The Refrigeration Cycle. Jerry Cohen President Jacco & Assoc.

Similar documents
Presented By: John Dolan, P.E.

System Components with ` Emphasis on Packaged Rooftop Application and Installation. Jerry Cohen President Jacco & Assoc.

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1.

For an administrative fee of $9.97, you can get an un-locked, printable version of this book.

Energy Use in Refrigeration Systems

Technical Development Program

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division

SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS

APS Chiller Seminar. Don Brandt, CEM-AEE, BEAP-ASHRAE ASHRAE and IEEE Life Member 3/16/2017

Instructors: Contact information. Don Reynolds Doug McGee Factory Tech Support

Chiller Plant Design. Julian R. de Bullet President debullet Consulting

Chapter-8 Capacity Control of Refrigeration Systems

SERVICE ASSISTANT OVERVIEW FDSI Online Training

Warm Case Troubleshooting Guide 9/18/2014

Series. Chillers and. Features: Application Flexibility Minimizes Installation Time and Reduces Cost

To accomplish this, the refrigerant fi tis pumped throughh aclosed looped pipe system.

SECTION 2 SAFETY, TOOLS AND EQUIPMENT, SHOP PRACTICES UNIT 10 SYSTEM CHARGING

GTX Series Thermal Xchange Cycling Refrigeration Dryers GREAT LAKES AIR ANDARD ELECTRONIC DRAIN 5 -YEAR WARRANTY F PRESSURE DEWPOINT

ORTEC HIGH CAPACITY REFRIGERATED AIR/GAS DRYERS

Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants

Air Conditioning Components

2. CURRICULUM. Sl. No.

Case 15 Refrigeration System for Chemical Fertilizer Plant Ammonia Storage

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES

How to Select and Size a Chiller

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

Air Conditioning Clinic. Absorption Water Chillers One of the Equipment Series TRG-TRC011-EN

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

Inverter scroll compressors VZH hybrid manifold

Best Practices for Applied Rooftop ` Systems - Application and. Jerry Cohen President Jacco & Assoc. Installation

CL SERIES Installation, Operation & Maintenance

Superheat charging curves for technicians

Smardt Oil-Free Chillers

Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

Chiller Manufacturer should have been manufacturing chillers utilizing magnetic bearing, oil free technology for more than 10 years.

LL Series Chillers and Outdoor Mechanical Rooms. Engineering Catalog

MAXIMUM SERIES. Maximum Series portable chillers can be used on a variety of process applications that require 20 F to 70 F chilled water.

CONTENTS. B. System Design and Performance Requirements

Series PACKAGED ROOFTOP UNITS, HEAT PUMPS AND OUTDOOR AIR HANDLING UNITS. Features:

Some of these procedures need to be performed to conform to requirements of the Clean Air Act.

System Drop-in Tests of R-134a Alternative Refrigerants ARM-42a and R-1234ze(E) in an Air- Cooled Screw Chiller and a Water-cooled Centrifugal Chiller

RECORD SUBMITTAL COVER SHEET

Otherwise, you can continue reading the file on the following pages.

MODELS LIST. Nominal Capacity RT

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler

CL SERIES Installation, Operation & Maintenance

Typical Piping Diagram

ORTEC INDUSTRIAL FLUID CHILLERS FC SERIES ( TONS) Compressed Air, Gas & Fluid Technologies. i e n d. l y. t a. R e. f r. i g e.

CTI Sponsored Educational Program

EN aquatech.piovan.com

Refrigeration and Air Conditioning

Inverter scroll compressors VZH hybrid manifold

30GT FLOTRONIC AIR-COOLED CHILLERS

Method to test HVAC equipment at part load conditions

PDF Created with deskpdf PDF Writer - Trial ::

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES UNIT OBJECTIVES 3/22/2012

Service Step by Step Trouble-Shooting Check-List

A Series Inertia Compressor Applications. Application Bulletin 115

Math. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb.

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM

For Modules: ASM002X, ASM003X, ASM005X, ASM008X, ASM010X, ASM015X, ASM020X, ASM030X. Air Cooled Medical Chiller Product Data Catalog

Magnetic Bearing Technology: Achievements in Higher Efficiency

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency

Class 1: Basic Refrigera0on Cycle. October 7 & 9, 2014

Residential Piping and Long Line Guideline

Partial Load Performance Of Refrigeration System

Appendix A. Glossary of Common Terms

CF Series. Installation, Operation, & Maintenance. Condenser and Condensing Units WARNING

MAC-120HE-03 Air-Cooled Chiller

Product Data. Features/Benefits. 07DA, DB 07EA, EB, ED Condensing Units. 06D, 06E Compressors. 3 to 40 Nominal Tons

Product Data. Features/Benefits. 38AH Commercial Air-Cooled Condensing Units 50/60 Hz. 20 to 130 Nominal Tons (63 to 390 Nominal kw)

GP SERIES Packaged Chillers

TEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller

Commercial Refrigeration

The Book of AERMEC NRL Sequence of Operation

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

Series. Packaged Rooftop Units, heat pumps and Outdoor air handling Units. Features:

TITAN SERIES Complete Central Chiller & Pump Tank Package 20 to 70 Tons 20 F to 70 F

Use this Construction/HVAC Glossary to answer the questions below.

