N2 BLAST Datasheet Preaction double interlock, Electric/Pneumatic c/w N 2 Blast Nitrogen generating system Self contained unit

Similar documents
N2 BLAST Datasheet SUREFIRE double interlock c/w N 2 Blast Nitrogen generating system Self contained unit

N2 BLAST Datasheet Preaction double interlock, Electric/Pneulectric c/w N 2 Blast Nitrogen generating system Self contained unit

Datasheet. Dry-pipe Vacuum Sprinkler System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description

Datasheet. Vacuum Double-interlock Preaction System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description

TotalPac 3 Double interlock Preaction, Electric/PneuLectric release Self-contained system

TotalPac 3 Single interlock Firecyle III Preaction Self-contained system

TotalPac 3 Firecyle III Deluge Remote controlled system

TotalPac 3 Wet pipe system c/w retard chamber

TotalPac X Single interlock SUREFIRE system

TotalPac 3 Deluge, Electric release Self-contained system

TotalPac X Firecycle III Preaction Double interlock system

FireFlex DUAL Double Interlock, Self-contained system

TotalPac 3 Single interlock Preaction, Electric release Self-contained system

TotalPac 3 Non interlock Preaction, Electric release Self-Contained system

TOTALPAC2 Integrated Fire Protection System

Advanced Integrated Fire Protection Systems TOTALPAC 2. Owner's Operation and Maintenance Manual FIRECYCLE III. September 2009 FM-086G-0-5E

FireFlex 1230 Self-contained system

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEUMATIC RELEASE 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC RELEASE

Not to be distributed outside of FM Approvals and its affiliates except by Customer APPROVAL REPORT

TECHNICAL DATA. 319a. January 27, 2012

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEU-LECTRIC RELEASE

Technical Data. Approvals The 1-1/2 in. to 8 in. (DN40 to DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types:

Technical Data. Approvals The 1-1/2 thru 8 inch (DN40 thru DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types:

TECHNICAL DATA OBSOLETE

Worldwide Contacts.

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014

DV-5 Red-E Cabinet Integrated Deluge Fire Protection Package. General Description. Technical Data. Page 1 of 6 AUGUST 2018 TFP1300. Worldwide Contacts

Technical Data. Working Pressure Range 20 to 250 psi (1,4 to 17,2 bar)

TECHNICAL DATA 1. SYSTEM DESCRIPTION 2. SYSTEM OPERATION 3. INSTALLATION. Page 1 of 5

Pre-Pack INTEGRATED PRE-ACTION SYSTEM

Specification/ Data Sheet

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Preaction Fire Protection Package General Description

Deluge & Preac tion Systems

DOUBLE INTERLOCK, PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC RELEASE

Instructions for. Care and Maintenance 10 psi (0,7 bar) Pneumatic Supervising Pressure. Single Interlock

TECHNICAL DATA. Factory Mutual Approval is pending for the system as a whole.

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE

Instructions for Installation, Operation, Care and Maintenance

30.45 Electric Release PDRP-2001

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Deluge Fire Protection Package General Description

Deluge System. Pneumatic Release. Deluge System. Pneumatic Release

SINGLE INTERLOCK, SUPERVISED PREACTION SYSTEM WITH ELECTRIC RELEASE

SINGLE INTERLOCK, SUPERVISED PREACTION SYSTEM WITH WET PILOT ACTUATION

Operation & Maintenance Manual

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

TECHNICAL DATA DELUGE SYSTEM CONTROLLED BY ELECTRIC RELEASE

1935, Lionel-Bertrand Blvd. Boisbriand, Quebec, Canada J7H 1N8 Tel.: (450) Fax: (450) Toll Free: (866)

DIVISION 21 FIRE SUPPRESSION SECTION FIRE PROTECTION SPECIALTIES

TECHNICAL DATA OBSOLETE

ECS Protector Nitrogen Generator PGEN-40FK/PGEN-50FK/PGEN-60FK PGEN-40M/PGEN-50M/PGEN-60M

