AlarmLine Linear Heat Detector

Similar documents
AlarmLine Addressable Linear Heat Detector

ALARMLINE ANALOGUE Linear Heat Detection System

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION

Linear Heat Detection for Coal Conveyors. Application Guide

ThermoCable Linear Heat Detection System

Alarmline Linear Heat Detection

Tel: +44(0) Fax: +44(0) /17 LGM Products Ltd. Web: ISO 9001:2015 certified

LINEAR HEAT SENSING DETECTION. System Sensor India 2014

AnaLASER II Detector. Protection Systems. A UTC Fire & Security Company. High-Sensitivity Smoke Detector (HSSD ) FEATURES DESCRIPTION

LINEAR HEAT DETECTION CABLE DURÁN-SAFE

STOCKIST OF LINEAR HEAT SESNING CABLE in INDIA

Basic Vehicle Fire Protection Manual

Alarmline II Digital Linear Heat Sensor Cable Technical Manual

FireSystems PROTECTOWIRE. Installing Protectowire Linear Heat Detector

Model 17A00 Expansion Enclosure

SERIES VAC Microprocessor-Based Direct Spark Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION. Export Information (USA)

ALARMLINE ANALOGUE LINEAR TEMPERATURE DETECTION

Installing Protectowire Linear Heat Detector

Heat Sensor Cable Alarm Units DT650L / DT950L

LINEAR HEAT DETECTION CABLE DURÁN-SAFE

Reference Guide 2.1. Certificate Number

DETECT-A-FIRE Heat Detectors

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

SERIES VAC Microprocessor-Based Hot Surface Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION AGENCY CERTIFICATIONS

Multi-Spectral, Digital, Infrared Electro-Optical. FSC Model No. s. Unitized, Two Stage, Quick Response Flame Detectors.

FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel

Commercial and Light Industrial Fire Alarm Control Panel

TECHNICAL DATA OBSOLETE

AEGIS FEATURES DESCRIPTION. Conventional Fire Alarm-Suppression Control Unit. Effective: March Programmable Relays

Gardian W51. Approvals

WFDE Series Waterflow Detector

DAF DETECT-A-FIRE. DAF DETECT-A-FIRE Detection and Release Devices

DOOR MONITORING/DURESS SYSTEM

SERIES VAC Microprocessor-Based Direct Spark Ignition Control with Inducer Blower Relay FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION

Instructions Dual Spectrum Infrared Flame Detector PM-5MPX. 4.1 Rev: 8/

These instructions detail procedures to follow in order to avoid damage to equipment.

Linear Heat Detection

Alarmline II Analogue Linear Heat Sensor Cable Technical Manual

PEGAsys. Multi-Loop Intelligent Suppression Control System FEATURES DESCRIPTION. Effective: March 2007 K

INSTALLATION INSTRUCTIONS FOR 6797A737 HEAT PUMP FLUSH MOUNT CEILING PLENUM

DiMM Unit. LST Digital Interface Monitor Module (LST-DiMM) MAN3109

CHECKFIRE 210 Detection and Actuation System

7638 Standish Place Derwood, MD Tel: (301) Fax: (301) Page 1 of 12. Website:

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

INSTALLATION INSTRUCTIONS FOR 7330C740 FLUSH MOUNT CEILING ASSEMBLY

FIRE SPRINKLER SYSTEM FREEZE PROTECTION XL-TRACE SYSTEM

D296/D297. Installation Instructions Long-Range Beam Smoke Detectors

Addressable NAC Output Module D327A

Fire Alarm System Accessories

SERIES VAC Microprocessor-Based Intermittent Pilot Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION

0 A EIS Intrinsically-Safe Plug-in Intelligent Photoelectronic Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS

RDM LOCK G Series Electromagnetic Lock. Listings. Standard Features. Ordering Information:

F220-B6PS/M. Installation Guide. Addressable Detector Bases

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

FiberSystem. Fiber Optic Linear Heat Detection for Special Hazard Applications

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES

MANUAL RESET ALARM RELEASE

FIRE AND SAFETY. Manual Call Points p15-1 Magnetic Door Holders p15-3 Detection Cables p15-4 Portable Signals p15-7 Solar Powered Signals p

