C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM

SPRINKLERS TABLE OF CONTENTS

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

SECTION WET-PIPE SPRINKLER SYSTEMS

Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040

A. This section includes design and performance information for fire protection and suppression systems.

B. Galvanized-Steel-Sheet Sleeves: inch minimum thickness; round tube closed with welded longitudinal joint.

Gas Station & C Store SECTION CWM Job No

Revision May All designs must be submitted to FM Global for review and approval prior to issuing such for bids.

AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations)

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

2. Welding Materials and Procedures shall conform to the ASME Code.

CITY OF PASADENA FIRE DEPARTMENT

PLAN REVIEW CHECKLIST

B. The sprinkler system shall be designed to meet the more stringent of the requirements of NFPA 13 and FM Global requirements.

West District Library Section Campeau Drive, Ottawa SPRINKLER SYSTEMS City of Ottawa Project No. CR Page 1 of 8

MLA Architects Pierz Public Schools ISD #484 Healy High School Multi-Purpose & Choir Additions Pioneer Elementary School Class Room Addition Pierz, MN

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements

SECTION WET-PIPE SPRINKLER SYSTEMS

THE JAMES RUSHTON EARLY LEARNING AND FAMILY SUCCESS CENTER #2616 ISSUE FOR CONSTRUCTION

4 June This circular supersedes MSC/Circ.914. *** I:\CIRC\MSC\01\1272.doc

DIVISION 21 - FIRE SUPPRESSION

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1

SECTION DRY-PIPE SPRINKLER SYSTEMS

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM

1.2 CODES AND REGULATIONS A. Sprinkler system design, equipment, materials, devices, and installation shall conform to the following:

FIRE SUPPRESSION SPRINKLER SYSTEM

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL

ATTIC UPRIGHT SPECIFIC APPLICATION SPRINKLER VK696 TECHNICAL DATA

IACS RESOLUTION CHANGES (GMO ) BEKİR SITKI TÜRKMEN

Sprinkler System Installer Level 2

DIVISION 21 - FIRE SUPPRESSION

SECTION DRY-PIPE SPRINKLER SYSTEMS

WET-PIPE SPRINKLER SYSTEMS

DESIGN & CONSTRUCTION GUIDELINES

B. Related Sections: The following Sections contain requirements that relate to this Section.

SECTION (15530) - REFRIGERANT PIPING

SECTION WET-PIPE SPRINKLER SYSTEMS

STANDARD/QUICK RESPONSE ECOH ELO FUSIBLE ELEMENT UPRIGHT SPRINKLER VK535 (K11.2) TECHNICAL DATA

GASEOUS HYDROGEN SYSTEMS

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University.

UC Santa Cruz Campus Design Guide. Includes the following sections: None DESIGN REQUIREMENTS

NFPA Edition Update

SECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM

SECTION FIRE-SUPPRESSION STANDPIPES

SECTION WET-PIPE SPRINKLER SYSTEMS

culus Listed: Category VNIV Refer to the Approval Chart on page 3. VK697 Attic Upright Sprinkler Specifications:

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

SECTION SPRINKLER SYSTEMS

Report on First Revision November 2013 NFPA 750

International Water Mist Conference, Istanbul October 22-23, 2014 The background and development of the guidelines in IMO Resolution A.

REVISED GUIDELINES FOR THE DESIGN AND APPROVAL OF FIXED WATER-BASED FIRE-FIGHTING SYSTEMS FOR RO-RO SPACES AND SPECIAL CATEGORY SPACES

SECTION (15530) - REFRIGERANT PIPING

Model ESFR K-factor Pendent Sprinkler Early Suppression, Fast Response General Description. Sprinkler Identification Number (SIN)

RESOLUTION MSC.98(73) (adopted on 5 December 2000) ADOPTION OF THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE

Inspection of Fire Sprinkler Systems. NFPA 25, Inspection, Testing & Maintenance of Water Based Fire Protection Systems

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE

Model MBEC-14. Extended Coverage Ordinary & Extra Hazard Horizontal Sidewall Sprinklers for Metal Building Applications. Model MBEC-14 (SIN R6932)

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE

TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION WATER BASED FIRE PROTECTION SYSTEMS... 5

Subchapter 7. General Industry Safety Orders Group 27. Fire Protection Article 157. Portable Fire Extinguishers. Return to index New query

B. Section Identification for Fire Suppression Piping and Equipment.

Guidance on the construction of CO 2 systems

A. Section includes wet-pipe sprinkler system, system design, installation, and certification.

Part 6 Additional class notations Chapter 6 Additional fire protection for passenger vessels

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements.

RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Pendent Wet Pipe and Dry Pipe Systems General Description

CITY OF MADISON FIRE DEPARTMENT (MFD) FIRE PROTECTION SYSTEM PLANS

MONTECITO FIRE PROTECTION DISTRICT

American Society of Safety Engineers Professional Development Conference June 9-12, Fire Protection. Stephen J.

Design & Construction Standards, Revised January

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

North Hanover Township School District North Hanover Township, New Jersey

GLENDALE FIRE DEPARTMENT FIRE MARSHAL S OFFICE

FIRE SAFETY REQUIREMENTS FOR PRE RESIDENTIAL BUILDINGS OF THREE OR MORE STORIES (DOROTHY MAE ORDINANCE - NO. 158,963)

SECTION FIRE SUPPRESSION SYSTEMS

SECTION : FIRE PROTECTION SYSTEMS

Annual Report of Inspection, Testing & Maintenance of Automatic Sprinkler System

standard/quick response extended coverage light and ordinary hazard elo sprinklers

MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS

freedom residential flush pendent sprinkler vk476 (K4.9)

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright and Pendent Extended Coverage Light and Ordinary Hazard General Description

CERTIFICATE OF FIRE APPROVAL

A. Standard-Pressure Piping System Component: Listed for 175-psig minimum working pressure.

Fire. IMO fire control signs - according to IMO Resolution A.654 (16) (mm) 150x x200

RESOLUTION MSC.265(84) (adopted on 9 May 2008) AMENDMENTS TO THE REVISED GUIDELINES FOR APPROVAL OF SPRINKLER SYSTEMS EQUIVALENT TO THAT REFERRED TO

AUTOMATIC FIRE SPRINKLER SYSTEMS

BMA INFORMATION BULLETIN No. 97 FIRE FIGHTING EQUIPMENT

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

SECTION PREACTION SPRINKLER SYSTEMS

Transcription:

S. J. Kelly, CDR, Chief of Engineering Division References a. Title 46 CFR 56.20, 56.50 & 56.60 (Subchapter F) b. National Fire Protection Association (NFPA) 13, 1996 Edition, Installation of Sprinkler Systems c. Navigation and Vessel Inspection Circular (NVIC) 8-93 and NVIC 8-93 Change 1, Equivalent Alternatives to 46 CFR Subchapter H Requirements Related to Means of Escape, Safe Refuge Areas and Main Vertical Zone Length d. Policy File Memorandum (PFM) 1-97, Guidance for Use of Exposed Copper Pipe with Automatic Fire Sprinkler and Water Mist Systems on U.S. Vessels e. IMO Resolution MSC.44(65), Standards for Fixed Sprinkler Systems for High Speed Craft f. International Code for Fire Safety Systems (FSS Code) Contact Information: If you have any questions or comments concerning this document, please contact the Marine Safety Center by e-mail or phone. Please refer to the Procedure Number: E1-27. E-mail: msc@uscg.mil Phone: 202-475-3402 Website: http://homeport.uscg.mil/msc Responsibilities: The submitter shall provide adequate documentation to indicate compliance with the applicable requirements; this includes a complete bill of materials, component listing/specifications, pump curves, hydraulic calculations and arrangement plans. Detailed plan submittal guidance is provided in reference (b). The submission shall be made in triplicate. Unless otherwise noted, references for the following guidance are provided as corresponding paragraph numbers from NFPA 13-1996. The design to later editions of NFPA 13 is acceptable provided the systems are designed and installed to be fully operational without a reduction in system performance when the vessel is upright and inclined at the angles of inclination specified in 46 CFR 58.01-40. (Plans and Calculations section of Marine Systems chapter in post-1996 editions of NFPA 13)