Becoming an Expert on Dry-pipe, Preaction, and Deluge Sprinkler Systems

Model DDX Deluge Valve

OPEN SPRINKLER SYSTEM

BERMAD Fire Protection

ECS Pre-Engineered Nitrogen Generator. ECS Pre-Engineered Wall Mount Nitrogen Generator PGEN-10/(PGEN-10E)

VIZOR Electronic Dry Pipe Accelerator (EDPA) Quick-Opening Device for Dry Pipe Systems General Description

SECTION PREACTION SPRINKLER SYSTEMS

ECS Protector Nitrogen Generator. ECS Protector Nitrogen Generator PGEN-30. Specifications

Commercial and Light Industrial Fire Alarm Control Panel

Discontinued Product

VSR-M REPLACEMENT Waterflow Switch for Globe Sprinkler Model UMC Manifold

ECS Pre-Engineered Nitrogen Generator. ECS Pre-Engineered Wall Mount Nitrogen Generator PGEN-3/(PGEN-3E) PGEN-5/(PGEN-5E)

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

CONSTRUCTION REQUIREMENTS

B. The sprinkler system shall be designed to meet the more stringent of the requirements of NFPA 13 and FM Global requirements.

FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

TECHNICAL DATA OBSOLETE

AutoTest VSR (VSR-AT) (EU) Vane Type Waterflow Alarm Switch With Electronic Retard and Auto Test Feature

DELUGE VALVE MODEL: SD-DVH2 TECHNICAL DATA TRIM DESCRIPTION DESCRIPTION VALVE OPERATION. 82 ASTM A 216 WBC.

I-745. Series 745 FireLock Fire-Pac for FireLock NXT Valves WARNING INSTALLATION, MAINTENANCE, TESTING, AND WIRING MANUAL WARNING

Technical Data. Minimum Inlet Supply Pressure All MCC Models...0 psi. Minimum Inlet Supply Capacity Match system design calculations

Technical Data. Minimum Inlet Supply Pressure All MCC Models...0 psi. Minimum Inlet Supply Capacity Match system design calculations

Electric Release Panel Wiring Tips

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL

INTELLIGENT FIRE ALARM CONTROL PANEL

Installation Guide for models:

SECTION SPRINKLER SYSTEMS

1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1 ANSI/NFPA 20, Centrifugal Fire Pumps.

FUEL OIL DAY TANKS. SST Level Controller: UL 508 LISTED

TECHNICAL DATA. model c-2

Addressable Fire Alarm Control Panel

Release Control Fire Alarm Systems

MR-2602 Two Zone Fire Alarm Control Panel

ENGINEERING SPECIFICATIONS FOR FM-200 CLEAN AGENT INDIRECT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS

Series 759 FireLock Alarm Check Valve

Integrated Fire Protection System. Owner's Operation and Maintenance Manual

Installation Guide for models:

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE

PHYSICAL FACILITIES. 1 General. 2 Related Requirements. 5 Quality Assurance. 3 Wiring. 4 Submittals

good things in small packages

Power Flame Incorporated

AQUAMIST Mist Control Center (MCC) Pump Skid Unit. General Description. Technical Data. Page 1 of 8 JANUARY 2016 TFP2270. Worldwide Contacts

Smoke Detector Activation of any smoke detector shall start the alarm verification mode.

LifeAlarm Fire Alarm Control Panels

AEGIS FEATURES DESCRIPTION. Conventional Fire Alarm-Suppression Control Unit. Effective: March Programmable Relays

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description.

POWERPATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262)

Transcription:

FireFlex N 2 Blast description The FIREFLEX N2 Blast integrated system consists of an integrated double interlock Electric/Pneumatic release preaction automatic sprinkler system combined with a Nitrogen generating system, factory-assembled in a single cabinet. All the necessary components are integrated. The FIREFLEX N2 Blast is fully tested at factory. The FIREFLEX N2 Blast System uses the N2 Blast Nitrogen generator system Type 1 FPS-250 or FPS-750 system, made by South-Tek Systems. All the deluge valves are rated up to a maximum of 250 psi WWP (1724 kpa) max. and are available in the following diameters: 1½" (40 mm) 3" (80 mm) 6" (150 mm) 2" (50 mm) 4" (100 mm) Warning: 6" (150 mm) available with N2 Blast Type 1 FPS-750 only. Features Inhibits corrosion with 98%+ pure Nitrogen Trouble-free design for safe and easy application Available in 2 cabinet sizes Uses South-Tek N2 Blast Best value in nitrogen generation technology Limits the liability of early pipe replacement Uses the Viking deluge valve Trim is fully assembled and tested at the factory All trims are galvanized steel, Listed and Approved for 250 psi (17.2 bar) service maximum Quick connections to water supply and drain on left side, and sprinkler riser on top of unit, all available with grooved end or flanged fittings No open drain cup inside unit Separate unlocked access hatch to emergency manual release Compact, aesthetic and easy to move User-friendly standardized owner's manual with every unit Unique serial number on every unit Uses UL, ULC and/or FM Approved components Designed in accordance with NFPA Standards Sturdy 14 gauge steel cabinet painted fire red with oven baked polyester powder on phosphate base Textured rust proof finish Neoprene gasket on all doors to eliminate vibrations Manufactured under ISO-9001 quality control procedures Prewired to the Viking VFR-400 releasing control panel. 1 of 14 FM-076D-0-119D

System configurations Double Interlock Preaction combined with N2 Blast Type 1 FPS-250 (250 gallons system) Double Interlock Preaction combined with N2 Blast Type 1 FPS-750 (750 gallons system) Systems hydraulic limitations The information contained herewith is for estimation and evaluation purposes only. Its use remains the responsibility of the designer. Designers should refer to the appropriate NFPA Standards and any other applicable codes for their final design. Also refer to FireFlex Systems Inc. appropriate user manuals and to manufacturer's data sheets for additional details. Systems limitations indicated below are nominal flow limitations. Piping Equivalent Lengths w/o System size Usage Range shut off valve (in.) (gpm) Piping Equivalent Lengths c/w shut off valve (m.) (ft.) (m.) (ft.) GPM 1½ 0 210 8.3 27.2 8.5 27.9 272 2 0 360 11.65 38.2 11.85 38.9 272 3 100-700 16.8 55.1 20.33 66.7 762 4 200 1400 21.89 71.8 25.33 83.1 1597 6 400-3500 33.28 109.15 37.28 122.3 1597 Sequence of operation Drain flow @ 250 PSIG w.p. Preaction operation 1. The activation of the detection condition AND the opening of an automatic sprinkler are necessary to cause the deluge valve actuation. 2. Detection condition: Single zone (the operation of one detector in the protected area is required to fulfill the detection condition). Crossed zone (the operation of two detectors in the protected area is required to fulfill the detection condition). 3. The activation of the detection condition alone will activate the solenoid valve (F1) open, but the deluge valve will not open. 4. Activation of the detection condition AND the opening of an automatic sprinkler will activate the solenoid valve (F1) ant the pneumatic actuator (F3) open causing the deluge valve to open and water will flow out of any open sprinklers. The alarm pressure switch (C1) will activate 5. The opening of an automatic sprinkler OR damage to system piping without the detection condition satisfied will activate the low air supervisory (E4) switch contact but will not allow the water to enter the system piping. 6. Operation of the emergency manual release will depressurize the priming chamber, causing the deluge valve to open and allowing water to enter the system piping and water will discharge through any open sprinklers.the alarm pressure switch (C1) will activate. N2 Blast Nitrogen generator system operation 1. The initial air supply fill of the piping system within 30 minutes as per NFPA 13 is accomplished using the initial fill air compressor. This compressor is equipped with a factory-adjusted ON/OFF pressure switch which is tied into the sprinkler system piping. It is factory-set at 20 and 35 psi for the cut-in and cut-out pressures respectively. There is a "low air" supervisory pressure switch which monitors system piping air/nitrogen pressure at all times. It is factory-set at 25 psi to provide a "low air" supervisory signal. 2. The nitrogen generation/maintenance air compressor is supplied as an integral part of the STS N2-Blast Nitrogen Generation System. It is equipped with a factory-adjusted ON/OFF pressure switch which is tied into the nitrogen storage tank. It is factory-set at 65 psi and 75 psi for the cut-in and cut-out pressures respectively. The Viking D-2 Air Pressure Maintenance Device is installed and factory-adjusted to 35 psi (normal system air/nitrogen pressure) downstream of the nitrogen storage tank. As the system continually purges with Nitrogen, the APMD will continually draw from the Nitrogen storage tank to maintain supervisory pressure (35 psi). Should the N2- Blast generator run for more than 6 hours consecutively, the Leak Detection System (LDS) will automatically shut it down and activate a trouble contact. 3. The air and nitrogen supply systems are fully integrated and fully automatic in the FireFlex - N2- Blast. No shut-off or bypass valve is required. The nitrogen generator is equipped with a BlastOff Leak Detection System (LDS). Should the nitrogen generator compressor fail or a leak occur that can not be compensated by the nitrogen generating system, the preaction system air compressor will act as a back-up and start-up at 20 psi system pressure. FM-076D-0-119D 2 of 14

