Releasing Systems. Rob Mennie Senior Consultant Gage-Babcock & Associates Ltd.

Similar documents
SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

Unified Fire Authority - Fire Prevention Bureau

Deluge & Preac tion Systems

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

FIRE SUPPRESSION SYSTEM

rpsa FIRE PROTECTION ENGINEERS

Fire Sprinkler Plan Submittal Form

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

Doc. No Part No Rev. U * T*

Vaults 5/03/2015. Introduction. Vault Types. Stand alone building Free standing structure VAULTS

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

NFPA Changes

COURSE SYLLABUS FIRE ALARM AND FIRE SUPPRESSION SYSTEMS CORRESPONDENCE COURSE

SECTION TOTAL FLOODING ECARO-25 CLEAN AGENT FIRE EXTINGUISHING SYSTEM

CAN/ULC-S INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE CHEETAH Xi 50 CONTROL PANEL SYSTEM

Protecting Your Property: Well Do You Know Your Fire Fire Systems Systems. Joe Szewczyk, Risk Control Consultant

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS

Checklist For Life Safety

Functional Performance Test

CAN/ULC-S1001, INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION & LIFE SAFETY SYSTEMS Simon Crosby, LEL, CET, CFPS October 21, 2015

Advanced Fire Alarm Systems Training Program Outline (5 Day)

CAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning

CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS

Detection, and Suppression Systems

Revised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required*

Agency for Health Care Administration

REED COLLEGE DEPARTMENT OF COMMUNITY SAFETY DEPARTMENTAL DIRECTIVE CSO FIRE & FIRE ALARM SYSTEM RESPONSE GUIDELINES

Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL

El Reno Fire Department Fire Alarm Plan Review Worksheet

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE

FIRE SAFETY UPGRADING CONSIDERATIONS for EXISTING SENIOR CITIZEN LODGES

I am Rick Jeffress and I handle sales for Fike Video Image Detection. We thank the AFAA for coordinating the venue for this presentation, and we

Specification/ Data Sheet

12/14/2013. Fire alarm and emergency power SPRINKLER HEAD

Fire Alarm System Fundamentals

NFPA CODE TESTING & INSPECTION. Requirements & Recommendations for. Licensed Florida Hospitals, Ambulatory Surgery Centers,

Building Fire Safety in New York City s Existing Office Buildings

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

Fire Alarm Wiring. Circuit types, styles and limitations

DCSS (ACB) Data Center Fire Suppression Procedures

An Overview of Extinguishing Systems for Computer Equipment

Symbols for Control Panels

FIRE INSPECTORS GUIDELINES FOR PLAN REVIEWS AND INSPECTIONS OF NEW CONSTRUCTION / ADDITIONS AND CHANGE OF OCCUPANCY

FIRE DETECTION & ALARM SYSTEM BASICS

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM

COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN

CITY OF MADISON FIRE DEPARTMENT (MFD) FIRE PROTECTION SYSTEM PLANS

INTEGRATED LIFE SAFETY COMPLIANCE TESTING AND ITS PROCEDURES

Date Issued: December 14, 2017 Revision: 2.1

CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS

System Test Report CLEAN AGENT

INSPECTION AND TESTING FORM

Plan Review Check List Fire Alarm System

Video Imaging Detection Systems

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

109-B Concord Drive Casselberry, FL DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72. Owner s Address: Owner's Phone Number:

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

Smoke Detector Activation of any smoke detector shall start the alarm verification mode.

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

Global Property. QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:

FDF Foam Pump Controllers Features

a) Establishment of emergency procedures to be followed at the time of an emergency;

FIRE SAFETY INSPECTION REPORT

Division 28 - Electronic Safety and Security

FIRE SAFETY PRACTICES AND PROCEDURES

UNPRECEDENTED SPEED ULTIMATE POWER. EXTREME intelligence

Winnipeg Fire Department Fire Prevention Branch

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment

SPECIFICATION: CARBON DIOXIDE ENGINEERED FIRE SUPPRESSION SYSTEM

INFORMATION BULLETIN

3.1 Introduction. 3.1 Introduction

Explosion Protection Engineering Principles

Active & Passive Fire Protection System. Page 1 Kalidasan S BT IN SSP-OP

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPULSE VALVE, FK AGENT & CHEETAH Xi 50 CONTROL PANEL

(h) Pesticide Application.

