P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification

Similar documents
SPECIFICATION MODEL 5200 GAS MONITOR SYSTEM. User Instructions For The Model 5200 Gas Monitor System

SIL 2. Ultima X Series Gas Monitors CERTIFIED

5New features & EXtreme design, now with HART Protocol and DuraSource Technology. Ultima X Series Gas Monitors

ULTIMA XL/XT Series Gas Monitors. [ Ultimate Features Extreme Design ]

Toxic Gas Detection. Model F12. Toxic Gas Detection

Model D12. Digital Gas Transmitter

Digital Gas Transmitters with Auxiliary Inputs & Control. PolyGard 2 DC6

Model D12-IR. Digital Gas Transmitter...

Sieger Apex. Flexibility that meets your requirements

GasSens. Self Checking Gas Sensors. Modular Gas Detector... Gas & Range Availability

Self-contained and intrinsically safe wireless stand-alone multi-point gas detector.

ULTIMA XIR ULTIMA X 3 ULTIMA XE. ULTIMA X Series. [ State-of-the-Art Gas Monitoring]

Frequently Asked Questions

ALTAIR 5X Multigas Detector Product Specification

REMOTE TOXIC, COMBUSTIBLE, AND OXYGEN GAS SENSORS WITH LOCAL DIGITAL DISPLAY

ULTIMA X5000. MSAX5000.com

REMOTE TOXIC, COMBUSTIBLE, AND OXYGEN GAS SENSORS

EAGLE 2. 6 Channel Capacity. Inlet fitting. Loud buzzer (95dB) IrDA communication port Low flow shutoff and alarm Alarm LED s with wide visibility

SPECIFICATION CHEMGARD INFRARED GAS MONITOR SERIES

UniSens. 2-Wire Gas Transmitter. 6 Iron Bridge Drive Unit 1 & 2 Gatehead Business Park

OLC(T) 100 FIXED GAS DETECTOR

3years. Detection of explosive gases, toxic gases and oxygen. Infrared XP IR version. SIL 2 high reliability IP 66.

FREEDOM SERIES 5000 AND 5600 GAS TRANSMITTERS

Toxic Smarter Transmitter Instruction Manual

Detection of explosive gases, toxic gases or oxygen. Infrared XP version. SIL 2 high reliability IP 66. Certifications. The Fixed Gas Detection People

FX-SMT Series INSTRUCTION MANUAL P/N THERMO ELECTRON CORPORATION ENVIRONMENTAL INSTRUMENTS 27 FORGE PARKWAY FRANKLIN MASSACHUSETTS 02038

WARRANT Y AND LIMITS OF LIABILIT Y Vulcain Inc. warrants to the original purchaser that its product, and the component parts thereof, will be free fro

Product Selection Guide Fixed Gas Detection Systems for Personnel & Equipment Safety

Detection of explosive gases, toxic gases or oxygen. Infrared XP version. SIL 2 high reliability IP 66. Aluminium or Stainless Steel version

M2A Transmitter Operator s Manual

Two-Channel Gas Controller

Warranty Registration

4-20mA CYBER Cyber Transmitter for flammable, toxic and IR gas detection Cyber Head Increased security in ATEX certified head

M2 Transmitter Operator s Manual

SAFETY CERTIFIED MODEL FP-700 COMBUSTIBLE GAS DETECTOR

Xgard. Fixed detectors For flammable, toxic or oxygen gases

UniSens 2-Wire Gas Transmitter

Model C Combustible Gas Transmitter. 6 Iron Bridge Drive Unit 1 & 2 Gatehead Business Park

Sieger Sensepoint. Easy to Use Factory set operation Simple to replace Minimal training required

3M Oldham OLCT 100. Description. Fixed Gas Detector

compact detector Detection of more than 200 flammable and toxic gases iso 9001:2008

The Art of Gas Detection

5 Operating Modes GX Smallest 6 gas sample draw PID library of over 600 VOC s 2 Interchangable smart sensor slots

5 Operating Modes GX Smallest 6 gas sample draw PID library of over 600 VOC s 2 Interchangable smart sensor slots

Fixed Gas & Flame Detection International Product Range Overview

GAS DETECTOR ST400EC PART.NO

ESD3000 ESD200 Combustible / Toxic Gas Detector

IGD.CO.UK

OLCT 100 DETECTION DE GAZ FIXE. Certifications. Better detection. Better protection. Detection of Combustible, Toxic or Oxygen gases

INSTALLATION AND OPERATING INSTRUCTIONS

FIXED POINT SINGLE OR DUAL GAS MONITOR WITH DUAL ANALOG OUTPUTS

Combustible Gas Detection and Control System

APPLICATION DATA SHEET

MSA Gas Detection. for the Water and Wastewater Industries. Does your facility meet NFPA 820?