User's Manual: Series 260A Model 260A Process Current Loop-Powered Alarm

MVP-D-TEK Vehicle Loop Detector 9 Volts DC to 240 Volts AC. Operating Instructions

Installing the Cisco ONS FAP-4 Fuse Alarm Panel

DL423 DirectLine Sensor Module for Conductivity Measurement Specifications

Installation Instructions

MANUAL RESET ALARM RELEASE BOX

Public Safety DAS Annunciator Panel

ALK-V PHOTOELECTRIC SMOKE SENSOR

Model 3300 Technical Support and Installation Manual

ISC-PDL1-W18G-H. Installation Instructions Professional Series Dual Detector

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection

Carbon Monoxide Transmitter

Instructions R8471J Gas Controller for use with Model OPECL Open Path Eclipse IR Gas Detector 1.1 1/

CIR CRUSH & IMPACT RESISTANT ARCTIC GRADE OIL & GAS CABLES

SL-3 Vibration Sensor line A&E Specifications Page 1 of 12 SL-3 AE v doc

D7044. Installation Instructions Multiplex Single Input Module

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

CIR AG Power Cables. CIR AG Control Cable. CIR Type VFD Cable. CIR AG Ratings & Approvals. n UL Listed as Type TC-ER n UL Listed as TC-ER-HL (E123629)

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual

D7053. Installation Instructions Multiplex Input/Output Module

INSTALLATION INSTRUCTIONS FOR 7370A736 FLUSH MOUNT CEILING PLENUM

RCR-REX Request-to-Exit Dual Technology Motion Sensor Installation Guide

vibration switch

DL424/425 DirectLine Sensor Module for Dissolved Oxygen Probes Series DL5000 Specifications

A. This Section includes the following lighting control devices:

Sierra Series 900 Single & Dual Channel System. Instruction Manual

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger

Conventional Releasing Control Panel

SERIES 35-63J APPLICATIONS FEATURES SPECIFICATIONS AGENCY CERTIFICATIONS

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Duct smoke housings, 4-wire D341/D341P and D342/D342P

General Routing Interface

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL

STT 3000 Series STT250 Smart Temperature Transmitters Specifications Models STT25T EN0l-6091 February 2009

Intelligent Detection Devices

TrueAlarm Analog Sensing

CIR CRUSH & IMPACT RESISTANT OIL & GAS CABLES

ICS Regent. Fire Detector Input Modules PD-6032 (T3419)

Frost Heave Protection System Installation and Operation Manual

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES

MANUAL RESET ALARM RELEASE

Transcription:

7.01 7/11/2000 8:1 AM Page 1 CP Scan#1:Desktop Folder:hold:90 Catalog:7.01.job: 7.01 AlarmLine Linear Heat Detector FEATURES Integrating Type Linear Heat Detector Analog Sensing Field Adjustable Alarm Set Point Three Cable Styles Two Module Styles Restorable up to 27 F Short Circuit Discrimination Insrtinsicallyt Safe Option Factory Mutual Approved, 0 ft Spacing CSFM Listed 7270-074:1 APPLICATIONS Open Area Protection Cable Trays Rack Storage Freezer Warehouses Belt Conveyers Floating Roof Fuel Tanks Cooling Towers Dust Collectors Waste Fuel Drum Storage Power Distribution Apparatus Escalators DESCRIPTION The Fenwal AlarmLine Linear Heat Detector provides early detection of fire or overheating conditions by detecting changes in temperature in localized areas or over its entire length. It is especially suited for confined areas or harsh environments where adverse ambient conditions cause other detection devices to be unreliable or difficult to use. The system consists of two major components: a small diameter sensor cable and an interface module. The sensor cable is constructed with a negative temperature coefficient material, where a change in temperature results in an exponential decrease in resistance of the sensor. The interface moduleinterprets this resistance change and provides anoutput to the fire control panel once the fieldprogrammable alarm set point is exceeded. BENEFITS FLEXIBLE: -Mechanical - Allows installation at point of risk. -Electrical - Compatible with all central control panels. -Alarm Levels - Adjustable for different temperatures. DURABLE: Extrusion & Braiding options to satisfy environmental conditions and project risks. RELIABLE: Fault signaling of open and short circuit conditions. RECOVERABLE: Self restoring after fire event to 27 F. SENSITIVE: Proven superiority over point type

