DETECTOR HOUSING INSTALLATION AND MAINTENANCE INSTRUCTIONS

INSTALLATION AND MAINTENANCE

DH500ACDC Intelligent Air Duct Smoke Detector Housing

DH100ACDCI Ionization Air Duct Smoke Detector

MANUAL RESET ALARM RELEASE

DH400 Air Duct Smoke Detector

DH100ACDCI Ionization Air Duct Smoke Detector

E-PDD Duct Smoke Detector Installation Sheet

D350PL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS

D350RPL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS

1400 Direct Wire Ionization Smoke Detector

MANUAL RESET ALARM RELEASE BOX

MANUAL RESET ALARM RELEASE

TRN100BPT, TRN100BP, and TRN100BPC Air Duct Smoke Detector with Extended Air Speed Range

DH100ACDCLP Air Duct Smoke Detector with Extended Air Speed Range

DH100LP Air Duct Smoke Detector with Extended Air Speed Range

DH500 Intelligent Air Duct Smoke Detector Housing

DH200PL Intelligent Air Duct Smoke Detector with Extended Air Speed Range

DH200PL Intelligent Air Duct Smoke Detector with Extended Air Speed Range

D2E Duct Smoke Detector

D285DH. Installation Instructions Photoelectric Duct Smoke Detector

DH200RPL Intelligent Air Duct Smoke Detector with Extended Air Speed Range

SK-Duct Air Duct Smoke Detector

D7050DH. Installation Instructions. Multiplex Photoelectric Duct Smoke Detector

7251DH Intelligent Air Duct Smoke Detector

Air Specialties Express, 448 S. Main St., P. O. Box , Verona, WI Phone: (877) Fax: (608)

Installation Guide for models:

RELEASE DEVICES RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: :100 GENERAL DESCRIPTION:

DUCTSD Duct Smoke Detector

FX-PDD Duct Smoke Detector Installation Sheet

F I R E G A R D D C EXTENDED PERFORMANCE RELEASE DEVICE SAFE A N D SECURE

DNR Duct Smoke Detector

Firefly II Multi Voltage RELEASE DEVICES. Firefly II & IIB-MV INSTALLATION MANUAL

SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. SS90-WPS MODEL A/B INSTALLATION MANUAL

Installation Guide for models:

ACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F

Cookson Company 1901 South Litchfield Road Goodyear, AZ Phone:

Duct smoke housings, 4-wire D341/D341P and D342/D342P

Addressable Detectors & Bases

2408/2900. Fire Guard. SARGENT Manufacturing Company 2004, 2007 All rights reserved

7200 Series. Electromechanical Closer/Holder Releasing Devices

IDP-Zone-6 Six Zone Interface Module

2408/2900. Fire Guard

THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL

TECHNICAL DATA SHEET CONVENTIONAL FIRE ALARM SYSTEMS Conventional Fire Alarm Control Panel

MODEL B2 INSTALLATION MANUAL

Control Panel For Water Wash Hoods AM2

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL

Installation Instructions

RELEASE DEVICE CONTROLS

2409/2900. Fire Guard

MMF Six Zone Interface Module

, -9686, -9688, -9755, Duct Detector/Sensor Installation Instructions

An ASSA ABLOY Group brand Series. Electromechanical Closer-Holder Releasing Device

MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL

WARNING. Installation Tip: Try out this unit before installing onto a fire door system. Test and learn the release INTRODUCTION

120 VOLT POTENTIAL PRESENT. MAKE SURE POWER INPUT TO UNIT IS TURNED OFF DURING INSTALLATION AND WIRING PROCEDURE.

PURGE/PRESSURIZATION SYSTEM

D4120 Duct Smoke Detector D4S Sensor Component D4P120 Power Board Component

Specification/ Data Sheet

ASSA ABLOY Series Power Operator Installation and Instruction Manual 6060 / Reveal. Adjusting Rod (08-13)

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL

M O D E L S FIREGARD BV EXTENDED PERFORMANCE RELEASE DEVICE

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep.