Standard equipment Releasing control panel 120 VAC / 60 Hz, 165VA. 220 VAC / 50 Hz, 185VA. 12VDC / 7Ah batteries. (factory installed) 12VDC / 12Ah batteries. (optional) Single Zone detection (Activated by Zone 1 or Zone 2) Crossed-Zone detection (Activated by Zone 1 and Zone 2) The releasing control panel integrated into the TOTALPAC 3 cabinet is Viking's Model VFR-400. This panel includes four Class B, programmable detection zones (optional Class A); two Class B supervisory zones and four Class B, programmable output circuits (optional Class A). It is also provided with menu driven programming, including a specific program assigned at the factory. The panel is compatible with many types of fire alarm & supervisory devices such as linear heat detectors, spottype heat and smoke detectors, water flow and release indicators, low and high air pressure switches, manual pull stations. The releasing control panel also includes an alphanumeric display with 2 lines of 16 characters describing all the system conditions, as well as a set of red and yellow LED lamps individually indicating each of the alarm and trouble conditions of the system Easy to operate control buttons are also provided to activate and operate the system's various functions. Releasing circuit disconnect switch The releasing circuit disconnect switch is used to disable the releasing solenoid. When the key is set to Disable, the releasing solenoid will be disconnected from the control panel s releasing circuit, causing a trouble signal and preventing accidental discharge during maintenance or inspection. Deluge valve The Viking Model F-1 Deluge Valve is a quick-opening, differential diaphragm flood valve with one moving mechanism. The deluge valve is used to control water flow in preaction sprinkler systems. The valve is held closed by system water pressure trapped in the priming chamber, keeping the outlet chamber and system piping dry. In fire conditions, when the releasing system operates, pressure is released from the priming chamber. The deluge valve clapper opens to allow water to flow into the system Water supply control valve The water inlet control valve is a supervised, indicating butterfly valve. Purpose of this vale is to manually shutoff the preaction system. 3 of 14 FM-076D-0-119D

Preaction riser check valve The Viking 1-½ and 2 spring loaded In-Line check valve is a general purpose rubber-faced check valve approved for use in fire-service systems. The Spring Loaded In-Line check valve is manufactured with a brass body, brass seat, and a rubber-faced clapper assembly. The Viking 3, 4 and 6 Easy Riser Swing check valve is a general purpose rubber-faced check valve approved for use in fire service systems. The valve is for use in preaction system risers. Low air supervisory switch The low pressure switch monitors the pressure within the sprinkler piping should a loss of the air below 25 Psi occur. The pressure switch contacts transfer indicating supervisory signal. POTTER PS40-1A Alarm pressure switch The alarm pressure switch monitors the water flow within the sprinkler piping. Should the Deluge Valve clapper opens to allow water to flow into the sprinkler piping. The alarm pressure switch will activate, indicating a water flow signal Solenoid valve The high pressure solenoid valve is a two-way type with one inlet and one outlet. It is a packless, internal pilot operated valve, suitable for use in releasing water pressure from the priming chamber of Viking Deluge Valves. The solenoid valve has floating diaphragm construction, which requires a minimum pressure drop across the valve to operate properly. POTTER PS10-1A IN OUT Pneumatic actuator Used in conjunction with the solenoid valve, the Viking Pneumatic Actuator is a spring loaded, rolling diaphragm and piston operated valve. It is used wherever a combination is required between the detection and system s loss of air. FM-076D-0-119D 4 of 14

