TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 07/16/08 TSEWG TP-8: ELECTRICAL EQUIPMENT ENCLOSURES AND HAZARDOUS LOCATIONS

Similar documents
S T R I T T & P R I E B E I N C.

Introduction to Hazardous Electrical Location Classifications

Overview of Hazardous Locations as They Relate to Solenoid Valves

Hazardous area descriptions

Fire Alarm System Accessories

Fire Alarm System Accessories

Guide for hazardous areas

Explosion-proof Duct Heaters

Electrical Area Classification 101 An Introduction to Area Classification the Basics IEEE Houston CED

ON THE BUTTON A reference guide to environmental ratings used for push button enclosures

SAFETY APPROVED FLASHLIGHTS: UNDERSTANDING THE REQUIREMENTS INTRODUCTION & OVERVIEW

Specifying Temperature Sensors for Hazardous Areas

Products Solutions Services CT287. Hazardous Area Classifications and Protection Systems

REGULATIONS EUROPEAN ATEX DIRECTIVE. INTERNATIONAL SCHEME: IECEx AREAS CLASSIFICATION DEFINED BY DIRECTIVE 1999/92/EC

VSD AND SS DRIVING ATEX MOTORS February 2014

Airo Wireless Intrinsically Safe White Paper. Written By: David Schmitt

Beamex. Calibration White Paper. Calibration in hazardous areas

1. GENERAL TECHNICAL INFORMATION

Selecting an Electrical Enclosure

Beamex Calibration White Paper. Calibration in hazardous areas

Working safely with flammable liquids

A Guide to Safe Electronic Weighing in Hazardous Locations

INSTALLATION AND OPERATING INSTRUCTIONS R-3F2-LXX

GLOBAL ENCLOSURE STANDARDS WITHIN THE ELECTRICAL INDUSTRY

Hazardous Area Classification in Oil & Gas Industry. A Fire Prevention Tool

A GUIDE TO EUROPEAN (EEC) CERTIFICATION FOR ELECTRICAL EQUIPMENT IN HAZARDOUS AREAS

Hazardous Area Classifications and Protections

For technical questions, contact: Grace Engineered Products Inc./ 5001 Tremont Ave, Davenport, IA /

HLA Series Hazardous Location Fan Forced Unit Heater Data Sheet

HLA Series Hazardous Location Fan Forced Unit Heater

Organization Summary and Directory. Standards Organization Summary and Directory Overview. Technical Information: Standards

Hazardous Areas - EXPLOSIONPROOF SOLENOIDS

CLASS I LOCATIONS ZONE CLASSIFICATION

UL HAZARDOUS LOCATIONS SERVICES

Selection of Explosion Protected Equipment for Hazardous Locations. Compiled by: Pieter Coetzee ZONE 2 ZONE 1 ZONE 0.

SERIES & NO. SMI SUBJECT: SAFE CONSIDERATIONS FOR AN APPLICATION OF SPECIAL ELECTRICAL SYSTEMS

A guide to the use of electrical equipment in potentially explosive atmospheres To view this document in PDF format click here.

Selecting a Safe Tank Gauging Product. Understanding Hazardous Area Definitions for Equipment Approvals

HLA Series Hazardous Location Fan Forced Unit Heater

[ TECHNOLOGY ] and does this definition affect a burner.

HAZARDOUS AREA CLASSIFICATION AND SELECTION OF EQUIPMENT FOR SAFE USE THEREIN FROM AN ELECTRICAL VIEWPOINT

Flow Switches. Liquid Flow Switches. Mounting Methods

Electron Microscopy Sciences

Explosion-protected actuator Page 259 of 292

Relays for use in hazardous locations. Class I, Division 2 and ATEX

NFPA 33 Standard for Spray Applica4on Using Flammable or Combus4ble Materials

Brasch Hazardous Location Unit Heaters

NEMA Enclosures for Electrical Equipment (1000 Volts Maximum)

The R. STAHL Technology Group Worldwide Success with Competence and Customer Support

Manufacturers of Explosion Proof, Corrosion Resistant and Severe Duty HVAC/R Systems, and Pressurization Equipment.

