Fire Protection Systems Operation and Maintenance 3 PDH / 3 CE Hours

Similar documents
Fire Protection System Contractors and Systems. Submission of the Application for a Water-Based Fire Protection Inspector Permit

Fire Protection System Contractors and Systems. Submission of the Application for a Water-Based Fire Protection Inspector

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016

CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS

Winnipeg Fire Department Fire Prevention Branch

Risk Based Reliability Centered Maintenance of DOD Fire Protection Systems

CHAPTER A-6 FIRE PROTECTION

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment

Florida Building Code 2010

STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT

PERFORMANCE TECHNICAL SPECIFICATION *************************************************************************** SECTION D40 FIRE PROTECTION 02/18

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

Changes in NFPA

Service Requirements SEMI- ANNUAL ANNUALLY OTHER REF. REQUIREMENT

Revision May All designs must be submitted to FM Global for review and approval prior to issuing such for bids.

Inspection and Testing of Water-Based Systems

Life Safety Code NFPA 10 NFPA 13 NFPA 25 NFPA 72 NFPA 90A NFPA 110 NFPA 99 THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #7

PINETOP FIRE DEPARTMENT TIMBER MESA FIRE AND MEDICAL DISTRICT

MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS

Fire Alarm Inspection, Testing, Maintenance. Assuring the System s Operational Reliability

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

FIRE PROTECTION ENGINEERING FOR FACILITIES

CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS

Global Property. SEMIANNUAL FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:

Narrative Reports As Regulated by 780 CMR, Section 903.0

CAN/ULC-S1001, INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION & LIFE SAFETY SYSTEMS Simon Crosby, LEL, CET, CFPS October 21, 2015

UNIFIED FACILITIES CRITERIA (UFC) FIRE PROTECTION ENGINEERING FOR FACILITIES

Global Property. QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:


TRI-LAKES MONUMENT FIRE PROTECTION DISTRICT

2018 NICET Code Transition Changes

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition

BP U.S. Pipelines and Logistics (USPL) Safety Manual Page 1 of 6

MNEC NFPA 72 WHITE PAPER

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE, 2000 EDITION SECTIONS

Report on First Revision June 2014 NFPA 5000

UNIFIED FACILITIES GUIDE SPECIFICATIONS

INSPECTION AND TESTING FORM

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

CAN/ULC-S INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS

TetraTek, Inc. Regulatory. Compliance. Emergency Response. Nuclear Facility Compliance. Compliance. Fire Protection.

Public Input No. 4-NFPA [ Section No. 4.2 ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

EC 5.10 FIRE PREVENTION MANAGEMENT

FIRE PROTECTION PROGRAM

OPTIONAL INFORMATION PORTABLE FIRE EXTINGUISHERS SELF INSPECTION CHECKLIST

Oklahoma. 265: Incorporated national codes and standards The following national codes and standards are incorporated by reference:

CAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning

Table OUT OF SERVICE. Building Fire Video 1/15/ Inspection, testing and maintenance. Standards Further Referenced by FCNYS

*HB0217* H.B. 217 H.B STATE FIRE CODE ACT AMENDMENTS. LEGISLATIVE GENERAL COUNSEL 6 Approved for Filing: C.R. Gilbert :11 PM 6

Fire Suppression Introduction Contact Information

Fight or Flee? Extinguisher Basics Extinguisher Use Extinguisher Placement and Spacing Hydrostatic Testing OSHA Requirements Test Your Knowledge

System Test Report CLEAN AGENT

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements

Understanding, Applying and Enforcing NFPA 25. James D. Lake NFSA Director of Training

UNIFIED FACILITIES CRITERIA (UFC)