measurement. ANALOG HEAT SENSING AlarmLine s analog heat sensing characteristics offer several distinct advantages: Field adjustable alarm setpoint Restorable Integrating Short circuit discrimination Alarm threshold may be programmed to meet specific system requirements. Cable does not need to be replaced after an alarm event up to 27 F (12 C). It is not necessary to reduce sensor spacing with increased ceiling height per NFPA 72-1996, Section -2.4.1.2 Exception (a). System sensitivity remains constant as ceiling height increases without reducing the spacing. The system will produce a trouble condition instead of a false alarm in the event of a conductor to conductor short due to damage or electrical faults. SENSOR CABLE The AlarmLine sensor cable consists of four 26 AWG copper conductors, each color-coded in an insulated sheath containing a negative temperature coefficient polymer. Two of the conductors are enameled, and provide loop continuity supervision, but not temperature sensing. The conductors are twisted at 0 turns per foot ( 90 per meter) and protected by a flame-retardant outer extrusion (see Figure 1). The color-coding of the four inner conductors is repetitively marked on the outer coating every feet as an aid in installation. Cable is sold on standard rolls of 200m (66 ft). NOTE: The maximum length of sensor cable per zone depends on the maximum ambient temperature defined on the nomogram. Regardless of ambient, however, the maximum length of cable is 200 feet (00m) per zone for Type T cable. Sensor cable is available with the following part numbers: Standard Sensor Cable 7-117068-01: Recommended for environments ranging from clean and dry to moderate dust and moisture. Nylon Coated Sensor 7-117068-016: Recommended for use in wet, oily or corrosive environments or outdoors. Use in freezer warehouses. Phosphor Bronze Braided Sensor 7-117068-019: Recommended for applications requiring superior abrasion protection or increased tensile strength. CABLE SENSOR FIGURE 1 STANDARD SENSOR CABLE INTERFACE MODULE NEGATIVE TEMPERATURE COEFFICIENT MATERIAL SENSOR CONDUCTOR WIRE PROTECTIVE INSULATION HIGH TEMPERATURE PVC The interface module is available in two versions, a twowire version for use with Kidde-Fenwal control panels, and a 4-wire version for use with any 24VDC control panel. The 4-wire version is powered by an external 24 VDC source and is connected to a fire alarm control panel s detection input circuit via alarm and trouble relay contacts. The interface module monitors the resistance of the sensor cable, and generates an alarm whenever the resistance drops below the preset threshold. The module also supervises the sensor cable for opens and shorts to generate a fault condition. These conditions are displayed on the module faceplate by the two LED indicators: - red LED, and - yellow LED. Modules are available with the following part numbers: 7-117068-046 4-Wire interface module, in gray polycarbonate enclosure. Provides alarm and trouble relay contacts. 7-117068-042 2-Wire interface module circuit board. 7-117068-044 Gray polycarbonate enclosure only. 6.62 (16.8 cm) H x 4.12 (. cm)w x 4. (11.4 cm) D. 7-117068-00-Wire interface module, with mounting plate for mounting in the Fenwal Model 2 control panel.

