MODEL QTS-1800 SERIES WALL MOUNT DIGITAL AND ANALOG TRANSMITTER/SENSOR

Similar documents
QAS-101 SERIES SINGLE CHANNEL CONTROLLERS

QAS SERIES PLUG-IN CONTROLLERS c/w SOLID STATE SENSOR

1040 Gas Monitor INSTALLATION AND OPERATING INSTRUCTIONS AMC-1040 WITH INTEGRAL ELECTROCHEMICAL SENSOR

1022 R/T Remote Monitor

! "! # Please read these installation and operating instructions completely and carefully before starting.

RAM3 Remote Alarm Module

INSTALLATION AND OPERATING INSTRUCTIONS

GAS MONITOR Model Model

GASGUARD H 2-1% Hydrogen Sensor OPERATING & INSTALLATION MANUAL

MODEL QTS-8000 SERIES NON-INTRUSIVE CALIBRATION INDUSTRIAL TRANSMITTER/SENSOR

GASGUARD NH 3 2% Ammonia Sensor OPERATING & INSTALLATION MANUAL

User Manual. PolyGard CO LC-1112 V3. Electrochemical analog carbon monoxide transmitters serial no. EC-S 002. August 29, 2006

Controllers. Instruction Manual WARNING

GG-NH3-2% AMMONIA GAS SENSOR. Installation and Operation Manual

EXAMPLES OF HOW TO ORDER

WARRANT Y AND LIMITS OF LIABILIT Y Vulcain Inc. warrants to the original purchaser that its product, and the component parts thereof, will be free fro

EXAMPLES OF HOW TO ORDER

Model Gas Alarm Panel APPLICABILITY & EFFECTIVITY. This manual provides instructions for the following Sierra Monitor products:

GASGUARD LEL 3 OPERATING & INSTALLATION MANUAL

Instruction Manual WARNING

AMC-RAM-4. Refrigerant Alarm Module USER MANUAL. Please read the installation and operating instructions completely and carefully before starting.

GG-VL-R REFRIGERANT VENT LINE SENSOR. Installation and Operation Manual

Warranty Registration

GASGUARD VENT LINE3. Ammonia Sensor OPERATING & INSTALLATION MANUAL

Digital Gas Transmitters with Auxiliary Inputs & Control. PolyGard 2 DC6

GASGUARD NH 3. Ammonia Sensor OPERATING & INSTALLATION MANUAL

GG-LEL2 COMBUSTIBLE GAS SENSOR. Installation and Operation Manual

Warranty Registration

Model 4001 Series Single Channel Controller

GASGUARD Cl 2. Chlorine Sensor OPERATING & INSTALLATION MANUAL

GG-R REFRIGERANT SENSOR. Installation and Operation Manual

1228s Multidrop INSTRUCTIONS. Installation and Operation of the AMC-1228s Electrochemical Sensor Module For Use With Multidrop AMC Monitors

GG-NH3 AMMONIA GAS SENSOR. Installation and Operation Manual

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

Operation Manual. Rev. E GEM-II Self Contained Gas Detector.

Instruction Manual PCS-400-XY. Pump Controller. Y=2: 4-20 ma Y=6: 0-10 VDC X=5: 1-5 VDC. 4 Pump Control Relays 1 Alarm Relay 1 Signal Fail

AMC-CD2. Human Occupancy Detector INSTRUCTION MANUAL. Please read these instructions completely and carefully before starting.

GG-CO-EXP CARBON MONOXIDE SENSOR. Installation and Operation Manual

GASGUARD O 2. Oxygen Sensor OPERATING & INSTALLATION MANUAL

RK/ RK Combustible Gas Detector Operator s Manual

Model D12-IR. Digital Gas Transmitter...

Operation Manual. Rev. D GEM-II Self-Contained Gas Detector.