Standard equipments (continued) N2 Blast Nitrogen generator South-Tek Systems utilizes Membrane technology in the N2-Blast Corrosion Inhibiting Systems in order to efficiently separate Nitrogen molecules from the air we breathe. Membrane technology, used in our smaller applications, has a simple air flow design, is wall-mounted and easy to service. PSA technology is more cost effective and energy efficient in larger Fire Protection Systems, those requiring more Nitrogen to compensate for the NFPA acceptable leak rate. BlastOff Leak detection system Unless the leak rate is catastrophic, the supervisory low pressure alarm on the BlastOff will not activate. Minor leaks cause the air compressor and N2-Blast to run excessively in order to maintain supervisory pressure. The unnecessary additional run-time decreases the lifespan of the equipment. The Patent Pending BlastOff - Leak Detection System is designed to detect significant leaks before they compromise the FPS and the Nitrogen Generation System. It has an internal audible alarm and dry contact that s is wired on the Sprinkler Low Air Supervisory Zone. Nitrogen generator storage cylinder Type 1 Nitrogen Generation Systems include a 16 gallon Nitrogen receiver tank (12.2 dia x 44.8 H). Nitrogen generated by the N2-Blast is stored in the tank, and then sent to the sprinkler system through the Nitrogen air pressure maintenance device. N2 Blast AutoPurge System High purity Nitrogen must be equally distributed throughout the entire sprinkler piping system in order to effectively inhibit corrosion. The Patent Pending AutoPurge System provides a low volume, constant purge of Nitrogen within sprinkler piping. The rate in which gas is evacuated from the sprinkler piping is within NFPA guidelines and allows breathing to occur. The AutoPurge System also assists in drying out the residual water from a hydro test. Computational Fluid Dynamics modeling proves that this is the most effective way to ensure that high purity Nitrogen reaches all branches within the sprinkler piping. Install one AutoPurge System per system at a high point. There is a Label on one side of the housing that lists the proper setting for a variety of zone sizes. The Label list: Gallons in Zone, and APS Flow Setting. The Flow Setting is labeled from A-E and has three Settings in between each letter. Nitrogen generator air pressure maintenance device FIREFLEX N2 Blast use the Viking Model D-2 Air Pressure Maintenance Device (APMD) which is a pressure regulator that automatically reduces the supply air pressure to a preset requirement when connected to a constantly maintained air supply. The APMD is used to regulate the nitrogen pressure to 35Psi in the sprinkler piping at the specified system pressure for FIREFLEX N2 Blast Double interlock preaction system. 5 of 14 FM-076D-0-119D

Optional preaction equipment Shut-off valve & sight glass (optional) The Shut-off Valve & Sight Glass Option is intended to be used for applications where testing of the system operation without filling the sprinkler piping network is desirable and where it is critical that all functions of the preaction system be tested under actual discharge conditions. Main drain valve Sight glass assembly Shut-off valve Riser check valve Semi-flange inlet / outlet (optional) When required by the user, FIREFLEX N2 Blast units can be provided in a semi-flanged configuration. The semi flanged option provides flanged fittings only on the water inlet pipe (left side) and on the system riser outlet. The drain manifold is provided with a threaded connection (left side). The rest of the fittings are the same as usual with the main components being provided in the standard flanged / grooved configuration. Flange fitting outside cabinet Point flashlight HERE Deluge valve Riser check valve Main water supply control valve Deluge valve FM-076Z-0-4B-1 Anti-column device option The model LD-1 anti-column device is an optional trim component designed for use with preaction sprinkler systems. The anti-column device automatically prevents an unwanted water column from establishing within the system riser. On preaction sprinkler systems the anticolumn device prevents water from columning downstream of the easy riser check valve. Threaded drain output Flange fitting outside cabinet FM-076Z-0-4B-2 Main water supply control valve From Sprinkler Riser To Drain Collector FM-061H-0-146A FM-076D-0-119D 6 of 14

