0XV Variable Speed ir-cooled Screw Chiller Nominal cooling capacity 7~85KW
Turn To The Experts Inheriting a rich legacy of innovation including inventing modern air-conditioning, Carrier has been a global leader in innovations for Heating Ventilation ir Conditioning (HVC) and refrigeration solutions. Carrier is a part of UTC Climate, Controls & Security, a unit of United Technologies Corp., a leading provider to the aerospace and building systems industries worldwide. With a broad portfolio of advanced technical patent awards, our global R&D center in Shanghai develops innovative heat, ventilation and air-conditioning (HVC) solutions. In 998, Time magazine named Dr. Carrier oneof its 0 most influential builders and titans of the 0 th century.
Nomenclature 0XV07 PT05/54 Unit option PT00 PT00 PT0 PT05 PT00 PT04 PT09 PT04 PT07 PT48 PT48C PT48D PT49 PT56 PT58 PT54 PT8 PT84 PT99 PT0 PT PT PT lygold PoluL Golden fins High static fan Low noise IP54 protection Evaporator anti-freezing Discharge Valve.6MPa Evaporator Reversed water connections J-us protocol acnet gateway Lon-Talk protocol acnet IP protocol Energy management module (EMM) 7" touch screen Cu/l condenser coils EMC Clasification C Electric Plug 8mm evaporator insulation lue fins Conformance with ustralian regulations 5% THD 0% THD Design Series Unit Model ir cooled variable speed screw chiller Operating Range Evaporator Min. temperature Max. temperature Entering water temperature (at start) - 45 Entering water temperature (operating) 6.8 Leaving water temperature (operating). 5 Condenser Min. temperature Max. temperature Outdoor air temperature -0* 46 * When OT<0, PT04 is mandatory 0XV0/07 0XV05/068 0XV09 0XV086/0/6/ /0/40 Outdoor air temperature, 55 50 46 44 0 0-0 Outdoor air temperature, 55 50 46 44 40 0 0-0 Outdoor air temperature, 55 48 46 44 40 0 0-0 Outdoor air temperature, 55 50 46 44 40 0 0-0 -0-0 -0-0. 0 5. 7 0 5. 7 0 5. 5 7 0 5 Evaporator leaving water temperature, Evaporator leaving water temperature, Evaporator leaving water temperature, Evaporator leaving water temperature, Part load Operating range, standard unit elow 0 air tempature the unit must either be equipped with evaporator frost protection option (4), or the water loop must be protected against frost by using a frost protection solution (by the installer)
Introduction The quaforce chillers with Greenspeed Intelligence are the premium solution for commercial and industrial applications where installers, consultants and building owners require superior reliability and optimal performances, especially at part load. 0XV are designed to meet current and future requirements in terms of energy efficiency, versatility and operating sound levels. Through the optimised combination of proven best-in-class technologies that include: - Exclusive screw compressors with Greenspeed Intelligence - an evolution of the proven traditional Carrier twin-screw compressor design - The new Touch Pilot control - Condenser fans with Greenspeed Intelligence - Mechanically cleanable flooded evaporator Furthermore, with 0XV, Carrier offers its unique expertise and know-how to take care of the machine long after the sale. With the new CRRIER CONNECT system in fact, energy and facility managers and end-users in general can rely on the most qualified remote monitoring services. Low Energy Consumption The air conditioning system could use 0%~40% of anual buidling engery consumption, 0XV helps customer involved in green building certification with Greenspeed inveter -driven technology. With advanced unit mounted inverter-driven technolgy, the 0XV is designed for high performance both at full load and at part load. Exceptional efficiency performance at part load which is up to 5.7. Cooperating with primary viarable flow system, the system efficiency would be further enhanced by synchronized control of chillers and pumps. The high energy efficiency is reached thanks to: - Inverter driven twin-rotor screw compressors allowing precise capacity matching of buliding load and reducing unit power input, especially at part-load. - Inverter driven fan motors minimizing power consumption while granting optimum air flow. - Flooded shell-and-tube evaporator characterized by high efficiency of heat exchange. - Electronic expansion device permitting operation at a lower