EHT/EHTD. Electromechanical Closer-Holder Release Devices

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

AL600ULADA. NAC Power Extender. Installation Guide

Conventional Smoke Detectors KFAPO

Installation Manual: PAD100-DUCTR Analog Addressable Duct Detector

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

DNR Duct Smoke Detector

Model 17A00 Expansion Enclosure

CZ-6A Six Zone Interface Module

THE "SS90" SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL

Duct and Rough Service Carbon Monoxide Sensor

3500 SERIES CONVECTION STEAM COOKER PARTS AND SERVICE MANUAL

Booster Power Supply Manual

D4120 Duct Smoke Detector D4S Sensor Component D4P120 Power Board Component

ANSUL ANSUL AUTOMAN II-C RELEASING DEVICE

TT /97. Features INSTALLATION INSTRUCTIONS. Horn. Lamps

SP-1000X. Panic Device Power Controller Installation Guide. Rev

Duct smoke housing, 2-wire D340/D340P

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

Application Data ! WARNING FACTORY INSTALLED SMOKE DETECTORS FOR SMALL AND MEDIUM ROOFTOP UNITS 2TO25TONS TABLE OF CONTENTS PART NUMBERS

M O D E L S F I R E G A R D M C V ADVANCE FIRE CONTROL RELEASE DEVICE

MODEL LP3 INSTALLATION AND SERVICE INSTRUCTIONS FOR STREAMLINE LP3 STROBE LIGHTS

DNR-AUS Duct Smoke Detector

Addendum for STI-6406 with Dual Access Control

For a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

Cautions and Warnings. Introduction 4009 NAC POWER EXTENDER

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES

MR-2602 Two Zone Fire Alarm Control Panel

Transcription:

TS EMR WITH SMOKE GENERAL DESCRIPTION Each TS EMR series unit contains a door closer, hold open electromagnet and smoke detector. The unit can be used as a single installation or as a series of singles powered from one or more power supplies. When a series of TS EMR units are wired together in a run, groups of up to units may be interconnected. Interconnection is accomplished through terminals # and # and results in all units alarming when any one of them senses smoke. In turn, all associated hold open solenoids are deenergized. Within any run of detectored units, it is permissible to form as many interconnected groups as the total power supply amperage will allow; but, again no more than units can be interconnected together. Any detectored TS EMR series unit can be connected to an auxiliary EMF nondetectored unit, or remote detector, or both. It can be a single installation or part of any of the multiple arrangements described above. An auxiliary unit (double door applications) is a companion to the main unit, and its electromagnet deenergizes along with the main unit. A remote open area detector sensing smoke alarms the TS EMR to which it is connected and any other TS EMR to which it is interconnected. Single installations or groups of installations can be connected to the alarm initiation circuit of a compatible UL/ULC listed fire alarm control unit in wire or wire configurations. Additional functions are provided to separately power the hold open electromagnet directly from the alarm control panel as well as connections for a remote alarm indicator lamp. INSTALLATION. Read entire instruction sheet prior to installation and refer to NFPA E. Standards may be obtained from THE NATIONAL FIRE PROTECTION ASSOCIATION, Batterymarch Park, Quincy, MA 0.. Reference unit carton for unit mounting type.. Prepare door and frame for fasteners using the appropriate template. Mark, drill, and tap holes as indicated. If surface wiring is used, omit /" hole for wire access. CAUTION: SEX NUTS ARE REQUIRED FOR ATTACHMENT OFCOMPONENTS TO UNREINFORCED DOORS AND TO WOOD OR PLASTIC FACED COMPOSITE TYPE FIRE DOORS, UNLESS AN ALTERNATIVE METHOD IS IDENTIFIED IN THE INDIVIDUAL DOOR MANUFACTURER'S LISTINGS. INS NO. INSPK NO. 00 Rev.0/ 000 PAGE of Rev. 0/

