Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

Similar documents
Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

BiWire Flexi. BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI Installation Manual

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL

Installation and user manual for the BiWire / Conventional Repeater Panel

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

Installation, Operating and Maintenance Manual

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

Intelligent Security & Fire Ltd

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

Application, Installation, Operation & Maintenance Manual

Fire Control Panel. Installation & Programming Manual TABLE OF CONTENTS

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

Control Panel Engineering and Commissioning Instructions

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3

Saffire User & Installation Manual. IMPORTANT This manual should be left with the panel after installation.

Noby-448 User Operating Manual & Log Book Page 1 of 12. Fire Control Panel. User Operating Manual & Log Book

OPERATION AND INSTALLATION MANUAL

Fire Control Panel. Installation & Programming Manual TABLE OF CONTENTS

Conventional Fire Alarm System 2014 V1.2

GAS SUPRESSION CONTROL PANEL:

FIREPRO INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL. Approved Document No. GLT Issue: 1. 8 Author: NRPJ Date: 7/ 3/201 4

Excel-EN Conventional Fire Control Panel

BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL

Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses

NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL

FIRE ALARM CONTROL PANEL. COMPLIES WITH EN54 part 2 & part 4 MEETS THE FUNCTIONAL REQUIREMENT OF BS:EN 5839 part 1 INSTALLATION MANUAL

Panel Functions & Indicators - Key to Icons General & Zone Fire LEDs ACCEPT SOUNDERS START/ STOP RESET BUZZER MUTE KEYSWITCH DELAY ON/OFF ITEM SELECT

Operating manual and Log book for the range of 1,2,4 and 8 zone fire Control and Repeat panels

Intelligent Security & Fire Ltd

Conventional Fire Control Panel (FKEP2, FKEP4, FKEP8) Operation and Maintenance Manual. Man-1078EL Issue 01 February 2014

Industries. As a premier global manufacturing company, we believe that great brands are

Operating manual and Log book for the range of 1,2,4 and 8 zone fire Control and Repeat panels

3200 NON-ADDRESSABLE FIRE ALARM CONTROL PANEL

Menvier Fire System MF9300

USER MANUAL & MAINTENANCE GUIDE OG OO

MAG2/4. AL MAG2 Soft. Version 2.1 MAG4 Soft.Version 2.0 USER MANUAL

Surveyor Excel. Fire Alarm Control Equipment Network version. Programming Manual MASTER MANUAL. VERSION 14.0 and Above

Installation Manual Premier 412/816/832. Issue 10

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL

SECURIT 700L PLUS ENGINEERING MANUAL

VoCALL - CFVCC5. Compact 5 Line Exchange Unit. Installation & Commissioning Manual

Door Release Power Supply

Fire Alarm Control Panel. System Maintenance and Log Book

6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL

PAT E N T System 88. COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00

Hydrosense. Vimpex Limited. Star Lane. Great Wakering. Essex SS3 0PJ. Tel: +44 (0) Fax +44 (0)

FIRE ALARM CONTROL PANEL FVC01-08

CONVENTIONAL CONTROL PANEL FL2/4/8/12 LT-XP

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER

NFS Supra / VSN-2Plus / ESS-2Plus Conventional Fire Alarm Control Panel. Installation and Operating Manual

OPERATION & INSTALLATION MANUAL FOR ALARM PANEL M2AP01

System 800 Addressable Fire Detection & Alarm System

FSTP2-2-wire 2 Zone Conventional Fire Control Panel Operation and Maintenance Manual. Man-1078FS2 Issue 01 April 2012

Operating manual and Log book for the range of 1,2,4 and 8 zone fire Control and Repeat panels

Conventional Leaflets

FSTP4-2-wire 4 Zone Conventional Fire Control Panel Operation and Maintenance Manual. Man-1078FS4 Issue 01 April 2012

Precept Marine Control Panel Application Guide

Control Panel User Guide

Surveyor Envoy-MINI 4

Conventional Fire Control Panel

Intruder - Fire - Water Combined Alarm

INFINITY 8 INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL

USER MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 & EN54 PARTS 2 & 4

ORION Mini-Rep INSTALLATION MANUAL

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

FEC400 Series. Installation Manual

Conventional Fire System. BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI User Manual

