ADDENDUM NO. 3 March 19, 2018

Similar documents
DIVISION 21: FIRE SUPPRESSION WATER BASED FIRE SUPRESSION SYSTEMS

SECTION DRY-PIPE FIRE-SUPPRESSION SPRINKLERS

SECTION WET-PIPE FIRE-SUPPRESSION SPRINKLERS

DIVISION 21 FIRE SUPPRESSION SECTION FIRE PROTECTION SPECIALTIES

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION FIRE PROTECTION. A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section

Mercury Plastics New Building February TABLE OF CONTENTS

SECTION FIRE PROTECTION

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University.

SECTION WET-PIPE SPRINKLER SYSTEMS

THE JAMES RUSHTON EARLY LEARNING AND FAMILY SUCCESS CENTER #2616 ISSUE FOR CONSTRUCTION

FIRE SUPPRESSION SPRINKLER SYSTEM

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements.

Division 21: FIRE SUPRESSION WET-PIPE SPRINKLER PROTECTION SYSTEM. The Academy Sept Table of Contents 1 Division 21

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

DARTMOUTH COLLEGE DESIGN November 15, 2007 & CONSTRUCTION GUIDELINES

SECTION DRY-PIPE SPRINKLER SYSTEMS

West District Library Section Campeau Drive, Ottawa SPRINKLER SYSTEMS City of Ottawa Project No. CR Page 1 of 8

Gas Station & C Store SECTION CWM Job No

SECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM

SECTION WET-PIPE SPRINKLER SYSTEMS

DIVISION 21: FIRE SUPPRESSION

B. Related Sections: The following Sections contain requirements that relate to this Section.

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

New Rigby Elementary School February TABLE OF CONTENTS

TABLE OF CONTENTS

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

DIVISION 21: FIRE SUPPRESSION

A. This section includes design and performance information for fire protection and suppression systems.

MLA Architects Pierz Public Schools ISD #484 Healy High School Multi-Purpose & Choir Additions Pioneer Elementary School Class Room Addition Pierz, MN

SECTION SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE

May 2017 Middleton Heritage 09T SC DIVISION 21: FIRE SUPPRESSION END OF TABLE OF CONTENTS

Kenworth Sales Co. - North Las Vegas, Nevada November TABLE OF CONTENTS

North Hanover Township School District North Hanover Township, New Jersey

A. Section includes wet-pipe sprinkler system, system design, installation, and certification.

SECTION DRY-PIPE SPRINKLER SYSTEMS

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE

SECTION FIRE-SUPPRESSION STANDPIPES

A. Standard-Pressure Piping System Component: Listed for 175-psig minimum working pressure.

WET-PIPE SPRINKLER SYSTEMS

1.2 CODES AND REGULATIONS A. Sprinkler system design, equipment, materials, devices, and installation shall conform to the following:

A. All Fire Suppression System design and installation shall comply with the most current and adopted version of NFPA 13.

A. This Section includes the following fire-suppression piping inside the building:

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE

Port of St Helens SIA Aircraft Hanger Scappoose, OR

Environmental Health & Safety

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

DIVISION 21 - FIRE SUPPRESSION

SECTION PREACTION SPRINKLER SYSTEMS

2. Welding Materials and Procedures shall conform to the ASME Code.

B. Standard-Pressure Standpipe Piping: Fire-suppression standpipe piping designed to operate at working pressure 175 psig (1200 kpa) maximum.

Addendum No. 2 to the Contract Documents

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 21 FIRE SUPPRESSION

DIVISION 21 - FIRE SUPPRESSION

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

SPRINKLERS TABLE OF CONTENTS

SECTION AUTOMATIC SPRINKLER PIPING

UC Santa Cruz Campus Design Guide. Includes the following sections: None DESIGN REQUIREMENTS

SECTION SPRINKLER SYSTEMS

2016 CDM Smith All Rights Reserved July 2016 SECTION FIRE PROTECTION - SPRINKLER AND STANDPIPE SYSTEMS

Essex County College - West Essex Campus Addition And Renovations dlb # / 11-14

ACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO

UBC Technical Guidelines Section Edition Fire Protection General Requirements Page 1 of 6

SECTION GENERAL-SERVICE COMPRESSED-AIR SYSTEMS

B. The sprinkler system shall be designed to meet the more stringent of the requirements of NFPA 13 and FM Global requirements.

ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1. The Curators of the University of Missouri

DIVISION 21: FIRE SUPPRESSION

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM

SECTION FIRE-SUPPRESSION PIPING

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION FIRE-SUPPRESSION SYSTEMS

DIVISION 21 FIRE PROTECTION ISSUE DATE REVISION

B. Section Identification for Fire Suppression Piping and Equipment.

SECTION ADDENDUM NO. 1 FIRE SPRINKLER SYSTEM

SECTION WET-PIPE SPRINKLER SYSTEMS

Lucy s Pizza 100% CD Specification 06/22/2018

PART 1 - GENERAL SECTION FIRE PROTECTION BASIC MATERIALS AND METHODS

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 21 FIRE SUPPRESSION

TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION WATER BASED FIRE PROTECTION SYSTEMS... 5

B. Galvanized-Steel-Sheet Sleeves: inch minimum thickness; round tube closed with welded longitudinal joint.

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1

Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040

SECTION WET AUTOMATIC FIRE SPRINKLER SYSTEMS

SECTION FIRE SUPRESSION

UNIFIED FACILITIES GUIDE SPECIFICATIONS

SECTION (13900) - FIRE SUPPRESSION SYSTEMS

Design and Construction Standards SECTION FIRE SUPPRESSION

SECTION DRY-PIPE SPRINKLER SYSTEMS

SECTION WET FIRE SPRINKLER SYSTEMS

UMC El Paso Far East Clinic and Neighborhood Healthcare Center West Issue for Construction Page Project No and April 13, 2015

SECTION ELECTRIC-DRIVEN, FIRE PUMPS

SECTION COMPRESSED AIR SYSTEM. A. Pipe and pipe fittings, including valves, unions and couplings.

SECTION WATER BASED FIRE SUPPRESSION SYSTEMS

DIVISION 21: FIRE SUPPRESSION SYSTEMS SECTION Fire Protection Systems Protecting Cold Storage and Unheated Warehouses

SECTION : FIRE PROTECTION SYSTEMS

Model F3-80 Dry K8.0 (115 metric) Standard-Response, Standard Spray Sprinklers

Transcription:

ADDENDUM NO. 3 March 19, 2018 PROJECT: MT. VIEW ELEMENTARY CASSIA SCHOOL DISTRICT NO 151 BURLEY, IDAHO The following addenda apply to the Project Manual and / or Drawings for this project and shall be a part of the Contract Documents. Receipt of this Addendum shall be acknowledged on the Bid Form. GENERAL This building has a cold attic. The Fire Sprinkler Contractor for this Project shall engineer and provide a complete code compliant system for the building. This may be a combination of Dry- Pipe and Wet-Pipe Automatic Sprinkler Systems. PROJECT MANUAL Specification Section 211321 Dry-Pipe Automatic Sprinkler System Add Specification Section 212321 Dry-Pipe Automatic Sprinkler System, attached to this Addendum, shall be part of the Contract Documents for this Project. DRAWINGS Sheet A3.2 through A3.5 At all exterior wall locations revise wall type W2 to be wall type W7. Wall type W7 shall be existing exterior wall assembly of face brick, 15# asphalt felt, ½ plywood sheathing, 2x wood studs at 16 o.c. and batt insulation. Contractor shall not remove insulation. Contractor shall install new vapor retarder per Specifications and new 5/8 gypsum board at interior side of existing 2x framing. AMBER VAN OCKER BROOK THORNTON - WAYNE THOWLESS 2400 E. Riverwalk, BOISE, IDAHO 83706 PHONE 208-336-3443 FAX 208-336-3680

END OF ADDENDUM NO. 3 ATTACHMENTS Specification Section 211321 AMBER VAN OCKER BROOK THORNTON - WAYNE THOWLESS 2400 E. Riverwalk, BOISE, IDAHO 83706 PHONE 208-336-3443 FAX 208-336-3680

SECTION DRY-PIPE AUTOMATIC SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings, General Provisions of Contract, including General and Supplementary Conditions apply to this Section. 1.2 SUMMARY A. Furnish and install complete fire sprinkler system as specified in Contract Documents. B. Products Installed But Not Furnished Under This Section: 1. Firestopping 1.3 SUBMITTALS A. Shop Drawings: 1. Size sprinkler system by one of following methods: a. Pipe schedule method in accordance with NFPA 13 b. Hydraulic calculation design method based on water supply evaluation performed at building site. 2. Submittal Procedure: a. After award of Contract and prior to purchase of equipment, submit seven sets of shop drawings with specifications and hydraulic calculations, if pipe schedule method is not used, to Architect and two sets to local jurisdiction having authority for fire prevention for review. b. After integrating Architect's and local jurisdiction's comments into drawings, licensed certified fire protection engineer of record submitting fire sprinkler system design construction documents shall stamp, sign, and date each sheet of shop drawings and first page of specifications and calculations. c. Submit stamped documents to area office and local jurisdiction having authority for fire prevention for final approval. d. After final approval, submit four copies of approved stamped documents to Architect. e. Failure of system to meet requirements of authority having jurisdiction shall be corrected at no additional cost to Owner. 1.4 QUALITY CONTROL A. Qualifications: 1. Installer shall be licensed by jurisdiction over installed fire protection systems for area of Project. Furnish verified list of similar projects installed during past five years minimum. 2. Engineer for fire protection system shall be licensed fire protection engineer certified by NICET to level three minimum and engaged in design of fire protection systems. Engineer shall be responsible for overseeing preparation of shop drawings, hydraulic calculations where applicable, and system installation. Engineer shall make complete inspection of installation. Engineer shall provide corrected record drawings to Owner with letter of acceptance. Engineer shall certify that installation is in accordance with Contract Documents. B. Requirements of Regulatory Agencies: 1. Unless noted otherwise, system shall conform to: a. NFPA 13-1989 Light & Ordinary Hazard Occupancies b. NFPA 24-1987 c. NFPA 101-1991 d. Requirements of local water department and local authority having jurisdiction for fire protection. e. Applicable rules, regulations, laws, and ordinances.