Install track to frame. TST and TSTDE Install with detector cut out toward latch edge of door using () /0 x " metal or () No. x /" wood screws. C L HINGE END CAP () () Install with detector cutout toward hinge edge of door using () /0 x " metal or () No. x /" wood screws. TSPT C L HINGE END CAP () () Install detector. Slide detector slot under standoff and attach with () screws. STANDOFF NOTE: If construction is still being completed near detector installation, DO NOT install detector at this time or protect the detector from construction dust contaminants. SLOT Remove () wire access plug according to the installation type. T & TDE (RH) NOTE: NO TOP PLUG ON PT MOUNTS NOTE: Three access wire holes on optional surface wired units only. T & TDE (LH) (SURFACE CONDUIT) INS NO. 000 PAGE of Rev. 0/

Attach mounting plate to door. () WOOD DOORS () METAL DOORS TST AND TSTDE RIGHT HAND DOOR LEFT HAND DOOR TSPT RIGHT HAND DOOR LEFT HAND DOOR Attach closer to mounting plate. () TST AND TSTDE RIGHT HAND DOOR LEFT HAND DOOR TSPT LEFT HAND DOOR RIGHT HAND DOOR INS NO. 000 PAGE of Rev. 0/

Attach arm to pinion of closer and secure arm with pinion screw and washer. TST RIGHT HAND DOOR () Attach arm to pinion of closer and secure arm with pinion screw and washer. LEFT HAND DOOR TSTDE () LEFT HAND DOOR RIGHT HAND DOOR Attach arm to pinion of closer. With door in closed position, rotate spindle approximately 0 to with wrench and hold in place. TSPT Place arm on spindle parallel to door and secure arm with pinion screw and washer. 0 0 0 Attach arm to slide shoe. Use / inch hex head wrench. Adjust spring tension, if required. TS Closer is normally as a size spring setting. Clockwise turns increase spring tension. CAUTION: DO NOT OVERTIGHTEN TS Adjust according to chart. INCREASE DECREASE TS Adjust only if more spring tension is required to positively close and latch door. DOOR WIDTH FULL TURNS OF CLOSER INT. EXT. SPRING ADJUSTER SIZE ' '" 0 '" ' ' '" NOTE: DO NOT ADJUST SPRING LOWER THAN SIZE ULC LABELED UNITS "ONLY" Adjust according to chart. IN CANADA, USE THIS CHART FOR ADJUSTMENT. CLOSER TYPE MAX. DOOR WEIGHT (LBS.) SPRING SIZE FULL TURNS OF SPRING ADJUSTER 0 TS 0 00 TS 0 0 INS NO. 000 PAGE of Rev. 0/

Adjust sweep, latch and backcheck or delayed action cycles. CAUTION: DO NOT REMOVE VALVES. DECREASE INCREASE LATCH RANGE SWEEP RANGE BACKCHECK (INTENSITY) OR DELAYED ACTION (TIME) INCREASE DECREASE BACKCHECK RANGE DELAY RANGE SWEEP speed from maximum opening to 0. LATCH speed from approx. to 0. (INCREASE ONLY) BACKCHECK cushion effect. CAUTION: DO NOT CLOSE VALVE COMPLETELY. DELAY speed from approx. 0 to 0. TS SZ. TS SZ. The following six pages contain wiring options. Wire the units according to building and system requirements. Observe all applicable codes. ELECTRICAL SPECIFICATIONS Voltage input: VDC 0% % VAC 0% % SD Maximum input current: Maximum output to Remote Alarm Indicator Lamp: Contact ratings: NOTE: 0 Volt applications require optional external transformer. @ VDC ma ( solenoid), 0 ma ( solenoids) @ VAC ma ( solenoid), 0 ma ( solenoids) NOTE: Excludes accessories 00 ma Alarm and or accessory contacts. A at VDC or. A at 0 VAC resistive, maximum. Trouble contacts 00 ma at VDC resistive maximum. LED & TEST CONNECTION LIST FUNCTION TERMINAL AC/DC V INPUT ALARM CONTACTS (NORMALLY OPEN) SOLENOID ALARM INDICATOR LAMP ALARM INDICATOR LAMP INTERCONNECT INTERCONNECT TROUBLE CONTACTS (NORMALLY CLOSED) VDC OUTPUT (UNFILTERED),,,, 0 0 IF JUMPER WIRE J/J IS CUT, TERMINALS, AND 0 ARE CHANGED TO FORM C RELAY CONTACTS, RAIL OUTPUT IS LOST, AND HOLD OPEN SOLENOIDS MUST BE POWERED FROM A SEPARATE SOURCE. CONSULT FACTORY IF S ARE USED IN THIS APPLICATION. COM 0 N.C. N.O. INS NO. 000 PAGE of Rev. 0/