Sieger Sensepoint. Easy to Use Factory set operation Simple to replace Minimal training required

Dräger Polytron 5700 IR Detection of flammable gases and vapours

Dräger Polytron Fixed Gas Detector. Dräger Polytron 5700 Infrared DrägerSensor PIR 7000 to detect combustible gases and vapors

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

GAS DETECTION MANUFACTURED BY. Aerionics, Inc. Sioux Falls, SD Phone:

Operation and Maintenance Manual

PolyGard Single Point Controller SPC-X3-11XX for Toxic Gases and Oxygen

S5000 Gas Monitor. GMS5000.com

Duct and Rough Service Carbon Monoxide Sensor

OLCT 10N. Digital Gas Detector. User Manual. The Fixed Gas Detection Experts. Part Number: NPO10NEN Version: G.1

Quality. Water. Water Quality. Testing. Testing. Toxic Gas Detection. Toxic Gas. Detection. Air Quality. Monitoring. Monitoring. Monitoring.

MERIDIAN UNIVERSAL GAS DETECTOR

Sensepoint. Fit For Purpose Flammable, toxic and oxygen versions available High performance, low cost Suitable for new and retro fit applications

Satellite XT. Analogue or digital Point-of-Use gas detection transmitter to detect toxic, corrosive and combustible gases

Dräger Polytron 8310 IR Detection of flammable gases and vapour

Intelligent combined sensor for Air Quality (VOC) + Humidity (rh) + Temperature (T) with analogue outputs, Modbus and LCD display. Features.

SAFESITE Multi-Threat Detection System

Model 1000 H 2 S E-Chem/ CO 2 Process Analyzer

Warranty Registration

GLD-30 Gas Leak Detector

SEC 2000 Millenium Infrared Gas Detector

EXAMPLES OF HOW TO ORDER

MSA Customer Service MSA-INST

SP-220. Features. Combustible handheld gas leakage detector

EXAMPLES OF HOW TO ORDER

Combustible and Toxic Gas Detection Solutions. Performance and Safety Beyond Compliance

GasSens. Hydrogen Peroxide Monitor. 6 Iron Bridge Drive Unit 1 & 2 Gatehead Business Park

Instructions TXL Series Oxygen and Toxic Gas Detectors 4/

Gas Detection. - Disposable - Serviceable. Single Gas Detectors

Equipment. Model R002. Description. SF6 leak detector

MSA Fixed Gas & Flame Detection for the Automotive Industry

Detectors-Transmitters for Flammable, Toxic Gases and Oxygen. Non-intrusive operation via intrinsically safe infrared remote control.

FIXED POINT SINGLE OR DUAL GAS MONITOR WITH DUAL ANALOG OUTPUTS

GasAlertMicroClip X3 Specifications

Inc Series Digital Gas Detector/Controller. Operation Manual

Combustible and Toxic Gas Detection Solutions. Performance and Safety Beyond Compliance

Sensepoint. Fit For Purpose Flammable, toxic and Oxygen versions available High performance, low cost Suitable for new and retro fit applications

GAS MONITOR Model Model

Series F12/D Toxic Gas Transmitter

Carbon Monoxide Transmitter

GAS PLUS ALARM SYSTEM

GG-LEL2 COMBUSTIBLE GAS SENSOR. Installation and Operation Manual

Dräger Polytron 8700 IR Detection of flammable gases and vapors

RIG RAT III. Wireless Multi-Point Gas Detection System. The Stand-Alone Solution

Oxygen (O2) Single-Point Gas Detection System

Carbon Monoxide (CO) Gas Detectors with (0)2-10 Vdc or (0)4-20 ma Output

Transcription:

