NEW. MB control board. communication protocol. for Modbus. Air Conditioning Carisma CRSO High Pressure Fan Coil Units

Similar documents
Air Conditioning Carisma CRS High Pressure Fan Coil Units.

Carisma Fly. Made in. Italy. Wall-mounted Fan Coil. Air Conditioning ENVIRONMENTAL COMFORT.

Carisma Fly Carisma Fly-ECM. Made in. Italy. High Wall Fan Coil. Air Conditioning ENVIRONMENTAL COMFORT

High wall fan coils Climmy FHW/FHW-ECM. Technical Catalogue

SABIANA ENVIRONMENTAL COMFORT. Air Conditioning Futura Fan Coil Units ICIM

NEW. SkyStar SkyStar ECM. Cassette Fan Coil Units. consumption ECM motors. Low energy. Air Conditioning ENVIRONMENTAL COMFORT

NEW. communication protocol. Control board with Modbus. Air Conditioning SkyStar SkyStar ECM Cassette Fan Coil Units

consumption ECM motors NEW Low energy Cassette Fan Coil Units YHK ECM YHK

SkyStar SK. Cassette Fan Coil Unit with Asynchronous Motor

NEW GREEN TECHNOLOGY

Product is subject to and complies with Regulation (UE) N.327/2011. cert. n Fan Coil Unit Cassette SkyStar Jumbo ECM. technical catalogue

NEW. Wall Controls. Air Conditioning Ceiling Air Conditioning Elegant. Cert. n 0545

UniTrane Ductable Units D-line and B-Line

The Sabiana. of Fan Coil

ECM Technology. Technology. Features. Advantages (compared to traditional brushed motors) Power consumption: YFCN versus YFCN-ECM (W/kW)

SkyStar SK-ECM. Cassette Fan Coil Unit with EC Brushless Electronic Motor and Inverter Board

YFCN Fan Coil Unit centrifugal fan

QZHW Fan Coil Unit. Key features. Specifications

SABIANA ENVIRONMENTAL COMFORT. Air Conditioning Ceiling Air Conditioning Elegant

UniTrane Terminals. High Wall Fan Coil: W-Line Ducted Fan Coil: D-Line Blower coil: B-Line. Product Presentation September 2016

QZB "Standard" comfort fan coil

DUCTED UNITS EBH EDS INTEGRATED COMFORT SYSTEMS

Controls for fan coil units and cassettes

a-life Hydronic terminals Fan-coil for professional applications, with cabinet or built-in version 1,50-7,50 kw <<< BACK INDEX

Application guide. ARMONIA ARMONIA EC 1,3-11 kw. Chilled water cassette Chilled water cassette - EC motor ARMONIA-AGU-1010-E

TECHNICAL MANUAL YEFB HIGH PRESSURE DUCTED UNIT

Fan Coil Range HYDRONIC TERMINALS

ELFODuct MP. Technical Bulletin. New generation horizontal and vertical built-in water-source ductable terminal for medium and large systems

Blower-YEFB-020-3R-1maxVel

DUCTIMAX 2-8 kw. Medium available static pressure ducted hydronic units. Duct unit DUCTIMAX

QFDK "ägir II" chilled water cassette

SIGMA PRISMA LOW BODY CONCEALED

All side discharge units are having high pressure switch (LP switch- Optional) and time delay relay. Compressors are scroll type, Copeland make.

Energy. The Energy ducted units have been designed. Heat Recovery Unit

EHH SERIES DRAW THROUGH FAN COILS CFM

Heating / Air Conditioning Energy Heat Recovery Units ENVIRONMENTAL COMFORT

THIN PROFILE CENTRIFUGAL FAN COIL UNITS SLIM

Elegance and design for your residential comfort

SMART. 4,9 49,5 kw. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans T_SMT_0609_GB

COMFORT HYDRONIC TERMINALS

WATER COOLED HEAT PUMP VERTICAL UNIT CONSOLE TYPE OR RECESSED

30RB Air-Cooled Liquid Chillers. Nominal cooling capacity 8-14 kw. Features. Quiet operation

Fans Air Handling Units Air Distribution Products Fire Safety Air Curtains and Heating Products Water terminals SYSWALL. Wall mounted fan coil units

Premium Efficiency Heat Recovery Unit. D-AHU Modular L. Air Handling Units

CASSETTE UNIT. Comfort Circle

MULTIPLO PF Multifunction chillers for indoor installation. Cooling Capacity: kw Heating Capacity: kw

