Protecting Your Property: Well Do You Know Your Fire Fire Systems Systems. Joe Szewczyk, Risk Control Consultant
|
|
- Frederick Armstrong
- 5 years ago
- Views:
Transcription
1
2 Protecting Your Property: Protecting How Well Your Do Property: You Know How Your Well Do You Know Your Fire Fire Systems Systems Joe Szewczyk, Risk Control Consultant Joe Szewczyk, Risk Control Consultant
3 Objectives Where regulations related to fire systems come from Who enforces the laws related to fire system installation, maintenance, and testing What the different components that make up a fire system
4 Objectives Review testing and inspection requirements and frequency for components of your fire system Discuss the benefits of different components of fire systems Discuss the importance of prevention relating to protecting your property
5 General Information NFPA TSFMO Extinguishers Alarm Sprinkler Suppression Installation Maintenance Licensing AHJ NOI
6 Fire Systems Overview Fire Alarm Systems Detection and Notification Sprinkler Systems Water Based Fire Protection Fire Systems Suppression Systems Chemical Based Fire Protection Fire Extinguishers Portable Extinguisher Protection
7 Fire Extinguishers First line of defense Minimum standard Size Shape Labeling
8 Extinguisher General No universal ext Classifications Training Fire Safety Training Bullox Simulator 911 Fire Alarm Fight/Flight
9 Extinguisher General Inspections Annual/Monthly Tags/Seals Service Signage Mounting
10 Fire Alarm Systems FACP Signals Alarm (Red) Trouble Supervisory Ground Fault
11 Fire Alarm Systems Inspection Tags Blue Yellow Red White Frequency Monitoring
12 Fire Alarm Systems Initiating Devices Smoke Detector Pull Station Heat Detector Sprinkler Duct Detector Smoke Detector Heat Detector Pull Station Sprinkler
13 Fire Alarm Systems Notification Devices Strobes Speakers Horns Beacons Evacuation Alarm detected Speaker Strobe Strobe
14 Control Functions Power Relays Door/Fan Controls Suppression Release AHU Shutdown Elevator Recall Fire Alarm Systems
15
16 Fire Sprinkler Systems
17 Fire Sprinkler Systems Roof 3rd Floor The Main and Primary Branch lines are also called Risers because they rise up through the floors 2ndFloor 1 st Floor Branch Secondary Branch Primary Branch Sprinklers are like the leaves They can be anywhere along the branch, but are the final extension The endpoint Main Trunk
18 Fire Sprinkler Systems Sprinkler Heads Glass Bulb Solder Link Control Valves Reporting
19 Fire Sprinkler Systems Wet Systems Uses Anti Freeze Loop Testing Maintenance Internal 5 yrs Gauges
20 Fire Sprinkler Systems Dry Systems Uses Deluge Testing Maintenance Internal 3yrs Gauges AIR WATER
21 Fire Sprinkler Systems Pre Action Systems Uses vs. dry system Testing Maintenance Internal 3yrs Gauges
22 Protection Sprinkler Systems Inspection Tags White Yellow Red Valves Signs
23 Fire Sprinkler Systems All fire sprinkler systems have means of isolation, via valve control. There are numerous types of control valves: Underground Curb Valves Covers painted Red PIV Post Indicator Valves Named because they show OPEN or SHUT in the window Used to isolate Fire Hydrants and Fire Loop Supply lines Tamper control valves are used once the supply line comes out of the ground. Called Tamper valves because they are supervised by the fire alarm system.
24 Fire Sprinkler Systems Valves are located throughout the sprinkler system, for isolation without rendering the entire system in an isolated state. Roof 3rd Floor 2ndFloor 1 st Floor
25 Fire Suppression Systems
26 Fire Suppression Systems
27 Fire Suppression Systems Uses Testing Maint 6 mo Links Hydro
28 Risk Control Consultants Northwest Risk Control Jack Coffey Northeast Risk Control Isaac Garcia Southwest Risk Control Larry Boccaccio Southeast Risk Control Joe Szewczyk