P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification 1.0 This specification details the attributes and operating characteristics of the MSA Ultima X Series sensors/transmitters. The following table can be used to identify and document gas sensing requirements: None Carbon Monoxide Carbon Monoxide 0-500 PPM Oxygen 0-10% Oxygen 0-25% Chlorine 0-5 PPM Nitric Oxide Hydrogen Cyanide Hydrogen Chloride Chlorine Dioxide 0-3 PPM 0-500 PPM Hydrogen Fluoride Chlorine 0-100% LEL - Natural Gas & H2 0-100% LEL Petroleum Vapors 0-100% LEL Solvents Acetylene IR 0-100% LEL Carbon Dioxide IR 0-5000 PPM Carbon Dioxide IR 0-2% Carbon Dioxide IR 0-5% IR Combustible 0-100% LEL- Methane IR Combustible 0-100% LEL Propane Phosphine 0-2 PPM Arsine 0-2 PPM Silane 0-25 PPM Diborane Bromine 0-5 PPM Fluorine Ammonia 0 100 PPM Hydrogen 0-1000 PPM Rev 2 3/2014 Page 1 of 6

Ethylene Oxide 0-100% LEL - ATEX - 4.4% CH4, Natural Gas and H2 0-100% LEL - ATEX - 1.7% Propane Petroleum Vapors 0-100% LEL - ATEX - 1.7% Propane Solvents Ammonia 0-1000 PPM Solvent Tolerant Oxygen Carbon Monoxide 0-1000 PPM IR Methane 0-100% LEL ATEX - 4.4% CH4 IR - Non Methane 0-100% LEL - ATEX 1.7% Propane Chlorine 0-20 PPM Solvent & CO2 Tolerant Oxygen 0-25% Low Oxygen 0-25% Low Solvent Tolerant Oxygen 0-25% Sulfur Dioxide 0-25 PPM Sulfur Dioxide Nitrogen Dioxide 2.0 The Ultima X Series Sensors/Transmitters consist of Series Models XA and XE. The Ultima XA is contained in a plastic, general-purpose enclosure and the Ultima XE is contained in a 316 stainless steel explosion-proof enclosure. Both models have common electronics, software and optional features. 3.0 Sensor/Transmitter Requirements 3.1 Catalytic Bead Type Combustible Sensor/Transmitter 3.1.1 The catalytic bead type combustible sensor must have a demonstrated resistance to degradation of silicones and reduced sulfur gases. 3.1.2 The catalytic combustible sensor/transmitter shall detect for an above 100%LEL condition (over-range). This condition must be indicated on the front panel LCD. 3.1.3 The interconnect wiring from the combustible transmitter to the sensor shall be a 5-wire cable. 3.2 Infrared Combustible Sensor/Transmitter 3.2.1 The infrared (IR) combustible sensor must be capable of calibration without gas. The sensor/transmitter must be capable of performing a full calibration by zero adjustment only. 3.2.2 The IR sensor/transmitter shall detect for an above 100%LEL condition (over-range). This condition must be indicated on the front panel LCD. 3.2.3 The IR sensor/transmitter shall not contain a flashback arrestor / frit. 3.2.4 The IR sensor/transmitter must allow for a gas check without alternate calibration / gas check fittings or cap. 3.3 Electrochemical (Toxic and Oxygen) Sensors/Transmitters 3.3.1 The electrochemical sensor/transmitters shall not require the periodic addition of reagents. 3.3.2 The interconnect wiring from the electrochemical transmitter to the sensor shall be a 5-wire cable. Rev 2 3/2014 Page 2 of 6