30GN FLOTRONIC II AIR-COOLED CHILLERS

MECHANICAL ENGINEERING ME.2017 FUNDAMENTAL OF REFRIGERATION AND AIR CONDITIONING. Sample Questions and Answers

Product Data. Features/Benefits. GEMINI 38AKS Commercial Air-Cooled Split Systems 50/60 Hz. 25 to 40 Nominal Tons (82.8 to 127.

HVAC Service Technicians Training Center

JCseries EVAPORATIVE CONDENSER. engineering data

Refrigeration/Troubleshooting Manual

APOGEE Open Processor with McQuay Microtech Driver: European Reciprocating Chiller (CR1)

Calhoon MEBA Engineering School. Study Guide for Proficiency Testing Refrigeration

Evaporative Condenser Engineering Manual

Case 8 Basic Performance of Screw Compressor

MECHANICAL SERVICES 101. Ian White

A Treatise on Liquid Subcooling

Unit Dimension. Unit Nomenclature DEHUMIDIFIER NOMENCLATURE UNIT VOLTAGE: 2: 240/1/60 5: /3/60 9: 480/3/60 8: 600/3/60

AC SYSTEM CONFIGURATION- CENTRAL CHILLER PLANT

Best Practices for Applied Rooftop ` Systems, Applications and. Jerry Cohen President Jacco & Assoc. Installation

LC Series. Installation, Operation & Maintenance. Air-Cooled Condenser Chillers WARNING WARNING WARNING

LF Series. Installation, Operation, & Maintenance. Air-Cooled Condenser Chillers WARNING WARNING WARNING

Centrifugal Chiller. GFG-S/SIT Series GXG-S/SIT Series GSG-S/SIT Series

APOGEE Open Processor with McQuay Microtech Driver: Series 200 Centrifugal Chiller

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

Transcription:

The Refrigeration Cycle Jerry Cohen President Jacco & Assoc.

Basic Refrigerant Cycle P/h Chart Compressor Options Condenser Options Head Pressure Control Thermal Expansion Evaporator Options Lift Evaporative Condensing Water Treatment A Word From Our Sponsor Agenda

Basic Refrigeration Cycle

P/h Chart - Isotherm

P/h Chart

Superheat & Subcooling Defining Superheat Superheat is defined as the difference between the temperature at which the refrigerant boils at the given pressure in the evaporator, and the temperature of the refrigerant gas as it leaves the evaporator. In essence, it's how much extra temperature the refrigerant picks up after it has boiled. Heating of a gas, at a constant pressure, above the point at which it has boiled. Defining Sub-Cooling Sub-Cooling is defined as the difference between the temperature at which the refrigerant condenses at the given pressure in the condenser, and the temperature of the liquid refrigerant gas as it leaves the condenser. In essence, it's how much extra temperature the refrigerant cools after it has condensed. Cooling of a liquid, at a constant pressure, below the point at which it was condensed.

P/h Chart

What is a Compressor?

Scroll Compressor Limited to ~ 25 HP Tandem Compressor Options With or Without VFD

Digital Scroll Compressor Digital Scroll

Screw Compressor Limited to ~ 500 HP With or Without VFD

Reciprocating Compressor Limited to ~ 100 HP

Centrifugal Compressor Virtually Unlimited With or Without VFD Non Positive Displacement compressors raise the pressure and temperature of the refrigerant by converting kinetic energy into pressure. pressure

Centrifugal Compressor Oil Free Magnetic Bearing Centrifugal With VFD Limited to 75 & 150 HP

Magnetic Bearings Oil Free Magnetic Bearing Centrifugal Limited to 75 & 150 HP

Hot Gas Bypass

Hot Gas Bypass

Fraction of Full Load Power Partial Load Ratio

Condenser Air Cooled Given 95 db/75 wb 125 Condensing Temperature

Condenser Water Cooled Given 95 db/75 wb 105 Condensing Temperature

Condenser Evaporative Cooled Given 95 db/75 wb 105 Condensing Temperature

Why Head Pressure Control Variable Speed Compressors Fluctuating Ambient Conditions Energy Savings Assure Proper TXV Operation

Common Head Pressure Control Condenser Fan Cycling Variable Speed Condenser Fan Picture Cooling Tower w/ VFD

Low Ambient Head Pressure Control Flooded Condenser

Capillary Tube, Fixed Orifice, Cheap but Effective Thermal Expansion

Pressure Thermal Expansion Old and Stable Technology

Electronic Thermal Expansion Very Controllable

Evaporator Air Cooled Given 55 Degree LAT 45 Degree Suction Temperature

Evaporator Chilled Water Given 55 Degree LAT 45 Degree Chilled Water/Glycol 35 Degree Suction Temperature

Heat Pump Refrigeration Cycle

Pump Out vs. Pump Down The purpose of Pump Down and Pump Out is to minimize the effects of migration, which can result in a flooded start on the next startup.