INSTALLATION. and INSTRUCTION MANUAL. for QUALITY AIR BREATHING SYSTEMS. Model ABM - 715

M3050 Detector Operator s Manual

GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL. Installation and Operation Manual

Two-Channel Gas Controller

GG-H2S HYDROGEN SULFIDE GAS SENSOR. Installation and Operation Manual

Oxygen (O2) Single-Point Gas Detection System

SEC 2000 Millenium Infrared Gas Detector

GASGUARD SO2 Sulfur Dioxide Sensor OPERATING & INSTALLATION MANUAL

GG-NO2 NITROGEN DIOXIDE GAS SENSOR. Installation and Operation Manual

4-20mA CYBER Cyber Transmitter for flammable, toxic and IR gas detection Cyber Head Increased security in ATEX certified head

CMF, CMX & CMA series

Mark 25 Ultrapure Water Conductivity Analyzer

RK-05 Combustible Gas Transmitter Operator s Manual

Falcon-II Next Generation, Air Quality Monitor CO2 & Temperature

GG-EM ENTRANCE MONITOR. Installation and Operation Manual

WATCHMAN Model LBW-WATCHMAN Ammonia Leak Detector

PolyGard Controller LGC/LG2-04. Multi-Point Controller Serial Number S00 User Manual Preliminary Version. August 11, 2006

Model C Combustible Gas Transmitter. 6 Iron Bridge Drive Unit 1 & 2 Gatehead Business Park

MODEL: Q8 SERIES NON-INTRUSIVE CALIBRATION GAS TRANSMITTER/SENSOR

GASGUARD H2S EXP. Hydrogen Sulfide Sensor OPERATING & INSTALLATION MANUAL

P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification

Model OEM-2 INSTRUCTIONS FOR USE

RK Carbon Monoxide Transmitter Operator s Manual

SEC Signature Process Gas Analyzer

MACURCO INC. CONTROLLERS & CARBON MONOXIDE DETECTORS SS103-3A, SS103-10A SS102H, SS102HC-1 INSTALLATION & OPERATING INSTRUCTIONS

DL424/425 DirectLine Sensor Module for Dissolved Oxygen Probes Series DL5000 Specifications

Models LBW-420-LEL (24 VDC powered) Ammonia Leak Detector

RK / RK Methane Detector Operator s Manual

For the Safety of Your

Duct Humidity/Temp Sensor

GASGUARDIAN Channel Controller OPERATING & INSTALLATION MANUAL

Carbon Monoxide Transmitter

RK Carbon Monoxide Transmitter Operator s Manual

IR200 INFRARED HCFC & AMMONIA (NH3) REFRIGERANT SENSOR. User Manual

RK Combustible Gas Transmitter Operator s Manual

GasScanner 4C. Four Channel Monitor. Operator s Manual. MINT-0280-XX Rev. A 02/25/08

Installation & Operation Manual

Carbon Monoxide Sample-Draw Detector Operator s Manual

Setra Model SRH Relative Humidity Sensor Series with Active or Passive Temperature Sensing Installation Instructions

RAM 50 Series Operation Manual

FW-RA-LED Remote Multiplex Annunciator Panels

Combustible Gas Sample-Draw Detector Operator s Manual

SIL 2. Ultima X Series Gas Monitors CERTIFIED

OPERATION & MAINTENANCE MANUAL

Beacon 110 Gas Monitor Operator s Manual

INSTALLATION. and INSTRUCTION MANUAL. for QUALITY AIR BREATHING SYSTEMS. Model ABM - 700

Tox-COMB/ANA Combustible Gas Transmitter Operator s Manual

Combustible Gas/Carbon Monoxide Sample-Draw Detector Operator s Manual

Sieger Sensepoint. Easy to Use Factory set operation Simple to replace Minimal training required

5New features & EXtreme design, now with HART Protocol and DuraSource Technology. Ultima X Series Gas Monitors

Room Humidity/Temp Sensor

GS100M Gas Detection Controller

RK CO 2 Transmitter Operator s Manual

M2 Transmitter Operator s Manual

RK Carbon Monoxide Transmitter Operator s Manual

RK Transmitter Technical Notice

Hydrocarbon Gas Detector

Installation Manual. Expansion Module 0100 Version 1.0 EXP HBX Control Systems Inc.