WEST VIRGINIA UNIVERSITY

UNIFIED FACILITIES CRITERIA (UFC) FIRE PROTECTION ENGINEERING FOR FACILITIES

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement

EXHIBIT D ATTACHMENT G - UNIT PRICING DMS-14/15-039B - SIMPLEXGRINNELL, LP FIRE SPRINKLER SYSTEM INSPECTIONS YEARS 1-5

Owner/Operator Guide for Successful Sprinkler and Fire Pump Systems

Fire Prevention Plan Program

DOE STANDARD FIRE PROTECTION

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1

CAMPUS COMMUNITY FIRE AND LIFE SAFETY POLICY

DESIGN AND O&M: MASS NOTIFICATION SYSTEMS

Health Chapter ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE

UNIVERSITY. Facilities Management

Hydrostatic Retest Requirements for ANSUL Pressure Vessels

NFPA CODE TESTING & INSPECTION. Requirements & Recommendations for. Licensed Florida Hospitals, Ambulatory Surgery Centers,

COURSE SYLLABUS FIRE ALARM AND FIRE SUPPRESSION SYSTEMS CORRESPONDENCE COURSE

Risk Based Reliability Centered Maintenance of DOD Fire Protection Systems

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD

2018 International Fire Code. Add new text as follows:

Southaven Fire Department Fire Marshal s Office 8710 Northwest Drive Southaven, Mississippi Phone: Fax:

Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016

OUTLINE FOR FIRE PREVENTION ACTIVITY

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION

BUILDING CODE INTERPRETATION

El Reno Fire Department Fire Alarm Plan Review Worksheet

DOD FUELS LABORATORY STANDARDS UFC

DRAFT REGULATORY GUIDE DG-1069 FIRE PROTECTION PROGRAM FOR NUCLEAR POWER PLANTS DURING DECOMMISSIONING AND PERMANENT SHUTDOWN


Fire Prevention Plan

FIRE PREVENTION OFFICE Placer Hills Fire Protection District NEW PROJECT GUIDELINES

USAF Built Infrastructure Inventory and Assessments Manual

Subchapter 7. General Industry Safety Orders Group 27. Fire Protection Article 157. Portable Fire Extinguishers. Return to index New query

DESIGN AND O&M: MASS NOTIFICATION SYSTEMS

An Overview of Extinguishing Systems for Computer Equipment

FIRE PROTECTION SYSTEMS

UNIFIED FACILITIES CRITERIA (UFC) HOST NATION FACILITIES IN SUPPORT OF MILITARY OPERATIONS

NFPA 99 for Facility Managers

4/18/2017. *2012 edition of NFPA 99 has gone through a major overhaul. *This document is now a Code.

DEALING WITH FIRE SAFETY

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

UNIFIED FACILITIES GUIDE SPECIFICATIONS

NFPA Changes

UFGS (June 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS

Transcription:

Fire Protection Systems Operation and Maintenance 3 PDH / 3 CE Hours United Facilities Criteria U. S. Department of Defense UFC 3-601-02 PDH Academy PO Box 449 Pewaukee, WI 53072 www.pdhacademy.com pdhacademy@gmail.com 888-564-9098 Continuing Education for Architects and Engineers

Fire Protection Systems Operation and Maintenance Final Exam 1. When the impairment will exist for more than hours, the local maintenance activity, the local fire authority, the local safety authority, and the facility or area user shall jointly develop written compensatory measures to ensure personnel safety. a. 24 b. 72 c. 36 d. 48 2. Unrequired features can be abandoned in place pending final removal if all public interface devices are: a. removed b. disabled c. taped off d. re-labeled 3. The type and frequency of ITM tasks for fire detection and alarm systems depend on whether the system is: a. older or newer b. in a larger or smaller building c. under-designed d. monitored or not 4. As per Table 2-1, certain ITM tasks for Control Panel and Annunciator Equipment (monitored) should be performed: a. monthly b. annually c. bi-annually d. weekly 5. As per Table 2-3, certain ITM tasks for Strainers should be performed every: a. year b. 10 years c. 5 years d. 3 years

6. Main drain static or residual test pressures that vary more than percent from the previous test readings or the original acceptance readings require immediate evaluation to determine the cause. a. 5 b. 15 c. 10 d. 18 7. Low-expansion foam systems for flammable liquid tanks are covered in: a. NFPA 212 b. AFFF 11 c. AWWA Manual 17 d. NFPA 11 8. Flow tests results that vary more than percent from the previous test readings or the original acceptance readings require immediate evaluation to determine the cause. a. 10 b. 15 c. 5 d. 20 9. Flow tests results that vary more than percent from the previous test readings or the original acceptance readings indicate an emergency situation. a. 10 b. 5 c. 18 d. 20 10. To prevent accidental release of gas to the environment, do not disconnect and weigh cylinders to accomplish the annual agent quantity verification. a. carbon dioxide b. Halon c. foam concentrate d. Hydrochloric