FEC403EN Installation Manual

EXTINGUISHING AGENT RELEASE MODULE

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

User Operation Manual

General Routing Interface

Control Panel Engineering and Commissioning Manual (TO BE RETAINED BY THE COMMISSIONING ENGINEER)

Smoke Vent Control Panel PCB4 V4 Installation Manual

909e Series 2/4 Zone Panel. Operating and Configuration. Manual Version V01

Operation and Maintenance Manual

Unity DAU Voice Alarm System

MR-2602 Two Zone Fire Alarm Control Panel

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual

PERTRONIC INDUSTRIES LTD F4-RMAX Installation Note

INSTALLATION MANUAL SECURIT 802 CONTROL PANEL

EX8. Instruction Manual: COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 AND EN54 PARTS 2 & 4

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

Installation, Commissioning & Operating Manual

Doc. No.: OMPII.DOC Rev. 2 Written By: Raj Patel Checked By: AJC Approved By: JBJ Date: 03/05/05

4 wire conventional alarm system

ID2000. operating manual

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0

VSN PLUS VSN 4 PLUS ; VSN 8 PLUS ; VSN 12 PLUS

RE 102 RE Fire Alarm Control Panel. Installation, Commissioning & Operating Manual

highline SVCS-1 INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10

Control Panel User Guide (TO BE RETAINED BY THE USER)

TECHNICAL DATA OBSOLETE

FIREBETA EXTINGUISHING CONTROL PANEL (ECP)

SYSTEM MANUAL FT1-SB. Single Zone Fire Alarm System

VSN-RP1r Extinguishing Control Panel. User Manual (Software version 3.x) by Honeywell. doc. MIE-MN-570I rev.008

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

EvacU Emergency Warning Control and Indicating Equipment (Occupant Warning Systems) Technical Manual MAN3072-5

installation & maintenance manual LPCB APPROVED CFP 2/4/8 ZONE FIRE ALARM CONTROL PANEL approved document no. DFU rev 5

Premier Hazard STC Instructions

Transcription:

CF5000, MF5000 and FXP5000 Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels 16 zone panels

Contents PANEL INSTALLATION...3 Installation...3 PANEL WIRING... 3 Mains power supply... 3 Recommended Wiring Types... 3 Fuse Ratings...3 Battery connection... 3 Zone Wiring...5 Sounder Wiring...5 WIRING CONNECTION DRAWING...5 Wiring Connection Drawing 16 Zone... 5 Fault Fire Relay... 5 Class Change...5 Repeater Panel... 6 Auxiliary Relays...6 Interlink Panels... 7 Installation Check... 7 Zone Circuits...7 Sounder Circuits... 7 COMMISSIONING THE SYSTEM... 8 USER INFORMATION... 9 Mute buzzer...9 Silence alarm... 9 Reset after alarm activation...9 Reset without a fire activation...9 Evacuate... 10 Enable sounders... 10 Disable sounders... 10 Disable a zone Enable a zone... 10 MAINTENANCE...11 User Inspections and Tests... 11 One man walk test (by engineer)... 12 Individual zone test facility...12 Latch on fault facility...13 PANEL PROGRAMMING OPTIONS...14 Non latching zones... 14 TABLES... 15 Sounder and Visual Indication...15 Technical Specification...16 2