POWER SUPPLY Insulate all connections. Observe all local codes. 0 VAC, 0/0 HZ 0 VAC, 0/0 HZ: Connect the 0 VAC incoming voltage wires to the primary wires of the transformer. Connect the secondary transformer wires to terminals # and # of the detector module. This connection is not polarity dependent. SD SECONDARY TRANSFORMER WIRES PRIMARY TRANSFORMER WIRES NOTE: FOR ULC INSTALLATIONS, TRANSFORMER MUST INSTALL IN " X " ELECTRICAL BOX X " DEEP MINIMUM. EXTERNAL STEP DOWN TRANSFORMER (OPTIONAL) 0VAC POWER INPUT 0 V AC/DC V AC/DC NOTE: The step down transformer is not used in this connection. Connect V AC/DC power to terminals # and # on the detectors. These connections are not polarity dependent. If the unit is connected to a second unit, connect terminal # of the first unit to terminal # of the second unit and connect terminal # of the first unit to terminal # of the second unit. Continue this process for any subsequent units to be powered from the same power supply. SD SD () () SD () VAC/DC POWER SUPPLY 0 0 0 V AC/DC WITH S V AC/DC WITH S NOTE: The step down transformer is not used in this connection. Perform wiring connections as illustrated below. Additional units are wired in the same manner as unit #.Installations using a combination of SD modules with and without remote area detectors can be wired accordingly by substituting the wiring diagram section from unit #, #, or # in step # above instead of unit #, #, or # below with remote detector. The vertical dashed lines indicate where one diagram would be exchanged for another. NOTE: Input voltage must match detector voltage. SD SD SD () () () VAC/DC POWER SUPPLY 0 0 0 INS NO. 000 PAGE of Rev. 0/

WIRE GAUGE WIRE GAUGE: The maximum wire gauge for wiring the SD detector module is # AWG. The method for determining wire gauge is given below. NOTE: A minimum of 0. VDC must be supplied to each solenoid in the run. No. OF ELECTRO MAGNET No. OF ELECTRO MAGNET No. OF ELECTRO MAGNET No. OF ELECTRO MAGNET (E) (E) (E) (E) POWER SUPPLY WIRE LENGTH TO E (D) WIRE LENGTH TO E (D) WIRE LENGTH TO E (D) WIRE LENGTH TO E (D) TO NEXT HOLD OPEN SOLENOID E, E, E etc. are the number of electromagnets at each subsequent station. D is the distance from the power supply to the first electromagnet station. D, D, D etc. are the distances from the previous electromagnet station to the next electromagnet station in the run. To determine the correct wire gauge multiply E times D. Add that quantity to E times D. Repeat the same procedure for each electromagnet to test the last unit in the run. Compare the quantity calculated to the chart below. The calculated value must be less than or equal to the value corresponding to the appropriate wire gauge. 0 GAUGE, GAUGE,0 GAUGE, GAUGE, GAUGE, The procedure described above can be expressed in the following equation: (ExD) (ExD) (ExD)...(EnxDn) The above values correspond to the wire gauge to be used. If the calculated value is, # AWG wire can be run and connected directly to the detector module. If the calculated value exceeds, larger wiring will be required. Since the detector will only accept # AWG wire, a wiring splice will be necessary as illustrated below. SD NOTE: FOR ULC INSTALLATIONS, GAUGE WIRE IS REQUIRED TO # 0 # ## ## ## ## SD TO MAIN SOLENOID CONNECTION Strip approximately /" of plastic insulation from the end of the two solenoid wires supplied. Connect one end each of the solenoid wires to terminals & of the SD detector as shown. SD MAIN HOLD OPEN SOLENOID 0 INS NO. 000 PAGE of Rev. 0/