condensing pressure and improved utilization of the evaporator heat exchange surface. - Economizer system with electronic expansion device increases cooling capacity by 0% and efficiency by 4%. Optimised electrical performance: - Negligible start-up current (value is lower than the maximum unit draw) - EMC compliancy with Class requirements of the EU standard EN6800- Enviromental care HFC-4a refrigerant with zero ozone d Efficiency (kw/kw) Start-up current() Leak tight refrigerant circuits: - No capillary tubes and flare connection - Verification of pressure transducers and refrigerant charge - Discharge line shut-off valve and liquid li (option) 00% 75% 50% 5% Chiller load Time(s) 0X085 0XV086 Fixed speed 0XV
High Reliablity and Easy Service 0XV offer increased global performance as well as Carrier's acclaimed product quality and reliability. Screw compressors with Greenspeed Intelligence: - Industrial-type screw compressors with oversized bearings and motor cooled by suction gas - Specifically sized inverter for each compressor motor ensures reliable operation and easy maintenance - ll compressor components assembly are easily accessible on site minimising down-time Fans with Greenspeed Intelligence: - 4th generation of Flying ird fans equipped with inverter-driven asynchronous motors - Specifically sized inverter optimize air flow management reducing cost - Easily accessible inverter of fan speed control for easy service Evaporator: - Carrier designed flooded evaporator with mechanically cleanable water tubes - Electronic paddle-free flow switch to ensure prompt alarm in case of poor liquid flow rate - Thermal insulation with aluminum sheet finish (option) for perfect resistance to external aggression (mechanical and UV protection) Two independent refrigerant circuits ensures system redundancy in case one fails* uto-adaptive control: - Control algorithm prevents excessive compressor cycling (Carrier patent) - utomatic compressor unloading in case of abnormally high condensing pressure. If condenser coil fouling or fan failure occurs, the quaforce continues to operate, but at reduced capacity. Exceptional endurance tests: - Partnerships with specialised laboratories and use of limit simulation tools (finite element calculation) for the design of critical components - Transport simulation test equivalent to 000 km by truck under harsh conditions - Salt mist corrosion resistance test in the laboratory for increased corrosion resistance * vailable for 0XV068/086/0/6//0/40 Minimised Operating Sound Levels The inverter technology used for the compressor and fan motors minimises noise levels at part load operation. When the unit is delivering 5% for example, compressors and fans are running at minimum speed which implies lower noise. epletion potential s are used temperature sensors without transferring ne service valve for simplified maintenance Standard unit features include: - Discharge dampers integrated in the oil separator (Carrier patent) - Silencer on the economizer return line - Condenser coils in V-shape with an open angle, allowing quieter air flow across the coil Fix speed screw unit - Low-noise 4th generation Flying ird fans, made of a composite material (Carrier patent) which do not generate intrusive low frequency noise. - Rigid fan mounting preventing start-up noise (Carrier patent) 0XV with option05 Multiple options are available to further reduce the global sound level. Sound pressure level 0 0 40 60 80 00 uilding load (%) 4
Technical Insight Touch Pilot Control General Features New innovative smart control features: - n intuitive and user-friendly, 5" colored interface (7" as option) - Screen-shots with concise and clear information in local languages - Complete menu, customized for different users (end user, service personnel and Carrier-factory technicians) - Easy access to the controller box with touch screen mounting to ensure legibility under any lighting conditions - Safe operation and unit setting: password protection ensures that unauthorized people cannot modify any advanced parameters - Simple and smart intelligence uses data collection from the constant monitoring of all machine parameters to optimise unit operation - Night-mode: Cooling capacity management for reduced noise level. Energy management: - Internal time schedule clock