Panel Installation Please read the following instructions before installing and wiring the fire alarm panel. These ranges of panels are EN54 parts 2 and 4 certified and have been designed to comply with BS5839 part 1:2002 installations. The panels have two optional features: FIRE ALARM DEVICES: (EN54 part 2 clause 7.8) TEST CONDITION: (EN54 part 2 clause 10.0) In common with all electrical equipment the panel should be installed in a clean, dry, well-ventilated area, not in direct sun light and avoiding cold areas where possible. Note that temperatures in excess of 40 C and below -5 C will affect the panel operation. The panel should be located away from any potential hazard, in a position where it is readily accessible to authorised staff and the fire services. Ideally on the perimeter of a building near a permanent entrance. Panel Wiring Mains Power Supply The mains supply should be exclusive to the fire alarm as detailed in BS5839 part 1 or applicable local standard. It is recommended that a double pole fused spur unit is used and marked FIRE ALARM DO NOT SWITCH OFF, this should be for the sole use of the fire alarm. Within the panel, the mains supply should be isolated from the zone and alarm line wiring and should be connected to the terminal block marked MAINS. Recommended Wiring Types The following cable type and size are recommended: Mains wiring Zone wiring Sounder wiring 1.5mm 2, 2 core, fireproof cable 1.5mm 2, 2 core, fireproof cable 1.5 to 2.5mm 2, 2 core, fireproof cable Fire/Fault Output Wiring 0.5mm 2, 2 core, fireproof cable WARNING DO NOT USE A HIGH VOLTAGE TESTER WHEN WIRING IS CONNECTED TO ANY ELECTRONIC EQUIPMENT Fuse Ratings Mains Fuse Battery Fuse Sounder Circuits 1.6A AT Anti Surge 6.3A AT Anti Surge 500mA PolySwitch device Mount the panel, using pre drilled screw positions, to the wall. This will prevent any possible brick dust contamination of the panel internal circuitry. Use Three No.10 x 1 ¼ (5.0 x 30mm approx.) pan head screws. When using 20mm conduit entry direct to ensure a wide distribution of pressure when tightening the coupling. 3

Battery connection The 16 zone panel requires two YUCEL 12V 4Ah Batteries (supplied). Connect the red battery wire to the red battery terminal (+) of battery one. Connect the black battery wire to the black battery terminal (-) of battery two. Then connect the link cable as shown here. Battery Installation 1. Ensure that the panel is disconnected from mains power. Carefully remove the ribbon cable from the main board. Note: Do not attempt to remove the cable from the display board connector. 2. Attach battery cables to battery as shown in illustration above Battery connection. Note: Do not attach battery cables to main PCB before completing the next stage. 3. Carefully reattach the ribbon cable. The 16 Zone panels have a battery bracket to secure the batteries this should be fitted before reattaching the ribbon cable. 4. Connect the mains cable and power up the panel. Once powered up attach the battery cable to the main panel PCB following the illustration above Battery connection. 4

Zone wiring Each zone circuit is supplied with an End of Line Monitor unit (EOLM-1). All zone circuits must be terminated with an EOLM-1, taking care to observe the correct polarity. Sounder wiring The fire alarm control panel has four separately protected, line monitored, sounder circuits for use with polarised and suppressed bells, sounders, strobes, relays etc. The wiring for each sounder circuit is to be a parallel circuit with the 6K8, end of line resistor (EOLR), fitted at the end of the installed sounder circuit wiring. No spurs nor tee s are permitted. Wiring Connection Drawing On-board Fault/Fire relay Each panel has one Fire and Fault relay fitted. The Fault relay provides a fused volt free set of change over contacts. These contacts are not monitored. The relay has been designed to be fail safe, so that in the event of a total power loss, the relay contacts will be active. The Fire relay provides a fused volt free set of change over contacts. These contacts are not monitored. The relays are fused with a PolySwitch device rated at 500mA / 60V DC. Class change The sounder circuits can be operated by an external volt free contact (Relay, Switch, Timer etc.). A short circuit at this terminal will activate the sounder circuit outputs (nonlatching), removal of the short circuit will de-activate the sounder circuit output. It should be noted that activation of the class change input will give no visual indication on the panel and will not operate the auxiliary relays. 5