3.4 Sensor/Transmitter Operating Requirements 3.4.1 Operating Voltage - The sensor/transmitter can operate between 8-30 VDC. 3.4.2 Sensor/transmitter electronics shall consist of one PCB. This PCB shall offer expandability to allow for optional LED s and relays. 3.4.3 The single PCB shall not require tools for installation or removal. 3.4.4 The single PCB must be self-aligning in the enclosure. 3.4.5 Sensor/transmitter shall require the following wiring configurations: 3.4.5.1 2-wire cable for electrochemical (toxic and oxygen sensors) units configured without LED or relay options. 3.4.5.2 3-wire cable for electrochemical (toxic and oxygen sensors) units configured with LED and relay options. 3.4.5.3 3-wire cable for all combustible units (configured with or without LED or relay options). 3.4.6 Sensor/transmitter shall allow for optional reset connector for resetting latched alarms. 3.4.7 Set-up and start-up of the sensor/transmitter will be so that the enclosure need not be opened during this process. 3.4.8 Sensor/transmitter shall be factory calibrated, ready for use out of the box. A gas check is all that is required to ensure proper operation. 3.4.9 Sensor/transmitter shall contain no pots, jumpers or switches. 3.4.10 Sensor/transmitter output signal shall be 4 to 20mA or HART. The combustible sensor/transmitter will be a sourcing type of signal capable of operating into a 600-ohm load. The toxic gas or oxygen sensor/transmitter will operate on a 2-wire or 3-wire current loop. 3.5 Sensor/Transmitter Display 3.5.1 There will be a local display indicating the gas type being monitored and the concentration of gas present. The display will alternate between the gas type (1 second) and gas concentration (5 seconds). The display will be an integral part of the sensor/transmitter enclosure. The display will be visible from a minimum of 5 feet and will be present always, and will not require being turned on or off. This readout will be three, one half-inch (3 1/2") digit Liquid Crystal Displays (LCD). 3.5.2 Sensor/transmitter display shall indicate all diagnostic check/fault conditions with a scrolling message detailing the condition. Error codes shall not be used. 3.5.3 Sensor/transmitter will display 3 levels of alarm. Alarm levels will be adjustable by means of a hand held infrared controller or a HART hand held communicator. 3.6 Smart Sensor Technology 3.6.1 Sensors shall be contained in sensor modules mounted external to the main enclosure. All sensor modules shall have the capability of replacement while the unit is under power (hazardous areas) without the need for tools. 3.6.2 Sensor modules shall contain all relevant sensor information within the module. This information shall include sensor manufacturer date, gas Rev 2 3/2014 Page 3 of 6

type, gas range, calibration data, and default relay parameters. 3.6.3 Sensor module shall store all calibration data so that the module may be calibrated off site and installed in the field without the necessity of recalibration. The sensor module shall not require a battery or power source to store this data. 3.7 LED / Relay Options 3.7.1 Sensor/transmitter shall have optional LED s, viewable from 50 feet, minimum. The LED s shall operate as follows: 3.7.1.1 Solid green LED normal operation (measure mode) 3.7.1.2 Solid red LED fault condition 3.7.1.3 Blinking red LED alarm condition 3.7.2 Sensor/transmitter shall have optional relays. Relays shall be rated at 5 amps @ 30VDC, 5 amps @ 220VAC, single-pole, double-throw and consist of three for alarm levels and one for fault. All relay contact activation will be monitored. If the relay cannot activate for any reason, the trouble relay will change state. All relays shall be field selectable through a non-intrusive hand-held wireless remote control unit (Controller) or a HART hand held communicator. Selectable features include: 3.7.2.1 Alarm level 3.7.2.2 Latching / Non-latching 3.7.2.3 Upscale / Downscale 3.7.2.4 Normally-opened / Normally-closed 3.7.2.5 Energized / De-energized 3.8 Other Features 3.8.1 Sensor/transmitter shall allow for full range scaling of the 4-20mA-output signal. 3.8.2 Sensor/transmitter will be capable of storing and displaying average, minimum and maximum gas concentrations over selected periods of time. 3.8.3 The sensor/transmitter will give an indication of when sensor is nearing the end of its useful life by means of the front panel LCD. This indication that the sensor is nearing its useful life will be based on the sensor output. It shall not be based on the time the sensor was in service. 3.8.4 The sensor/transmitter units can be located remote from a monitor/readout unit by up to 4000 feet via properly gauge wire. 3.9 Sensing Element Warranty 3.9.1 All electrochemical and catalytic bead sensing elements (sensors) will have a minimum useful life of one year. The supplier will provide replacement sensors at no charge for any sensor that does not meet the minimum requirement. 3.9.2 The IR source in the infrared sensor will have a minimum useful life of ten (10) years. The supplier will provide replacement sensors at no charge for any sensor that does not meet the minimum requirement. 4.0 Sensor Enclosure Parameters Rev 2 3/2014 Page 4 of 6