controls chiller on/off times and operation at a second set-point - The DCT (Data Collection Tool) records the alarms history to simplify and facilitate service operations Remote Management (Standard) Units with Touch Pilot control can be easily accessed from the internet, using a PC with an Ethernet connection. This makes remote control quick and easy and offers significant advantages for service operations. quaforce with Greenspeed technology is equipped with an RS485 serial port that offers multiple remote control, monitoring and diagnostic possibilities. When networked with other Carrier equipment through the CCN (Carrier Comfort Network - proprietary protocol), all components form a HVC system fully-integrated and balanced through one of the Carrier s network system products, like the Chiller System Manager or the Plant System Manager (optional). The 0XV also communicates with other building management systems via optional communication gateways. The following commands/visualizations are possible from remote connection: - Start/Stop of the machine - Dual set-point management: Through a dedicated contact is possible to activate a second set-point (example: unoccupied mode) - Demand limit setting: To limit the maximum chiller capacity to a predefined value - Water pump control: These outputs control the contactors of one/two evaporator water pumps - Operation visualization: Indication if the unit is operating or if it s in stand-by (no cooling load) - larm visualization Remote Management (EMM option) The Energy Management Module (EMM) offers extended remote control possibilities: - Room temperature: Permits set-point reset based on the building indoor air temperature (if Carrier thermostat are installed) - Set-point reset: Ensures reset of the cooling set-point based on a 4-0 m or 0-0 V signal - Demand limit: Permits limitation of the maximum chiller power or current based on 0-0 V signal - Demand limit and : Closing of these contacts limits the maximum chiller power or current to two predefined values - User safety: This contact can be used for any customer safety loop; opening the contact generates a specific alarm - Ice storage end: When ice storage has finished, this input permits return to the second set-point (unoccupied mode) - Time schedule override: Closing of this contact cancels the time schedule effects - Out of service: This signal indicates that the chiller is completely out of service - Chiller capacity: This analogue output (0-0 V) gives an immediate indication of the chiller capacity - lert indication: This volt-free contact indicates the necessity to carry out a maintenance operation or the presence of a minor fault - Compressors running status : Set of outputs (as many as the compressors number) indicating which compressors are running. 5
Technical Insight Greenspeed intelligence Inverter- driven screw compressor The new generation of Carrier inverter-driven screw compressors benefits for Carrier s long experience in the development of twin-rotor screw compressors. The design of the thunderbolt compressors is based on the successful 06T screw compressor, core of the well-known quaforce series. Furthermore, it is designed for high performance both at full load and part load (IPLV/NPLV*). Micro-class manufactured screw rotors mesh precisely with high durability. Oversized bearing and motor allow wide cooling capaicty range. Inverter-driven Flying ird IV fan Low-noise 4th generation Flying ird fans, made of a composite material (Carrier patent) which do not generate intrusive low frequency noise. Condenser coils in speically sized V-shape with an open angle, allows quieter air flow across the coil. With smart control algorithms, inverter driven fan motors precisely match the buliding load while granting optimum air flow for minimized energy consumption and reduced noise level. dedicated oil separator is installed at the discharge of each compressor to ensure maximum oil return: oil separates from refrigerant per gravity and returns to the low pression side of the compressor without use of additional pumps. d() 0XV FS-screw (%) dvanced control algorithms combine inverter frequency output with motor input logic to minimise mechanical part stress, resulting in best compression performance and high chiller reliability. The compressor is