29 Questions?
Functional Performance Test
Fire Alarm Control Panel & Fire Alarm Annunciator Panel Notify all building occupants that testing will be conducted. Fire alarm contractor shall have personnel with 2-way radios at the fire alarm control
More information109-B Concord Drive Casselberry, FL DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72. Owner s Address: Owner's Phone Number:
109-B Concord Drive Casselberry, FL 32707 407.830.6500 DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72 Pg 1 of 4 Equity One 11180600 Owner/Representative: WO#: _Customer#: 1550 NE Miami Garden Dr
More informationFire Alarm System Fundamentals
Fire Alarm System Fundamentals Mircom is the largest and oldest privately owned fire alarm and life safety manufacturer in North America and 5th largest overall with 50 years of industry experience. Mircom
More informationRocky Mountain Fire Protection District 4390 Eldorado Springs Drive Boulder, CO
Rocky Mountain Fire Protection District 4390 Eldorado Springs Drive Boulder, CO 80303 303-494-3735 Contractor s Checklist and Installation Guide TABLE OF CONTENTS Fire Protection Narrative........... 3
More informationINSPECTION AND TESTING FORM
INSPECTION AND TESTING FORM Date: Time: SERVICE ORGANIZATION Name: Address: Representative: License No.: MONITORING ENTITY Contact: Monitoring Account Ref. No.: TYPE TRANSMISSION McCulloh Multiplex Digital
More informationFire Alarm Wiring. Circuit types, styles and limitations
Fire Alarm Wiring Circuit types, styles and limitations What we will cover Types Classes Notification Appliance Circuits (NAC) Initiating Device Circuits (IDC) Signaling Line Circuits (SLC) Class A, B,
More informationGlobal Property. QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:
Global Property QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Plant: Date of Inspection Location: Inspected By: Reviewed By CONTROL VALVES (If Valves are Not Locked Open or Electronically Supervised
More informationBurnsville Fire Department 100 Civic Center Pky, Burnsville, MN Fire Marshal: FAX:
Burnsville Fire Department 100 Civic Center Pky, Burnsville, MN 55337 Fire Marshal: 952-895-4579 FAX: 952-895-4512 2018 FIRE SUPPRESSION PERMIT APPLICATION PERMIT Wet System Dry System Cooking Hood Clean
More informationWinnipeg Fire Department Fire Prevention Branch
Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved
More informationSECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD
PART 1 - GENERAL PURPOSE This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible. SCOPE This standard
More informationWHEA FSE inspections.
WHEA FSE inspections www.jfahern.com FEC.02.03.05 Features of Fire Safety Buildings are protected from fire by a series of detection, notification and suppression devices Each feature of fire safety must
More informationSkilled Healthcare Documentation Requirements Life Safety and Fire Protection
DATE OF EVALUATION: FACILITY NAME: FACILITY ADDRESS: ADMINISTRATOR: MAINTENANCE DIRECTOR: All required documentation must be written and saved for at least 2 years and some documentation may be required
More informationFire Alarm Testing and Inspection Report
Fire Alarm Testing and Inspection Report Property Name: Property Address: Property Manager: Contact: Phone Number: Central Station: Phone Number: PELICAN ISLE II 35 DOCKSIDE RD. NAPLES, FLORIDA 3110 BILL
More informationNFPA CODE TESTING & INSPECTION. Requirements & Recommendations for. Licensed Florida Hospitals, Ambulatory Surgery Centers,
NFPA CODE TESTING & INSPECTION Requirements & Recommendations for Licensed Florida Hospitals, Ambulatory Surgery Centers, ICF/IID Healthcare, & In-patient Hospice Facilities per NFPA Life Safety Code 101
More informationGlobal Property. SEMIANNUAL FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:
Global Property SEMIANNUAL FIRE PROTECTION EQUIPMENT INSPECTION REPORT Plant: Date of Inspection Location: Inspected By: Reviewed By CONTROL VALVES (If Valves are Not Locked Open or Electronically Supervised
More informationFinal EC Inspection Report 03/2010
2491 Alluvial Avenue, Suite 59 Clovis, California 93611 Tel: (559)392-2838 - Fax: (559)325-7599 Contractor License #933910 (C-10/C-16) Final EC.02.03.05 Inspection Report 03/2010 This Final Report Covers
More information2. HVAC and smoke control systems; fire, smoke, and combination fire/smoke dampers. 5. Central control and monitoring system.
PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible.. This
More informationOxnard Fire Department 360 W. Second Street Oxnard, CA (805) Fax (805)
Oxnard Fire Department 360 W. Second Street Oxnard, CA 93030 (805) 385-7722 Fax (805) 385-8009 FIVE YEAR CERTIFICATION REPORT Service and maintenance report for automatic fire extinguishing systems, including
More informationTABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2
Division 28 ELECTRONIC SAFETY AND SECURITY TABLE OF CONTENTS 28 0000 GENERAL... 2 A. DEFINITIONS...2 28 3111 DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 A. DESIGN REQUIREMENTS...2 B. CONSTRUCTION REQUIREMENTS...2
More informationFIRE INSPECTION CHECKLIST
Applicable Base Codes FIRE INSPECTION CHECKLIST Florida Fire Prevention Code, 5th Edition NFPA 1, Uniform Fire Code, Florida 2012 Edition NFPA 101, Life Safety Code, Florida 2012 Edition NFPA 13, 2010
More informationMoreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline
Moreno Valley Fire Department Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: May 8, 2017 Alarm & Signaling Systems PURPOSE Fire alarm and signaling systems are designed to
More informationUniversity Design Standard Fire Alarm Systems
1.0 Overview University Design Standard Fire Alarm Systems This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit
More informationRevision May All designs must be submitted to FM Global for review and approval prior to issuing such for bids.
SECTION 211300 FIRE SUPPRESSION SYSTEMS 1.0 All new and renovated buildings shall be provided with automatic sprinklers throughout and fire standpipe systems. The design and installation of these systems
More informationNew Construction Fire Inspection Process
New Construction Fire Inspection Process This document is intended to provide the Owner, Designer, and/or Contractor of new construction with an outline of required fire inspections and with the specific
More informationFIVE YEAR AUTOMATIC FIRE EXTINGUISHING SYSTEMS CERTIFICATION REPORT
SANTA MONICA FIRE DEPARTMENT Fire Prevention Division 333 Olympic Drive 2 nd Floor Santa Monica, CA 90401 310-458-8915 / Fax 310-395-3395 FIVE YEAR AUTOMATIC FIRE EXTINGUISHING SYSTEMS CERTIFICATION REPORT
More informationSECTION : FIRE ALARM & DETECTION SYSTEMS
SECTION 28 31 10: FIRE ALARM & DETECTION SYSTEMS 1. GENERAL A. This section applies to fire detection/alarm system and carbon monoxide system components and equipment installed during new construction
More informationUnified Fire Authority - Fire Prevention Bureau
Unified Fire Authority - Fire Prevention Bureau FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance
More informationType of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number:
DATE OF SUBMISSION TO: Department of Licenses and Inspections Commercial and Industrial Fire Inspection Unit 990 Spring Garden Street, 3 rd Floor, Philadelphia, PA 19123 AP# CITY OF PHILADELPHIA FIRE ALARM
More informationMOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Alarm System Plan Review 2009 International Fire Code and 2010 NFPA 72 Date of Review // BLD201 - Project Address: Project Name: _ Professional
More informationReleasing Systems. Rob Mennie Senior Consultant Gage-Babcock & Associates Ltd.
Releasing Systems Rob Mennie Senior Consultant Gage-Babcock & Associates Ltd. Releasing Systems What is a releasing system? System designed to detect a fire Causes release of an extinguishing system in
More informationOther EC and LS documents may be requested by surveyors, as needed, throughout the survey.
Documentation required by the Hospital Accreditation program Life Safety (LS) and selected Environment of Care (EC) standards is presented in the following pages. These documents will be reviewed by the
More informationFire Alarm and Life Safety System Inspection Certificate
Fire Alarm and Life Safety System Inspection Certificate For Sample FireScan Healthcare 123 Main Street Anytown, State 55555 Tested to NFPA 72 Standards, 2007 Edition This Inspection was performed in accordance
More informationBlack Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment
Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment February 2017 Alberta Fire Code safety equipment maintenance requirements: The Black Diamond Fire Department has
More informationFollowing are the systems proposed as per NBC & Local Fire Authority:
1. OBJECTIVES AND STRATEGIES OF THE FIRE PROTECTION DESIGN This report describes the design parameters, system requirements of fire protection system for mixed occupancy (Assembly + Business) building
More informationA. This section includes design and performance information for fire protection and suppression systems.