CONTENTS

FIGURES UFC 3-601-02 TABLES

CHAPTER 1 UFC 3-601-02 INTRODUCTION BACKGROUND PURPOSE AND SCOPE APPLICABILITY

AUTHORITY Title 10 United States CodeMilitary Child Care Title 15 United States CodeFire Safety Systems in Federally Assisted Buildings Title 15 United States CodeUtilization of Consensus Technical Standards by Federal Agencies Title 29 United States CodeFire Protection Title 29 United States CodeBasic Program Elements for Federal Employee Occupational Safety and Health Programs and Related Matters REFERENCES OBJECTIVE CRITERIA Systems and Applications Not Covered

Conflicts Exemptions Authority Having Jurisdiction (AHJ) Note:

PERSONNEL QUALIFICATIONS UFC 3-601-02 ITM Tasks

Other Inspections RECORDS SYSTEM IMPAIRMENT OR OUT-OF-SERVICE WARNING REPAIR OR CORRECTION OF IMPAIRMENTS TO SYSTEM OR FEATURE PERFORMANCE

SYSTEM IMPAIRMENTS AND REPAIRS AND CORRECTIONS REPORTING

Figure 1-1. System Out-of-Service or Impaired Sign UFC 3-601-02

CHAPTER 2 UFC 3-601-02 FACILITY SYSTEMS RCM METHODOLOGY Features Requiring Maintenance Unrequired Features ITM TASK DESCRIPTIONS AND FREQUENCIES Note: Task Descriptions Supervised Components

Event-Driven Tests Excluded National Fire Code Tasks Non-ITM Activities Medical Facilities Fire Extinguishers Fire Detection and Alarm Systems WARNING Fire alarm systems with more than two abnormal conditions (trouble conditions) are outside their minimum tested or listed operating parameters and may not meet their performance requirement for receipt or transmission of subsequent alarm or additional trouble conditions. WARNING Any fire alarm system with more than three unexplained activations (fire indication conditions) in a 6-month period is experiencing a system instability that should be evaluated by a technician or engineer, and appropriate corrective measures should be implemented immediately.

CAUTION UFC 3-601-02 NOTE Table 2-1. Fire Detection and Alarm System ITM Tasks

Table 2-1. Fire Detection and Alarm System ITM Tasks (Continued)

Wet Pipe Automatic Sprinkler Systems CAUTION WARNING Main drain static or residual test pressures that vary more than 20 percent from the previous test readings or the original acceptance readings indicate an emergency situation. Immediate distribution system flow testing (paragraph 2-2.11) is indicated. Immediately conduct main drain tests on all adjacent sprinkler systems to determine the extent to which the sprinkler systems are compromised. Table 2-2. Wet Pipe Sprinkler Systems ITM Tasks

Table 2-2. Wet Pipe Sprinkler Systems ITM Tasks (Continued) UFC 3-601-02 Dry Pipe Automatic Sprinkler Systems CAUTION

WARNING UFC 3-601-02 Main drain static or residual test pressures that vary more than 20 percent from the previous test readings or the original acceptance readings indicate an emergency situation. Immediate distribution system flow testing (paragraph 2-2.11) is indicated. Immediately conduct main drain tests on all adjacent sprinkler systems to determine the extent to which the sprinkler systems are compromised. Table 2-3. Dry Pipe Automatic Sprinkler Systems ITM Tasks

Table 2-3. Dry Pipe Automatic Sprinkler Systems ITM Tasks (Continued)

Deluge Sprinkler Systems CAUTION WARNING Main drain static or residual test pressures that vary more than 20 percent from the previous test readings or the original acceptance readings indicate an emergency situation. Immediate distribution system flow testing (paragraph 2-2.11) is indicated. Immediately conduct main drain tests on all adjacent sprinkler systems to determine the extent to which the sprinkler systems are compromised. Table 2-4. Deluge Sprinkler Systems ITM Tasks

