TECHNICAL DOCUMENTATION WOLF WARM AIR CURTAIN TL-2 30m 3 /h
TL-2 WARM AIR CURTAIN Additional silencer mat in the discharge section Attractive intake grille with rectangular perforations, self-centring mounting, easy to unhook for a quick filter change (may be secured with arrestor wires) Adjustable discharge element, black plastic dividers, anodised aluminium fins BENEFITS OF THE WOLF WARM AIR CURTAIN TL-2 CNC-manufactured, stable and self-supporting sheet steel casing in a modern design, powder-coated in RAL 9016 (traffic white) Easily accessible inspection flap located underneath the unit, designed to open downwards Manufactured in compliance with the EN ISO 9001-2000 quality management system CASING Self-supporting casing made from powder-coated sheet steel (RAL 9016); vertical installation next to the entrance on request INTAKE GRILLE FILTER Intake grille made from perforated sheet steel (CNC-manufactured, rectangular perforations), powder-coated in the appliance colour, easy to unhook for a quick filter change; the grille is self-centring and, after being removed, can be suspended on arrestor wires during filter maintenance Renewable filter element (category G2) ensures a consistently high heat transfer and a long service life for the appliance (only for PWW, PHW or appliances heated by steam) HEAT EXCHANGER IMPORTANT INFORMATION ALTERNATIVE: ALTERNATIVE: FANS 3 types of heat exchanger for each air curtain for pumped hot water PWW / PHW (steam available on request) Heat exchanger made from Cu/Al, collector made from Cu, secured to prevent twisting, heat exchanger fins made from Al Imperial threaded connections (¾" female thread) For PWW and PHW connections for PN 16 up to 110 C: water flow and return in the top left (when viewed in the direction of airflow) for the TL-2 A10 to TL-2 A30; in the top right (when viewed in the direction of airflow) for the TL-2 A40 Change to top right or to the left or right side on request Electric heat exchanger Electric heating coil, base frame made from zinc-plated sheet steel with resistance heater elements, corrosion-resistant with spiral-shaped fins and thermal overheating protection, available on request Zinc-plated steel heat exchanger Heat exchanger and collector made from zinc-plated steel, suitable for pumped hot water PWW/PHW, available on request Radial fans with double-sided air intake, supported to provide vibration-free running, equipped with 230 V/50 Hz AC motors, direct drive, multiple fan vanes, operates quietly with high fan draught, motor protected via thermal cutouts routed to the outside AIR DISCHARGE APERTURE Air discharge can be pivoted by rotating the discharge system. 02
DIMENSIONS UNIT DIMENSIONS T TL-2 A10 - TL-2 A30 T 555 555 555 555 555 H 260 260 260 260 260 H B TL-2 A40 T 610 610 610 610 610 H 290 290 290 290 290 TOP VIEW OF THE UNIT CEILING MOUNTED B B/2 B/2 d d TL-2 A10 - TL-2 A30 a 35 35 35 35 35 b 295 295 295 295 295 c 225 225 225 225 225 d 40 40 40 40 40 B/2 - - - 1250 1500 c b a M8 female thread Intake grille TOP VIEW OF THE UNIT PIPE CONNECTION T TL-2 A40 a 50 50 50 50 50 b 325 325 325 325 325 c 235 235 235 235 235 d 40 40 40 40 40 B/2 - - - 1250 1500 h g f e Flow 1) (with valve) B All connections: 3/4" female thread Flow 2) (without valve) Return Intake grille T TL-2 A10 - TL-2 A30 e 80 80 80 80 80 f 175 175 175 175 175 g 366 366 366 366 366 h 50 50 50 50 50 1) Connection only if valves are pre-assembled. 2) Connection without valves or if valves are supplied loose. TL-2 A40 e 80 80 80 80 80 f 175 175 175 175 175 g 416 416 416 416 416 h 50 50 50 50 50 03 WOLF WARM AIR CURTAIN
