User Guide. Shaft Speed 6 6-Channel Shaft Speed Monitor. Calibration and Operation Software Reference UDJ701-5

Similar documents
10yr O2NE & Safe-Ox. User Manual

Software Version 2.01 LEVEL MONITOR MODEL 220

C-Bus Four Channel Analogue Output Unit Installation Instructions

ND4000 Manual Marine Hydraulics

MS200/300/400 Magnetic Stirrer. Instruction Manual

Quantum Production Limited

APS-1650 LEVEL SENSOR INSTALLATION AND CALIBRATION

MS200/300/400 Hotplate Magnetic Stirrer Instruction Manual

Analox Safe-Ox/Safe-Ox He

C-Bus Four Channel General Input Unit Installation Instructions

VT4810 SINGLE / DUAL ZONE CONTROLLER INSTALLATION MANUAL

LOUP II DRILL MONITOR OPERATION MANUAL. SOFTWARE v45

MWS3A-PRM. Ceiling microwave presence/absence detector. Product Guide. Overview. Features

Ceiling PIR presence detector DALI / DSI dimming. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. PIR Sensor.

Installation Guide. Ceiling PIR Detector (311) Features and Connections

FLOW CONTROLLER TYPE S/601

Commercial in Confidence

Operators Manual. E15 Seeder Console Air Seeder Monitor A600 R1.3 V2.0.18

Ax60+ Multi-Gas. Service Manual

MWS6-PRM. Ceiling microwave presence/absence detector. Product Guide. Overview. Features

Accessible Toilet Alarm

Programmable Towel Radiator Manual

Programmable Room Thermostat Installation Instructions

Sentry G3 Machinery Protection Monitor

1U ULTRA Compact System

UPON COMMENCMENT OF INSTALLATION IT IS OF PARAMOUNT IMPORTANCE THAT THE STEP BY STEP GUIDE (INCLUDED) IS FOLLOWED COMPLETELY

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

ANALOX SENSOR TECHNOLOGY LTD ANALOX DD1101 INSTALLATION & OPERATION MANUAL

Ceiling PIR HS presence detector. Product Guide. Overview. Features

Tachometer/Hourmeter/Trip. Installation and Operation Manual

Product Guide. Ceiling microwave presence detector DALI / DSI. Microwave Sensor. IR Receiver. Light Level Sensor. Status LEDs.

Sentry G3 Machinery Protection Monitor

Ceiling Microwave presence detector - DALI / DSI 12-24V AC/DC. Microwave Sensor. IR Receiver. Light Level Sensor. Status LEDs.

Analox 1000 Series. User Manual. Analox Sensor Technology Ltd. 15 Ellerbeck Court, Stokesley Business Park North Yorkshire, TS9 5PT, UK

Quick Setup Guide for IntelliAg Model NTA607HD

CellarSafe. Carbon Dioxide and Oxygen Safety Monitor

CORNELL Emergency Response Systems

USER MANUAL CEF AP28 CONTROL PANEL

RS Pro Infrared Temperature Sensor

Dry Contact Probe DCP (#30008)

EBDSPIR-PRM-VFC & EBDSPIR-PRM-VFC-NC

PPAD-C-230V. Ceiling PIR presence/absence detector. Product Guide. Overview. Features

COMMANDER 150. User Guide Universal Process Indicator A1

High bay PIR presence detector DALI / DSI dimming. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. IR Receiver

Ceiling PIR HS presence detector 1-10V, low temperature. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. IR Receiver

SWITCHLITE MRE SLD MAN SWITCHLITE MRE SLD IP55

High bay PIR presence detector 1-10V dimming. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. IR Receiver

Pendant V3.00a Installation Guide

Electronic Dual Cylinder Thermostat Installation Instructions

2604 Controller Melt Pressure Controller

F PC and AO OUTPUT BOARDS INSTRUCTION MANUAL. Blue-White. Industries, Ltd.

GUARDIAN CX10 PRIORITY/EVACUATION INTERFACE USERS MANUAL

5U Compact System. Installation Manual V1.0. Manufactured by Enatel Ltd. 321 Tuam Street PO Box Christchurch New Zealand

4 & 8-POINT ANNUNCIATORS Instruction Manual

Snifter. User Manual. Distributor

DataSheet. Thermocouple Logger

RF Programmable Room Thermostat Installation Instructions

Tinytag Plus LAN Data Logger with Temperature & Relative Humidity Probe (-25 to +85 C/0 to 100% RH) Standalone. Tinytag Connect

Door Release Power Supply

DataSheet. Thermocouple Logger

RangerNET Network Ready Constant Monitor Model CM2815

DWYER INSTRUMENTS, INC. P.O. BOX 373 MICHIGAN CITY, INDIANA 46360, U.S.A. Series 670 Hood Monitor. Bulletin AV-670

