PoolPak SWHP with CommandPak Control System CPCS BACnet IP User s Guide DOCUMENT #: SVW05-BACNETIP

Similar documents
CPCS SWHP BACnet MS/TP Interface User s Guide DOCUMENT #: SVW05-BACNET-MSTP

ComPak Series with CommandPak Control System CPCS BACnet MS/TP BAS Interface User s Guide DOCUMENT #: SVW06-CPBACNETMSTP

POOLPAK SWHP SERIES (SR, S, SE, SEP)

C-TRAC3 COMMUNICATION MANUAL FOR. BACnet NOVEMBER 2010 TO JANUARY 2014 USA HEAD OFFICE AND FACTORY

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products

LYNX Quick User Guide

Reference Guide for Microprocessor Controller

Reference Guide for Microprocessor Controller

CM3500 Controller - ClimateMaster DOAS Water-Source Heat Pumps - Rev.: 7 Oct, 2008B

Installation, Operation and Maintenance

PoolPak MPK Series. PoolPak.com. Environmental Control Systems REDUCED FOOTPRINT & WEIGHT COMPARED TO EARLIER GENERATIONS

Reference Guide for Microprocessor Controller

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

POOLPAK R-410A MPK SERIES

CONTROLS MANUAL For all Innovent and Valent air handling products


MicroTech Self-Contained Air Conditioning System

Siemens Thermostats. RDY2000BN Thermostat

SA Series Start up Report

Marvel J MICROPROCESSOR CONTROLLER

Siemens RDY2000BN. Start Up Guide

*IG1583EW* Aurora Touch UPC Kit Instruction Guide. Aurora Touch UPC Kit Instruction Guide

GeneSys Air-Cooled Screw Compressor Chiller

Standard Instructions For MC-2000/3000/4000 Controllers

BACnet Points for Single Compressor Water-to- Air Heat Pumps With Hot Gas Reheat Utilizing the FX10 Controller

Manual for the integration in BMS/GTC

Instruction, Operation, and Maintenance: Controls Software Versions: R37+

IntesisBox BACnet/IP Server - Notifier ID3000 series

InfinityPro. Control System for Rapid Engineering, LLC Air Handlers. User, Operation & Troubleshooting Manual

MicroTech Series 200 Centrifugal Chiller

DAP III Zone Master User s Guide

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

Marvel S MICROPROCESSOR CONTROLLER. Installation, Operation and Maintenance Manual Effective October 2018 DISCONTINUED. For Reference Only

Daikin Loop Water Manager Protocol Information

PIR Ready VT76xx Series Programmable & Non-Programmable Thermostats For Commercial HVAC Applications. BACnet Integration Manual September 1, 2010

ICC INDUSTRIAL CONTROL COMMUNICATIONS, INC.

ENTOUCH ONE USER GUIDE

Controls Lite. Controls Instruction, Operation, and Maintenance. IOM-C Part Number

Cultivator & Hybrid Cultivator

1.0 Digital Controller

Manual Supplement. Model Number: 8680-N2. Communications Protocol. Contents of this manual supplement include:

VPR Series VPRE Series VPRC/P Series VPRX Series. IOM-C Software Version 4 Part Number

MicroTech Series-200 Flooded Screw Chiller

NGC-40 Bridge. Modbus Overview. Raychem-AR-H58862-NGC40BridgeModbusOV-EN-1805 nvent.com 1

BACnet Integration Manual ITG-VH72xx-BAC-E00 ( _R0 Issue Date: October 21, 2008)

Installation and Operation Manual for QS/QV and Aura Units

Installation, Configuration and User Manual

Tempered Water Logic Control OPERATION l TROUBLE SHOOTING

Danfoss gas detection unit Type GD Heavy Duty

INSTALLATION INSTRUCTIONS

Introduction. What is the W2W Open controller?