CABLE SPECIFICATIONS Part Number Jacket Construction Standard Length External Diameter Weight per 66 ft (200m) Tensile Strength Ambient Insulation Colors Material Diameter Twist of Inner s Dielectric Material Voltage Proof Between PVC Jacket and a Service Life Maximum spacing between parallel runs Standard Sensor 7-117068- 01 High Blue PVC 0.117 in. (.2 mm) 7 lb. (.2 kg) Nylon Coated Sensor 66 feet (200m) reel 0.1 in. (4.2 mm) 9. lbs. (4. kg) 7-117068- 016 Black nylon extrusion over blue PVC Bronze Braided Sensor 7-117068- 019 Phosphor bronze braid over blue PVC 0.1 in. (4.2 mm) 18. lbs. (8. kg) 0 N 0 N 0 N 0 F (-17 C) to 212 F (0 C) -40 F (-40 C) -40 F (-40 C) to 212 F to 212 F (0 C) (0 C) 1 = Orange; 2 = White; = Red; 4 = Blue 26 AWG Solid Copper 0.018 in. (0.460 mm) 0 per ft. (90 per meter) Specially Doped Polymer KV Up to 212 F (0 C) = 0 Years. At 27 F (12 C) = 24 Hours. Self Restores below 27 F (12 C). Above 74 F(190 C) is the destructive temperature. 0 feet ( 9 meters) SENSOR MOUNTING HARDWARE Three types of standard mounting hardware (master clamp, flange clamp, nylon cable tie) for AlarmLine permit safe, secure sensor cable installation in most applications. Other mounting means may be used as required by the specific application. The sensor should be supported at a minimum of ten foot intervals on straight runs when under tension, and more as conditions dictate at corners and transition points to provide suitable strain relief. Local codes or conditions may also require the sensor cable to be supported at closer intervals. Refer to manual MC-428 for specific mounting information. MODULE SPECIFICATIONS Supply voltage Current Consumption Standby Current Consumption Current Consumption Fault Noise Performance Visual Indicators Controls Relay Auxiliary Outputs Outputs Operating Range 2-WIRE VERSION 4-WIRE VERSION + 8 to 0 VDC +17 to 0 VDC 40 to 60µA 0 to 70µ A ma 82 ma 1 to 10µA 16 ma Will withstand % RMS 60 Hz supply voltage noise or 1 Vrms 60 Hz sensor noise with negligible performance change. RFI immunity at V per meter, field strength over the band 20-900 MHz. F ire: Panel mounted continuous red LED. F ault: Panel mounted flashing yellow LED. T est Switch: Fault and positions. Verifies module operations in both modes. Trip Selection: 12 position pre- calibrated switch to select alarm threshold. None Alarm: remote alarm LED. Fault: Normally closed Alarm: Form C relay rated 2A @ 0VDC. Energizes on alarm. Fault: Form C relay rated 2A @ 0VDC. Energizes on trouble. Terminals for connection of transistor output -1 F(-2 C) to 12 F(0 C) INTRINSIC SAFETY BARRIERS In classified hazardous areas where potentially explosive vapors, dust, or fibers exists, AlarmLine cable must be installed using an intrinsic safety barrier. Barrier P/N 7-117068-01 is a shunt-diode safety barrier which limits the current and voltage in the sensor cable to safe levels. Each barrier handles two conductors, so two barriers are needed for each sensor cable. The barriers are designed to mount in separate weathertight enclosures. The intrinsic safety barrier specifications are as follows: FM Approvals Class I, Division 1, Groups A, B, C, D Class II, Division 1, Groups E, F, G: Class III, Division 1 Operating -4 F (-20 C) to F (60 C)