Transcription:

MODEL QTS-1800 SERIES WALL MOUNT DIGITAL AND ANALOG TRANSMITTER/SENSOR INSTALLATION OPERATION AND MAINTENANCE MANUAL QUATROSENSE ENVIRONMENTAL LTD. 5935 OTTAWA STREET, PO BOX 749 RICHMOND, ONTARIO CANADA K0A 2Z0 PHONE: (613) 838-4005 FAX: (613) 838-4018 Web: www.qelsafety.com Email: QEL@QELsafety.com

General Specifications Item Specification Sensor Type Solid State Dimensions 4.2 W x 8.6 H x 2.6 D (107mm x 218mm x 66mm) Environment Temperature -4ºF to 104ºF (-20ºC to 40ºC) Humidity 0-99% non-condensing Enclosure NEMA 1 ABS plastic fire retardant cover (94 V-O) NEMA 4X ABS plastic fire retardant cover (94 V-O) Package Type Wall mount Wall mount with splashguard option Output 4-20mA Analog Linear Communicatio RS-485 Digital for interface to QEL QDCS-4000 Monitor (Option) n Power 24 VAC/VDC (nominal) 18-50 VDC 15-36 VAC @ 47-63 Hz * = As Delivered Analog Warning/Alarm Setting * Gas Type Range Low (Warning) High (Alarm) Carbon 0-125 ppm in VE (Vehicle Exhaust) 50 ppm (in VE) 100 ppm (in VE) Monoxide Propane 0-50% LEL 10 %LEL 20 %LEL Ammonia 0-500 ppm 50 ppm 300 ppm R11, R12, R22 0-1000 ppm 500 ppm 1000 ppm R134A 0-1000 ppm 500 ppm 1000 ppm R123 0 to 100 ppm 10 ppm 50 ppm 29050-007-000-RM i

TABLE OF CONTENTS 1 Introduction...1 1.1 Mounting Method...1 1.2 Mounting Height...2 2 Wiring...2 2.1 Digital Multi-Drop Installations...2 2.1.1 RS-485 Cable Type...2 2.1.2 Cable Shield Grounding...2 2.2 Analog Signaling (4-20) Installations...3 2.3 Operating Voltages...3 2.4 Fuses...3 3 Calibration...3 3.1 Equipment Needed...4 3.2 Calibration Set-up...4 3.3 Calibration Facility Locations...5 3.4 Calibration Gas Required...5 3.5 Procedure...5 3.6 Humidity Calibration...6 3.7 Electronic Setup (Gain)...6 4 Digital Addressing (Digital Model Only)...6 4.1 Analog/Digital Signal Options In A Digital System...7 5 Alarm Settings (Digital Model Only)...7 6 Warranty Statement...9 29050-007-000-RM ii

1 Introduction The QTS-1800 Series Transmitter series is a microprocessor-based sensor/transmitter, using a variety of solid-state sensors for detection of hydrocarbons and other gases. Refer to the front of this manual for specifics of gas type, range and sensor type and other settings. These sensors have varying degrees of interfering response to humidity and temperature. Depending upon the gas being sensed and the application, there may be a humidity sensor and/or a temperature sensor on the unit to allow the microprocessor to adjust the reading according to changes in the atmosphere. The sensors used are to some degree all non-specific, which is to say that they will respond to other gases which may be present, notably hydrocarbons and solvents, and this can cause nuisance alarms. The microprocessor cannot distinguish between these gases and the target gas. 1.1 Mounting Method The unit is supplied with a 1/2" conduit entry hole at the top end and on the rear. Screw holes are provided on the rear, which match a standard switch box. 29050-007-000-RM 1