Table 2-4. Deluge Sprinkler Systems ITM Tasks (Continued) UFC 3-601-02

Pre-Action Automatic Sprinkler Systems CAUTION WARNING Main drain static or residual test pressures that vary more than 20 percent from the previous test readings or the original acceptance readings indicate an emergency situation. Immediate distribution system flow testing (paragraph 2-2.11) is indicated. Immediately conduct main drain tests on all adjacent sprinkler systems to determine the extent to which the sprinkler systems are compromised. Table 2-5. Pre-Action Automatic Sprinkler Systems ITM Tasks

Table 2-5. Pre-Action Automatic Sprinkler Systems ITM Tasks (Continued)

Table 2-5. Pre-Action Automatic Sprinkler Systems ITM Tasks (Continued) Water Spray Systems CAUTION WARNING Main drain static or residual test pressures that vary more than 20 percent from the previous test readings or the original acceptance readings indicate an emergency situation. Immediate distribution system flow testing (paragraph 2-2.11) is indicated. Immediately conduct main drain tests on all adjacent sprinkler systems to determine the extent to which the sprinkler systems are compromised.

Table 2-6. Water Spray Systems ITM Tasks UFC 3-601-02

Table 2-6. Water Spray Systems ITM Tasks (Continued)

Water Mist Systems Table 2-7. Water Mist Systems ITM Tasks Frequency Component Task

Table 2-7. Water Mist Systems ITM Tasks (Continued) UFC 3-601-02 Frequency Component Task Foam and Foam-Water Systems Table 2-8. Low-Expansion Foam Systems for Flammable Liquid Tanks ITM Tasks

Table 2-8. Low-Expansion Foam Systems for Flammable Liquid Tanks ITM Tasks (Continued)

Table 2-9. Foam Spray and Sprinkler Systems ITM Tasks

Table 2-9. Foam Spray and Sprinkler Systems ITM Tasks (Continued) Table 2-10. Foam Monitors Nozzle Systems ITM Tasks

Table 2-10. Foam Monitors Nozzle Systems ITM Tasks (Continued)

Table 2-11. Grate Nozzle Foam Systems ITM Tasks

Table 2-12. High-Expansion Foam Systems ITM Tasks

Standpipe Systems Table 2-13. Standpipe Systems ITM Tasks Hydrants and Monitors CAUTION WARNING Flow tests results that vary more than 20 percent from the previous test readings or the original acceptance readings indicate an emergency situation. Immediate distribution system flow testing (paragraph 2-2.11) is indicated. Immediately conduct main drain tests on all adjacent sprinkler systems to determine the extent to which the sprinkler systems are compromised.

Table 2-14. Hydrants ITM Tasks UFC 3-601-02 Frequency Component Task

Table 2-15. Yard Hydrant Monitors and Hose Houses ITM Tasks Frequency Component Task Fire Pumps Table 2-16. Fire Pumps ITM Tasks

Table 2-16. Fire Pumps ITM Tasks (Continued)

Water Supply Tanks Table 2-17. Water Supply Tanks ITM Tasks

Table 2-17. Water Supply Tanks ITM Tasks (Continued) Dry Chemical Systems NOTE: Table 2-18. Dry Chemical Systems ITM Tasks

Table 2-18. Dry Chemical Systems ITM Tasks (Continued) Wet Chemical Systems Table 2-19. Wet Chemical Systems ITM Tasks

Table 2-19. Wet Chemical Systems ITM Tasks (Continued)

Halon Systems Table 2-20. Halon Systems ITM Tasks

Table 2-20. Halon Systems ITM Tasks (Continued) UFC 3-601-02 WARNING To prevent accidental release of Halon gas to the environment, do not disconnect and weigh cylinders to accomplish the annual agent quantity verification. Disconnecting cylinders to verify agent quantity damages seals and o-rings. Only liquid level methods should be used to determine agent quantity. CAUTION

Figure 2-1. Liquid Level Measuring System UFC 3-601-02 Clean Agent Systems Table 2-21. Clean Agent Systems ITM Tasks

Table 2-21. Clean Agent Systems ITM Tasks (Continued) WARNING To prevent accidental release of extinguishing agents to the environment, do not disconnect and weigh cylinders to accomplish the annual agent quantity verification. Disconnecting cylinders to verify agent quantity damages seals and o-rings. Only liquid level methods should be used to determine agent quantity.