SD TO AUXILIARY SOLENOID CONNECTION NOTE: Make this connection the same time as the main hold open solenoid connection. Strip approximately /" of plastic insulation from the ends of the wires. Connect auxilliary hold open solenoid wires to & of SD detector. SOLENOID ATTACHMENT TO UL/ULC LISTED ALARM CONTROL PANEL AUXILIARY HOLD OPEN ELECTROMAGNET SD MAIN HOLD OPEN ELECTRO MAGNET Some applications may require input power to the hold open electromagnet to be supplied through a UL/ULC listed alarm control panel so the hold open electromagnet functions separately from the internal detector module. This application requires the alarm contacts of the SD detector and any remote detectors to be connected to the alarm contacts of the control panel. An alarm indication to the panel results in the loss of power to the hold open electromagnets in the related zone, which allows the doors to close. Wire main electromagnet to alarm control panel as illustrated. UL/ULC LISTED ALARM CONTROL PANEL POWER IN HOLD OPEN ELECTRO MAGNET VOLT ONLY 0 SD INTERCONNECTION. Up to () SD detectors, with or without connection to an auxiliary unit or remote area detector may be interconnected. This limitation applies only to interconnected units and assumes a power supply large enough to handle this load if the power supply is common to all units interconnected. Separate power supplies may be used for each SD detector while permitting the units to be interconnected. a. For units without connection to remote detectors, connect terminal # () between the units to be interconnected. Connect terminal # () between the units to provide a common for the interconnection. Additional units are wired in the same manner as unit # but no more than five () units can be interconnected. SD SD SD () () () 0 0 0 b. For units used in conjunction with remote area detectors, complete wiring connections as illustrated below. Heed caution note in SD TO AREA section of instruction sheet. Additional units are wired in the same manner as unit # but no more than five () units can be interconnected. Installations using a combination of SD detector modules with or without remote area detectors can be wired accordingly by substituting the wiring diagram from unit,, or in step a. above for unit,, or below. The vertical dashed lines indicate where one () diagram would be exchanged for another. C NO SD SD C NO () () C NO SD () 0 0 0 INS NO. 000 PAGE of Rev. 0/

SD TO AREA CAUTION: A remote open area detector can only be connected to a unit whose trouble relay contacts (# & #) are connected in a circuit for the purpose of obtaining an audible trouble signal in the event of a circuit fault. In the event that the unit is used for releasing service only, the trouble contacts are connected to the trouble circuit of a UL/ULC listed alarm control panel. This condition is satisfied by the four () and six () wire supervisory connections in the alarm initiation wiring section. Perform wiring connections as illustrated below. NOTE: The SD is wired as the E.O.L. (end of line) device for the remote detector. Therefore, it must act as the last item in the loop. SD VAC/DC POWER SUPPLY UL/ULC LISTED AUDIBLE SIGNAL APPLIANCE OR CONTROL UNIT 0 SD TO AUDIBLE SIGNAL APPLIANCE. Connect terminals # & # of a singular unit directly to a UL/ULC listed audible signal appliance or alarm control panel. SD 0 UL/ULC LISTED AUDIBLE SIGNAL APPLIANCE OR CONTROL UNIT. Installations with multiple units in a run must be connected to a UL/ULC listed audible signal appliance or alarm control panel as illustrated below. SD SD SD UL/ULC LISTED AUDIBLE SIGNAL APPLIANCE OR CONTROL UNIT 0 0 0 INS NO. 000 PAGE of Rev. 0/