MicroTech III Applied Air Handling Unit Controller Protocol Information

ibox Modbus Server Gateway for the integration of Notifier ID3000 / ID3002 / ID60 / ID50 fire panels in Modbus enabled monitoring and control systems

Networkable Fan Coil Controller Specification and Installation Instructions

Fan Coil Thermostat Controller Specification and Installation Instructions. Model TFHB24F3XYZ1 with External Humidity Sensor and BACnet Communication

MicroTech Rooftop/RMC

Master devices. Type X-AIR-ZMAS. Zone master module for up to 25 zone modules, with integral webserver and interfaces to higher-level systems

ARO Series. Description. Features. Modbus CO2 VOC. Networkable* ARO AROB24TGVH AROB24TGH. room controller. (AROB series only) or network

AQUATROL Zone Synchronizing Universal Injection/Mixing Boiler Reset Controls AQ252

NE Series TM. Indoor Pool Dehumidifiers The industry benchmark in quality and customer satisfaction

Trident User s Manual

The system shall be described in the following specification as manufactured by Schneider Electric

NetworkAIR AFX. Operation and Maintenance AFX65 AFX18

MicroTech Water-Cooled Screw Chiller Controller

TEC2620 Series Non-Programmable Fan Coil Network Thermostat Controller and Remote I/O Relay Packs

IMC BACnet Module. Service Literature. Table of Contents. General. Field Connections. Physical

Sales and Engineering Data Sheet ED

Contents. Appendix E: LonWorks Protocol Implementation Conformance Statement Document revision history... 47

BACnet MODBUS N2 LON Description Type Point Description Name # Object Type Register Type ID SNVT # Name SNVT Read Only

TWLC - Tempered Water Logic Controller. The Intelligent Control

PLC / HMI Modbus (Slave) Addressing

I/O ZONE 560/583 USERS GUIDE

C5 controller Bacnet

C5-12 OPERATION MANUAL

Air and Water cooled inverter chillers

EMERSON BLUE Wireless Comfor t Inter face 1F98EZ-1621 HOMEOWNER USER GUIDE

Daikin ENVi Thermostat installation overview

FieldServer Driver - Serial FS McQuay Microtech Open Protocol

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide. SE8600 Series Room Controllers

RSC 1000 User Manual. Rev /25/16

Introduction. What is the RTU Open controller?

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP 100% OUTSIDE AIR

AD-1272 Advanced Thermal Dispersion Probe Airflow Measuring System

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas

MARVEL PREMIUM HVAC MICROPROCESSOR CONTROLLER

TECHNOLOGY GUIDE. :: the dawn of a new era in commercial HVAC technology. The all-new Rheem Commercial Renaissance Line featuring:

CT224 Setup Tutorial

Wilo CO-Helix Booster Systems. Product Presentation July, 2017

CONTROL PANEL OPERATING MANUAL AIR-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMAC00A10-12EN

Air and Water cooled scroll chillers & heat pump

Installation Instructions / User s Manual TSTAT0406 and TSTAT0408

Laboratory Enclosed Scroll Air Compressor System with Premium NFPA Controls

Installation, Operation and Maintenance Manual

Operation manual. Rooftop Packaged Unit

Some alarms can be manually cleared from the current alarms list. This is indicated for the alarms where this is possible.

CONTROLS MANUAL. CARRIERrtc basic & medium electronic control 48/50 EN/EH 50 HB/HF/NZ/NF. Original document

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide

SCC Inc. Master Panel. Specifications. Document No. TS 2010 February 11, Product Description. Sample Specification

MicroTech Unit Ventilator

Transcription:

PoolPak SWHP with CommandPak Control System CPCS BACnet IP User s Guide DOCUMENT #: SVW05-BACNETIP-20180529 UPDATED: MAY 2018