Repeater panel The panel has a RS485 repeater output as standard. The repeater panel has been designed to provide a cost effective installation solution, requiring only two interconnecting wires from the master panel. Several repeater panels can be installed from the master panel by cascading each repeater panel; again only two interconnecting wires are required between each repeater panel. As each repeater has its own mains supply and standby battery, the main panel standby time is not affected by the number of repeater panels installed. The repeater panel is suitable for up to 16 zones and displays all the same indications as the main panel, but with the addition of an indicator test and mute buzzer facility. Wiring Connect the repeater, RS485 TX+ and TX- terminals of the main panel, to the repeater panel positive and negative input terminals. Main Panel Repeater Panel TX+ to +ve input terminal TX- to -ve input terminal Auxiliary Relays The Auxiliary ( Zonal ) relays provide additional external fire indications per zone, for example AUX 1 will activate when there is a fire condition on Zone 1 and will deactivate when the fire condition is cleared. The polarity of the auxiliary relay can be changed to either Normally Open or Normally Closed via the associated jumper on the auxiliary relay board. Normally Open = Jumper across 1&2 Normally Closed = Jumper across 2&3 6

Interlinking Panels Two panels can be linked together as illustrated below. Zone 1 of Panel 1 must be connected to AUX 1 of Panel 2, with and EOLM-1 and 680Ω resistor as shown in the diagram above. Zone 1 of Panel 2 must be connected to AUX 1 of Panel 1, with and EOLM-1 and 680Ω resistor as shown in the diagram above. Zone 1 on both panels must be configured to Non-latching mode. This changes the operation of AUX 1 so that it triggers on any zone fire condition excluding zone 1. When Panel 1 detects a fire on zones 2-8/16, AUX 1 will activate placing the 680ohm resistor across Zone 1 of Panel 2. This will cause Panel 2 to go into fire but will not activate its AUX 1 output. Likewise, when Panel 2 detects a fire on zones 2-8/16, AUX 1 will activate placing the 680ohm resistor across Zone 1 of Panel 1. This will cause Panel 1 to go into fire but will not activate its AUX 1 output. Installation Check With the EOLM-1 s and EOL resistors fitted in the main panel, connect the mains supply and battery. Check the green power on LED is lit and that no other indicators are lit. Zone circuits Disconnect the mains and battery supply, wire in the zone circuits, one at a time, with the EOLM-1 transferred to the end of the zone (check polarity) but with no detectors fitted. Power up the panel by connecting the mains supply and battery. Check that the last call point in each zone operates correctly by using the supplied call point test key. Reset the panel after each activation. Fit all the detectors (a zone at a time) and check that the panel shows a healthy state. If there is a problem (zone fault showing) check the faulty circuit for continuity, correct polarity and polarity of the base diodes. (DO NOT USE A HIGH VOLTAGE INSULATION TESTER). Sounder circuits Disconnect the mains and battery supply. Wire in the sounder circuits, one at a time, transferring the end of line resistor to the end sounder/bell on each circuit. Power up the panel as before and verify that no fault shows. If there is a fault indication, check the affected circuit for short circuit, continuity and polarity. (DO NOT USE A HIGH VOLTAGE INSULATION TESTER). Check that the panel operates correctly by entering the access code (3112), followed by silence, followed by reset, check all indicators light up momentarily. Check each zone and alarm line for open and short circuit fault monitoring. 7

Commissioning the system Assuming that the installation instructions and installation checks have been carried out successfully, the fire alarm system is ready for commissioning. Each detector and call point should be tested in turn to ensure that it operates, indicates the correct zone fire LED and operates the alarm output correctly, ensuring all sounders/bells operate. Walk test facility A walk test function has been included in this range of panels to enable one person (electrical contractor or installer) to test the fire detection system without an assistant. This function is for the sole use of the electrical contractor or installer and not for normal operational use. The walk test facility access code is located inside the fire detection control panel. Once the walk test code has been correctly entered the test in progress indicator will show and the buzzer will pulse, this sets a time window of 10 minutes. If a detector or call point is triggered within this period the sounders will operate for a short time then the system will automatically reset ready for the next call point or detector activation. If a detector or call point is not operated within the 10 minute period then the system will automatically reset and return to normal operation. The walk test facility can be terminated at any time during test by pressing the reset button. 8