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPULSE VALVE, FK AGENT & CHEETAH Xi CONTROL PANEL

Pakenham Branch Library Section MacFarlane Street MULTIPLEX FIRE ALARM SYSTEM Project No Page 1 of 12

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition

AEGIS FEATURES DESCRIPTION. Conventional Fire Alarm-Suppression Control Unit. Effective: March Programmable Relays

ICC CODE CORNER 2012 IFC Code & Commentary

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPUSLE VALVE, Fike FK AGENT & SHP PRO CONTROL PANEL

FIRE SAFETY PLAN. BUILDING NAME: Pathobiology / AHL BUILDING NUMBER: 089. DATE: 15-August-10 FPO #2

American Society of Safety Engineers Professional Development Conference June 9-12, Fire Protection. Stephen J.

FIRE PROTECTION SYSTEMS

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

FIRE PROTECTION SYSTEMS

BP U.S. Pipelines and Logistics (USPL) Safety Manual Page 1 of 6

Hi, welcome to the topic on Fire Detection and Alarm Systems. This topic forms one of the critical knowledge areas for prospective fire safety

Florida Building Code 2010

CHILD CARE CENTER INSPECTION CHECKLIST 06C

Agency for Health Care Administration

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics.

Release Control Fire Alarm Systems

Fire suppression systems for server rooms and data centres

ThermoCable Linear Heat Detection System

5 Key Stages to Risk Assessment

Transcription:

Releasing Systems Rob Mennie Senior Consultant Gage-Babcock & Associates Ltd.

Releasing Systems What is a releasing system? System designed to detect a fire Causes release of an extinguishing system in response to the fire

Types of Extinguishing Systems Releasing systems may control the release of: Sprinklers pre-action or deluge, water or foam, water mist Clean agents Inergen, Novec, Co 2, FM200

Releasing Systems Concept Three elements: Input detection Process sequence of operation Output notification, annunciation, and release of suppression agents Elements are similar to structure of a building fire alarm system, but different in detail

More Harm than Good? Fire suppression systems sometimes do more damage than fire Sprinklers spraying computer equipment or valuable artifacts Frozen piping in cold storage facilities Foam discharge on aircraft being serviced in hangars

More Harm than Good? Damage can result from fire suppression operating in absence of fire Sprinkler heads provide both fire detection and suppression Physically damaged sprinklers may discharge water as if activated Damaged piping has the same effect Even if there is a fire, water may inflict unacceptable damage

The Solution Separate fire detection and suppression activation Provide electrical detection of fire Prevent water release if sprinklers or piping are damaged Allow for use of systems that do not use water as a suppression agent

Releasing vs. Fire Alarm Systems Releasing systems: Use fire alarm equipment and components Do not meet Building Code requirements for building fire alarm systems Include functions not found in building fire alarm systems Provide detection only in limited area covered by associated fire suppression system

Codes and Standards Fire Alarm System BCBC CAN/ULC-S524 & CAN/ULC-S537 Clean Agent Releasing System no BCBC requirements Clean Agent Releasing systems not BCBCregulated nor mentioned in CAN/ULC-S524 Design is based on good engineering practice Installation and verification should follow ULC- S524 and ULC-S537 requirements for the systems/components provided

Why Use a Releasing Panel? Not all building fire alarm panels are listed for releasing Allows for continuous protection even if the building system is being serviced Less chance of accidental discharge during inspection of building system

Stand-alone Releasing Panels Panels must be listed by ULC for releasing Panels normally protect a single hazard Panels usually are pre-programmed with some releasing options Some panels are for pre-action systems and some for clean agent systems

Building Alarm Panels Most current panels have releasing capabilities Panel must be listed by ULC for releasing Panels may protect multiple hazards for single panel Releasing options normally selectable through panel software

Input Detection Automatic detection of a fire is based detection of heat Smoke light from flame

Heat Detection Heat detection is used where high-heatrelease fires are expected Types: Spot-type heat detectors Linear heat detectors (Protectowire)

Spot-Type Heat Detectors Spot-type heat detectors are used for area protection where a ceiling exists to bank heat Ex. Cold storage warehouse with pre-action sprinkler system