INTRODUCTION PoolPak dehumidifiers equipped with the CommandPak Control System (CPCS) can be directly connected to a BACnet/IP based Building Automation System (BAS). Based on Carel s pcoweb serial card, the interface allows connection to an Ethernet network. 80 control points, including all basic information and set points for the PoolPak dehumidification system, are available through the interface. BACnet Configuration Parameters The BACnet configuration parameters for the controller are accessed in the configuration menu. To access this menu: 1. Press the I button on the RIU (Esc on the CM1 module). 2. Enter the password 9995. 3. Use the arrow keys to scroll down to the following parameters 062. BAUDRATE Sets the baud rate for the onboard serial port. It must be set to 19200 for use with the BACnet interface. 19200 is the factory default setting for this parameter. BAS Addr Sets the address of the BACnet interface card in the serial slot of the controller. It must be set to 1 for proper operation of the BACnet interface. The factory default setting is 1. LonWorks Inst Sets the type of BAS interface board installed in the control module, CM1. It must be set to NO for use with a BACnet interface. Ser Port Proto Sets the protocol the control module will use with the installed BAS board. It must be set to RS485 for use with a BACnet interface. 4. After changing any of the above parameters, reboot the controller by cycling power with the unit control power switch. This switch is located within or adjacent to the main control panel of the dehumidifier. PHYSICAL NETWORK CONNECTION The 8P8C ( RJ-45 ) Ethernet socket is located on the pcoweb interface card. The pcoweb card occupies the BMS card slot directly below the keypad built into the CM1 control module. This control module is located in the main control panel of the PoolPak dehumidifier. The Ethernet connection to the interface card should comply with standard installation practices. Use care to route the cable away from sources of interference and keep the maximum cable length less than 300 feet. CONTROL POINTS MAPPING 80 objects are accessible through the BACnet interface. Set points, sensor values, and enumerated variables are shared as analog-value objects. Status information points are shared as binary-value objects. The interface card is pre-configured at the factory with a device instance number of 77000. To change this value, follow the instructions shown in the Interface Card Field Setup and Configuration section of this document. 2018 PoolPak LLC. All rights reserved. Page 2

The following table lists the available points along with their object types and instance numbers OBJECT TYPE OBJECT INSTANCE OBJECT NAME DESCRIPTION UNITS AV 1 SplyFanCurr Supply Fan Current Amperes AV 2 RtnFanCurr Return Fan Current Amperes AV 3 Cmpr1Curr Compressor System1 Current Amperes AV 4 RtnAirTemp Return Air Temperature ºC AV 5 OutsAirTemp Outside Air Temperature ºC AV 6 ExhDprFdBk Actual Exhaust Damper Position (%) % Open AV 7 RecircDprFdBk Actual Recirc Damper Position (%) % Open AV 8 OutsDprFdBk Actual Outside Air Damper Position (%) % Open AV 9 AirOffEvapTemp Air Leaving Evaporator Temperature ºC AV 10 SurfTemp Cold Surface Temperature ºC AV 11 RtnAirRH Return Air Relative Humidity % AV 12 OutsAirRH Outside Air Relative Humidity % AV 13 AirOffEvapRH Air Leaving Evap Relative Humidity % AV 14 Cmpr2Curr Compressor System 2 Current Amperes AV 15 PoolTemp1 Pool Temperature 1 ºC AV 16 PoolTemp2 Pool Temperature 2 ºC AV 17 SplyAirTemp Supply Air Temperature ºC AV 18 RtnAirCO2Lvl Return Air CO2 Level PPM AV 19 FuzzyDprChg Fuzzy Logic Damper Control Variable N/A AV 20 FuzzyRatCmprChg2 Fuzzy Logic Space Temp Ctl Variable N/A AV 21 FuzzyDptCmprChg Fuzzy Logic Space Dewpt Ctl Variable N/A AV 22 ReqOutsDprPos Requested Outside Air Damper Position % Open AV 23 RtnAirTemp_F Return Air Temperature in Fahrenheit ºF AV 24 OutsAirTemp_F Outside Air Temperature in Fahrenheit ºF AV 25 AirOffEvapTemp_F Air Off Evap Temperature in Fahrenheit ºF AV 26 SurfTemp_F Cold Surface Temperature in Fahrenheit ºF AV 27 PoolTemp1_F Pool Temperature 1 in Fahrenheit ºF AV 28 PoolTemp2_F Pool Temperature 2 in Fahrenheit ºF AV 29 SplyAirTemp_F Supply Air Temperature in Fahrenheit ºF AV 60 Cmpr1SucPrs Compressor 1 Suction Pressure PSI AV 61 Cmpr1DisPrs Compressor 1 Discharge Pressure PSI AV 62 Cmpr1SucTmp Compressor 1 Suction Temperature ºF 2018 PoolPak LLC. All rights reserved. Page 3

