B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

Similar documents
MLA Architects Pierz Public Schools ISD #484 Healy High School Multi-Purpose & Choir Additions Pioneer Elementary School Class Room Addition Pierz, MN

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE

B. Section Identification for Fire Suppression Piping and Equipment.

A. Section includes wet-pipe sprinkler system, system design, installation, and certification.

SECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

FIRE SUPPRESSION SPRINKLER SYSTEM

SECTION SPRINKLER SYSTEMS

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL

PART 1 - GENERAL SECTION FIRE PROTECTION BASIC MATERIALS AND METHODS

B. Galvanized-Steel-Sheet Sleeves: inch minimum thickness; round tube closed with welded longitudinal joint.

Lucy s Pizza 100% CD Specification 06/22/2018

THE JAMES RUSHTON EARLY LEARNING AND FAMILY SUCCESS CENTER #2616 ISSUE FOR CONSTRUCTION

TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION WATER BASED FIRE PROTECTION SYSTEMS... 5

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1. The Curators of the University of Missouri

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM

SECTION DRY-PIPE SPRINKLER SYSTEMS

SECTION DRY-PIPE SPRINKLER SYSTEMS

SPRINKLERS TABLE OF CONTENTS

Mercury Plastics New Building February TABLE OF CONTENTS

SECTION FIRE PROTECTION. A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University.

SECTION WET-PIPE SPRINKLER SYSTEMS

Gas Station & C Store SECTION CWM Job No

SECTION WET-PIPE SPRINKLER SYSTEMS

TABLE OF CONTENTS

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements.

SECTION WET-PIPE SPRINKLER SYSTEMS

WET-PIPE SPRINKLER SYSTEMS

SECTION WET AUTOMATIC FIRE SPRINKLER SYSTEMS

B. Related Sections: The following Sections contain requirements that relate to this Section.

DIVISION 21: FIRE SUPPRESSION

West District Library Section Campeau Drive, Ottawa SPRINKLER SYSTEMS City of Ottawa Project No. CR Page 1 of 8

North Hanover Township School District North Hanover Township, New Jersey

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

DIVISION 21 FIRE SUPPRESSION SECTION FIRE PROTECTION SPECIALTIES

A. Standard-Pressure Piping System Component: Listed for 175-psig minimum working pressure.

SECTION SPRINKLER SYSTEMS

Mercy Hospital of Buffalo Catholic Health System 2 nd Floor Patient Holding Center 3 rd Floor Locker Rooms Shaflucas Architects, PC Project No.

DIVISION 21: FIRE SUPPRESSION

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

ADDENDUM NO. 3 March 19, 2018

B. Standard-Pressure Standpipe Piping: Fire-suppression standpipe piping designed to operate at working pressure 175 psig (1200 kpa) maximum.

New Rigby Elementary School February TABLE OF CONTENTS

2. Welding Materials and Procedures shall conform to the ASME Code.

SECTION AUTOMATIC SPRINKLER PIPING

Kenworth Sales Co. - North Las Vegas, Nevada November TABLE OF CONTENTS

Wayne State University WSU Project No Chatsworth Tower Apts. Misc. Bldg. Upgrades DSD Project No

Design & Construction Standards, Revised January

1.2 CODES AND REGULATIONS A. Sprinkler system design, equipment, materials, devices, and installation shall conform to the following:

DESIGN & CONSTRUCTION GUIDELINES

WET AUTOMATIC FIRE SPRINKLER SYSTEMS

SECTION FIRE-SUPPRESSION STANDPIPES

SECTION SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 21 FIRE SUPPRESSION

SECTION GENERAL-SERVICE COMPRESSED-AIR SYSTEMS

B. The sprinkler system shall be designed to meet the more stringent of the requirements of NFPA 13 and FM Global requirements.