System architecture. Air treatment Index

ELFODuct MP. Technical Bulletin. New generation horizontal and vertical built-in water-source ductable terminal for medium and large systems

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module

CMA TECHNICAL MANUAL CONDENSING UNITS FOR OUTDOOR INSTALLATION O L S A F RA N

CWX 3 - CWX 5 CASSETTE TYPE TERMINAL UNIT. Cooling

SELF CONTAINED HORIZONTAL AIR CONDITIONERS WATER COOLED CONDENSER (COAXIAL REFRIGERANT-WATER HEAT EXCHANGER)

COMPACT AIR HANDLING UNIT

COMFORT APPLICATION HYDRONIC TERMINALS ELEGANCE AND DESIGN FOR YOUR RESIDENTIAL COMFORT

ENERGY TOP. Condensing boiler solutions

CWX 6 - CWX 8 - CWX 10 CASSETTE TYPE TERMINAL UNIT

VEX100 series Air handling units with cross-flow heat exchanger

30RB Air-Cooled Liquid Chillers PRODUCT SELECTION DATA. Easy and fast installation. Compact, reliable and efficient

Next P kw COOLING 5 93 kw HEATING. technicalcatalogue. Heat pump air conditioners with upflow air delivery T_NXTP_0411_GB

DYNACIAT LGN. Description. Split system Water chillers. High energy efficiency Compact and quiet Scroll compressors Brazed-plate heat exchangers

WATER TO AIR DUCTABLE INDOOR HORIZONTAL HEAT PUMP

Cassette units Model Comfort Circle. - heating - cooling - ventilation

CONDENSING UNITS AIR COOLED CONDENSER. COOLING ONLY

SPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw

CFI VERTICAL WATER RECESSED DUCTABLE TERMINAL UNIT

BRIZA_038. EC MOTOR Briza Hybrid: High performance technology

FHE FHE. Dehumidifiers for radiant cooling systems with heat recovery. Versions

CATALOGUES SUMMARY - WCHBZ Pages WCHZ Pages 19-42

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual

FAN COIL UNITS LASER / LOW BODY / CONCEALED

Also available with the new i-life R-Slim inverter and radiant panel version. Perfect comfort. Silent operation. Real energy savings

Helios. Unit Heater. Thickness 1 mm. Diameter 22 mm. Pitch 2,5 mm. Fin 0,12 mm

30RBY/RQY Ductable Air-Cooled Liquid Chillers/ Ductable Air-to-Water Heat Pumps PRO-DIALOG +

TECHNICAL DATA. F.H. Biddle B.V. P. O. Box 15, NL-9288 ZG Kootstertille,The Netherlands. Tel: Fax:

technical data Fan coil unit FWB small duct unit

Technical Data Ducted Three Phase Split System Air Conditioner

CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL

NEXT EVO DXR410A NEXT EVO DX NEW SOFTWARE. rcgroupairconditioning

BRAN Residential chillers and heat pumps. Reversible unit, air source for outdoor installation 4,81-27,2 kw <<< BACK INDEX.

Technical Data OPA 101, 150, 180. Ducted Three Phase Packaged Air Conditioner kw 18.5 kw. Extra Long Life Epoxy Coated Outdoor Coil

NEXT DL NEXT DL. rcgroupairconditioning

BRT C/H Series PACKAGED AIR TO AIR UNITS COOLING / HEATING APPLICATIONS OUTDOOR INSTALLATION. Ver. 1.01

CUMULUS CUMULUS. Key figures. Construction. Function Integrated chilled beams

WATER CHILLER UNITS AIR COOLED CONDENSER CENTRIFUGAL FANS HEAT PUMP. EWCBZ COOLING ONLY. EWCZ

GHE GHE. Dehumidifiers for radiant cooling systems with heat recovery VERSIONS ACCESSORIES

GHE Dehumidifiers for radiant cooling systems with heat recovery

Specification Data. General:

LDK LDK. Air to water chillers and heat pumps VERSIONS ACCESSORIES

Galletti IWC THE HYDRONIC CASSETTE UNIT PAR EXCELLENCE A guide to choosing Create value to design better

Scholar III Unit Ventilator

TOSHIBA AIR CONDITIONING

CZT CZT. High efficiency air to water heat pumps with E.V.I. compressors E.V.I. HP OTHER VERSIONS ACCESSORIES

Adsolair 56/58. Comfort air conditioning unit with double plate heat exchanger and adiabatic evaporative cooling system

UCS UCS/M UCS/H UCS900

AIR COOLED HEAT PUMP FOR OUTDOOR INSTALLATION FROM 4,2 TO 35,1 kw

SAM. Small Air Handling. VES SMALL AIR HANDLERS part of a complete range of innovative, flexible products from the HVAC experts

LCP kw. Outdoor monobloc air-water unit. Total heat recovery multi-purpose units LCP PLUS

Product Specifications. Vertical Floor Consoles By First Co.