equipped with bearings with oversized rollers, oil pressure lubricated for reliable and durable operation, even at maximum load. 5% 50% 75% 00% Night mode: During user defined period, precisely limit the cooling capaicty within pre-defined value for lower energy consumption and noise level by reducing inverter frequency of compressors and fan motors. The silencer in the oil separator line (at the compressor outlet) considerably reduces discharge gas pulsations for much quieter operation. *IPLV(Integrated Part-Load Value), a single number of part-load efficiency, it s rated at 00%, 75%, 50%, and 5% load relative to the full-load rating net refrigerating capacity at the standard rating HRI conditions. Condenser entering air temperature is 5 C 6.7 C 8. C.8 C respectively. Evaporator LWT is kept constant 7.0. NPLV(Non-Standard Part-Load Value), a single number of part-load efficiency referenced to conditions other than IPLV conditions. t 00% load, the condenser entering air temperature is user-defined; at 75% and 50% load, condenser entering air temperature is vary linearly from the selected EWT at 00% load to 8. at % load, and fixed at 8. for % to minimum load. Evaporator LWT at each load is user-defined as well. 6
Designed to Support Green uilding Design green building is a building that is environmentally sustainable and has been designed, constructed and is operated to minimize the total impact on the environment. The underlying principles of this approach: the resulting building will be economical to operate, offer increased comfort and create a healthier environment for the people who live and work there, increasing productivity. The air conditioning system can use between 0 and 40% of the annual building energy consumption. Selection of the right air conditioning system is one of the main aspects to consider when designing a green building. For buildings with a variable load throughout the year 0XV units offer a solution to this important challenge. number of green building certification programs exist in the market and offer third-party assessment of green building measures for a wide variety of building types. The following example looks at how Carrier's new 0XV range helps customers involved in LEED building certification. 0XV and LEED certification. The LEED (Leadership in Energy and Environmental Design) green building certification programme is a pre-eminent programme to rate the design, construction and operation of green buildings with points assigned in seven credit categories: -Sustainable Sites (SS) -Water Efficiency (WE) -Energy & tmosphere (E) -Materials & Resources (MR) -Indoor Environmental Quality (IEQ) -Innovation in Design (ID) -Regional Priority (RP) There are a number of different LEED products. Whilst the strategies and categories assessed remain the same, the point distribution varies to address different building types and application needs, for example according to New Construction, Schools, Core & Shell, Retail and Healthcare. 5 ll programmes now use the same point scale: 40-49 points Certified 0 possible LEED points 50-59 points Silver 60-79 points Gold 80-00 points Platinum The majority of credits in LEED rating systems are performance-based and achieving them is dependent on the impacts of each component or sub-system to the overall building. Whilst the LEED green building certification programs don t certify products or services, the selection of the right products, systems or service programs is critical to obtaining LEED certification for a registered project because the right products or service programmes can help meet the goals of green construction and ongoing operation and maintenance. The choice of heating, ventilating and air conditioning (HVC) products in particular can have a significant impact on LEED certification, as the HVC system directly impacts two categories that together influence 40% of the available points. Overview of LEED for new construction and major renovations Regional priority (4 points) Sustainable site (5 points) Innovation & design process (6 points) Water efficiency (0 points) Indoor environmental quality (5 points) HVC contribution 6 of 5 points Energy & atmosphere (5 points) HVC contribution 6 of 5 points Material & Resources (4 points) The new 0XV units from Carrier can assist building