AV 63 Cmpr1LiqTmp Compressor 1 Liquid Temperature ºF AV 64 Cmpr2SucPrs Compressor 2 Suction Pressure PSI AV 65 Cmpr2DisPrs Compressor 2 Discharge Pressure PSI AV 66 Cmpr2SuctTemp Compressor 2 Suction Temperature ºF AV 67 Cmpr2LiqTemp Compressor 2 Liquid Temperature ºF AV 68 Cmpr1SucSH Compressor 1 Suction Superheat ºF AV 69 Cmpr2SucSH Compressor 2 Suction Superheat ºF AV 70 Cmpr1LiqSC Compressor 1 Liquid Sub-cooling ºF AV 71 Cmpr2LiqSC Compressor 2 Liquid Sub-cooling ºF OBJECT TYPE OBJECT INSTANCE OBJECT NAME DESCRIPTION UNITS AV 1001 Cmpr1ActvFlt Cmpr System 1 Active Fault Code See Below AV 1002 Cmpr2ActvFlt Cmpr System 2 Active Fault Code See Below AV 1003 CmprStgsDesired Compressor Stages Desired Stages AV 1004 CmprStgsHtCool Cmpr Stages of Heating / Cooling Stages AV 1005 CmprstgsDpt Compressor Stages of Dehumidification Stages AV 1006 Spc1DprLim Damper Position Limit Code See Below AV 1007 Cmpr1FaultCount Cmpr System 1 Faults Since Powerup Faults AV 1008 Cmpr2FaultCount Cmpr System 2 Faults Since Powerup Faults AV 1009 RtnTempSetp_R Return Air Temp Set Point (Readable) ºF AV 1010 PoolTempSetp_R Pool 1 Temp Set Point (Readable) ºF AV 1011 PoolTemp2Setp_R Pool 2 Temp Set Point (Readable) ºF AV 1012 RtnRHSetp_R Return Air RH Set Point (Readable) % AV 1013 DprMinLimSetp_R Min Damper Limit Set Point (Readable) % Open AV 1014 DprMaxLimSetp_R Max Damper Limit Set Point (Readable) % Open AV 1015 RtnTempSetp_W Return Air Temp Set Point (Writable) ºF AV 1016 PoolTempSetp_W Pool 1 Temp Set Point ºF (Writable) ºF AV 1017 PoolTemp2Setp_W Pool 2 Temp Set Point ºF (Writable) ºF AV 1018 RtnRHSetp_W Return Air RH Set Point (Writable) % AV 1019 DprMinLimSetp_W Min Damper Limit Set Point (Writable) % Open AV 1020 DprMaxLimSetp_W Max Damper Limit Set Point (Writable) % Open AV 1021 AuxAirHtStgs Aux Air Heat Stages Active Stages AV 1022 Cmpr1Mode Compressor System 1 Mode See Below AV 1023 Cmpr2Mode Compressor System 2 Mode See Below 2018 PoolPak LLC. All rights reserved. Page 4