User Information There are 2 access codes used by the control panel: Access level 2 - client code (3112) Access level 3 - engineers code These codes are displayed on the rear of the front panel. The access level 2 code is also shown on the panel key fob. Level 2 access permits the following functions: - Silence alarm - Evacuate - Enable and disable zones - Enable or disable sounders - System reset The access code (level 2 or 3) is enabled by pressing the six control panel front buttons in the correct sequence. 1 2 3 4 5 6 An audible signal indicates that the access code keyed in is correct. Mute buzzer Silences control panel s internal buzzer Access code level 2 + 5 Silence alarm Silences buzzer, resets the panel indicators, resets detectors and resets control relays Access code level 2 + 1 + 5 Reset after fire alarm activation Silences buzzer, resets the panel indicators, resets detectors and resets control relays Access code level 2 + 2 Reset without a fire activation (e.g. to reset a fault indication when zone fault latch facility) Silences buzzer, resets the panel indicators, resets fault relay Access code level 2 + 1 + 2 9

Evacuate Operates the control panel s sounder circuits and fire relay(s) Operates the control panel s sounder circuits and fire relay(s) Access code level 2 + 3 Access code level 2 + 1 Enable Sounders Enable Sounders 2 + 4 Internal buzzer will rapidly pulse. Push button until sounder LED turns off. several times Push button 1 to confirm enable sounders Disable Sounders Isolates sounder circuits from the system Access code level 2 + 4 The internal buzzer will pulse at a slow rate and the disabled and sounders disabled LED s will remain lit. To silence the internal buzzer Access code level 2 + 5 The yellow LED of the zone 1 will light and the internal buzzer will pulse rapidly, push button several times until both the disabled and sounders disabled yellow LED s are lit. Push button 1 to disable sounders. Disable a zone Isolates required detection zone from the system Access code level 2 + 4 The internal buzzer will pulse at a slow rate and the disabled and zone disabled LED s will remain lit. To silence the internal buzzer Access code level 2 + 5 The yellow LED of the zone 1 will light up and the internal buzzer will pulse rapidly, push button several times until both the required zone and disabled yellow LED s are lit. Push button 1 to disable the indicated zone. Repeat this procedure to disable further zones. 10

Enable Zone Operates the control panel s sounder circuits and fire relay(s) Access code level 2 + 4 The yellow LED of the zone 1 is flashing. Push button 4 several times until the yellow led of the relevant zone is flashing. Push button 1 to enable the indicated zone. Repeat this procedure to enable further disabled zones. Maintenance General It is vital that the fire alarm system is checked for correct operation as per the requirements of BS5839 or applicable local standard. Daily inspection (by user) The panel should be visually inspected daily to ensure that the green power on indicator is lit and that no fault indication is showing. Notify any fault indication to your maintenance company. Weekly Test (by user) Visually inspect panel as per daily inspection. Test panel indicators: Access code level 2 + 6 All indicators will light up and the panel internal buzzer will sound. The test in progress LED will light up, the panel is now in a one- shot auto reset mode. The call point can now be activated using the test key, the sounders will operate for a short period (3 seconds) after which the panel will automatically reset and return to normal operation. If a call point or detector is not operated within a short period, the panel reverts to normal operation and the test is abandoned. It is advised that a different call point is tested each week to ensure that all call points are tested in rotation. Log test results in log book. 11

Inspection and servicing (by service provider) Quarterly Test Check log book entries since last visit and verify that remedial action has been taken (if required). Visually inspect panel as per daily inspection. Carry out weekly test. Visually inspect battery and battery connections. Carry out battery load test by disconnecting the mains supply and check that the battery is capable of supplying the alarm sounder load by activating a call point. Log test results in log book. Bi-yearly Test As per quarterly test. Visual inspection of site to check for compliance of system to recommendations of local standard. All controls and indicators of control panel need to be checked for correct operation. All external circuits should be tested for correct fault monitoring. Log test results in log book. Annual Test As per by-yearly test Also all call points on the system should be tested and the automatic fire detectors should be visually inspected to ensure they have not been damaged or painted over. The automatic detectors should then be test- operated. Log test results in log book. Every 5 years Replace sealed lead acid battery every 5 years (recommended). 12