SECTION 21 00 10: FIRE PROTECTION SYSTEM DESIGN 1. SUMMARY A. This section includes design and performance information for fire protection and suppression systems. 2. GENERAL A. All fire protection materials
More informationPROTECTED PROPERTY. City: State: Zip Code: ALARM SERVICE COMPANY. City: State: Zip Code: COMMENTS AND CLARIFICATIONS ALARM SYSTEM DESCRIPTION
Underwriters Laboratories Inc. FIRE ALARM SYSTEM PRE-INSPECTION DATA SHEETS PLEASE RETURN COMPLETED FORMS TO UL PRIOR TO INSPECTION PROTECTED PROPERTY City: State: Zip Code: ALARM SERVICE COMPANY File
More informationSECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS
PART 1 GENERAL 1.1 SECTION INCLUDES A. Fire alarm and smoke detection systems 1.2 REFERENCES A. NFPA 72 B. NFPA 101 1.3 REGULATORY REQUIREMENTS A. System: UL listed B. Conform to requirements of NFPA 101
More informationRevised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required*
1.0 Description of Services Required: Revised March 2015 Fire Alarm Systems Verification Schedule I(A) Services *Manditory Site visit required* Perform the annual fire alarm system and sprinkler system
More informationOwner/Operator Guide for Successful Sprinkler and Fire Pump Systems
Owner/Operator Guide for Successful Sprinkler and Fire Pump Systems Adam Olomon, P.E. Associate Consultant Fire & Life Safety and Fire Protection Introduction Adam Olomon Licensed Professional Engineer
More informationCOMMERCIAL (IBC) FIRE ALARM SUBMITTAL GUIDE
COMMERCIAL (IBC) FIRE ALARM SUBMITTAL GUIDE SUPERVISION OF AUTOMATIC FIRE SPRINKLER SYSTEMS SUPERVISION OF ALTERNATIVE AUTOMATIC FIRE-EXTINGUISHING SYSTEMS FIRE ALARM AND DETECTION SYSTEMS The Fire Alarm
More informationSANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)
FIRE DEPARTMENT SANTA CLARA COUNTY 14700 Winchester Blvd., Los Gatos, CA. 95032-1818 (408) 378-4010 (408) 378-9342 (fax) www.sccfd.org STANDARD DETAILS & SPECIFICATIONS Spec No C-4 Rev. Date 03/10/10 SUBJECT:
More information1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.
PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire alarm and signaling systems at Sam Houston State University provide the highest level of life safety possible. This
More informationSmoke Detector Activation of any smoke detector shall start the alarm verification mode.
Description: The purpose of the section is to provide the UMCP Design Standards for the design and implementation of Fire Alarm Systems at the UMCP campus. Related Sections: TBD Effective Date: July 10,
More informationInspection Report Nursing Home Life Safety Code Section 4 - Annual Fire Alarm Testing and Maintenance. For
Inspection Report Nursing Home Life Safety Code Section 4 - Annual Fire Alarm Testing and Maintenance For CarDon & Associates Fall Creek Health & Living Prepared by: L.Thompson/T.Roe 7/31/2014 Report Length:
More informationMINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry
MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Fire Alarm Systems Plan Review Checklist Date: Permit Number: Business Name: Address: Fire Alarm System Submittal
More informationFire Alarm System Inspection and Testing Report
Fire Alarm System and ing Report Date of : Time of : 1. PROPERTY INFORMATION: Name of Property: Address: of property: Occupancy Type: Name of property representative: Address: Phone: Fax: E-mail: Local
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST FIRE AND LIFE SAFETY SYSTEMS FOR STRUCTURES FIVE OR MORE STORIES IN HEIGHT AND LESS THAN 75 FEET IN HEIGHT FROM THE POINT
More informationSECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM
SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationAdvanced Fire Alarm Systems Training Program Outline (5 Day)
Advanced Fire Alarm Systems Training Program Outline (5 Day) Day 1 Prescriptive and Performance-Based Design Understand the methodology in accessing the threat of fire within a structure. Know the difference
More informationCOUNTY OF KINGS KINGS COUNTY JAIL EXPANSION PHASE III
SECTION 28 3111 - DIGITAL ADDRESSABLE FIRE ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationArchitect s Project Number of 12 Fire Alarm/Smoke Detection Systems District Master Specs 2013 Edition
PART 1 GENERAL 1.1 SECTION INCLUDES SECTION 28 31 00 FIRE ALARM AND SMOKE DETECTION SYSTEMS A. Fire alarm and smoke detection systems 1.2 REFERENCES A. NFPA 72 B. NFPA 101 1.3 REGULATORY REQUIREMENTS A.