owners to earn LEED points in particular in the Energy & tmosphere (E) credit category and help address the following prerequisites and credit requirements: E prerequisite : Minimum energy Performance The 0XV exceeds the energy efficiency requirements of SHRE 90,-007; therefore it complies with the presequisite standard. E prerequisite : Fundamental Refrigerant Management The 0XV does not use chlorofluorocarbon (CFC) refrigerants thus satisfying the prerequisite statement. E credit : Optimise energy performance ( to 9 points) Points for this credit are assigned depending the energy cost reduction virtually achievable by the new building, compared to SHRE 90,-007 reference. The 0XV, which is designed for high performance especially during part load operation, contributes reducing the energy consumption of the building and therefore helps gaining points within this credit. In addition, the Carrier HP (Hourly nalyses Program) can be used as an energy analyses program complying with the modeling requirements for this credit and produce reports that are easily transferable to LEED templates. E credit 4: Enhanced refrigerant management ( points) With this credit, LEED awards systems that minimize the Ozone Depletion Potential (ODP) and Globlal Warming Potential (GWP) of the system.the 0XV uses a reduced R4a charge and therefore contributes toward satisfying this credit under LEED. NOTE: This section describes the prerequisites and credit require-ment in LEED for New Construction and is directly related to the 0XV. Other prerequisites and credit requirements are not directly and purely related to the air-conditioning unit itself, but more to the control of the complete HVC system. i-vu, Carrier s open control system, has features that can be valuable for: -E prerequisite : Fundamental commissioning of energy management system -E credit : Enhanced commissioning ( points) -E credit 5: Measurements and verification ( points) NOTE: Products are not reviewed or certified under LEED. LEED credit requirements cover the performance of materials in aggregate, not the performance of individual products or brands. For more information on LEED, visit www.usgbc.org. 7
Technical Specification Model 0XV 0 05 068 07 086 09 0 6 0 40 Nominal cooling capacity* kw 7.0 58.0 679.0 7.0 864.0 895.0 05.0 47.0.0 94.0 85.0 Compressor power input kw 99.8 6. 07. 6.4 70.5 76.6.5 59. 90. 4. 49.0 Nominal COP kw/kw.006.05.060.96.00.00.96.000.96.960.96 IPLV.IP** kw/kw 5.06 5.088 5. 5.06 5.66 5.05 5.0 5.060 5.080 5.06 5.09 Compressor VFD Semi-hermetic screw compressor Circuit Circuit - - - - Minimum capacity % 5% 5% 7% 5% 7% 5% 7% 7% 7% 7% 7% Refrigerant R4a Circuit kg 05 5 00 0 45 50 78 08 00 08 Circuit kg - - 0-97 - 40 7 4 5 08 Control Condenser Fans Touch pilot system Cu/I heat exchanger IV generation Flyingird axial fan Quantity 6 8 0 4 6 8 8 0 l/s 7084 6 4540 5468 5468 5868 696 74 85 85 9080 Fan speed rpm 950 Evaporator Flooded multi-pipe Water content l 54 77 94 98 0 0 40 58 68 86 86 l/s 5.59 5.7.6 4.4 4.9 4.66 48.8 54.68 58.7 6.68 66.0 Nominal water pressure drop kpa.0 5.0 45.5 49. 4.6 4.0 9. 4. 6. 7.5 5. Max. water-side pressure (without hydronic module) kpa 000 Water connection Victaulic Nominal Diameter DN 5 5 50 50 50 50 00 00 00 00 00 Electrical data Nominal power supply Control power supply Start-up method 400V-Ph-50Hz VFD start 4V via internal transformer Fan and control power kw 9.0.8 4.6 7.4 7.4 8.8 0..0 5.8 5.8 8.6 Nominal unit current draw, Circuit + 7 75 5 87 457 468 548 607 660 697 77 Maximum uint current draw, Circuit + 9 4 469 5 545 650 74 79 79 94 Maximum start-up current, Circuit + 9 4 469 5 545 650 74 79 79 94 Max operation power, Circuit + kw 6 0 68 99 8 47 44 47 504 504 589 Unit length mm 604 4798 599 786 786 880 880 9574 0768 0768 96 Unit width mm 5 Unit height mm 97 Unit weight kg 4 4749 647 695 7569 68 88 8 964 9666 067 Operating weight (Standard) kg 68 486 64 69 7699 695 85 8469 978 985 080 Notes: Evaporator fouling factor 0.08m K/kW ** IPLV calculations according to standard performances (in accordance with HRI 550-590) 8