BV 1 WtrFlow1OK Cmpr System 1 Flow Switch Status On / Off BV 2 WtrFlow2OK Cmpr System 2 Flow Switch Status On / Off BV 3 OccMode Occupied Status On / Off BV 4 PurgeModeActv Purge Mode Status On / Off BV 5 Cmpr1ACCAllow Cmpr System 1 ACC Proof Status On / Off BV 6 Cmpr2ACCAllow Cmpr System 2 ACC Proof Status On / Off BV 7 AuxWtrHt1 Aux Pool Water Heater Status On / Off BV 8 AuxWtrHt2 Aux Pool Water Heater 2 Status On / Off BV 9 ForceOcc Force Occupied Mode (Writable) On / Off BV 10 ForceUnocc Force Unoccupied Mode (Writable) On / Off BV 11 ForcePurge Force Purge Mode (Writable) On / Off BV 12 ForceNoPurge Force Non-Purge Mode (Writable) On / Off BV 13 ActvAlmPres Active Alarm Present On / Off BV 14 NetMaster Indicates unit is master in multi-unit installation On / Off BV 15 ForceEvent Force System to Event Mode (Writable) On / Off BV 16 ForceNoEvent Force System to Non-Event Mode (Writable) On / Off COMPRESSOR ACTIVE FAULT CODE AV1001 and AV1002 are enumerated values indicating the most significant active fault in each compressor system of the dehumidifier. The present value for these objects can be decoded as follows: 0 Normal Operation - No Active Fault 1 Compressor System in OFF Mode 2 System Startup Active 3 Return Fan Not Running 4 Supply Fan Not Running 5 Fire Trip Active 6 Smoke Purge Active 7 Return Air Temp Out of Range (60 F < Normal < 105 F) 8 Both Fans Not Running 9 Freeze Alarm 11 Low Oil Pressure 13 Low Refrigerant Pressure 14 High Compressor Motor Temperature 15 High Refrigerant Pressure 16 Cmpr Current Transducer Failure 17 Crankcase Heater Breaker Off 50 Compressor Locked Out After 10 Faults 2018 PoolPak LLC. All rights reserved. Page 5

DAMPER POSITION LIMIT CODE AV1006 is an enumerated value indicating the reason for any current limitations on damper position. These limitations override the normal damper control routine under certain conditions. The present value of this object can be decoded as follows: 0 Normal Damper Limits Apply 1 Fire Trip Active All dampers closed. 2 Smoke Purge Active Exhaust damper 100% open, Outside and Recirc 0% Open 3 Unoccupied and No Dew Point Override Active Mixing Box Allowed to Close to 0% 4 Flywheel AC Mode Active Mixing Box Allowed to Open to 100% during Unoccupied 5 Outside Air Temperature Less Than 50 F Outside Air Damper Position Limited 6 Cooling Required and Compressor Running 7 Heating or Dehumidification and Compressor Running 8 Supply Temperature Less Than 40 F Mixing Box Forced to 0% Open 9 Heating and Outside Air Temperature Less Than Air Off Evaporator Temperature 10 System Startup Active Mixing Box Held at 0% Open COMPRESSOR SYSTEM MODE AV1022 and AV1023 are enumerated values indicating the operation mode of the corresponding compressor system. The present value for these objects can be decoded as follows: 0 Compressor Off 1 Air Heating Mode 3 Pool Water Heating Mode 4 Air Cooling Mode CHANGING A SET POINT Two analog value objects are allocated for each set point, a readable value and a writable value. To change a set point, set the present value of the writable object to the new set point value. Verify that the controller accepted the change by reading the value of the corresponding readable object. The controller applies limits to the set point values. If the BAS tries to set an inappropriate value, the readable object will show the min or max allowed value instead of the requested value. The BAS can detect this event by verifying the change in the readable object s present value. The following limits are applied by the controller: Return Air Temperature: 75 F 95 F Return Air Humidity: 40% - 65% Pool Water Temperature: 75 F - 95 F Damper Position: 0% - 100% Set points for temperature are represented by integer values in degrees Fahrenheit. CONTROLLING OCCUPANCY MODE The BAS can control the dehumidifier s occupancy mode directly. This control overrides all internal schedules. To force occupied mode, set the ForceOcc object value to the On state and the ForceUnocc object value to the Off state. To force unoccupied mode, set the value of the ForceOcc object to Off and the ForceUnocc object to On. 2018 PoolPak LLC. All rights reserved. Page 6