Linear Heat Detectors Linear heat detectors (Protectowire) are used: for detection near fuel sources that do not have a ceiling to bank heat where spot-type detectors are difficult to install Warehouse storage racks storage freezers Conveyor galleries

Smoke Detectors Smoke detectors are used where low-heat release or smoldering fires are expected Types: Spot-type smoke detectors Air aspirating smoke detectors

Spot-Type Smoke Detectors Spot-type smoke detectors are used for area protection where a ceiling exists and air currents are limited Small computer or server room Electrical rooms

Air Aspirating Smoke Detectors Air aspirating smoke detectors are used: for high value occupancy where expense is justified where greater sensitivity is required where spot-type detectors are difficult to install or service Large computer rooms Museums Atriums High voltage electrical rooms

Flame Detectors Flame detectors are used: for long range detection in large areas in outside areas where wind may move smoke and heat away from detectors Petrochemical plants Aircraft hangars

Manual Detection Manual detection is used as a backup for automatic detection It uses dedicated manual pull stations Manual pull stations are: clearly labeled for suppression agent releasing a different color from building pull stations at exits for egress from hazard area

Process and Output Sequence of Operation Releasing systems provide more control over response than building fire alarm systems Response: is based on a number of detectors or zones detecting fire may be automatically time-delayed manually delayed provides different stages of action

Pre-action Systems Common types of releasing sequences: Single interlock Double interlock

Deluge Systems Primarily open head sprinklers with solenoid release by single or cross-zoned signal

Cross-zoning: Process and Output Cross-Zoning helps reduce unwanted suppression agent discharges divides detectors into two zones Agent does not release unless at least one detector on each of two zones is activated First zone provides alarm Second zone provides releasing

Process and Output Automatic Time Delay Automatic time delay: provides time for occupants to leave the area is used where suppression agent may be harmful to human health provides time for investigation and prevention of unwanted agent release provides time for ancillary functions air handling door closers

Process and Output Manual Time Delay Manual time delay: uses an abort switch to prevent agent release while switch is held provides time for investigation and prevention of unwanted agent release while switch is held can be a mechanical delay in discharge piping

Process and Output Different Response Stages Cross-zoning: allows for escalating response First zone activation provides notification to start personnel response or evacuation calls fire department initiates alarm condition on building fire alarm system Second zone activation provides different notification signal releases suppression agent

Interaction with Base Building Fire Alarm System Releasing system must report: Alarm Supervisory Common Trouble

Additional Operations Building or Stand-alone systems may: Operate ancillary functions Air handling equipment Process equipment Shutdown equipment in hazard area Release motorized dampers to Seal room for some agents Pressure relief for Inergen

Device Types Alarm bells Alarm horns Strobe lights Notification Devices Signage Over exit/entrance doors for hazard area

Common Problems There are a number of common problems with: Releasing system panels Pre-action sprinkler system releasing Manual switches

Common Problems with Releasing System Panels Releasing solenoid connected to bell circuit rather than releasing panel Not listed for such service No releasing function if bells are by-passed Releasing function located on building fire alarm panel instead of releasing panel No suppression agent releasing if building system out of service Danger of accidental release during servicing

More Common Problems Releasing system not connected to building fire alarm system No alarm to other tenants May not be monitored

Common Problems with Pre-Action Sprinkler Releasing System Cross-zoned detection Pre-action sprinklers only release water after system detects fire and sprinkler activates because of heat If detection is cross-zoned, water will not release until: 1. First zone activates 2. Second zone activates 3. Sprinkler activates Required cross-zoning exists between electrical detection and sprinkler, not within electrical detection

More Common Problems Missing detectors Every space containing a pre-action sprinkler must contain a detector connected to the releasing panel Includes small rooms and closets Without this, no water is released (even if sprinkler operates) because the releasing panel will not activate if no detector exists in protected space

More Common Problems Abort switch on pre-action sprinkler system Water will not be released until sprinkler activates If sprinkler activates, water is immediately required to control fire Preventing water release is not appropriate

Common Problems with Manual Switches Manual release pull station same as building pull station May result in: accidental release of suppression agent delayed release if occupants do not understand system operation

More Common Problems with Manual Switches Abort switch is in isolated location Unless occupant can reach control panel or communicate with others, he is trapped while pressing abort switch

Any questions? Thank you for your attention.