SPECIFICATION TYPE TL-2 A10 A20 Part no. 2138003 2138004 2138005 2138006 2138007 2138008 2138009 2138010 2138011 2138012 Installed width [mm] 1000 1500 2000 2500 3000 1000 1500 2000 2500 3000 Installed height Max. m 2.3 2.3 2.3 2.3 2.3 2.6 2.6 2.6 2.6 2.6 Air volume Stage 3 m³/h 1400 1800 2700 3600 4100 1900 2700 3800 4600 5400 Max. discharge speed m/s 5.4 5.4 5.4 5.4 5.4 7.5 7.5 7.5 7.5 7.5 Sound pressure level* (3 m distance)db(a) 53 54 55 56 58 54 55 56 57 59 Heating output (70/50 C)** kw 7.7 9.9 14.8 19.7 22.5 10.4 14.8 20.8 25.2 29.6 (60/40 C)** kw 6.1 7.9 11.8 15.8 18.0 8.3 11.8 16.7 20.2 23.7 Flow rate (70/50 C) m³/h 0.33 0.42 0.64 0.85 0.97 0.45 0.64 0.90 1.08 1.27 (60/40 C) m³/h 0.26 0.34 0.51 0.68 0.77 0.36 0.51 0.72 0.87 1.02 Water pressure drop (70/50 C) kpa 0.76 0.63 1.18 1.73 2.52 1.36 1.35 2.03 2.46 3.94 (60/40 C) kpa 0.73 0.73 1.43 2.15 3.68 1.05 1.19 2.14 2.87 5.11 Pipe connections (fem.) flow/return inches 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" Electrical data, fans 230 V kw 0.46 0.46 0.69 0.92 1.15 0.46 0.69 0.92 1.15 1.38 A 2.10 2.10 3.15 4.20 5.25 2.10 3.15 4.20 5.25 6.30 Weights kg 40 45 65 75 100 40 50 70 90 105 SPECIAL VERSION WITH ELECTRIC HEATING COIL (three-stage, 400 V, 3 phase, 50 Hz) Stage 1 kw 3 4 6 6 8 3.5 5 6 8 10 Stage 2 kw 6 8 12 12 16 8.5 12.5 17 20 25 Stage 3 kw 9 12 18 18 24 12 17.5 23 28 35 TYPE TL-2 A30 A40 Part no. 2138013 2138014 2138015 2138016 2138017 2138018 2138019 2138020 2138021 2138022 Installed width [mm] 1000 1500 2000 2500 3000 1000 1500 2000 2500 3000 Installed height Max. m 3 3 3 3 3 3.5 3.5 3.5 3.5 3.5 Air volume Stage 3 m³/h 2700 3600 5400 6300 7200 2900 4300 5700 7100 8300 Max. discharge speed m/s 10.0 10.0 10.0 10.0 10.0 11.0 11.0 11.0 11.0 11.0 Sound pressure level* (3 m distance)db(a) 55 56 57 58 60 58 60 62 63 64 Heating output (70/50 C)** kw 14.8 19.7 29.6 34.6 39.5 15.6 23.1 30.6 38.2 44.6 (60/40 C)** kw 11.8 15.8 23.7 27.6 31.6 12.5 18.5 24.5 30.5 35.7 Flow rate (70/50 C) m³/h 0.64 0.85 1.27 1.49 1.70 0.60 1.02 1.35 1.46 1.96 (60/40 C) m³/h 0.51 0.68 1.02 1.19 1.36 0.54 0.79 1.05 1.31 1.53 Water pressure drop (70/50 C) kpa 2.68 2.29 3.78 4.33 7.33 3.27 1.40 3.13 1.85 3.20 (60/40 C) kpa 1.53 1.64 3.17 4.10 7.11 2.86 1.27 2.47 2.00 3.55 Pipe connections (fem.) flow/return inches 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" Electrical data, fans 230 V kw 0.69 0.92 1.38 1.61 1.84 0.50 0.66 0.83 0.99 1.16 A 3.15 4.20 6.30 7.35 8.40 3.90 5.20 6.50 7.80 9.10 Weights kg 42 65 80 100 120 80 95 130 150 195 SPECIAL VERSION WITH ELECTRIC HEATING COIL (three-stage, 400 V, 3 phase, 50 Hz) Stage 1 kw 5 7.5 10 12 15 5 7.5 10 12 15 Stage 2 kw 10 15 20 24 30 10 15 20 24 30 Stage 3 kw 15 22.5 30 36 45 15 22.5 30 36 45 * Sound pressure level centre of area, distance 3.0 m, room volume 3000 m³, reverberation time 1.0 s ** Heating output at intake temperature 20 C, discharge temperature 35 C (70/50 C) or 32 C (60/40 C) 04
CHECKLIST Selection of warm air curtain unit taking all important criteria into account. TL-2 checklist to evaluate ambient and local conditions 1. Installation height: (passage) Max. 2.3 m... points Max. 2.5 m... Max. 3.0 m... 2. Passage width: Max. 1.5 m... Max. 2.0 m... Max. 3.0 m... Max. 4.0 m... 6.0 m... 3. Room surface area: Up to 100 m²... Up to 250 m²... Up to 500 m²... Up to 750 m²... Up to 1000 m²... Over 1000 m²... 4. Room height: Standard height... High ceiling... Upper floor with (indoor) staircase... 6. Porch: Closed (double doors)... Open... None... 7. Climatic conditions: Positive pressure... Pressure compensation... Negative pressure... 8. Local conditions: Separate row of houses... Corner location/ bordering a square... Extreme location (e.g. riverbank, lakeside, hill top)... 9. Wind exposure: Generally weak... Average... Strong... 