Preaction system - Air supply Direct air compressor (Style A ) Used only for the sprinkler piping network of the preaction system. Air supply style "A" includes the air compressor mounted inside the FIREFLEX N2 Blast cabinets with its supervisory trim and options. Compressors are of the tankless, oiless piston type and are factory piped to the sprinkler system riser, all within the FIREFLEX N2 Blast cabinets. Compressors are available in four (4) sizes: 1/6HP 1/2HP 1/3HP 1HP This section replaced by Dehydrator option (when used) E4 (plugged with SureFire trim) Copper tubing TO OPTIONAL ACCELERATOR (plugged when not used) Pressure relief valve Compressor Service Factor Amp (S.F.A) rating Compressor Size (HP) 115Vac / 60Hz 230Vac / 60Hz 1/6 5.0 Amp. 2.5 Amp. 1/3 7.4 Amp. 3.7 Amp. 1/2 10.0 Amp. 5.0 Amp. 1 18.0 Amp. 9.0 Amp. 115 / 220 Vac 60Hz Compressor selection Table: H.P CFM @ 40 PSI System capacity to fill system to 35 PSI in 30 minutes * System capacity to fill system to 55 PSI in 30 minutes ** 1/6 1.33 142 gal. 90 gal. 1/3 2.61 285 gal. 181 gal. 1/2 4.06 417 gal. 265 gal. 1 7.40 702 gal. 447 gal. * For systems with maximum water supply pressure of 175 PSI (1206 kpa) ** For systems with water supply pressure between 175 PSI (1207 kpa) and 250 PSI (1724 kpa) 3 TO PNEUMATIC ACTUATOR (plugged when not used) 2 TO DRAIN COLLECTOR 1 TO SPRINKLER RISER CONTRACTOR'S HYDROSTATIC TEST PORT (system side) FM-061H-0-118C WARNING The information contained herewith is for estimation and evaluation purposes only. Its use remains the responsibility of the designer. Air Pressure Maintenance Device (Style B ) Used only for the sprinkler piping network of the preaction system, when an external air supply is provided by others (tank mounted compressor, plant air or dry nitrogen cylinders) and piped to the air inlet port of the unit. Air supply style "B" provides an Air Pressure Maintenance Device (APMD) trim, factory mounted in the FIREFLEX N2 Blast cabinets. This section replaced by Dehydrator option (when used) E4 (plugged with SureFire trim) TO PNEUMATIC ACTUATOR (plugged when not used) 3 Contractor external Air or Nitrogen connection TO OPTIONAL ACCELERATOR (plugged when not used) 1 TO SPRINKLER RISER FM-061H-0-119B CONTRACTOR'S HYDROSTATIC TEST PORT (system side) 7 of 14 FM-076D-0-119D

Details & field wiring diagrams P & ID Autopurge System Sprinkler N2 Blast Compressor Preaction Compressor Air Maintenance Device/s (AMD/s) Supplied by Fireflex Riser towards the nozzles Tank Provided with brackets and Strap Low Air Pressure Switch Preaction Air Kit Preaction System Nitrogen Air FM-076D-0-119D 8 of 14

Details & field wiring diagrams Cabinet with main components, shown without door(s) FM-06LM-0-1A-4 9 of 14 FM-076D-0-119D