1.2 Mounting Height QTS-1800 Series Transmitter Operation And Maintenance Manual The various gases detected by this series have different weights and the mounting heights vary accordingly: Gas Type CO Combustible - Methane Combustible - Other gases Ammonia Freons 2 Wiring Mounting Height 4-6 ft (1.2m - 1.8m) above floor 1 ft (0.31m) below ceiling 1 ft (0.31m) above floor 1 ft (0.31m) below ceiling 1 ft (0.31m) above floor The Solid State Transmitter may be purchased with one or both of two modes of operation and signaling: Analog and/or Digital. It is necessary to know which type you have and install according to one following methods. Parameter 24VDC operation - 4 wire Wire Size Minimum Wire Size Maximum Recommended for RS-485 2.1 Digital Multi-Drop Installations Specification 12-24AWG 24AWG (0.51mm) 14AWG (0.16mm) Belden 9841 or equivalent Communication is via digital data communications over an RS-485 two-wire data link for use with the QDCS-4000 monitor. The power supplied is 24 VDC. 2.1.1 RS-485 Cable Type While it is theoretically feasible to use ordinary wiring techniques in many applications involving few sensors operating over short distances, it is not recommended. General installation techniques leave the communications line susceptible to noise, internal signal reflections and garbling. QEL recommends a true RS-485 cable (e.g. Belden 9841 or equiv.) two wire, shielded, 120-Ohm characteristic impedance. It is recommended to terminate each the ends of the line with a 120-Ohm impedance-matching resistor. The 120-Ohm line is also referred to as the RS-485 bus. A correctly terminated RS-485 bus will therefore have a 120-Ohm termination at each end. For most installations, the Monitor end will be terminated, as well as the transmitter at the end of the bus. If the monitor is not installed at the end of the bus, the two transmitters at the ends of the bus will require a termination resistor. 2.1.2 Cable Shield Grounding Cable shields must be grounded and only at one end. Ungrounded cables become capacitively coupled antennas. Grounding at more than one place produces ground loops. 29050-007-000-RM 2

2.2 Analog Signaling (4-20) Installations The signal out is a 4-20 ma linear signal. This device may be installed with either 24 VDC power or with 24 VAC power as per the following drawings. In the case of AC power the installation must be floating. Do not connect one side of the transformer secondary to ground; this will cause an internal short to Signal Common and blow the fuse or damage the card. 2.3 Operating Voltages Analog Installation 24 VAC/VDC (nominal) 18-50 VDC 15-36 VAC @ 47-63 Hz 2.4 Fuses Before replacing the fuses, inspect the Circuit Card Assembly (CCA) for any obvious damage such as overheated components. If any damage is observed, the CCA should be replaced. 3 Calibration The sensor element response is non-linear and the signal must be linearized as part of the algorithm implemented. Two gas concentrations are required to define the characteristic response of the sensor. The gas must be humidified after it leaves the tank. The calibration adapter has a reservoir for passing the gas through a wetted sponge to humidify the gas. 29050-007-000-RM 3

If the transmitter is equipped with a humidity sensor, the humidified gas must also go to the humidity sensor to enable the microprocessor to calculate the humidity response as shown. The Humidity Calibration Cover plugs directly into the humidity sensor access hole on the front cover. 3.1 Equipment Needed To calibrate the QTS-1800 successfully, a calibration kit can be purchased from our factory. The calibration kit is designed to match the requirements for the product and will ensure a reliable calibration. Please note that the microprocessor is programmed to expect only certain concentrations of gas and the concentrations must be as indicated in the calibration gas concentration table below. The items required for calibration are as follows: Two concentrations of gas: CONC 1 = the lower concentration gas CONC 2 = the higher concentration gas Regulator to supply gas at 0.1-0.2 liter/minute (2-4 SCFH) Single calibration adaptor for the bottom sensor (CO and combustibles only) or Dual Calibration adapter for bottom sensor + cover humidity sensor (all gas except CO and combustibles) Digital Multi-meter for 0-20 ma reading (3 1/2 Digit recommended) Meter Remote Calibration Plug 3.2 Calibration Set-up The figure below shows some of the calibration equipment required for calibration of the unit. 29050-007-000-RM 4