1.5 MAINTENANCE f. Underwriter's Laboratories Publication, "Fire Protection Equipment Directory", January 1990. g. Comply with backflow prevention requirements and, if required, include device in hydraulic calculations. h. Life Safety Code. A. Extra Materials: 1. Furnish twelve spare heads of each type and temperature rating used, properly boxed with sprinkler head wrench. PART 2 - PRODUCTS 2.1 PIPE A. Above Ground: 1. Schedule 40 black welded steel meeting requirements of ASTM A 795-89, "Specification for Black and Hot-Dipped Zinc-Coated (Galvanized) Welded and Seamless Steel Pipe for Fire Protection Use." 2.2 FITTINGS A. Flanged, Welded, & Screwed: 1. Carbon Steel meeting requirements of ASTM A 105-87a, "Specification for Forgings, Carbon Steel, for Piping Components." B. Grooved Pipe Coupling System: 1. Victaulic Coupling. 2. ITT Grinnell Coupling. 2.3 VALVES A. Butterfly Valve: 1. UL/FM approved 2. Indicating type 3. Approved Manufacturers: a. Mueller: 1) Model B-3250-00 Wafer type with valve tamper switch 2) Model B-3250-52 Grooved ends type with valve tamper switch b. Nibco: 1) Model WD3510-4 Wafer type with valve tamper switch 2) Model GD1765-4 Grooved type with valve tamper switch c. Norris Model NW285AC-2K Wafer type with optional tamper switch d. Pratt Model IBV B. Gate Valve: 1. UL/FM approved 2. Outside Screw and Yoke Type (O.S.&Y) 3. Class 150 psi 4. Approved Manufacturers: a. Nibco Model F-637-31 Flanged Ends b. Mueller Model A-2073-6 Flanged Ends C. Ball Valves: 1. UL/FM approved 2. Valve tamper switch 3. Approved Manufacturers: a. Milwaukee Model BBSC with threaded ends b. Nibco Model T-505 with threaded ends

c. Nibco Model G-505 with grooved ends D. Check Valve - Swing Check 1. ½" to 3" horizontal check 2. Regrinding type 3. Renewable disk 4. Bronze Class 125 with threaded ends 5. Approved Manufacturers: a. Nibco Model KT-403-W b. Walworth Figure 412 E. Check Valve - Swing Check 1. 2-1/2" to 12" Horizontal check 2. Bolted bonnet 3. Raised face Flanges 4. Bronze mounted w/ductile iron body 5. 125 Lb. Class.a 6. Approved Manufacturers: a. Nibco Model F-938-31 b. Walworth Fig. 883F c. Mueller Model A-2120-6 F. Check Valve - Wafer type 1. 4" to 8" Cast iron body 2. 175 psi minimum working pressure 3. Rubber Seat 4. Approved Manufacturers: a. Nibco Model W-900-W b. Mueller A-2102 G. Dry Pipe Alarm Valve: 1. Approved Manufactures: a. Reliable Model D with gauges, drain and trim. b. Viking Model E with gauges, drain and trim. c. Star Model A with gauges, drain and trim. H. Air Maintenance Device 1. Maximum inlet air pressure 125 psi. 2. Minimum outlet air pressure 65 psi. 3. Approved Manufacturers: a. Reliable Model B-1 b. Viking Model D-2 c. Star Model B I. Accelerator: 1. Install with pressure gauge 2. Approved Manufacturers: a. Reliable Model B-1 b. Viking Model D-1 c. Star Model A J. Inspector's Test Valve: 1. Ductile iron body with threaded ends 2. Combination sight glass/orifice 3. Bronze top works 4. Approved Manufacturer: a. Victaulic Testmaster Alarm Test Module Style 718