Trim diagram FIELD CONNECTION TO SPRINKLER PIPING NETWORK C1 To Air Supply System Trim 1 D2 3 To Air Supply System Trim B10 B8 C2 B5 D3 A1 B11 F1 F3 B6 To Air Supply System Trim 2 B7 D1 B9 B13 FIELD CONNECTION TO OPEN DRAIN (left side only) B12 B3 B4 B2 B1 FIELD CONNECTION TO WATER SUPPLY (left side only) TotalPac Base (shown without enclosure) CONTRACTOR'S HYDROSTATIC TEST PORT (water supply side) FM-076Z-0-63A Trim Components: A1 B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 B11 B12 B13 Deluge valve Priming valve Strainer 1/16" Restricted orifice Spring loaded check valve Alarm test valve Flow test valve Drip check valve Drain check valve Pressure operated relief valve (PORV) Emergency release valve Prime pressure water gauge & valve Water supply pressure gauge & valve Clapper check valve C1 C2 D1 D2 D3 F1 F3 Alarm pressure switch Connection to water motor gong (strainer supplied by contractor) Water supply control valve Riser check valve Main drain valve 24Vdc N.C. Solenoid valve Pneumatic actuator FM-076D-0-119D 10 of 14

Wiring diagram TBB WIRING OF INPUT POWER SOURCE 120VAC, 60Hz 1 LINE 2 3 NEUTRAL GROUND CONTROL PANEL 100VA MAX 4 GROUND 5 NEUTRAL N²BLAST UNIT 20A MAX 6 LINE 7 LINE 8 NEUTRAL AIR COMPRESSOR 1HP MAX 9 GROUND WITH AIR OPTION "A" ONLY Refer to Local Electrical Codes for wiring size. Branch circuit for air compressor shall not be the same as the control panel power source. TBA DETECTION ZONE 1 OPTIONAL WIRING IN CLASS A / STYLE D DETECTION ZONE 2 MANUAL PULL STATIONS ZONE 4 1 2 3 4 5 6 7 8 9 LEGEND SMOKE DETECTOR HEAT DETECTOR MANUAL RELEASE BELL OR HORN DRY CONTACT END OF LINE RESISTOR WIRING IN CLASS B / STYLE B 5.1K EOLR 5.1K EOLR 5.1K 5.1K EOLR EOLR 5.1K EOLR 5.1K EOLR NOTES: Class A / Style D requires CA2Z modules. End-of-line devices are not required for Class A / Style D wiring. 6 7 8 9 10 11 C MAIN VALVE NO NC CHICAGO OPTION LOS ANGELES OPTION C OPTIONAL 25 26 27 28 29 30 SHUT-OFF VALVE NO NC C 24VDC RESETTABLE NO NC C NO NC C 10 11 12 NO DETECTION ZONE 1 C DETECTION ZONE 2 NO MANUAL PULL STATIONS ZONE 4 WIRING IN CLASS B / STYLE Y NAC1 SILENCEABLE ALARM NAC2 NON SILENCEABLE WATERFLOW NAC SILENCEABLE SUPERVISORY TROUBLE ALARM SUPERVISORY WATER FLOW 24VDC NON RESETTABLE RS485 120 TBA TBC 1 2 3 4 5 SHIELD 9 10 11 12 13 14 TBA 1 2 3 4 5 6 7 8 15 16 17 18 19 20 21 22 23 24 POWER LIMITED 4-WIRE DETECTION CIRCUIT 1 2 29 30 24VDC COM UL-Listed 24VDC 4-Wire Smoke Detector 24VDC COM UL-Listed 24VDC 4-Wire Smoke Detector CONTACTS RATED 3A, 30VDC RESISTIVE 5.1K EOLR PAM-4 Power Supervisory Relay (EOL Relay) CONTACTS RATED: 5A, 1/6HP, 125/250VAC 0.5A, 250VDC 0.25A, 250VDC NOTE: Contact provided for connection to the building's central Fire Alarm Panel. NOTES: Control panel AC power source is supervised and non-power limited. All devices are shown in their normal supervisory state. Use dry contacts with power limited circuits only. FM-061H-0-210B Power Limited (supervised) Initiating Device Circuits Detection Zone 1, 2, 3, and 4. Max. loop resistance: 100 ohms End of line: 5.1K ohms, 1/4W Leave ELR (provided) on all unused circuits. Refer to Device Compatibility in the VFR-400 Releasing control panel Manual. Power Limited (supervised) Initiating Device Circuits Supervision Zone 1, and 2. Max. loop resistance: 100 ohms End of line: 5.1K ohms, 1/4W Leave ELR (provided) on all unused circuits. For dry contact supervisory devices such as tamper, low air, or high air switches. (Class-B only) Power Limited (supervised) Notification Appliance Circuits Output Circuit 1, 2, 3, and 4 Maximum operating voltage: 27Vdc (ripple: 0.3Vdc) Maximum usable current per circuit: 1.0A Total current available (all circuits): 2.5A Polarity is reversed in supervisory condition. Leave ELR (provided) on all unused circuits. Refer to Device Compatibility in the VFR-400 Releasing control panel Manual. Auxiliary Power 24Vdc Regulated Source Total current available: 0.2A Resettable for 4 wires smoke detectors WARNING Releasing control panel shall be supplied by a dedicated circuit breaker, as per NFPA 70, Section 760 and Canadian Electrical Code, Section 32. 11 of 14 FM-076D-0-119D