3.3 Calibration Facility Locations Additional circuitry, switches and connectors is provided to facilitate calibration of the unit. Please take not of the following in the figure below: Calibration selection DIP switch (detailed view in circle). Calibration jack (at top of CCA). Increase and Decrease LEDs. Adjustment potentiometers. The function of each item will be described below in the calibration procedure. 3.4 Calibration Gas Required Please note that for the calibration of each gas type, two specific concentrations are required as listed in the table below. It is important to obtain the exact concentration for each calibration point, since the concentration, levels are hard-coded in the firmware and form and important part of the algorithm used. If the correct calibration gas is not used or the humidity attachment is not used, the product will not meet it s specification after calibration. Gas CONC 1 CONC 2 CO 50 ppm (humidified) in VE equivalent 100 ppm (humidified) in VE equivalent Combustible 10% LEL (applicable gas) 20% LEL (applicable gas) NH 3 (Ammonia) 50 ppm (humidified) 300 ppm (humidified) R11 500 ppm (humidified) 1000 ppm (humidified) R12 500 ppm (humidified) 1000 ppm (humidified) R22 500 ppm (humidified) 1000 ppm (humidified) R123 30 ppm (humidified) 100 ppm (humidified) R134A 500 ppm (humidified) 1000 ppm (humidified) 3.5 Procedure All calibrations are done with prescribed concentrations of gas (See table above). Calibration requires two concentrations for gas and one for humidity. When the DIP switches for calibration are set, the microprocessor calculates adjustments for temperature and humidity compensation as appropriate and compares the reading to the pot adjustment. 29050-007-000-RM 5

If the pot setting is above the reading, the DECREASE LED will be ON; if it is below, the INCREASE LED will be ON. When the setting is correct, the calibration LEDs will flash alternately. The circuit board is supplied with a jack to measure the output signal using a digital multi-meter (20 ma scale). Inserting the plug for measuring diverts the signal through to internal ground, thus giving a FAIL (0.0 ma) reading at the monitoring equipment. When calibrating this transmitter, refer to the Functions set of 4 DIP switches. Setting these switches tells the microprocessors which of the two concentrations of gas you are applying. A reading may be monitored by applying gas with the switches off. The switches are labeled CONC 1 for the lower concentration and CONC 2 for the higher concentration. Concentration 1: Set CONC 1 DIP switch to ON, CONC 2 DIP switch to OFF. The analog signal goes to 4.0 ma. Apply gas as shown. Wait about 5 minutes for both sensors to stabilize. Adjust the CONC 1 potentiometer until the Calibration LEDs switch from one to the other. Switch OFF the DIP switch and remove gas. Concentration 2: Set CONC 1 DIP switch to OFF, CONC 2 DIP switch to ON. The analog signal goes to 4.0 ma. Apply gas as shown. Wait about 5 minutes for both sensors to stabilize. Adjust the CONC 2 potentiometer until the Calibration LEDs switch from one to the other. Switch OFF the DIP switch and remove the gas. 3.6 Humidity Calibration Humidity calibration (Pot #3) is a factory setting and should not be attempted in the field. Set CONC 1 and CONC 2 DIP switch settings both ON. The Analog signal goes to 4.00 ma. Apply 44% Relative Humidity to the Humidity sensor and adjust Pot #3 per the Calibration LEDs. When set turn CONC 1, CONC 2 OFF. Humidity Sensor Present: No = For CO and Combustible Yes = R22, R11, R12, R123, R134A, Ammonia (set at factory; Calibration Concentration + 44% relative humidity) 3.7 Electronic Setup (Gain) When calibration mode is entered, the microprocessor puts out an equivalent of 4.0 ma. Adjust the GAIN potentiometer to get 4.0 ma reading on the meter. 4 Digital Addressing (Digital Model Only) For the digital model, there are two sets of four DIP switches on the circuit board for setting the address: an upper group (ten) and a lower group (one's). They are arranged as ordinary numbers - the one s switch can be set to numbers from 0 to 9, and the ten s switch can be set only from 0 to 7 as shown and are arranged, e.g. 13 is coded 1 on the lower group and 3 on the upper group. The highest allowable address is 79. 29050-007-000-RM 6