INTRODUCTION TO DUSTS AND THEIR EXPLOSIVE PROPERTIES

Smoke detection in hazardous areas:

Sioux EN-Series. All-Electric Extra Heavy Duty Industrial Steam Cleaners and Pressure Washers

Knowledge Objectives (2 of 2) Fuel Gas Systems. Skills Objectives. Introduction. Fuel Gas Systems (1 of 6) 12/20/2013

Guide to Intrinsically Safe Portable Radios

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS

Explosion protection Marijan Gorše, dipl. ing.

CENTRAL STATE HOSPITAL PLAN SAFE USE HANDLING AND STORAGE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS

Explosion-protected network cameras Safety first

Fluke 568 Ex Intrinsically Safe Infrared Thermometer

Process Instrumentation. Product Guide. Registered Quality System to ISO 9001

ATEX, NOMENCLATURE AND CODING

Type SP87300 SAFE-T SHP9 Explosion Proof Stirring Hot Plate

Rating. Class I Div II

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

PYROS. Código: FT-PY01-I Revisión: TECHNICAL DATA. Polycarbonate tube of 4 mm. thickness LIGHT FITTING. Laquered steel painted white

Special Occupancy Requirements

RE: USE OF FIREPRO IN POTENTIALLY EXPLOSIVE ATMOSPHERES

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) F-1000T DUAL FUEL CONSTRUCTION HEATER

Articles , & National Electrical Code Review & Application Guide

Ross SysCon Control Panels

Ventilating Hazardous Classified Locations. Steve Brandt, P.E. D.F. Brandt, Inc. Isolation Air Systems, Inc.

Copy Right By: Thomas T.S. Wan

Tempco s process controllers provide integrated solutions to manage your thermal loop system.

Installation guide for hazardous areas

Drive Technology \ Drive Automation \ System Integration \ Services * _0817* Inquiry Forms for Explosion-Proof Gearmotors

Understanding Hazardous and Explosion-Protection Environments

Understanding Hazardous Locations Concepts

Meeting the Requirements of NFPA 820:

S150 S300 CONSTRUCTION HEATERS. Rev: August 15, 2008 SERVICE AND MAINTENANCE MANUAL No PLEASE RETAIN FOR FUTURE REFERENCE PRODUCTS

NEMA Enclosures for Electrical Equipment (1000 Volts Maximum)

Frequently Asked Questions

Meeting NFPA standards for

ATEX, NOMENCLATURE AND CODING

First Revision No. 1-NFPA [ Chapter 2 ]

Weighing Solutions for Hazardous Areas FULL COMPLIANCE WITH ATEX DIRECTIVE

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content

Type VSA Suspended Wet Pit Sewage Pumps BULLETIN 228E-1 September 2014

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) F-400T DUAL FUEL CONSTRUCTION HEATER

Intrinsic Safety. Intrinsically Safe Solutions. Accurate Weighing in Hazardous Areas

ATEX Safety Switches. More than safety.

Guide to Hazardous Location Approvals:

Aluminum Dust Management in a Metallizing Facility

Guide to Hazardous Location Approvals: MICRO SWITCH Hazardous Area Limit Switches

HOW TO FIND THE RIGHT DEVICE FOR YOUR FACILITY

Star Teck. Teck and Tray Cable Fittings. Table of Contents

Safety Considerations for Hydrogen Installations

Flow Switches. Liquid Flow Switches. Mounting Methods

Options for Diesel Fire Pump Controllers

TECHNICAL NOTE. Response Factors for Flame Ionization Detector Operation FLAME IONIZATION DETECTOR OPERATION BASICS

Transcription:

TSEWG TP-8: ELECTRICAL EQUIPMENT ENCLOSURES AND HAZARDOUS LOCATIONS ENCLOSURES. Select equipment enclosures to provide the following: To protect facility personnel from coming in contact with live parts. To protect the equipment as necessary. NEMA classifies enclosures based on the degree of protection provided by the enclosure and the environmental conditions to which the enclosure will be eposed. Table 1 summarizes the NEMA enclosure types. For additional information, refer to NEMA 250, Enclosures for Electrical Equipment (1000 Volts Maimum). If needed, contact the enclosure manufacturer to determine the closest International Electrotechnical Commission (IEC) equivalent designation (NEMA 250, Appendi A, also provides limited information). 1

Table 1 NEMA Enclosure Types NEMA Type Description Application NEMA 1 (vented) General purpose. Primarily used to provide a degree of protection against contact with the enclosed equipment or locations where unusual service conditions do not eist. NEMA 1 NEMA 2 (vented) NEMA 2 General purpose against limited amounts of falling dirt. Primarily used to provide a degree of protection against contact with the enclosed equipment or locations where unusual service conditions do not eist. General purpose and drip-proof. Provides protection against limited amounts of falling water and dirt. Not dusttight. General purpose, drip-proof and dust-proof. Provides protection against limited amounts of falling water and dirt. NEMA 3 Dust tight, rain tight, and sleet/ice resistant. Outdoor NEMA 3R (vented) Rain-proof, sleet/ice resistant. Vented version is not dusttight. Outdoor NEMA 3R Rain-proof, sleet/ice resistant. Outdoor NEMA 3S Dust tight, rain tight, and sleet/ice proof. Outdoor NEMA 4 NEMA 4X Water tight, dust tight. Provides protection against windblown dust and rain, splashing water, and hose directed water. Undamaged by ice formation. Water tight, dust tight, corrosion resistant. Provides protection against corrosion, windblown dust and rain, splashing water, and hose directed water. Undamaged by ice formation. NEMA 5 General purpose against dust and falling dirt NEMA 6 NEMA 6P Temporary submersion, dust tight, rain tight, sleet/ice resistant. Prolonged submersion, dust tight, rain tight, sleet/ice resistant. /Outdoor /Outdoor /Outdoor /Outdoor NEMA 7 Class 1, Division 1, Groups A, B, C, or D. hazardous locations NEMA 8 Class 1, Division 1, Groups A, B, C, or D. /Outdoor hazardous locations NEMA 9 Class 2, Division 1, Groups E, F, or G. hazardous locations NEMA 10 Mining enforcement safety requirements. NEMA 11 Corrosion resistant by oil immersion. NEMA 12 Industrial use, drip tight, dust tight, non-corrosive liquids. NEMA 12K Industrial use with knockouts, drip tight, dust tight, noncorrosive liquids. NEMA 13 Oil tight, dust tight, non-corrosive coolants. 2

Select enclosures for indoor applications in accordance with the conditions specified in Tables 2 and 3 for non-hazardous and hazardous locations, respectively. Refer to NEC Article 500 (2005 Edition) for the definition of various hazardous locations. Contact the equipment manufacturer for assistance with hazardous environment applications. Table 2 Nonhazardous Locations NEMA Enclosure Type 1 2 4 4X 5 6 6P 11 12 13 Accidental Contact Falling Dirt Light Splashing Dust and Fibers Washdown with Water Oil and Coolant Seepage Oil and Coolant Spraying Corrosive Agents Occasional Submersion Sustained Submersion 3