Carbon Dioxide Systems Table 2-22. Carbon Dioxide Systems ITM Tasks

Emergency Lighting Systems Table 2-23. Emergency Lighting Systems ITM Tasks CAUTION

Figure 2-2. Typical Emergency Lighting Systems Typical Emergency Light Units with a 5-year Manufacturer s Estimated Service Life Battery Typical Emergency Light Units and Florescent Fixture Ballasts with a 10-year Manufacturer s Estimated Service Life Battery Typical Central Emergency Power Sources with a 10-year Manufacturer s Estimated Service Life Battery Egress Marking Systems

Table 2-24. Egress Marking Systems ITM Tasks CAUTION

NOTE: Figure 2-3. Typical Egress Marking Units Typical Energy Star Egress Marking Units with a 10-year Manufacturer s Estimated Service Life Battery Figure 2-4. Typical Combination Egress Marking and Emergency Light Units Typical Combination Egress Marking and Emergency Light Units with a 5-year Manufacturer s Estimated Service Life Battery (not Energy Star compliant) NOTE:

Fire and Smoke Barrier Opening Protection Table 2-25. Fire and Smoke Barrier Opening Protection ITM Tasks

Table 2-25. Fire and Smoke Barrier Opening Protection ITM Tasks (Continued) Backflow Prevention Devices Table 2-26. Backflow Prevention Devices ITM Tasks

CHAPTER 3 UFC 3-601-02 MILITARY FAMILY HOUSING SYSTEMS SCOPE Residential Smoke Detectors Residential Sprinkler Systems ITM TASK DESCRIPTIONS

Caution UFC 3-601-02 Table 3-1. MFH Residential Smoke Detectors ITM Tasks Table 3-2. MFH Residential Sprinkler Systems ITM Tasks

GLOSSARY UFC 3-601-02 AFFF AHJ ANSI AWWA BOS CFR CO 2 DES-SO DLA DLSC-BIS DOD DOT FM FPEWG GOCO HQ AFCESA/CEO HQ DLA-D HQMC HQ USACE/CECW-CE ITM JCAHO LED MFH MS&O/ESO NAVFACENGCOM HQ-CHE NFPA NGA/SIO NICET

NRO OSHA RCM UFC U.S. USC UFC 3-601-02

APPENDIX A UFC 3-601-02 REFERENCES American National Standard for Safety Colors American National Standard for Environmental and Facility Safety Signs Recommended Practice for Backflow Prevention and Cross-Connection Control Installation, Field Testing, and Maintenance of Fire Hydrants Conduct of Inspections, Fixed Extinguishing Systems, General Fire Protection Standard Practice for Unified Facilities Criteria and Unified Facilities Guide Specifications Standard for Low-, Medium-, and High-Expansion Foam Standard on Carbon Dioxide Extinguishing Systems Standard on Halon 1301 Fire Extinguishing Systems

Standard for the Installation of Sprinkler Systems Standard for the Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes Standard for the Installation of Sprinkler Systems in Residential Occupancies up to and Including Four Stories in Height Standard for the Installation of Standpipes and Hose Systems Standard for Water Spray Fixed Systems for Fire Protection Standard for the Installation of Foam-Water Sprinkler and Foam-Water Spray Systems Standard for Dry Chemical Extinguishing Systems Standard for Wet Chemical Extinguishing Systems Standard for the Installation of Stationary Pumps for Fire Protection Standard for Water Tanks for Private Fire Protection Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems National Fire Alarm Code Standard for Fire Doors and Other Opening Protectives Life Safety Code Standard for Emergency and Standby Power Systems

Standard on Stored Electrical Energy Emergency and Standby Power Systems Standard on Water Mist Fire Protection Systems Standard on Clean Agent Fire Extinguishing Systems Operation and Maintenance: Water Supply Systems Fire Protection Engineering for Facilities Military Child Care Fire Safety Systems in Federally Assisted Buildings Utilization of Consensus Technical Standards by Federal Agencies