More informationNotification Appliance Circuit Module
Notification Appliance Circuit Module D192G en Installation guide Notification Appliance Circuit Module Notices en 3 1 Notices These instructions cover the installation of the D192G Notification Appliance
More informationMINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Plan Review
MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Plan Review Minooka Fire Protection District Maintaining Your Fire Safety Systems Fire continues to be a major threat
More informationEL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD
EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD INSTALLATION OF COMMERCIAL FIRE SPRINKLER SYSTEMS STANDARD #C-001 EFFECTIVE 03-25-2009 PURPOSE: To ensure that sprinkler plans submitted for review contain
More informationFIRE INSPECTORS GUIDELINES FOR PLAN REVIEWS AND INSPECTIONS OF NEW CONSTRUCTION / ADDITIONS AND CHANGE OF OCCUPANCY
FIRE INSPECTORS GUIDELINES FOR PLAN REVIEWS AND INSPECTIONS OF NEW CONSTRUCTION / ADDITIONS AND CHANGE OF OCCUPANCY PLAN REVIEWS SITE PLANS: 1) Access to buildings (Volume V NC Building Code sections 602.6.1
More informationMAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS
MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Introduction When properly installed and maintained, automatic fire sprinkler systems have proven to be the most effective means for protecting life and
More informationBold items are particular to the City of Euless
EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 8/2004 Fire Chief Lee Koontz Fire Marshal Paul Smith EFD-FMO 3-1 2003 International Fire & Building Code as Amended NFPA Standards
More informationMultiple Input and Output Modules
Kingfisher Company, inc. Multiple Input and Output Modules Features: Removable 12 to 18 AWG plug-in terminal blocks Individual LED indicators Unused addresses may be disabled Rotary address switches Class
More informationPART II: New Construction Inspections and Acceptance Testing Procedures
Stafford County Fire Marshal s Office Handbook for Building/Fire Code Policies and Guidelines PART II: New Construction Inspections and Acceptance Testing Procedures Phone: 540-658-8648 Fax: 540-658-9128
More informationValuation: # of Plans Submitted: # of pages: Type of Work (select one): New Addition Existing System/Modification Project Name: Scope of Work:
PERMIT FEE: $ 907 Billy Mitchell Blvd. P: (210) 228-1022 Fire Alarm Permit Application PAYMENT TYPE: Check Credit Card Charge to Job #: (Please complete all of the following information. Please PRINT).
More informationBusiness Fire Inspection. City of Guadalupe
Business Fire Inspection City of Guadalupe Intent Provide general information on the California Fire Code (CFC) and City of Guadalupe Municipal Code (GMC) requirements. Provide information and the most
More informationFire - Rescue. November 2016
Fire - Rescue Fire Alarm and Central Station Monitoring Plan Submittal Guidelines November 2016 Plan Submittal Guidelines are provided based on the 2015 International Fire Code, Policies, and Local Amendments.
More informationCHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS
CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS 61G15-32.001 61G15-32.002 61G15-32.003 61G15-32.004 61G15-32.005 61G15-32.006 61G15-32.007
More informationCITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM. Bid # Addendum #1
CITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM Bid #56-09 Addendum #1 This Addendum forms part of the original document marked Bid #56-09 MUNICIPAL COMPLEX FIRE ALARM. Device
More informationFIRE SAFETY PLAN. BUILDING NAME: Pathobiology / AHL BUILDING NUMBER: 089. DATE: 15-August-10 FPO #2
FIRE SAFETY PLAN BUILDING NAME: Pathobiology / AHL BUILDING NUMBER: 089 DATE: 15-August-10 FPO #2 INDEX Introduction 2 Locations of Fire Safety Plans 3 Forward 4 Audit of Building Data 5-6 Fire Fighting
More informationEl Reno Fire Department Fire Alarm Plan Review Worksheet
El Reno Fire Department Fire Alarm Plan Review Worksheet This Fire Alarm Plan Review Checklist is provided as a guide to assist with your Fire Alarm Plan Review Submittal requirements. Please contact us
More informationYou are required to READ ALL PAGES. of this application