10. Direction: North, east, south, - west... 5. Further passages None or on same wall... Lateral... Opposite... Sum of points CAPACITY SELECTION ACCORDING TO TABLE (depending on total number of points) Number of points Models Door widths in Air handling rate per m door width Heating output per m curtain Discharge velocity from curtain Installation height m m³/h kw * m/s m 10 TL-2 A10 1 / 1.5 / 2 / 2.5 / 3 1400 7.7 5.4 2.3 20 TL-2 A20 1 / 1.5 / 2 / 2.5 / 3 1900 10.4 7.5 2.6 30 TL-2 A30 1 / 1.5 / 2 / 2.5 / 3 2900 14.8 10.0 3 40 TL-2 A40 1 / 1.5 / 2 / 2.5 / 3 4000 15.9 11.5 3.5 * for PWW 70/50 C, intake temperature 20 C, discharge temperature 35 C 05 WOLF WARM AIR CURTAIN
ACCESSORIES CONTROLLERS Controller type WTMC 300 3-stage fan speed controller with additional functions for matching the air flow rate to different weather conditions; max. 10 A - Graphic touchscreen - Key lock - ON/OFF changeover key - Manual/automatic setting; e.g. automatic door contacts, room thermostat - Summer/winter setting (with or without heating medium) - Full motor protection; electronic processing and signalling in the event of motor failure - Fault messages can be retrieved from memory for remote diagnosis Controller type WTMC 500 5-stage fan speed controller with additional functions for matching the air flow rate to different weather conditions; max. 10 A - Graphic touchscreen - Key lock - Enable DDC/BMS - Integral electronic filter monitor - ON/OFF changeover key - Manual/automatic setting; e.g. automatic door contacts, room thermostat - Summer/winter setting (with or without heating medium) - Fault messages can be retrieved from memory for remote diagnosis - Run-on control via door contact with adjustable run-on time - Floating changeover contacts, operating and central fault messaging 16 A FROST STAT Frost stat type WTF, part no. 21 00 355 Version with capillary sensor Capillary length 3 m, with 1 switching circuit, designed as changeover switch. For units with WTC 3 and WTC 5 controllers. Function The frost stat has a changeover contact that switches over when the temperature falls below 5 C. The temperature can be set to between -10 C and +12 C. Example: If the temperature falls to 5 C, the frost stat switches off the fans to prevent the heating coils from cooling down or freezing. THERMOSTATIC CONTROL VALVE Type WTR 2 (2-way valve) / WTR 3 (3-way valve) WTR 2 / WTR 3 thermostatic control valve with thermostatic head for a constant discharge temperature. The WTR 2 / WTR 3 thermostatic control valves are automatic proportional controllers that regulate water flow rates. The valve opens when the sensor temperature drops. Capillary length: sensor 2 m WTR 2 design: straight-through valve DN 20, kvs = 5.0 or right angle valve DN 20, kvs = 7.0 WTR 3 design: three-way valve DN 20, kvs = 4.5 THERMOELECTRIC SHUT-OFF VALVE Type WTAV (2-way valve) Thermoelectric shut-off valve, type WTAV, 230 V, normally closed. In conjunction with WTC 3 or WTC 5 controllers. To shut off the water flow in "summer" mode in conjunction with our controllers, or to regulate water flow rates with control systems provided by the customer. WTAV design: straight-through valve DN 20, kvs = 5.0 or right angle valve DN 20, kvs = 7.0 CEILING SUSPENSION DEVICE Type WDH 4 / WDH 6 The ceiling suspension device, type WDH 4 / WDH 6 has threaded rods for length adjustment. The threaded rods allow the ceiling suspension devices (which are required for an air curtain) to be adjusted, thereby ensuring that the air curtain is level. Design options: WDH 4 up to 2.0 m installed width; WDH 6 for 2.5 m installed width or more. 06
07 WOLF WARM AIR CURTAIN NOTES
Dealer address WOLF GMBH / P.O. BOX 1380 / D-84048 MAINBURG / TEL. +49.0.875174-0 / FAX +49.0.875174-1600 / www.wolf.eu Doc. no. 4800188 GB 2017/05