PD154 & PD158 VIGILANTE II ANNUNCIATORS Instruction Manual

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

ProStar 325 UV-Vis Detector

NT DUAL CHANNEL DISPLAY. User Guide

EBDSPIR-PRM-2CH, EBDSPIR-PRM-2CH-NC

Alarm Tone Generator Model AG17

SENSA MRE DDM MR

INSTRUCTION MANUAL & 8200 Monitor. Manual Issue 06

Using the GammaRAE II Personal Radiation Detector

PowerCommand FT-10 Network LONWORKS System Annunciator

ENGINE MONITOR VOTT MODEL: YEAR WARRANTY

Dual Technology Wall Switch Occupancy Sensor. Manual & Specification

NEVER ACTIVATE THE STROBE WITH THE PCB OUT OF ITS PROTECTIVE CASE. EXTREME CARE IS ADVISED TO REMOVE THE RISK OF ELECTRIC SHOCK.

G-TECTA Cellaguard Carbon Dioxide and Oxygen Fixed Monitors

C2 Compact Range Installation & Programming Manual

FDA241, FDA221 Siemens ASD

1 MXS Strada: connect and configure alarm LEDs

MPAD-C 12-24V. Ceiling microwave presence/absence detector 12-24V AC/DC. Product Guide. Overview. Features

Ax60+ Kiosk Option. Quick Start Guide

Mounting bezel Retaining spring. Detects movement within the detection range, allowing load control in response to changes in room occupancy.

Dual Technology Wall Mounted Occupancy Sensor. Manual & Specification

18W Round LED Wall/Ceiling Light with Microwave Sensor

3. Intended use. 4. Function. 1. Product characteristics. 2. Safety. Functional description. Channel A light. Motion detector

Installation Manual. Premier IXP-W INS538

USER MANUAL Digital CO Monitor Model CO30

Sentry LIQUID LEVEL GAUGE MODEL 200 or 200C OWNER MANUAL REV 1.7 SEPT08 PAGE 1 OF 12

Instruction Manual SCD24. Read this document prior to installation. Contents

ANEMOMETER 4403-RF-BAT

Manual# User s Manual. DCU 410/408 Engine Control Unit RP 410 Remote Panel FW 2.3

VITMR-EBDSPIR-PRM. PIR Presence/Absence Detector IR with Ceiling Rose. Product Guide. Overview. Features

Gas Measurement Instruments Ltd User Handbook

AQUARIUS 45 MARINE SERVICE MANUAL

Siemens aspirating smoke detector (ASD) for the addressed FDnet/C-NET detector line or for standalone operation

SINGLE SPEED SYRINGE PUMP

installation guide installation guide electronic intelligent timer thermostat

OPERATION MANUAL Part No. MIL8001V4C

Operations Manual DS 220. Docking Station for Micro IV

MWS5. Miniature Microwave Presence Detector (standalone) Product Guide. Overview. Features

Transcription:

Electro-Magnetic Compatibility (EMC) This product complies with Council Directive 89/336/EEC when installed and used in accordance with the relevant instructions. Service and Technical Support PLEASE CONTACT YOUR NEAREST DISTRIBUTOR If unknown then fax: 44 (0) 1453 733322 Copyright RDS Technology Ltd 2002 Document number S/DC/500-10-356-1: Issue 1 : 9/7/02 \UK356-1.DOC User Guide Shaft Speed 6 6-Channel Shaft Speed Monitor Calibration and Operation Software Reference UDJ701-5 1

Contents Overview 3 Calibration... 3 The Control Switches 4 RPM Channels 5 Programme a Low Speed Alarm Threshold... 5 Enable/Disable Alarm Function... 6 Set Shaft Speed Sensor Cal Factor... 6 Wiring Connections Shaft Speed 6 8 Connections for Cable S/CB/327-1-064... 9 2

Overview The RDS Shaft Speed 6 has an illuminated 4-digit display with 6 display functions, monitoring and displaying the rotational speed (RPM) of up to 6 shafts. Each shaft speed channel has a programmable low-speed alarm. If any shaft speed drops below the programmed threshold, the display will flash the speed of that shaft, and also sound an audible alarm (an external audible alarm is optional) for 5 seconds. A second, continuous alarm output (O/P 2) is also triggered, which can be utilised for example, to physically inhibit further operation, or otherwise compensate for the alarm condition. This alarm output remains on until the alarm condition is resolved. The alarm function on any particular channel can be easily disabled/re-enabled as necessary during normal operation. The system comprises : Head unit 12V power supply kit. Individual Shaft Speed Sensor kits as required. Qikmate to AMP connector cable Pt. No. S/CB/327-1-064 Calibration NOTE: Each shaft speed channel in operation must be programmed with a calibration factor to enable the correct RPM display. This factor is the number of pulses received from the sensor per revolution of the shaft. This varies according to the type of sensor / number of sensor magnets installed. The sensor must provide a pulse rate of more than 1 pulse per second for the instrument to work properly. For slow turning shafts, a range of magnet carriers are available with up to 8 magnets fitted. For very slow turning shafts, a shaft encoder can be fitted, giving up to 360 pulses per rev. 3