CONTROLLING PURGE MODE The BAS can control the dehumidifier s Purge mode directly. This control overrides all internal schedules and controls except for the freeze protection algorithm. To force purge mode, set the ForcePurge object value to the On state and the ForceNoPurge object value to the Off state. To force non-purge mode, set the value of the ForcePurge object to Off and the ForceNoPurge object to On. ACTIVE ALARM FLAG CONTROL The ActvAlarmPres binary value object indicates the status of the system alarm flag. This status corresponds to the red light inside the alarm button of the control module, CM1. When the present value of this object is On, there is an uncleared alarm present in the controller. To clear the alarm flag, set the ActvAlarmPres object value to Off. If there are no active alarms present, the value of ActvAlarmPres will change to Off. If there are still active alarms present, the value of ActvAlarm will remain On. To determine the actual alarm condition, the BAS can examine the present value of the ActvFault objects. These enumerated values indicate the most significant active fault code. See the Compressor Active Fault Code section earlier in this document for a list of possible states. INTERFACE CARD FIELD SETUP AND CONFIGURATION The BACnet interface card is shipped from the factory with the following default settings: BACnet BACnet LAN Type: BACnetIP BACnet Device Instance: 77000 BACnet IP UDP: BAC0 APDU Timeout: 5000ms APDU Retries: 3 Password for Restart: 1234 TCP/IP IP Address: Obtain from DHCP Server Netmask: Obtain from DHCP Server Gateway: Obtain from DHCP Server The CM1 controller provides a the ability to change any of these settings. To make a change: 1. Connect the network cable to the network. 2. Connect the RJ-45 cable to the port on the pcoweb card located in the BMS card slot of the CM1 controller. 3. Press and hold the! (Alarm) and (Enter). Wait for the top line to display SYSTEM INFORMATION. 4. Arrow Down to put the crsor next to OTHER INFORMATION and press Enter. 5. Arrow down to place the cursor next to PCOWEB/NET CONFIG and press Enter. 6. Place the cursor next to PCOWEB settings and press Enter. 7. If the display shows DHCP: ON, press the Enter button to move the cursor under the ON and arrow Up to change it to Off. If the display shows DHCP: OFF, move to the next step below. 8. To change network settings, including the card s IP address, Netmask, Gateway, DNS1, DNS2 and BACnet ID, continue to press the Enter button to tab through all changeable fields and use the Up/Down arrows to set the desired settings. 2018 PoolPak LLC. All rights reserved. Page 7

9. The last screen will say PCOWEB CONFIG ENABLE Update pcoweb? No. Change it to Yes then press Enter. 10. The screen should say PCOWEB CONFIG ENABLE Update complete. Reboot pcoweb to apply new setting. 11. Reboot the card by turning the Control Power Switch off. Wait about 20 seconds then turn the CPS on. 12. Wait approximately 5 minutes and then verify the new settings are saved on the card by repeating steps 2 through 7 above and viewing the setting match the changes that were made. If you experience problems during this procedure, please contact PoolPak Service at 800-959-7725 Ext. 2. TROUBLESHOOTING SYMPTOM POSSIBLE CAUSE SOLUTION The dehumidifier cannot be seen on the BACnet network. The variable values sent by the controller are different than those shown on the RIU. The interface card is not properly connected to the network. Power to the controller is off. The BAS is trying to access the interface with the wrong device instance number. Incorrect setting of the BAS configuration parameters in the service menu. Correct network wiring. If safe to do so, turn on the main disconnect and the control power switch (CPS) in the control compartment of the dehumidifier. Follow the instructions in this document to set the instance number to a value appropriate for the BAS. Correct the parameter values to match the settings shown in this document. The variable values sent by the controller are different than those shown on the RIU. Set point changes are different than requested by the BAS. The BAS Type parameter is not set to BACnet. The LonWorks Board parameter is set to Yes. Requested set point change is outside of the acceptable range. Set the BAS Type parameter to BACnet. Set the LonWorks Board parameter to No. Select set points based on the acceptable range. For questions about the interface that are not answered in this document, please contact PoolPak Service at 800-959-7725 Ext. 2. BACnet is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE). This trademark is used in the text, but for the sake of readability, it is not individually marked. With more than 45 years of experience in indoor pool dehumidification equipment manufacturing, PoolPak LLC is the most well-known brand in the industry. Our people and products work daily to improve the quality and comfort of indoor pool environments. PoolPak dehumidification solutions include a variety of heating, ventilation, and air conditioning systems, in addition to an industry-leading PoolPak support network. For more information, please visit www.poolpak.com. 3491 Industrial Drive York, Pennsylvania 17402 USA 800-959-7725 Fax 717-757-5085 2018 PoolPak LLC. All rights reserved. SVW05-BACNETIP-20180529