4.1 General-purpose Sensor/Transmitter 4.1.1 Sensor/transmitter will be a plastic enclosure designed to meet Nema 4X requirements. 4.2 Explosion-proof Sensor/Transmitter 4.2.1 The sensor/transmitter will be in a 316 stainless steel enclosure suitable for location in Class I, Division 1 & 2, Groups A, B, C & D classified areas. 4.2.2 The enclosure shall have a minimum of four entries, allowing for flexible mounting options for sensor, power, signal, and optional relay wiring. 4.2.3 The enclosure shall offer a means to mount without using an entryway. 5.0 Sensor/Transmitter Single Condulet Mounting 5.1 General-purpose Sensor/Transmitter 5.1.1 Sensor/transmitter will be mounted in a single condulet. The back portion of the enclosure shall be separate from the electronics, allowing for mounting and wiring of the unit without the electronics present. 5.2 Explosion-proof Sensor/Transmitter 5.2.1 Sensor/transmitter will be mounted in a single condulet. The back portion of the enclosure shall be separate from the electronics, allowing for mounting and wiring of the unit without the electronics present. 6.0 Sensor/Transmitter Remote Sensor Mounting 6.1.1 The sensor portion of the sensor/transmitter unit will be capable of being able to be remotely mounted from the electronics and display. The separate sensor enclosure will be able to be mounted up to one hundred (100) feet from the main enclosure. 6.1.2 The sensor housing for the explosion-proof Gas Monitor will be in an enclosure suitable for location in Class I, Division 1, Groups A, B, C & D, Class II, Division 1, Groups E & F, Class III classified areas. 6.1.3 A two twisted pair cable will connect the sensor housing and the calibration electronics. 6.1.4 The readout portion of the sensor/transmitter shall have a display of the concentration of gas present. The display will be visible from a minimum of 5 feet and will be present at all times. It will not be required to be turned on or off. This readout will be three, one half inch (3 ") digit Liquid Crystal Displays (LCD). 7.0 Installation and mounting hardware 7.1 A mounting strap shall be used which mounts the sensor/transmitter to a wall or similar structure. 7.2 The mounting strap shall attach to the sensor/transmitter via two tapped and threaded holes on the rear of the sensor/transmitter. There shall be no brackets or clamps to secure this strap to the sensor/transmitter. 8.0 Approvals 8.1 The general-purpose monitor shall have CE approval. 8.2 The explosion-proof monitor shall have Class I, Division 1 & 2, Groups A, B, C, and D; Class II, Division 1, Groups F & G; Class III approval. Rev 2 3/2014 Page 5 of 6

8.3 The explosion-proof Remote Sensor shall have Class I, Division 1 & 2, Groups A, B, C, and D, Class II, Division 1, Groups F & G; Class III approval. 8.4 The explosion-proof infrared monitor shall have Class I, Division 1 & 2, Groups A, B, C, and D; Class II, Division 1, Groups F, and G, Class III approval. 9.0 Non-intrusive Calibration Capability 9.1.1 All sensor/transmitters can be calibrated without opening any enclosures. 9.1.2 By means of a non-intrusive hand held wireless remote control unit or a HART hand held communicator, the sensor/transmitter will enter the calibration mode. The display of the sensor/transmitter will instruct the user on when to apply zero and span gas. The sensor/transmitter will automatically adjust its internal settings to the proper calibration values without further intervention by the user. Upon completion of a successful calibration, the sensor transmitter will exit the calibration mode. Date stamp of last successful calibration will be retained in the sensor/transmitter internal memory, with capability to be displayed on LCD. If calibration is unsuccessful for any reason, the display must show an unsuccessful calibration attempt and revert to its previous calibration settings. Use of flashlight type devices, magnets or clamp-on devices to achieve calibration is not acceptable. The acceptable methods are to use a transmitter, which employs a digitally encoded infrared light beam, or a HART hand held communicator. 9.1.3 There will be two types of non-intrusive hand held wireless remote control units available: 9.1.3.1 A small non-intrusive hand held wireless remote control will let the user only perform sensor zeroing, calibration and setting the multiplex address. 9.1.3.2 A larger non-intrusive hand held wireless remote control will let the user not only do the functions of the small remote control but activate all functions and features of the sensor/transmitter. 9.1.3.3 The sensor/transmitter will not be affected by low level ambient light either natural or man-made. 10.0 Manufacturer Capability Requirements - As a minimum, the Gas Monitoring Equipment manufacturer must meet the following requirements. 10.1 The manufacturer must be capable of supplying all equipment used to check or calibrate the sensor/transmitter units. 10.2 The manufacturer must be capable of providing on site service with factory trained personnel. 10.3 The manufacturer must be capable of providing on site training for owner/operator. 11.0 The sensor/transmitter shall be a MSA Ultima X Series Gas Monitor Sensor/Transmitter or equal. Rev 2 3/2014 Page 6 of 6