SETTING THE ALARM TEMPERATURE The alarm temperature and the correct position of the 12-position alarm trip switch on the interface module are determined by use of the AlarmLine nomogram. The use of the nomogram requires two known factors: Maximum ambient temperature of the alarm zone. (Scale A). The total length of the sensor cable to be used. (Scale L). The resistance change required to create an alarm can be a result of either a predetermined minimal increase in temperature over the entire length of the sensor, or a significant increase on a shorter section of cable. This integrating (averaging) effect of the sensor cable allows it to detect a localized hot spot or a low level temperature increase over its entire length. The alarm temperature in either case is determined only after the alarm trip switch position is determined. A shorter section of sensor cable exposed to an overheat condition will require a higher temperature to achieve an alarm than a longer length of sensor cable exposed to the same overheat condition. Refer to manual MC-428 for further programming information. EXAMPLE: A 00 foot length of AlarmLine type T sensor cable is required to operate in a space with a maximum ambient temperature of 11 F. METHOD: 1. On figure 2, a straight line is drawn from the 00 foot mark on Scale L through the 11 F mark on Scale A. The line crosses Scale S at approximately switch position 7. 2. On figure, a straight line is drawn from the alarm trip switch position 7 on Scale S to the 00 sensor cable length on Scale A. SOLUTION: 1. The AlarmLine linear heat detector in this example will operate in an ambient temperature up to about 11 F and not generate a false alarm. See Scale A on figure. 2. The AlarmLine linear heat detector in this example will generate an alarm if the temperature of the entire sensor length averages about 12 F as shown where the line crosses Scale T on figure. Higher temperatures would be needed to initiate an alarm over shorter sections of entire sensor length.. Alarm temperatures for shorter sections of the AlarmLine linear heat detector in this example with 00 feet of sensor and the alarm trip switch set to position 7 may also be calculated. On Figure, draw straight lines from position 7 on Scale S to any desired length less than 00 feet on Scale L. According to the above example: 00 ft at 12 F will cause an alarm ft at F will cause an alarm 20 ft at F will cause an alarm ft at 208 F will cause an alarm ALARM TRIP SWITCH POSITION 1 2 4 6 7 8 9 11 1 2 4 6 7 8 9 11 S A T MAXIMUM SPECIFIED AMBIENT ALARM TEMPERATURE TEMPERATURE (F) ( F) 7 8 9 11 10 17 18 7 8 9 11 10 17 18 9 11 10 17 18 20 2 220 240 20 27 9 11 10 17 18 20 2 220 240 20 27 L SENSOR CABLE LENGTH FEET (f) FIGURE 2 - EXAMPLE FOR TYPE T CABLE S ALARM TRIP SWITCH POSITION A T MAXIMUM SPECIFIED AMBIENT ALARM TEMPERATURE TEMPERATURE (F) ( F) Maximum Ambient Alarm Condition 200 2900 2600 0 2000 0 0 00 82 60 00 00 26 200 0 80 6 0 2 20 L SENSOR CABLE LENGTH FEET (f) FIGURE - EXAMPLE FOR TYPE T CABLE 200 2900 2600 0 2000 0 0 00 82 60 00 00 26 200 0 80 6 0 2 20

INITIATING CIRCUIT + - (-) (+) ORANGE CABLE SENSOR 4 6 9 WHITE RED 4BLUE TEST TROUBLE/ OUTPUT LED (-) (+) (-) (+) 7 8 11 12 E.O.L. RESISTOR FIGURE 4 2-WIRE MODULE WIRING DIAGRAM INTERFACE MODULE WIRING The 2-wire interface module, part number 7-117068-042, may be connected to a 2, 220, Scorpio, or Gemini fire control panel. The module is wired directly to the initiating circuit of the panel as shown in figure 4. The 4-wire interface module, part number 7-117068-046, may be connected to any 24VDC fire control panel. The control panel must have a 24VDC switched power output which is interrupted when the control panel is reset. The module s alarm and fault relays are wired as shown in figure. This interface module comes pre-mounted in a 7-117068-044 enclosure, and is designed to be mounted outside the control panel. Up to 6,000 feet of 4 conductor 16 AWG lead-in wire may be connected between the module and the beginning of the sensor. The end of the sensor cable is terminated with the orange & white, and red & blue conductors spliced together. Refer to manual MC-428 for complete wiring information. SENSOR CABLE HEAT PAD AlarmLine sensor cable heat pads P/N 7-117068-041 are used in critical areas. The heat pad concentrates the sensor into a compact area, thus enabling it to quickly detect localized overheating at a lower temperature, because a greater length of cable is heated at the same time. Heat pads can also be used at the end of a zone to accommodate testing of the sensor with a hot air gun. MODULE TEST FEATURE A three position Alarm-Normal-Fault test switch allows the user to perform a simple electronic test of the interface module s electronic circuitry. Before testing, care should be taken to disarm any suppression, alarm, or auxiliary functions since the fire and fault tests will be signaled to the control panel as genuine alarm and fault conditions. TEST INITIATING CIRCUIT + - (-) (+) ORANGE CABLE SENSOR 4 6 9 WHITE RED 4BLUE TROUBLE/ OUTPUT LED (-) (+) (-) (+) 7 8 11 12 E.O.L. RESISTOR FIGURE 4-WIRE MODULE WIRING DIAGRAM