Note: Position 4 of the ten switches must be ON for digital operation. 4.1 Analog/Digital Signal Options In A Digital System When making direct measurements of a device installed for digital operation, it is necessary to switch the ten s switch position 4 to OFF to access analog (4 to 20 ma) signals during operations such as calibration, or to take good quality direct local readings. Analog local readings are available during normal operation, but you may find that there may be excessive noise. Note: Activating the analog function will take the sensor out of the digital communication loop, and it will show fail on the main panel. 5 Alarm Settings (Digital Model Only) There is no possibility of indicating an alarm condition for the analog transmitters, however with the digital communication link, the digital transmitter does indicate its alarm condition to the host monitor (QDCS-4000 Monitor). LED s on the transmitter circuit board indicate status as well. The digital transmitters have the common alarm settings built in to the software of the microprocessor, for instance 50 and 100 ppm of CO. In order to provide a choice there are Function DIP switches on the circuit board, LO SET and HI SET (or Set 1 and Set 2), which allow choice between two common settings for WARNING and ALARM. Refer to the specification page in front of this manual for the settings for your particular device, depending on gas type. 29050-007-000-RM 7

When the HI SET and LO SET DIP switches are off, the unit performs no alarm or warning level evaluation for the digital communication. No indication is given via the LEDs on the circuit card either. * = As Delivered Digital Alarm Setting Set 1 (LO SET) Digital Alarm Setting Set 2 (HI SET) * Gas Type Range Low (Warning) High (Alarm) Low (Warning) High (Alarm) Carbon Monoxide 0-125 ppm in VE (Vehicle Exhaust) 25 ppm in VE 75 ppm in VE 50ppm in VE 100 ppm in VE Propane 0-50% LEL 5 %LEL 10 %LEL 10% LEL 20% LEL Ammonia 0-500 ppm 30 ppm 200 ppm 50 ppm 300 ppm R11, R12, 0-1000 ppm 400 ppm 900 ppm 500 ppm 1000 ppm R22 R134A 0-1000 ppm 400 ppm 900 ppm 500 ppm 1000 ppm R123 0 to 100 ppm 10 ppm 30 ppm 30 ppm 50 ppm 29050-007-000-RM 8

6 Warranty Statement The information contained in this manual is based upon data considered accurate; however, no warranty is expressed or implied regarding the accuracy of this data. All QEL equipment is warranted against defects in material and workmanship for a period of two years from date of shipment with the following exceptions: Electrochemical Sensors (Toxic) Catalytic Sensors (Combustible) Six Months One Year During the warranty period we will repair or replace, at our discretion, any components or complete units that prove, in our opinion, to be defective. We are not liable for consequential or incidental damage to auxiliary interfaced equipment. A returned material authorization number should be obtained from the factory prior to returning any goods. All return shipments must be shipped freight prepaid and a copy of the maintenance records should accompany the unit concerned. Warranty should be considered F.O.B. the factory. Labour and travel time are chargeable for any field site visits required for warranty work. LIMITED LIABILITY All QEL systems shall be installed by a qualified technician/electrician and maintained in strict accordance with data provided for individual systems in the form of installation/maintenance manuals. QEL assumes no responsibility for improper installation, maintenance, etc., and stresses the importance of reading all manuals. QEL shall not be responsible for any liability arising from auxiliary interfaced equipment nor any damage resulting from the installation or operation of this equipment. QEL s total liability is contained as above with no other liability expressed or implied as the purchaser is entirely responsible for installation and maintenance of systems. This warranty is in lieu of all other warranties, expressed or implied, and no representative or person is authorized to represent or assume for QEL any liability in connection with the sales of our products other than that set forth herein. NOTE: Due to on-going product development, QEL reserves the right to change specifications without notice and will assume no responsibility for any costs as a result of modifications. For further information or assistance, contact: QUATROSENSE ENVIRONMENTAL LTD. 5935 Ottawa Street, PO Box 749 Richmond, Ontario K0A 2Z0 Tel: (613) 838-4005 Fax: (613) 838-4018 Email: QEL@QELsafety.com Web: www.qelsafety.com 29050-007-000-RM 9