SD TO ALARM INDICATOR LAMP Connect the positive wire of the remote alarm indicator lamp to terminal # of the detector module. Connect the negative terminal of the indicator lamp to terminal # of the SD detector. SD ALARM INDICATOR LAMP 0 ALARM INITIATION WIRING ( WIRE CLASS B & WIRE CLASS A). Make all connections as outlined previously for all units required by the job specifications.. Make all signal initiating connections as illustrated in the appropriate figure below. Note wiring differences for units with remote detectors vs. units without remote detectors. Dashed lines to return loop represent wires required for six () wire applications. These wires are omitted in four () wire applications.. Connections to only one () SD are shown below. CONNECTIONS FOR SIX () WIRE INSTALLATION CONNECTIONS FOR SIX () WIRE INSTALLATION SD RETURN LOOP SD RETURN LOOP UL/ULC LISTED INITIATING CIRCUIT ALARM RELAY UL/ULC LISTED INITIATING CIRCUIT 0 0 *EOL *EOL *EOL USED IN WIRE APPLICATIONS ONLY *EOL USED IN WIRE APPLICATIONS ONLY CONTINUED ON PAGE INS NO. 000 PAGE0 of Rev. 0/

ALARM INITIATION WIRING CON'T.. Connections for two () SD detectors would consist of detector () in figure below connected to detector () in the same manner as it is shown connected to detector (). Detector () would be deleted.. More than three () SD detectors are connected by inserting additional units with connections as shown for unit. The last unit in the run must be connected in the same manner as unit. CONNECTIONS FOR SIX () WIRE INSTALLATION RETURN LOOP SD () SD () SD () UL/ULC LISTED INITIATING CIRCUIT 0 0 0 *EOL *EOL USED IN WIRE APPLICATIONS ONLY CONNECTIONS FOR SIX () WIRE INSTALLATION RETURN LOOP SD () SD () SD () ALARM RELAY ALARM RELAY ALARM RELAY UL/ULC LISTED INITIATING CIRCUIT 0 0 0 *EOL *EOL USED IN WIRE APPLICATIONS ONLY. In four () wire installations, it is the responsiblity of the installer to supply and connect the E.O.L. resistor specified by the fire alarm control panel used. The E.O.L. resistor is only installed in the first unit of the run as illustrated. INS NO. 000 PAGE of Rev. 0/

SD SENSITIVITY TEST (ULC REQUIREMENT ONLY) Voltage output terminals are provided to measure the sensitivity of the smoke detector. With power applied to the detector, connect a volt meter to the two test terminals. The normal range is between.. Vdc. SENSITIVITY TEST TERMINALS FINAL INSTALLATION AND TEST Hold open position is preset at approximately 0. Loosen set screws using / inch hex wrench. Slide hold open device to desired position. Retighten set screws securely. HOLD OPEN DEVICE LESS HOLD OPEN ANGLE GREATER HOLD OPEN ANGLE HOLD OPEN FORCE ADJUSTMENT / HEX CLOCKWISE = STRONGER After installation is completed, check all connections. The LED will blink every seven () to ten (0) seconds to indicate the unit is operating properly. LED HOLD OPEN SET SCREWS / HEX Open door so slide shoe engages with hold open assembly. To test the detector, insert a small screwdriver into the slot in the light pipe of the detector. Turn counterclockwise and hold for ten seconds. The LED should remain continually red and allow the door to close. Turn light pipe clockwise to reset the detector. The LED will go off. Turn the light pipe to the normal position and the unit will resume blinking every seven () to ten (0) seconds to indicate that it is reset and functioning properly. Install detector cover. Slide tab of cover under end of detector and rotate into possession. Insert () 0 screw and tighten. TAB ROTATE SCREW INS NO. 000 PAGE of Rev. 0/