ARCHITECT/ENGINEERING SPECIFICATIONS 1. The Linear Heat Detector shall be Fenwal AlarmLine P/N 7-117068-01 [or -016 or -019] or equal in quality, features and performance as described. 2. The linear heat detector shall be of the integrating (averaging) type and consist of four small gauge solid copper conductors each insulated with a negative temperature coefficient material. The conductors shall be twisted at a rate of approximately thirty turns per foot (90 per meter) to cancel out potential high voltage inductance. The conductor insulation shall be color coded for ease of installation. The sensor cable shall have an outer protective extrusion of high temperature PVC material. Option A for -016 sensor: The sensor cable shall have an additional outer extrusion of nylon as additional protection against harsh environments. Option B for -019 sensor: The sensor cable shall have an outer braid of Phosphor Bronze to increase its tensile strength and for protection against abrasion.. The linear heat detector shall have a field adjustable alarm set-point. 4. The sensor cable shall be self-restorable to its normal condition after an alarm up to 27 F.. The sensor cable shall be capable of being spliced in the field. 6. The sensor shall have Factory Mutual recommended spacing requirements of 0 feet (9 m), regardless of the height. ORDERING INFORMATION DESCRIPTION PART NUMBER Standard PVC Sensor Cable 66 ft (200m)Coil 7-117068-01 Nylon Coated Sensor Cable 66 ft (200m) Coil 7-117068-016 Bronze Braided Sensor Cable 66 ft (200m) Coil 7-117068-019 2-wire Interface Module with Mounting Plate for the 2 Panel 7-117068-001 4-wire Interface Module with Relay Output and Surface Mount Enclosure 7-117068-046 2-wire Interface Module circuit board only 7-117068-042 Surface Mount Enclosure only, for Interface Module circuit board 7-117068-044 Nylon Cable Tie (pkg 0) for pipe up to 8 7-117068-020 Master Clamp (pkg 0) for flanges to 1/2 7-117068-022 Flange Clip (pkg 0) for flanges to /16 7-117068-02 Flange Clip (pkg 0) for flanges to 1/4 7-117068-024 Nylon Cable Clamp (pkg 0) for use with Master Clamp, Flange Clips, or 7-117068-02 Nylon Cable Tie Weathertight Connector, used with Standard Sensor 7-117068-026 Weathertight Connector, used with Nylon Coated or Bronze Braided Sensor 7-117068-027 I n-line Sensor Splice (pkg ) 4 required per splice 7-117068-028 In-Line Sensor Splice Crimping Tool 7-117068-029 Sensor Termination Kit (pkg ) terminates zones 7-117068-00 Intrinsic Safety Barrier (2 required per zone) 7-117068-01 Enclosure holds (2) Barriers 7-117068-02 Enclosure holds up to () Barriers 7-117068-0 Enclosure holds up to (12) Barriers 7-117068-04 Enclosure holds up to (24) Barriers 7-117068-0 Intrinsic Safety Barrier Weathertight Enclosure holds up to (2) Barriers 7-117068-06 AlarmLine Installation Manual and Applications Guide MC-428 KIDDE-FENWAL, INC. 400 MAIN STREET, ASHLAND, MA 01721 TEL: (08) 881-2000 FAX: (08) 881-6729 www.fenwalcontrols.com 7.0/00 2000 Kidde-Fenwal, Inc. Printed in U.S.A. CP The literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes no responsibility for the products suitability for a particular application. The product must be properly applied to perform as described herein. If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721 (08) 881-2000.