General Guidance: Piping Materials: Ferrous piping materials shall conform to the material specifications and design standards listed in reference (b), tables 2-3.1 and 2-4.1. Ferrous materials subjected to salt water shall be galvanized or be extra heavy schedule material. Materials other than those noted are acceptable in wet pipe systems in accordance with their listing. (2-3, 2-4, 9-2.4) Steel pipe < 8 inches in diameter, joined by threaded fittings, shall be a minimum of schedule 40. Steel pipe 8 inches in diameter, joined by threaded fittings, shall be a minimum of schedule 30. (2-3.3) Steel pipe 5 inches in diameter, joined by welding or rolled groove fittings, shall be a minimum of schedule 10 (2-3.2). Listed grooved type fittings are acceptable only in sprinkler systems located outside of the engine room. Copper pipe is limited to ASTM B-88, types K, L, M, and ASTM B-42 materials. Copper and brass pipe shall be used only in wet pipe systems protecting light and ordinary hazard areas; pressures shall not exceed 250 psi. (PFM 1-97 and 9-2.4.2) Copper pipe shall not be located in, or routed through cargo or vehicle decks, machinery spaces containing boilers, internal combustion engines, pressurized fuel or lubricating line or storage spaces for combustible liquids or gasses under pressure. (PFM 1-97) Joints and connections for ASTM B-88 tubing shall be brazed. Joints and connections for ASTM B-42 tubing shall be brazed, threaded or UL listed mechanical type. (PFM 1-97) Brazing filler materials shall have a solidus melting temperature of not less than 1000 0 F. Bcup-2, Bcup-3, Bcup-4, Bag-5, Bag-1, Bag-2 and Bag-7 filler materials are acceptable. (PFM 1-97) Non-metallic piping is acceptable for wet pipe systems only in accordance with the following requirements: 1) The materials must be listed by an USCG acceptable laboratory for use in wet pipe sprinkler systems. The piping must be installed in accordance with the listing. Additionally, the pipe must be located behind a B-15 barrier. 2

2) Non-metallic piping not listed for use in sprinkler systems must meet IMO A.753(18) requirements for flame spread, fire endurance, smoke generations and toxicity, as appropriate. Valves, drains, test valves, etc shall meet the requirements of 46 CFR 56.20 and 56.60. Valves with resiliently seats shall be positive shut-off or category A type valves constructed in accordance with the material specification and design requirements (9-2.6.2). General Arrangements: Partial installation of sprinklers is not acceptable. Spaces protected by other fire protection systems that are separated by A-60 boundaries from the sprinkled areas need not be provided with sprinklers. Concealed spaces constructed of or containing combustible materials shall be sprinklered (9-1.3 & 9-4.4) Sprinkler zones shall not encompass more than two adjacent decks or more than one main vertical zone. Waterflow alarms shall be installed for every zone of the sprinkler system (9-4-12.2). The sprinkler system maximum coverage area on any one deck supplied by one sprinkler riser shall not exceed 52,000 ft 2 for a light or ordinary hazard and 40,000 ft 2 for a extra hazard (4-2) SOLAS vessels only: windows located along an egress route must be A-0 rated and be protected by the sprinkler system. (9-4.3 & SOLAS II-2 Reg. 4.1.3.3) Design Calculations: Select the correct occupancy hazard type for each protected space; see (1-4.7) for occupancy classification definitions. Light hazard includes public spaces and control stations; Ordinary Group I includes galleys, storage areas and laundries. (A-9-1.2) Either the area-density or room design methods must be used to design the system. If using the area-density method, the water supply shall be based on the area-density curves shown in figure 5-2.3 of reference (b). 1) For light hazard installations, a water application rate of 0.1 gpm/ft 2 over 1,500 ft 2 is common. 2) For ordinary group I hazard installations, a water application rate of 0.15 gpm/ft 2 over 1,500 ft 2 is common. (9-5.1) 3