Option & ccessories Options No. Description dvantage Model lygold PoluL 00 Coil with factory-applied lygold PoluL treatment Improved corrosion resistance, recommended for heavy marine and industrial environments 0XV0~40 Gold Fin 00 Fin made of pre-treated aluminium (polyurethane and epoxy) Improved corrosion resistance, recommended for light marine environments 0XV0~40 High static fan 0 High static fan (60Hz) vailable for ducted condenser air discharge optimized condensing temperature control 0XV0~40 Low noise (Compressor sound enclosure) 05 Compressor sound enclosure Low operating noise 0XV0~40 IP54 00 IP54 electrical box protection Increased leak tightness of control boxes 0XV0~40 Evaporator anti-freeze 04 Electric heater on evaporator Ensures evaporator anti-freeze protection down to -0 C without glycol 0XV0~40 Discharge valve 09 Discharge valve Easy for service 0XV0~40.6Mpa evaporator 04 Reinforced evaporator for extension of the maximum water-side pressure range to.6mpa Covers applications with a high water column (high buildings) 0XV0~40 Reversed water connections 07 Evaporator with reversed water inlet/outlet Simplification of water piping 0XV0~07 J-us gateway 48 Two-directional communication board with J-us protocol Easy connection by communication bus to building management system 0XV0~40 LonTalk gateway 48D Two-directional communication board with LonTalk protocol Easy connection by communication bus to building management system 0XV0~40 acnet gateway 48C Two-directional communication board with acnet gateway Easy connection by cmmunication bus to buiding management syetem 0XV0~40 9
Options No. Description dvantage Model acnet IP gateway 49 Two-directional communication with acnet protocol, using Ethernet bus Enables communication to MS systems with high-speed connection and the capability to read many variables 0XV0~40 Energy Management Module (EMM) 56 Energy Management Module (EMM) For economical operation and easy management 0XV0~40 7" touch pilot 58 7" touch pilot etter operation expierence 0XV0~40 Cu/l condenser coils 54 Coil made of copper tube with aluminium fin - 0XV0~40 EMC Clasification C 8 EMC Classification C For models Frame C 90kW the additional outdoor kit will not be applied;as these drive in the format C are already IP55rated;they will not have the fuses included 0XV0~40 Electric Plug 84 Electric Plug - 0XV0~40 8mm cooler insulation 99 8mm cooler insulation etter prevents condensation on high humidity environment 0XV0~40 lue fin 0 Hydrophilic aluminium foil Enhanced hydrophilic character and better aesthetics 0XV0~40 Conformance with ustralian regulations Evaporator and oil separator modified according to ustralian Conformance with ustralian regulations regulations 0XV0~40 5% THD Mitigate the harmonics by using harmonic filter (free standing/ Mitigate the harmonics of unit to 5% THDI outdoor) as the power supply to the unit 0XV0~40 0% THD Mitigate the harmonics by using harmonic filter (free standing/ Mitigate the harmonics of unit to 0% THDI outdoor) as the power supply to the unit 0XV0~40 0
Dimension&Clearances 0XV0/05 97 F Z X E D Y 5 500 C 500 00 500 Power supply connection Right view Required clearances for maintenance Recommended space for evaparator tube removal Safety valve Water inlet Water outlet ir outlet Power supply connection Center gravity 0XV C D E F X Y Z 0 604 66 7 5 0 0 0 759 05 4798 80 86 480 57 7 64 6 940 Note:Single power connection point, and arrive from the bottom. bove dimension drawing based on 0XV0 outline.
Dimension&Clearances 0XV068/086 97 F Z E D X Y 5 500 C 500 00 500 Power supply connection Right view Required clearances for maintenance Recommended space for evaparator tube removal Safety valve Water inlet Water outlet ir outlet Power supply connection Center gravity 0XV C D E F X Y Z 068 599 80 65 447 7 4 07 6 907 086 786 800 647 447 5 84 474 9 786 Note:Single power connection point, and arrive from the bottom.bove dimension drawing based on 0XV086 outline.
Dimension&Clearances 0XV07/09 Required clearances for maintenance Water outlet Recommended space for evaparator tube removal ir outlet Safety valve Power supply connection Water inlet Center gravity E F 97 Power supply connection X 500 C 500 00 500 Z D Y 5 0XV C D E F X Y Z 07 786 098 85 447 76 84 47 94 900 09 880 46 474 447 75 84 46 55 99 Note:Single power connection point, and arrive from the bottom. Reserve 0mm height space below the unit for power supply connection(unit aerial installation or cable slot arrangement in unit base). bove dimension drawing based on 0XV07 outline.