SECTION DRY-PIPE FIRE-SUPPRESSION SPRINKLERS

DIVISION 21 FIRE SUPPRESSION FIRE SUPPRESSION GENERAL PROVISIONS .1 PREPARATION OF CONTRACT DOCUMENTS

DIVISION 21 - FIRE SUPPRESSION

DIVISION 21: FIRE SUPPRESSION WATER BASED FIRE SUPRESSION SYSTEMS

Port of St Helens SIA Aircraft Hanger Scappoose, OR

SECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION

UMC El Paso Far East Clinic and Neighborhood Healthcare Center West Issue for Construction Page Project No and April 13, 2015

D. NEMA Compliance: Provide electric motors and components which comply with NEMA standards.

SECTION WET-PIPE FIRE-SUPPRESSION SPRINKLERS

Environmental Health & Safety

A. ASME Compliance: Fabricate and install hydronic piping in accordance with ASME B31.9 "Building Services Piping.

SECTION PREACTION SPRINKLER SYSTEMS

SECTION FIRE PROTECTION

Addendum No. 2 to the Contract Documents

REFRIGERANT PIPING

DIVISION 21 - FIRE SUPPRESSION

A. This Section includes the following fire-suppression piping inside the building:

D. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following:

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION FIRE PROTECTION

DIVISION 21 FIRE PROTECTION ISSUE DATE REVISION

D. Reference Standards (Utilize latest editions available):

DARTMOUTH COLLEGE DESIGN November 15, 2007 & CONSTRUCTION GUIDELINES

Design & Construction Standards, Revised January

Fire Pump Specification

SECTION ADDENDUM NO. 1 FIRE SPRINKLER SYSTEM

B. HI Compliance: Design, manufacture, and install pumps in accordance with HI "Hydraulic Institute Standards."

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code

D-11 OUTLINE SPECIFICATION FOR HTHW (ABOVE GRADE) HYDRONIC PIPING

SECTION (13900) - FIRE SUPPRESSION SYSTEMS

UC Santa Cruz Campus Design Guide. Includes the following sections: None DESIGN REQUIREMENTS

A. This section includes design and performance information for fire protection and suppression systems.

RESEARCH AND TECHNOLOGY BUILDING RENOVATION 05/18/09 SECTION REFRIGERANT PIPING AND SPECIALITIES

NITROGEN-GENERATING SPRINKLER CORROSION INHIBITING SYSTEM

***Specifications***

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 21 FIRE SUPPRESSION

Transcription:

DIVISION 21 21 05 00 COMMON WORK RESULTS FOR FIRE SUPPRESSION PART 1 GENERAL 1.1 SECTION INCLUDES A. Pipe, fittings, sleeves, escutcheons, seals, and connections for sprinkler systems. 1.2 RELATED REQUIREMENTS A. Section 21 13 00- Fire-Suppression Sprinkler Systems: Sprinkler systems design. 1.3 REFERENCE STANDARDS A. ASME B16.1 -Gray Iron Pipe Flanges and Flanged Fittings: Classes 25, 125, and 250; The American Society of Mechanical Engineers; 2010. B. ASME B16.3- Malleable Iron Threaded Fittings: Classes 150 and 300; The American Society of Mechanical Engineers; 2011. C. ASME B16.4- Gray Iron Threaded Fittings; The American Society of Mechanical Engineers; 2011. D. ASTM A47 I A47M -Standard Specification for Ferritic Malleable Iron Castings; 1999 (Reapproved 2014). E. ASTM A53/A53M- Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless; 2012. F. ASTM A795/A795M- Standard Specification for Black and Hot-Dipped Zinc-Coated (Galvanized) Welded and Seamless Steel Pipe for Fire Protection Use; 2013. G. NFPA 13- Standard for the Installation of Sprinkler Systems; National Fire Protection Association; 201 3 (Errata 2014). H. UL (FPED)- Fire Protection Equipment Directory; Underwriters Laboratories Inc.; current edition. 1.4 SUBMITTALS A. See Section 01 33 00- Administrative Requirements, for submittal procedures. B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings. C. Shop Drawings: Indicate pipe materials used, jointing methods, supports, floor, and wall penetration seals. Indicate installation, layout, weights, mounting and support details, and piping connections. D. Project Record Documents: Record actual locations of components and tag numbering. COMMON WORK RESULTS FOR 210500-1