3) SOLAS vessels require a minimum water application rate of 5 lpm/m 2 over 280 m 2 (0.12 gpm/ft 2 over 3,014 ft 2 ). (Ref (f) Chapter 8.2.5.2.3) Distribution piping pressure loss calculations shall be provided as a basis for the sprinkler pump flow and pressure requirements. Several design areas should be calculated to ensure the hydraulically most demanding area is ascertained. Sprinkler nozzle operating pressure shall not be < 10 psi. (9-2.1) Sprinkler Heads: Sprinklers shall be listed for the specific type hazard (light, ordinary, etc) and type of system (wet or dry) in which they are used. Manufacturer technical data sheets showing the listing should be provided. (4-3.1.1) A sprinkler orifice shall not be less than a nominal 3/8 inches; the minimum nominal discharge coefficient (K factor) is 2.9. Sprinkler nozzle operating pressure shall not be less than 10 psi. (9-2.1) Quick response sprinklers are required on vessels with long main vertical zones (Length > 131feet) for which NVIC 8-93 is applicable. (Contact MSC Hull Division for assistance in determining applicability) A sufficient number of sprinklers must be provided for the coverage area based on the type sprinkler, hazard type and space construction. The maximum coverage areas are: 1) Pendent sprinklers (4-6.2.2) a) Light hazard/noncombustible or combustible unobstructed construction: 225 ft 2 b) Light hazard/combustible obstructed construction 168 ft 2 c) Ordinary hazard: 130 ft 2 2) Sidewall sprinklers (4-7.2.2) a) Light hazard/noncombustible or limited combustible construction: 196 ft 2 b) Light hazard/ combustible construction: 120 ft 2 c) Ordinary hazard/noncombustible or limited combustible construction: 100 ft 2 d) Ordinary hazard/combustible construction: 80 ft 2 Sprinkler placement and spacing is based on the sprinkler type and hazard: 1) Pendent sprinklers (light and ordinary hazards) (4-6.3) a) Distance between sprinklers: 6 15 4

b) Distance from walls: 4 7.5 c) Distance below ceiling: 1 12 2) Sidewall sprinklers (4-7.3) a) Distance between sprinklers in light hazards: 6 15 b) Distance between sprinklers in ordinary hazards: 6 10 c) Distance from walls in light hazards: 4 7 d) Distance from walls in ordinary hazards: 4 5 e) Distance below ceilings: 4 6 Sprinklers shall be installed to protect windows at a distance not to exceed 1 foot (0.3m) from the window; sprinkler spacing shall not exceed 6 feet (1.8m). The window surface should be wetted at a rate not less than 6 gpm/ft. (9-4.3) Return bends are required on pendent type sprinklers that are used in wet pipe systems. (9-4.8) Sprinkler Pumps, Pressure Tanks and Water Supply: A dedicated pump sized to meet the water demand of the hydraulically most demanding area shall be provided. The pump shall be listed for marine service; UL listed fire pumps are acceptable. Pumps shall not exceed 120% of rated capacity. (9-6.3.1 & 2) Two sources of power with separate feeders are required for all sprinkler system pumps. The normal source of power shall be the emergency switchboard. (9-6.3.4) Vessels having extended main vertical zones (subject to NVIC 8-93), shall have two sprinkler pumps sized to meet the water demand of the hydraulically most demanding area. A dedicated fire pump is permitted to be used as the second pump provided that : (9-6.3.7) 1) The pump has the capacity to meet the fire hose and sprinkler system pressure and flow demands simultaneously. 2) A normally closed valve that opens automatically upon failure of the primary sprinkler pump segregates the fire main. 3) The fire pump starts automatically upon failure of the sprinkler pump or loss of sprinkler system pressure. A pressure tank meeting the following requirements shall be provided. Details of an alternative installation (a dedicated pump in lieu of a pressure tank) are provided in the standard: (9-6.2.1 and A-7-2.3.3) 5

1) The tank volume shall be sufficient to provide the hydraulic most demanding area for one minute 2) For hydraulically calculated systems, the pressure tank design shall be sufficient to provide the initial tank charge pressure (P i ) as follows: P i = ((P f +15)/A) -15 where: P i =initial tank pressure P f = final tank pressure (from calcs) A= proportion of air in tank The pressure tank shall be designed in accordance with ASME Pressure Vessel Code and be provided with a relief valve. (9-6.2.1). See Marine Safety Center PRG E1-19 for pressure vessel requirements. A suitable means of replenishing the air under pressure and the fresh water standing charge in the tanks shall be provided. A sight glass shall be provided on the tank. (9-6.2.1) Two sources of power with separate feeders are required for the air compressors that supply air to the pressure tank. The normal source of power shall be the emergency switchboard. (9-6.2.3) Valves shall be provided on the pressure tank air connection to prevent backflow of water into the air system and to restrict the amount of air entering the tank. (9-6.2.6) Fire department and Int l shore connections shall be provided near the gangway or other location so that they are readily accessible to a land based fire department. Connections may be required on both sides of vessels depending on shore access arrangements. (9-2.7.1) The firemain shall be cross-connected to the sprinkler system and fitted with a lockable, screw down, non-return valve to prevent backflow from the sprinkler system to the firemain. (9-6.4.3) The fire department cross connect for a wet pipe system shall be connected downstream of the sprinkler pump discharge check valve. For a dry pipe system, the connection shall be located between the sprinkler pump check valve and the dry valve. (4-15.2.3) Shut-off valves are prohibited in the fire department cross connect piping. A listed check valve shall be provided at each water supply including the fire dep t connection. (4-15.2.4.) 6