The Control Switches The front panel has five buttons. Only the middle three are normally used. Channel Indicator Not Used Not used PROGRAM SWITCH Select the channel then PRESS and HOLD to display the calibration factor. Continue holding the CAL button and programme the cal factor using the button. SELECT CHANNEL SET ALARM Select the channel then PRESS and HOLD to display the alarm speed. Continue holding the SET button and programme the alarm threshold using the button. Or Hold and then press the CAL button to enable/disable the alarm function 4

RPM Channels There are six RPM channels. Press the button to select a channel. For a shaft speed up to 100rpm, the speed is displayed to the nearest 1 rpm. For a shaft speed above 100 rpm the speed is displayed to the nearest 10 rpm. Programme a Low Speed Alarm Threshold NOTE: The default alarm speed is zero, i.e. the alarm is disabled. 1. Select the appropriate channel. 2. Press and hold the SET button and the display will show the current alarm threshold setting. 3. Continue holding the SET button and 4. PRESS to select the digit or decimal point to change. 5. HOLD to change the selected digit (or move the decimal point). Figure 2: Display Alarm Speed HOLD 6. RELEASE to select the next digit and repeat as above, otherwise simply release both buttons. The instrument will then return to the normal display mode. HOLD Figure 3: Set Alarm Speed 5

Enable/Disable Alarm Function The alarm function on any particular channel can be easily disabled/re-enabled as necessary during normal operation, without you having to re-programme the threshold figure each time. 1. Select the appropriate channel. 2. Press and hold the SET button and press the CAL button to enable/disable the alarm function. The display will alternate between zero and the set threshold. 3. Release the CAL button when the appropriate figure is displayed Figure 4: Enable/Disable Alarm HOLD Set Shaft Speed Sensor Cal Factor In order for RPM to be displayed correctly, The RPM Sensor Factor must be programmed correctly. The factor is the number of pulses received by the instrument per revolution of the sensed shaft, e.g. for measuring Engine RPM, PTO Speed, Shaft Speed, Fan Speed etc, depending on the particular installation. The default setting is 1 pulse per rev (p.p.r), which is OK in the case of a magnetic sensor with a single magnet on the sensed shaft. For an 8-magnet carrier, the cal. Factor is 8.000. In other cases, perform the following calibration procedure. 1. Run the sensed component at a known speed. If necessary measure this speed using a hand-held tachometer. 2. At the same time have someone note the RPM displayed on the instrument. 6

3. Calculate the new calibration factor New Factor = Initial Factor x Displayed Speed Actual Speed 4. Select the appropriate channel. 5. Press and hold the CAL button and the display will show the current Cal. factor. 6. Continue holding the CAL button and 7. PRESS to select the digit or decimal point to change. 8. HOLD to change the selected digit (or move the decimal point). 9. RELEASE to select the next digit and repeat as above, otherwise simply release both buttons. The instrument will then return to the normal display mode. Figure 5: Display Cal. Factor HOLD Figure 6: Set Cal. Factor 7

Wiring Connections Shaft Speed 6 A 12-way Qikmate to 2 x 11-way AMP extension cable Pt No. S/CB/327-1-064 is supplied to connect to the sensors, power supply etc. Optional 3metre extension cable for trailed implement Tractor wiring Implement wiring Refer to the Work measurement Installation manual S/DC/500-10-261 for details on fitting sensors / cutout switches etc. 8

Connections for Cable S/CB/327-1-064 CONNECTOR RED KEY COLOUR FUNCTION +V RED +V IN 0V BLACK 0V IN (+ 3 x COMMON 0V FOR SENSORS) Vss RED NOT USED IP6 WHITE RPM 6 +V OP3 GREY NOT USED OP2 ORANGE ALARM OUTPUT CONTINUOUS +V OP1 TURQUOISE AUDIBLE ALARM PULSED +V CONNECTOR GREEN KEY COLOUR FUNCTION 0V PINK/BLACK 5 x COMMON 0V FOR SENSORS IP5 BLUE RPM 5 +V IP4 BROWN RPM 4 +V IP3 PURPLE RPM 3 +V IP2 YELLOW RPM 2 +V IP1 GREEN RPM 1 +V NOTE: There is no provision for WCI connection on cable S/CB/327-1-064 In some cases for installations on trailed implements, in order to make all the necessary connections between the tractor and implement using the extension cable S/CB/327-1-065, you may need to switch one or more terminal blades between the two connectors. Carefully insert a suitable thin-bladed screwdriver into the appropriate blade housing and lever the locking tab slightly inwards. The blade can then be withdrawn from the rear of the connector housing. The tabs will probably need to be levered back out so that the blade will lock properly when re-inserted. 9

Issue 1: 19/6/02 Original Issue 10