Table 3 Hazardous Applications Protection Provided For: Type of Enclosure NEMA 7 and 8 NEMA 9 Class A B C D E F G Acetylene I Hydrogen, manufactured gas I Ethyl ether, ethylene, cyclopropane Gasoline, jet fuel, heane, butane, naphtha, propane, acetone, toluene, isoprene I I Metal dust II Carbon black, coal dust, coke dust II Flour, starch, grain dust II Fibers, flyings III X Note: Refer to NEC Article 500.4 (2005 Edition) for information regarding hazardous substances not listed in this table. Evaluate the enclosure temperature rise and determine if special cooling options will be required to dissipate the generated heat. Enclosure manufacturers can provide application guidance to assist in the selection and sizing of cooling options. HAZARDOUS LOCATIONS. NEC Article 500 (2005 Edition) establishes hazardous location classifications based on the flammable vapors, liquids, or gases, or combustible dusts or fibers that might be present. The classification also considers the likelihood that a flammable or combustible concentration or quantity is present. Electrical design criteria are based on the specific location classification. Table 4 lists the various hazardous location classifications; refer to NEC Article 500 (2005 Edition) for the definition of each location. 4

Table 4 Hazardous Location Classifications Class Group Eamples I A Acetylene I B Hydrogen, manufactured gas I C Ethyl ether, ethylene, cyclopropane I D Jet fuel, gasoline, heane, butane, naphtha, propane, acetone, toluene, isoprene II E Metal dust II F Carbon black, coal dust, coke dust II G Flour, starch, grain dust Referring to Table 4, a Class I location contains flammable gases or vapors that might be present in air in sufficient quantities to produce eplosive or ignitable mitures. Class I locations are further subdivided into Division 1 and Division 2, as described below. In accordance with NEC Article 500.5 (2005 Edition), a Class I, Division 1 classification applies to the following types of locations. Locations in which ignitable concentrations of flammable gases or vapors can eist under normal operating conditions. Locations in which ignitable concentrations of such gases or vapors might frequently eist because of repair or maintenance operations or because of leakage. Locations in which breakdown or faulty operation of equipment or processes might release ignitable concentrations of flammable gases or vapors, and might also cause simultaneous failure of electrical equipment in such a way as to directly cause the electrical equipment to become a source of ignition. In accordance with NEC Article 500.5 (2005 Edition), a Class I, Division 2 classification applies to the following types of locations. Locations in which volatile flammable liquids or flammable gases are handled, processed, or used, but in which the liquids, vapors, or gases will normally be confined within closed containers or closed systems from which they can escape only in cases of accidental rupture or breakdown of such containers or systems, or in case of abnormal operation of equipment. 5

Locations in which ignitable concentrations of gases or vapors are normally prevented by positive mechanical ventilation, and which might become hazardous through failure or abnormal operation of the ventilating equipment. Locations that are adjacent to a Class I, Division 1 location and to which ignitable concentrations of gases or vapors might occasionally be communicated unless such communication is prevented by adequate positive-pressure ventilation from a source of clean air, and effective safeguards against ventilation failure are provided. Evaluate each location for a possible classification as a hazardous area. All hazardous areas must comply with the design criteria specified in NEC Articles 500 and 501 (2005 Edition). Refer to NEC Article 504 (2005 Edition) for the design criteria for intrinsically safe systems. The Zone classification system described in NEC Article 505 [2005 Edition] can be applied as an alternative to the Class and Division designations. Refer to NEC Article 511 (2005 Edition) for design criteria for commercial-type garages in which service or repair operations are performed on all or all types of self-propelled vehicles. Refer to NEC Article 514 (2005 Edition) for design criteria for gasoline dispensing and service stations. This applies to any location where gasoline or other volatile flammable liquids or liquefied flammable gases are transferred to the fuel tanks (or auiliary fuel tanks) of self-propelled vehicles or approved containers. Refer to NEC Article 515 (2005 Edition) for design criteria for bulk storage plants. This applies to any location where flammable liquids are received by tank vessel, pipeline, tank car, or tank vehicle, and are stored or blended in bulk for the purpose of subsequent distributing of such liquids. Wherever possible, do not locate electrical distribution or utilization equipment in zones classified as hazardous. 6