Fire/Smoke/Heat/CO Application Checklist You are required to READ ALL PAGES of this application NEW ROCHELLE FIRE DEPARTMENT 90 Beaufort Pl, New Rochelle, NY 10801 - (914) 654-2213 APPLICATION FOR FIRE/SMOKE/HEAT/CO
More informationAutomatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems
Automatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems Your Presenter: Merton Bunker, PE Inspections and tests are intended to reduce or limit: Loss of life
More informationFire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016
Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting Prepared Especially for : OSFM TEC 2016 Acceptance Testing 11-2008 Agenda Before you begin Completing the
More informationTECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014
January 16, 2014 Release Control Panel 290a 1. Description The Viking VFR400 is a microprocessor based releasing control panel for use on preaction, deluge, Surefire, Firecycle multicycle sprinkler systems,
More informationFire alarm system specification for multiple tenant retail buildings
Date: June 20, 2011 Project name: Baederwood Shopping Center Multiple Tenant Buildings B & C City/ State: Abington, PA Landlord s Vendor Contact: Dan Morrin Jr., NECCO Security Phone: (215)638-7999 Email:
More informationDivision 28 - Electronic Safety and Security
Division 28 - Electronic Safety and Security 28 31 11 Fire Alarm Systems Fire alarm systems shall be installed in buildings when required by this section. 1. Purpose: The primary purpose of a fire alarm
More informationFlorida Building Code 2010
Introduction Florida Building Code 2010 Chapter 9 Fire Protection Systems This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors are familiar with
More information3.1 Introduction. 3.1 Introduction
DEPARTMENT OF ARCHITECTURE ABUBAKAR TAFAWA BALEWA UNIVERSITY, BAUCHI ARC 624: ADVANCED BUILDING SERVICES LESSON 3: FIRE DETECTION AND ALARM SYSTEMS IN BUILDINGS 3.1 Introduction 3.1 Introduction 3.2 Conventional
More informationSECTION FIRE DETECTION AND ALARM
PART 1 - GENERAL 1.1 RELATED SECTIONS: Refer to Section 15300 for requirements regarding fire protection systems. 1.2 SCOPE OF SECTION: This section contains the requirements for equipment and installation
More informationOsceola County Department of Fire Rescue and Emergency Medical Services
St. Number Dir Street Name Street Type Inspected Time of Day to be Re-inspected Zip Code Occupancy Type Emergency Contact Phone (Inc. Area Code) Building Owner Building Owner Mailing Address Bldg. Owner
More informationInspector: PROPERTY INFORMATION Photo Smoke Detector Notification Control Panel Stand Alone Smoke Detector Dialer SUMMARY ONLY
FIRE ALARM INSPECTION AND TESTING SUMMARY PAGE PER 2013 NFPA 72 Inspector: Jim Smith Test Date: 5/22/2014 PROPERTY INFORMATION Name of Property: Windsor Tower Owner of Property: Jim Gibbs Properties Address:
More informationMichigan State University Construction Standards FIRE DETECTION AND ALARM PAGE
PAGE 283100-1 SECTION 283100 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions
More informationSymbols for Control Panels
Symbols for Control Panels Symbol Description Control panel-basic shape FACP FSA FAA FTR ESR FAC Fire alarm control panel Fire systems annunciator alarm Annunciator panel-from NE 100, symbol 7.006 Fire
More informationFIRE & LIFE SAFTEY STANDARD
Title: Effective Date: 01/01/14 Revised Date: 1/1/14 Code References: Title 16, Chapter 16.16 of the Roseville Municipal Code, NFPA 72 Note: This standard is a summary of Fire Department clarifications
More informationMAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS
FIRE CODE BULLETIN December 2004 97 FCB 018 (R1) Page 1 of 5 BACKGROUND: MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS Fire protection service companies are
More informationNFPA 72 Code Changes vs 2013
NFPA 72 Code Changes - 2010 vs 2013 AFAA-NE Westborough, MA February 7, 2018 Richard Roux NFPA 72 National Fire Alarm and Signaling Code Overview and 2013 Changes NFPA 72 1993 Edition Aug 20, 1993 1996
More informationBrighton Area Fire Authority
615 W. Grand River Ave. Brighton, MI 48116 o: 810-229-6640 f: 810-229-1619 January 14, 2019 Fire Alarm Contractors RE: Fire Alarm Credential & Submittal Requirements To Whom It May Concern: The following
More information2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.