Maintenance Engineers code facilities The engineering access code label can be found in the panel back box (internal). One man walk test facility Access code level 3 + 6 Individual zone test facility This enables the engineer to test a relevant zone while the other zones can still be activated upon a fire event. Access code level 3 + 3 It is advised that a different call point is tested each week to ensure that all call points are tested in rotation. Log test results in log book.repeat the process for all zones. Once finished use Access code level 3 + 3 The test in progress LED will light up, the yellow LED of zone 1 will light up and the internal buzzer will pulse rapidly: push button 3 several times until the required zone is selected. Push button 1 to confirm the indicated zone. The internal buzzer will pulse at a slow rate and the corresponding zone LED s will remain lit. Toggle to the zone in test- use button test. 1 to cancel the zone If another zone sees a fire event then the panel will override the individual zone test and go into full fire. The call point can now be activated using the test key, the sounders will operate for a short period (3 seconds) after which the panel will automatically return to test mode operation. If a call point or detector is not operated within a short period the panel reverts to normal operation and the test is abandoned. Latch on zone fault facility This does not meet the requirements of EN54-2 All zone faults will latch on the panel Access code level 3 + 4 Test in progress LED will light up. Panel will now latch until reset on all faults. The latch on fault facility can be terminated at any time by pressing the reset button. 13

Panel Programing Options Switch setting facility The dip switches installed on the PCB allow certain programming options to be selected by the installation engineer. Optional zone monitoring Non latching zones Sounder configuration (see diagram) Note These DIP switches are only read at power-up and not after a reset. Please note the white blocks represent the switch position Optional Sounder Configuration The sounder circuits can be programmed to have a continuous or pulsed tone. The alarm panel must be programmed, via switch 4 of the DIP switch SW19 for the sounder settings required. Non latching zones Each zone circuit can be configured to be latched or unlatched. This can be done by setting the switches on DIP switches SW20 (Zones 1-4) and SW21 (Zones 5-8) as illustrated below. Zones 1-4 Zones 5-8 14

Panel Fire/Fault Indicators Indication Fire General Fault Disable Power On Charger Fault System Fault Disable/Fault Zone Disable/Fault Sounder circuit Test Buzzer Normal Condition Zone Wiring Open/Short Zone Disabled Sounder circuit Disabled Sounder and Zone circuit Disabled Power Supply Fault Situation Sounder Circuit Open/Short Panel in Test System Fault Panel Button Pressed Battery Open Circuit/Reversed Polarity Battery High/Low Voltage Fire Evacuation LED Flashing LED Illuminated Internal Buzzer Intermittent Internal Buzzer Steady 15

Technical Specification Power Supply Mains Voltage 230VA +10% -15% Batteries Number of Batteries 2 Nominal Current 70mA Part Number (Manufacturer) Yucell Y4-12 (Yuasa) Maximum Current 200mA Capacity 4Ah Input Fuse 1.6A AT Anti Surge Battery Fuse 6.3A AT Anti Surge Ripple Voltages 24V 500mV Max Battery Charge Current 500mA 24V Raw - 600mV Stand By Current 220mA 5V O/P 100mV Float Voltage 27.1V Output Voltages 24V 24V +/-5% 24V Raw - 24V +/-5% 5V O/P 5V +/-5% Maximum Load Imaxb 24V 650mV 24V Raw - 2000mA 5V O/P 300mA Standby Current Imaxa 24V 100mA 24V Raw - 80mA Battery Switching Off Threshold (Reinstatement Voltage) Battery Internal Resistance 19.98V (22.4V)+/- 200mV 1 Ohms Imin 24V 25mA 24V Raw - 25mA 5V 20mA Inputs Panel Type 16 Zone Detection Zones 16 Detectors per Zone 30 Outputs Alarm Lines 4 Sounder Circuit Maximum Alarm Line Load Sounder Circuit Minimum Alarm Line Load Fire/Fault Relay 24V External power supply output 400mA per Alarm Line 15mA per Alarm Line Yes 500mA Maximum Current Yes 300mA Maximum Current Zonal Inputs Load Quiescent 3.5mA Fire Indication Load 35mA 16