Dimension&Clearances 97 0XV0/6 Power supply connection X C 500 500 00 E F Z 500 Required clearances for maintenance Water outlet Recommended space for evaparator tube removal ir outlet Safety valve Power supply connection Water inlet Center gravity D Y 5 0XV C D E F X Y Z 0 880 477 7 48 97 90 4487 978 77 6 9574 585 804 447 96 90 484 07 890 Note:Single power connection point, and arrive from the bottom. Reserve 0mm height space below the unit for power supply connection(unit aerial installation or cable slot arrangement in unit base). bove dimension drawing based on 0XV6 outline. 4
Dimensions/Clearances 0XV/0/40 500 C 500 97 Power supply connection X DN50 DN50 00 500 Required clearances for maintenance Water outlet Recommended space for evaparator tube removal ir outlet D Z Safety valve Water inlet Power supply connection Center gravity 447 Y 5 0XV C D X Y Z 0768 4778 8 57 589 50 96 0 0768 4778 8 57 5885 46 94 40 96 597 8 57 660 94 Note:Single power connection point, and arrive from the bottom. Reserve 0mm height space below the unit for power supply connection(unit aerial installation or cable slot arrangement in unit base). bove dimension drawing based on 0XV outline. 5
Multiple Chiller Installation Wall Wall Outdoor air temperature 500 500 >40 00 000 00 500 500 Note:. Recommended distance between chiller and walls necessary for adequate space of heat exchange.. If the height of wall exceeds m, please contact local Carrier Sales & Service Corporation. Field Control Wiring.5mm² MX.5mm² MX.5mm² MX 4VC-0V MX 4VC-0m MX 4VC-48VDC MX 80m MIN 0V-MIN LRM REDY REMOTE ON/OFF SWITCH SET POINT SWITCH DEMND LIMIT SWITCH COOLER PUMP COMMND COOLER PUMP COMMND 80m MIN- MX 80m MIN- MX 0 7 8 65 66 6 64 90 90 J D005 J D006 J DI0 +C DI0 +C DI0 +C DI04 +C J6 D00 D004 4VC 0m.5mm² MX CCN CONNECTOR ETHERNET CONNECTOR - CCN GND Port 0 + X Ethernet X 6
Water Pressure Drop 00 90 80 70 60 Pressure drop, kpa 50 40 0 0 0XV0 0XV05 0XV07 0XV09 0 0 0 0 40 50 60 70 80 90 00 Water flow rate, l/s 00 90 80 70 60 Pressure drop, kpa 50 40 0 0 0XV068 0XV086 0XV0 0XV6 0 0 0 0 40 50 60 70 80 90 00 Water flow rate, l/s Water pressure drop, kpa 00 90 80 70 60 50 40 0 0 0XV 0XV0 0XV40 0 0 0 0 40 50 60 70 80 90 00 Water flow rate, l/s 7
Minimum Water Loop Volume For better control of leaving water temperature, the water loop minimum capacity is given by the formula: Capacity = CP (kw) N Liters pplication N Normal air conditioning 0XV0~40.5 Process cooling 0XV0~40 6.5 CP is the nominal system cooling capacity (kw) at the nominal operating conditions of the installation. This volume is necessary for stable operation and accurate temperature control. It is often necessary to add a buffer water tank to the circuit in order to achieve the required volume. The tank must be internally baffled in order to ensure proper mixing of the liquid (water or brine). Refer to the following examples. ad Good ad Good 8
The Manufacturer reserves the right to change any produt specifications without prior notices Version: Supersede: Effective Date: CT_0XV_ E-70-07 CT_0XV_ E-60-06 Mar, 07