Pump Out Also known as a "one time pump out", is conducted by closing a solenoid in the liquid line while the compressor is still running, all of the refrigerant in the system downstream of the solenoid is removed. The compressor is shutdown by a low pressure control, and remains off until the next call for cooling which opens the solenoid valve and closes the contacts for the compressor. Thus the compressor pumps out the system after each running cycle, then remains off until the next call for cooling.

Pump Down Also known as "continuous pump down", is conducted exactly the same way as pump-out with the exception that the call for cooling ONLY controls the solenoid. Thus, during a normal running cycle, when demand is met, the solenoid is closed. The compressor pumps out all of the refrigerant downstream of the solenoid then shuts of on a low pressure control. The difference being that the compressor is allowed to restart any time the low pressure control makes, thus keeping the suction side of the system pumped down continuously. This usually comes into play if there is a leaking pump down solenoid.

Accumulators and Receivers A Receiver is a vessel for holding refrigerant liquefied by the condenser. An Accumulator is a vessel for preventing liquid slugging of the compressor.

Condenser/Evaporator Balance

Refrigerant Field Piping

Evaporative Condensing Water Cooled WITHOUT the Condenser Pump

The Compressor is a Pump Air Cooled 35 Suction & 125 Condensing Water & Evaporative Cooled 35 Suction & 105 Condensing

Refrigerant Pressure/Temperature Chart HFC-134a 105 Condensing Temperature = 134.9 PSIG HFC-134a 125 Condensing Temperature = 184.5 PSIG HFC-410a 105 Condensing Temperature = 339.9 PSIG HFC-410a 125 Condensing Temperature = 444.5 PSIG

TurboCor Oil Free Magnetic Bearing Compressor

120 ton Evaporative Condensing Chiller with Oil Free Centrifugal Compressor 120 Ton Unit Ratings

300 ton Evaporative Condensing Chiller with Oil Free Centrifugal Compressor 300 Ton Unit Ratings

540 Ton Unit 540 Ratings Ton Unit Ratings 540 ton Evaporative Condensing Chiller with Oil Free Centrifugal Compressor Compressor IPLV =.42 kw/ton Unit IPLV =.55 kw/ton

540 Ton Evaporative Condensing Chiller

Aaon Evaporative Condensing Chiller

Aaon Rooftops w/ Oil Free Magnetic Bearing Centrifugal Compressors - from 90-300 Tons

Evaporative Condensing Water Treatment similar to but however

Water Treatment As recirculated water evaporates in an evaporative condenser, the dissolved solids in the makeup water continually increase as more water is added. Continued concentration of these dissolved solids can lead to scaling and/or corrosion problems. In addition, airborne impurities and biological contaminants are often introduced into recirculated water. If these impurities are not controlled, they can cause sludge or biological fouling. Simple blowdown (discharging a small portion of the recirculating water to a drain) may be adequate to control scale and corrosion on sites with good-quality makeup water, but it does not control biological contaminants such as Legionella.

Langelier Saturation Index (LSI) The potential for scaling is calculated using the Langelier Saturation Index (LSI). This is a calculated parameter to predict the calcium carbonate stability of water using ph as the main variable. Langelier Index Description General Recommendation Risk -5 Severe Corrosion Treatment Essential Plumbing Annihilation -4 Severe Corrosion Treatment Essential Plumbing Annihilation -3 Moderate Corrosion Treatment Recommended Long-term Pipe Death -2 Moderate Corrosion Treatment Recommended Possible Trouble -1 Milder Corrosion Treatment May Be Needed The Long Finger? -0.5 Milder Corrosion Treatment May Not Be Req. Hope All Goes Well -0.3 None Mild Corrosion Probably No Treatment Looking Good 0 Near Balanced No Treatment Just right 0.3 Some Faint Coating Probably No Treatment Looking Good 0.5 Some Mild Coating Treatment May Not Be Needed Hope All Goes Well 1 Mild Scale Coating Treatment May Be Needed The Long Finger? 2 Moderate Coating Treatment May Be Needed Possible Trouble 3 Moderate Coating Treatment Advisable Long-term Pipe Death 4 High Scale Coating Treatment Very Advisable Plumbing Annihilation

Traditional Evaporative Condenser Langelier Saturation Calculator WB = 75 DT =160F SCT = 105F SET = 45 F

Evaporative Condenser w/ De-Superheater

Evaporative Condenser w/ De-Superheater

Evaporative Condenser w/ De-Superheater Benefits 22-100% Less Water usage 22-100% Less Chemical usage Lower energy consumption due to reduced fouling and more efficient heat transfer Reduced tendency to form scale in the wetted coil section Longer condenser fan motor life due to reduced relative humidity of ambient air Unit can run dry

What Happens on a Warm Winter Day? At 70 DB the system will operate at ~60% capacity.dry

Thank You Jerry Cohen President Jacco & Assoc.