Dry pipe systems with capacities > 500 gallons shall be equipped with a listed quick opening device. Not more than 750 gallons system capacity shall be controlled by one dry pipe. Larger dry pipe non-gridded systems are acceptable if the design is such that water is delivered to the test connection within 60 seconds of activation. (3-2.3) Alarms, Indicators, Test Connections, Drains and Supports: Indicating, water supply and zone control valves shall be supervised in the open position at a central operating station. Locking open of valves is not an acceptable method of supervision. (9-2.6.1) Monitoring devices and individual alarms, located at a central operating station, shall be provided for the following: (9-4.12) 1) Water supply valve positions 2) Sprinkler pump power and operation 3) Pressure tank level, pressure and temperature 4) Zone water flow alarms 5) Dry pipe valve pressures (as applicable) Listed water flow alarms shall be provided for each zone. Paddle wheel type alarms are acceptable only on wet type systems. (2-9.1 & 2-9.2.4) Test connections shall be provided for each water flow alarm and dry pipe valve. (4-15.1.1.3) Flow alarm and dry pipe test connections shall not be less than 1 inch in diameter and shall have an orifice equivalent to that of the smallest sprinkler in the system. If required, the dry pipe test connection shall be located in the most distant sprinkler pipe. (4-15.4.2 & 3) A drain/test connection shall be provided on the discharge side of the sprinkler pump. The pipe should be of adequate size to discharge the amount of water required by the hydraulically most demanding area. (9-6.3.5) Drain and test lines shall not be connected to housekeeping, sewage or deck drains; drainage to the bilge is acceptable. Test/drain overboard discharge connections shall conform to the overboard discharge requirements of 46 CFR 56.50-95. (9-4.11). For wet pipe systems, listed pressure gauges are required in each riser and on both sides of alarm check valves and at each alarm flow switch of a wet pipe system. (3-1.1) 7

Control, drain and test valves shall be provided with metal or plastic identification tags secured with corrosion resistant wire or chain. (2-7.3) Pipes shall be supported by primary structural members of the vessel such as beams, girders, and stiffeners. Pipe supports shall be welded to the structure. Screw down type hangers are not permitted. With the exception of the portion welded to the structure, pipe supports shall be listed. (9-2.5.1) U-hook type pipe supports shall be sized in accordance with table 2-6.4.1 Additional Requirements for Dry Pipe Systems: For dry pipe systems, listed pressure gauges are required on both sides of the dry pipe valve, at the air compressor/receiver, air supply pipe to the dry pipe system, and at exhausters/accelerators. (3-2.1) The compressed air source for a dry pipe system shall be capable of restoring normal pressure on the system within 30 minutes. (3-2.6.2) The dry pipe air connection shall not be less than ½ inch in diameter and shall enter the system above the priming water level of the dry pipe. A renewable seat type stop valve and check valve are required. (3-2.6.3) The dry pipe pressure shall be maintained IAW dry pipe valve instructions or 20 psi in excess of the pressure required to trip the valve. (3-2.6.7) High Speed Craft Sprinkler Systems Manual and automatic sprinkler systems for high speed craft shall be designed in accordance with reference (e). Disclaimer: This guidance is not a substitute for applicable legal requirements, nor is it itself a rule. It is not intended to nor does it impose legally-binding requirements on any party. It represents the Coast Guard s current thinking on this topic and may assist industry, mariners, the general public, and the Coast Guard, as well as other federal and state regulators, in applying statutory and regulatory requirements. You can use an alternative approach for complying with these requirements if the approach satisfies the requirements of the applicable statutes and regulations. If you want to discuss an alternative, you may contact the Marine Safety Center (MSC), the unit responsible for implementing this guidance. 8