2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is
More informationInspection of Fire Sprinkler Systems. NFPA 25, Inspection, Testing & Maintenance of Water Based Fire Protection Systems
Inspection of Fire Sprinkler Systems NFPA 25, Inspection, Testing & Maintenance of Water Based Fire Protection Systems Objective To familiarize Facility Managers with the process of routine inspection
More informationMECKLENBURG COUNTY FIRE MARSHAL S OFFICE
Effective Date: 11/01/02 Purpose: MECKLENBURG COUNTY To establish a set of guidelines for performance testing of all newly installed or upgraded fire alarm systems in order to ensure that all devices and
More informationFACILITY PROFILE CALIFORNIA ASSOCIATION OF HEALTH FACILITIES DISASTER PLANNING GUIDE
This facility profile is a document that provides a general overview and listing of relevant information pertaining to operational and property characteristics. This information should be shared with local
More information2-SUPPRESSION REQUIREMENTS - CODE REQUIRED INSPECTIONS TEST Page 1 of 7
WET SPRINKLER Monthly Wet Sprinkler 2-SUPPRESSION REQUIREMENTS - CODE REQUIRED INSPECTIONS TEST Page 1 of 7 VISUALS [per NFPA 25-1998 ed] 1. Gauge (Ck for Condition, Normal Pressure) [per 2-2.4.1] 2. Valves
More informationSECTION DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM
SECTION 283111 DIGITAL, ADDRESSABLE FIRE ALARM PART 1 - GENERAL 1.1 GENERAL A. This Section includes the following: 1. Fire-alarm control panel. 2. Manual fire-alarm boxes. 3. Smoke detectors. 4. Heat
More informationDIVISION 21 FIRE SUPPRESSION FIRE SUPRESSION
DIVISION 21 FIRE SUPPRESSION 21 00 00 FIRE SUPRESSION 21 01 00 Operation and Maintenance of Fire Suppression 21 01 10 Operation and Maintenance of Water Based Fire Suppression Systems 21 01 20 Operation
More information/5121/5122 TrueAlert Power Supply Installation Instructions
4100-5120/5121/5122 TrueAlert Power Supply Installation Instructions Introduction This publication provides an overview of the features, specifications, and capabilities of the TrueAlert power supplies
More informationOKLAHOMA STATE UNIVERSITY
ENVIRONMENTAL HEALTH & SAFETY ADDRESSABLE FIRE ALARM SYSTEM STANDARD Revised 6/15 Revised: 6/15 Contact(s) Implementation Date Comments Gerald Petre, EHS June 2016 Review and Update Page 1 1.1 GENERAL
More informationFlorida Building Code Chapter 9 Fire Protection Systems Advanced Course
Florida Building Code 2010 Chapter 9 Fire Protection Systems Advanced Course 1 Introduction This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors
More informationModule 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements
Module 3 Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements 1 WATER-BASED SUPPRESSION SYSTEMS-PART TWO This module covers: 1. Ohio Building Code requirements and when and why
More informationCAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS
RANDAL BROWN & ASSOCIATES ENGINEERING LTD. CONSULTING ENGINEERS LIFE SAFETY & FIRE PROTECTION 105 6 LANSING SQUARE TORONTO, ONTARIO CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY
More informationSPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE CHEETAH Xi 50 CONTROL PANEL SYSTEM
SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Total Flood ECARO-25 TM clean agent fire suppression system utilizing HFC-125 as the fire extinguishing agent
More information17 Fire Alarm Systems Standards 354th Civil Engineering Squadron OPR: CES/CEOFA ISSUED: 12 September 2017 EIELSON AIR FORCE BASE DESIGN GUIDELINES
Purpose This standard shall be used in conjunction with the latest version of Unified Facilities Criteria (UFC) 3-600-01, FIRE PROTECTION ENGINEERING FOR FACILITIES and UFC 4-021-01, DESIGN AND O&M: MASS
More informationFacilities Management
Facilities Management Policy Number: 700.4 Title: Fire Protection & Life Safety Inspection Policy Implementation Date: August 1 st, 2008 Last Revised: September 14 th, 2017 Last Audited: August, 2017 Introduction
More informationScope of Section 2. AS vs. Application Issues. Schedules & Log- Contents. Books
Contents Scope of Section 2 Application Issues AS 1851-1997 vs 2005 Schedules & Log- Books Scope of AS1851 Section 2 Review and rewrite of all sprinkler maintenance activities AS 1851.3 1997 becomes General
More information