1.5 QUALITY ASSURANCE A. Manufacturer Qualifications: Company specializing in manufacturing the Products specified in this section with minimum three years documented experience. B. Installer Qualifications: Company specializing in performing the work of this section with minimum three years experience. C. Valves: Bear UL, FM, and Warnock Hersey label or marking. Provide manufacturer's name and pressure rating marked on valve body. 1.6 DELIVER)', STORAGE, AND HANDLING A. Deliver and store valves in shipping containers, with labeling in place. B. Provide temporary end caps and closures on piping and fittings. Maintain in place until installation. PART 2 PRODUCTS 2.1 FIRE PROTECTION SYSTEMS A. Sprinkler Systems: Conform to NFPA 1 3. B. Welding Materials and Procedures: Conform to ASME BPVC-IX. 2.2 ABOVE GROUND PIPING A. Steel Pipe: ASTM A 795 Schedule 10 or ASTM A 53 Schedule 40, black. 1. Cast Iron Fittings: ASME B16.1, flanges and flanged fittings and ASME B16.4, threaded fittings. 2. Malleable Iron Fittings: ASME B16.3, threaded fittings and ASTM A47/A47M. 3. Mechanical Grooved Couplings: Malleable iron housing clamps to engage and lock, "C" shaped elastomeric sealing gasket, steel bolts, nuts, and washers; galvanized for galvanized pipe. B. Above ground piping less than or equal to 1-1 /4" in diameter shall be schedule 40 black steel. Above ground piping 1-1 /2" in diameter and greater shall be schedule 1 0 black steel. Schedule 40 piping shall be threaded. Schedule 1 0 pipe should be roll grooved, not threaded. Fittings shall be cast iron or steel approved for a minimum of 175 psi working pressure. 2.3 PIPE HANGERS AND SUPPORTS A. Hangers for Pipe Sizes 1 /2 to 1-1/2 inch: Malleable iron, adjustable swivel, split ring. B. Hangers for Pipe Sizes 2 inches and Over: Carbon steel, adjustable, clevis. C. Multiple or Trapeze Hangers: Steel channels with welded spacers and hanger rods. COMMON WORK RESULTS FOR 210500-2

PART 3 EXECUTION 3.1 PREPARATION A. Ream pipe and tube ends. Remove burrs. Bevel plain end ferrous pipe. B. Remove scale and foreign material, from inside and outside, before assembly. C. Prepare piping connections to equipment with flanges or unions. 3.2 INSTALLATION A. Install sprinkler system and service main piping, hangers, and supports in accordance with NFPA 13. B. Route piping in orderly manner plumb and parallel to building structure. Maintain gradient. C. Install piping to conserve building space, to not interfere with use of space and other work. D. Group piping whenever practical at common elevations. E. Install piping to allow for expansion and contraction without stressing pipe, joints, or connected equipment. F. Pipe Hangers and Supports: 1. Install hangers to provide minimum 1/2 inch space between finished covering and adjacent work. 2. Place hangers within 12 inches of each horizontal elbow. 3. Use hangers with 1-1/2 inch minimum vertical adjustment. Design hangers for pipe movement without disengagement of supported pipe. 4. Where several pipes can be installed in parallel and at same elevation, provide multiple or trapeze hangers. G. Slope piping and arrange systems to drain at low points.. Use eccentric reducers to maintain top of pipe level. H. Prepare pipe, fittings, supports, and accessories for finish painting. Where pipe support members are welded to structural building framing, scrape, brush clean, and apply one coat of zinc rich primer to welding. I. Do not penetrate building structural members unless indicated. J Provide sleeves when penetrating footings, floors, walls, partitions, and foundations, and seal pipe and sleeve penetrations to achieve fire resistance equivalent to fire separation required. K. Escutcheons: 1. Install and firmly attach escutcheons at piping penetrations into finished spaces. 2. Provide escutcheons on both sides of partitions separating finished areas through which piping passes. 3. Use chrome plated escutcheons in occupied spaces and to conceal openings in construction. COMMON WORK RESULTS FOR 21 OS 00-3