0 Snap cover onto backplate and attach cover caps to closer. COVER CAPS REMOVE TAB RIGHT HAND DOOR COVER REMOVE TAB () SPRING ADJ. END LEFT HAND DOOR () VALVE ADJ. END An auxiliary door stop (by others) must be installed to limit the maximum degree of door swing. Failure to do so may result in damage to the unit. SD MAINTENANCE The SD Detector has been designed to be as maintenancefree as possible. Normal airborne dust, however, can accumulate in the detector sensing chamber and cause it to become more sensitive. All detectors must be tested and cleaned at least once a year. Detectors in dusty environments must be tested and cleaned more often. Detectors must also be tested and cleaned immediately after a fire. Failure to maintain detectors may result in needless false alarms. Measure and record test voltage at test points RP and RP. This voltage is a small signal, DC voltage. Set meter to the volt scale. IMPORTANT: THE UNIT MUST BE TESTED AFTER THE INSTALLATION, BY THE END USER, TO ASSURE THAT THE DOOR CLOSER UNITS FUNCTION PROPERLY WHEN THE ALARM SYSTEM IS ACTIVATED. THE ENTIRE SYSTEM MUST ALSO BE TESTED PERIODICALLY AFTER THE INITIAL INSTALLATION TEST, IN CONJUNCTION WITH THE TESTING OF THE FIRE ALARM SYSTEM. THE END USER IS ALSO RESPONSIBLE FOR THE ADJUSTMENTS AND MAINTENANCE TO RETAIN THE SYSTEM IN WORKING ORDER. First, vacuum or blow off any loose debris on outside of cover. Then, remove the detector cover and screen assembly by rotating a flat screwdriver in slot (both sides) and pulling it straight up. Cover may be difficult to remove the first time. RP RP Vacuum all areas illustrated below, and then blow off same areas with compressed air. Before reassembling the detector, be sure all parts are free of debris. COVER FINS UNDER COVER SCREEN PHOTO CHAMBER INS NO. 000 PAGE of Rev. 0/

Replace cover and screen assembly. Measure and record test voltage at test points RP and RP. If the product is operating normally, and was cleaned effectively, the test voltage will be within the normal range of.. VDC. SMOKE TESTING Point the Smoke Detector Tester tube at the detector and release a burst of aerosol by depressing the nozzle for second. Give the detector sufficient time to respond. This may be up to 0seconds. Adapter Tube Smoke Detector Tester Detector If the detector is in an area where air velocities exceed 00 feet/minute, the detector may not alarm on the first try. This could be due to the signal processing feature of the detector. Signal processing is a feature that adds a time delay to each detector which effectively increases its stability. If this is the case, spray in repeated bursts of second at approximately to 0 second intervals. The total number of sprays should not exceed five (). If the detector does not alarm after consecutive sprays, it will be necessary to generate larger volumes of smoke to overcome the air flow dilution factor. This can be accomplished by burning paper or fabric in a metal can. DORMA accepts the use of Home Safeguard Smoke Detector Tester (Models H and S) if, and only if, it is used:. With the Model 0 Accessory.. With the new formula aerosol as identified by a date code, located on the bottom of the can, of 0 or later. (This date code can be read as first numeral = last digit of year so that a B0xxx = 0 and Bxxx =.). In accordance with the instructions stated above. If the preceding requirements are not met, the use of Smoke Detector Tester is unacceptable and DORMA cannot guarantee the proper operation of detectors that have been subjected to this product. Alternative methods of generating smoke/aerosol such as the Gemini 0 Smoke Generator Machine may be used to cause alarm at the detector's installed location. Set the generator to represent a %/ft to %/ft obscuration as described in the Gemini 0 Manual and apply aerosol until the unit alarms. If the Gemini unit is not available, cigarette, punk, or cotton wick are also acceptable means of generating smoke to test this detector. REMEMBER: Aerosol testing is only a "go no go" test and is not an acceptable means to determine the smoke detector's sensitivity. See NFPA E. HOME SAFEGUARD INDUSTRIES 00 FAX () 0 Garlisch Drive Elk Grove, IL 000 INS NO. 000 PAGE of Rev. 0/