2.4 SPRINKLER HEADS A. Upright Sprinkler: 2. Approved Manufacturers: a. Reliable Model G b. Viking Model M c. Central Model A d. Star Model E B. Dry-Pendant: 2. Approved Manufacturer: a. Reliable Model G3 Dry Pendant Concealed b. Central Model A-1 Royal Flush Dry Pendant Concealed 2.5 WATER FLOW ALARM A. Mechanical Flow Alarm: 2. Approved Manufacturers: a. Reliable Model C b. Viking Model F-1 c. Central Model F d. Star Model CD 2.6 PRESSURE GAUGES A. Mechanical Water Pressure Gauges: 2. 3-1/2 inch diameter dial. 3. 0 to 300 psi in 5 psi increments. 4. Approved Manufacturers: a. Reliable Model UA b. Trerice model 500 2.7 PRESSURE DETECTORS A. Electrical Water Pressure Switch: 2. Switch activates on pressure rise between 4 and 8 psi. 3. Two single pole double throw switches. 4. Automatic reset. 5. Approved Manufacturers: a. Reliable Model J54-8295 b. Potter Electric Signal Co Model PS10 2.8 LOW PRESSURE SUPERVISORY SWITCH A. UL/FM approved. B. Adjustable pressure range 1- to 100 psi. C. Automatic reset. D. Factory adjusted to separate on pressure decrease of 30 psi. E. Approved Manufacturers: 1. Reliable Model J54-8300 2. Potter Electric Signal Co Model PS40-1

2.9 TAMPER SWITCH A. Weather and tamper resistant switch. 2. Two single pole double throw switches. 3. Approved Manufacturer: a. Potter Electric Signal Co Model PCVS 2.10 FIRE DEPARTMENT CONNECTION A. Two-way Inlet with Single Clapper. 1. Polished Brass. 2. 3/4 Inch Straight Design Automatic Drain Device by Potter-Roemer Fig. 5982. 3. Round "AUTO. SPKR." Identification Plate, Polished Brass by Potter-Roemer Fig. 5962. 4. Approved Manufacturer: a. Potter-Roemer Fig 5710 b. Reliable Model B 2.11 AIR COMPRESSOR A. Air compressor: 1. Tank-mounted, 17 gallon tank rated at 165 psi working pressure. Restrict speed of compressor to between 700 and 900 RPM. 2. Set tank-mounted air compressor on neoprene isolation pads located at each corner and sized 4" x 4" x 3/4" high. 3. Wire air compressor to circuit breaker. 4. Furnish with air intake filter and silencer. 5. Overload protected 1750 RPM motor. 6. Industrial grade with totally enclosed steel belt guard. 7. Auto control group mounted and pre-wired. Auto group includes pressure switch, check valve, manifold, safety valve, and mounting. 8. Approved Manufacturers: a. Emglo Model K1s-30S b. Equal as approved by Architect prior to bidding. See Section 01 630. PART 3 - EXECUTION 3.1 INSTALLATION A. Connect system to flange provided under Section 02 669. B. Install system to drain. Drain trapped piping in accordance with NFPA 13 3-3.3. 1. Install main drain from riser. 2. Install auxiliary drains in low points of piping system and inspector's test valve drain to mechanical pad located outside building, unless directed otherwise by Architect. C. Install piping system so it will not fail due to freezing temperatures. D. Do not use dropped, damaged, or used sprinkler heads. E. Pendants: 1. Do not use regular pendants. 2. Install dry pendants with tees and not elbows. Do not adjust length with pipe nipples and couplings. 3. Individually measure and order each dry pendant based on measured distance from ceiling to face of branch line tee. 4. Dry-Pendant Concealed Sprinkler: a. Use flat cover plate to conceal sprinkler head. Cover not to exceed 3/16 inch from ceiling.

F. Minimum slope of a branch line is ½ inch per 10 feet. G. Minimum slope of a main line is 1/4 inch per 10 feet. H. Install sprinkler lines concealed. I. Install tamper switches and pressure flow detectors where located by Architect. J. Install water powered motor gong on exterior wall in accordance with Manufacturer's instructions. K. Install automatic ball drip device in lowest point of piping to the fire department connection and drain to exterior of building. L. Install fire stopping at pipe penetrations through fire-rated floors, walls, and partitions. M. Brace and support system to meet seismic zone requirements for building site. 3.2 FIELD QUALITY CONTROL A. Test, Inspection: 1. Test system according to "Contractor's Material & Testing Certificate for Above Ground Piping" NFPA-13, figure 1-10.1(a). 2. Tests shall be witnessed by Architect and by representative of local jurisdiction having authority for fire prevention. 3. Test blanks shall have red painted lugs protruding beyond flange to clearly indicate their presence and be numbered to assure their removal when testing is completed. END OF SECTION