L. When installing more than one piping system material, ensure system components are compatible and joined to ensure the integrity of the system. Provide necessary joining fittings. Ensure flanges, union, and couplings for servicing is consistently provided. END OF SECTION COMMON WORK RESULTS FOR 210500-4

DIVISION 21 21 13 00 SPRINKLERS PART 1 GENERAL 1.1 SECTION INCLUDES A. Wet-pipe sprinkler system. B. System design, installation, and certification. C. Fire department connections. 1.2 RELATED REQUIREMENTS A. Section 21 05 00- Common Work Results for Fire Suppression: Pipe, fittings, and valves. 1.3 REFERENCE STANDARDS A. NFPA 13- Standard for the Installation of Sprinkler Systems; National Fire Protection Association; 2013 (Errata 2014). B. NFPA 1963- Standard for Fire Hose Connections; 2014. C. UL 405- Fire Department Connection Devices; Current Edition, Including All Revisions. D. UL (FPED)- Fire Protection Equipment Directory; Underwriters Laboratories Inc.; current edition. 1.4 SUBMITTALS A. See Section 01 30 00- Administrative Requirements, for submittal procedures. B. Product Data: Provide data on sprinklers, valves, and specialties, including manufacturers catalog information. Submit performance ratings, rough-in details, weights, support requirements, and piping connections. C. Shop Drawings: 1. Submit preliminary layout of finished ceiling areas indicating only sprinkler locations coordinated with ceiling installation. 2. Indicate hydraulic calculations, detailed pipe layout, hangers and supports, sprinklers, components and accessories. Indicate system controls. 3. Submit shop drawings, product data, and hydraulic calculations to authority having jurisdiction, owner's insurance carrier, Architect and Engineer for approval. Submit proof of approval to Architect/Engineer. D. Project Record Documents: Record actual locations of sprinklers and deviations of piping from drawings. Indicate drain and test locations. E. Operation and Maintenance Data: Include components of system, servicing requirements, record drawings, inspection data, replacement part numbers and availability, and location and numbers of service depot. SPRINKLERS 21 1 3 00-1

F. Maintenance Materials: Furnish the following for Owner's use in maintenance of project. 1. See Section 01 60 00- Product Requirements, for additional provisions. 2. Extra Sprinklers: Type and size matching those installed, in quantity required by referenced NFPA design and installation standard. 3. Sprinkler Wrenches: For each sprinkler type. 1.5 QUALITY ASSURANCE A. Maintain one copy of referenced design and installation standard on site. B. Conform to UL requirements. C. Designer Qualifications: Design system under direct supervision of a Professional Engineer experienced in design of this type of work and licensed in the State in which the Project is located. D. Manufacturer Qualifications: Company specializing in manufacturing the Products specified in this section with minimum three years documented experience. E. Installer Qualifications: Company specializing in performing the work of this section with minimum three years experience. F. Equipment and Components: Provide products that bear UL label or marking. 1.6 DELIVERY, STORAGE, AND HANDLING A. Store products in shipping containers and maintain in place until installation. Provide temporary inlet and outlet caps. Maintain caps in place until installation. 1. 7 DESCRIPTION OF WORK A. Furnish all labor, services, material and related items necessary to complete the fire protection work indicated on the drawings and/or specified herein. B. Provide complete Design-Build Sprinkler System for the fire protection work indicated on the drawings and/or specified herein as required by Codes. C. All work shall be designed and installed in accordance with the latest edition of the NFPA 13 and shall meet the requirements of all local building codes and the local Fire Marshal. D. It is intended that this specification shall describe a working installation complete in every detail, and all items necessary for such complete installation shall be furnished and installed whether specifically mentioned or not. 1.8 DESIGN A. Submit hydraulic calculations for areas of work. Include sufficient information to verify the hydraulically most remote area was selected. B. The densities are to be established by NFPA 13 shall be used in the design and hydraulic calculation. Hydraulic calculation shall be submitted as part of shop drawings review and approval. FIRE SAFETY IMPROVEMENTS MISSOURI HILLS YOUTH CENTER ST. LOUIS, MISSOURI 21 13 00-2