Cabinet The FIREFLEX N2 Blast cabinet is made of sturdy 14 gauge steel. Refer to figure 4 for dimensions. All surfaces are rust proof coated, inside and outside, with fire red, oven baked polyester powder on phosphate base. Cabinet is provided with two doors, all provided with a neoprene gasket to avoid vibrations, giving the access to the pressure gauges reading and the manual emergency release. The cabinet assembly is pre-assembled, pre-wired, and factory tested under ISO-9001 conditions. Refer to figures 2 & 3 for installation and clearances details. Electrical junction boxes are integrated inside the cabinet for connection of the supervisory and alarm devices contacts. Knockouts are pre-punched for the installing contractor as indicated on figure 1. Figure 1 - knockouts details Top of Cabinet High voltage 2½" Low voltage 2½" Typ. 8½" 3¾" 3" FM-061H-0-68B-12 Figure 2 - Floor anchoring template F 5'' Ø3/4" E G FM-061H-1-49B-6 Size E F G 46" 15" 48" 25" 54" 21" 56" 27" Figure 3 - Required clearance 12'' MIN 12'' MIN 22'' MIN FM-061H-1-49B-7 Size A 46" 24" 54" 32" FM-076D-0-119D 12 of 14

Figure 4 - Cabinet dimensions D P TBA, TBB & TBC Q TBB TBA & TBC CONTROL PANEL (except for Remote Controlled Unit) CONTROL PANEL OPTIONAL SHUT-OFF VALVE ØB SPRINKLER RISER SCH.40 GROOVED OUTLET F SPRINKLER RISER SCH.40 GROOVED OUTLET S R N DRAIN - SCH.40 GROOVED OUTLET ØA ØC M WATER INLET SCH.40 GROOVED OUTLET G T FM-06LM-0-2A System Size A B C D E F G H J K L M N P Q R S T 1½" 2" 1½" 2" 46" 25" 77¼" 4" 8¾" 11½" 13¾" 3¾" 2¾" 2¾" 15" 11½" 37½" 44¾" 50" 2" 2" 2" 2" 46" 25" 77¼" 4" 8¾" 11½" 13¾" 3¾" 2¾" 2¾" 15" 11½" 37¾" 45" 50" 3" 4" 3" 2" 46" 25" 77¼" 4" 10" 11½" 13¾" 3¾" 2¾" 2¾" 15" 11½" 44" 47¾" 50" 4" 4" 4" 2" 54" 31" 81¼" 4" 10" 11½" 13¾" 3¾" 2½" 2½" 23¾" 11½" 48½" 53" 58" 6" 6" 6" 2" 54" 31" 81¼" 4" 11" 13" 13¾" 5¼" 2¾" 2¾" 25" 13" 59¼" 65¼ 58" Dimensions are nominal and may vary by ¼ 13 of 14 FM-076D-0-119D