C. Perform hydraulic flow test and contact Fire Marshal and Owner's insurance carrier to verify the water pressure data at the site. Care shall be taken to insure the results are satisfactory to the authority having jurisdiction and the Owner's insurance carrier. D. The information given herein and on the plans is as exact as could be secured for bidding purposes, but its accuracy is not guaranteed. This Subcontractor must examine the job conditions and verify all measurements, distances, elevations, clearances, pipe sizes, etc., before starting his work. E. The complete sprinkler system shall have sprinklers inside of all new coolers and freezers (dry pendant heads) and above new coolers, (if required) per NFPA 13. F. Provide all necessary offsets, raises or drops in piping and auxiliary drains required by building conditions whether or not shown on the plans. G. Piping is to be held as high as possible and maintain natural drainage back to the main system risers whenever possible. PART 2 PRODUCTS 2.1 MANUFACTURERS A. Sprinklers, Valves, and Equipment: 1. Reliable. 2. Tyco Fire Suppression & Building Products. 3. Viking Corporation. 4. Substitutions: See Section 01 60 00- Product Requirements. 2.2 SPRINKLER SYSTEM A. Sprinkler System: Provide coverage for building areas noted on drawings. B. Water Supply: Determine volume and pressure from water flow test data. 2.3 SPRINKLERS A. Suspended Ceiling Type: Semi-recessed pendant type with matching push on escutcheon plate. 1. Coverage Type: Standard. 2. Finish: Chrome plated. 3. Escutcheon Plate Finish: Chrome plated. 4. Fusible Link: Glass bulb type temperature rated for specific area hazard. B. Exposed Area Type: Upright or pendant type. 1. Coverage Type: Standard. 2. Finish: Brass. 3. Fusible Link: Glass bulb type temperature rated for specific area hazard. C. Guards: Finish to match sprinkler finish as required. FIRE SAFETY IMPROVEMENTS MISSOURI HILLS YOUTH CENTER ST. LOUIS, MISSOURI 21 1 3 00-3

2.4 PIPING SPECIALTIES A. Fire Department Connections: 1. Type: Exposed, projected wall mount made of corrosion resistant metal complying with UL 405. a. Manufacturers: 1) Elkhart Brass Manufacturing Company, Inc. 2) Fire End & Croker Corporation. 3) Potter Roemer. 4) Substitutions: See Section 01 60 00- Product Requirements. b. Inlets: Single inlet, 2-1/2 inch swivel fittings, internal threaded. Thread size and inlets according to NFPA 1963 or Authority Having Jurisdiction. Brass caps with gaskets, chains, and lugs. c. Finish: Brass or bronze. d. Signage: Raised or engraved lettering 1 inch minimum indicating system type. PART 3 EXECUTION 3.1 INSTALLATION A. Install in accordance with referenced NFPA design and installation standard. B. Locate fire department connection with sufficient clearance from walls, obstructions, or adjacent siamese connectors to allow full swing of fire department wrench handle. C. Place pipe runs to minimize obstruction to other work. D. Place piping in concealed spaces above finished ceilings. E. Center sprinklers in two directions in ceiling tile and provide piping offsets as required. F. Apply masking tape or paper cover to ensure concealed sprinklers, cover plates, and sprinkler escutcheons do not receive field paint finish. Remove after painting. Replace painted sprinklers. G. Flush entire piping system of foreign matter. H. Install guards on sprinklers where required. END OF SECTION FIRE SAFETY IMPROVEMENTS MISSOURI HILLS YOUTH CENTER ST. LOUIS, MISSOURI 21 13 00-4