> HGA AIR - WATER HEAT PUMPS FOR OUTDOOR INSTALLATION. Available range. Unit description. Options. Accessories

COOLROW Close control air conditioners for In-Row installation Cooling Capacity: kw

Transcription:

NEW MB control board for Modbus communication protocol Compliant with ERP 0 Regulation (EU) No. 7/0 Quality management systems ISO 900 Cert. n 0/ www.eurovent-certification.com www.certiflash.com Air Conditioning High Pressure Fan Coil Units

INTRODUCTION In line with innovative trends and modern industrial design, the fan coil range meets today s demanding requirements of performance, size, acoustics, low energy, ease of installation and maintenance. The fan coil unit has been designed around a platform of models, versions and accessories, all of which have been independently tested and certified by Eurovent. All fan coils with centrifugal fans are equipped with electric motors which reduce electrical consumption comparative to previous models, with speed motors as standard offering greater flexibility in the selection of products. New market trends have also led to an extension of the four pipe model which now has a two row LTHW battery giving improved outputs at lower flow and return temperatures. A full range of control options is available including the Free patented wireless control offering greater flexibility in the installation of units, with the highest precision in monitoring and maintaining the desired comfort conditions. The model is complemented with a full range of accessories: various types of adjustment valves, additional electric heater, auxiliary condensate pump, air inlet/outlet diffusers for fitted installations. CONTENTS Presentation Construction features Dimension, Weight, Water content EUROVENT Certification Main performance and technical characteristics Cooling emission tables Heating emission tables Correction factors table Operation limits Water pressure drop Accessories Wall electronic controls FreeSabiana wireless control system Controls and units MB Management system for a network of fan coils PSM-DI and Sabianet electronic boards Sabiana take part to the Eurovent program of fan coil performance certification. The official figures are published in the web site www.eurovent-certification.com and in the web site www.certiflash.com. The tested performances are: Cooling total emission at the following conditions: - Water temperature +7 C E.W.T. + C L.W.T. - Entering air temperature +7 C dry bulb +9 C wet bulb Heating emission ( pipe units) at the following conditions: - Entering water temperature +0 C - Entering air temperature +0 C Cooling sensible emission at the following conditions: - Water temperature +7 C E.W.T. + C L.W.T. - Entering air temperature +7 C dry bulb +9 C wet bulb Heating emission ( pipe units) at the following conditions: - Water temperature +70 C E.W.T. +60 C L.W.T. - Entering air temperature +0 C Available pressure Fan absorption Water pressure drop Sound power

Presentation version with centrifugal fan Range includes air flow rates (from 7 to 0 m /h), each equipped with or row coil and with the possibility to add a or row coil for pipe systems. It is the most comprehensive range, perfect to meet all air-conditioning requirements of work environments like offices, shops, restaurants and hotel rooms featuring ducted installations with available pressure up to 80 Pa. Compliant with ERP 0 Regulation (EU) No. 7/0 Construction features Casing Made from mm galvanized steel insulated with polyolefin (PO) foam (class M). Filter Polypropylene cellular fabric regenerating filter. The filter frame of galvanized steel is inserted into special plastic sliding guides fastened to the internal structure for easy insertion and removal of the filter. Fan assembly The fans have aluminium or plastic blades directly keyed on the motor with double aspiration and they are dynamically and statically balanced during manufacture in order to have an extremely quiet operation. Electric motor The motor is wired for single phase and has five speeds with capacitor. The motor is fitted on sealed for life bearings and is secured on anti-vibration and self-lubricating mountings. Internal thermal protection with automatic reset, protection IP 0, class B. Coil It is manufactured from drawn copper tube and the aluminium fins are mechanically bonded onto the tube by an expansion process. The coil has two / inch BSP internal connections and /8 inch BSP air vent and drain. The coil is not suitable for use in corrosive atmosphere or in environments where aluminium may be subject to corrosion. The connections are on the left hand side looking from the air outlet of the unit (see picture). On request or on site the connections can be moved to the other side. Condensate collection tray Made from plastic (ABS UL9 HB) with an L -shaped plastic fitted on the inner casing; the tray is insulated with polyolefin (PO) foam (class M). The outside diameter of the condensate discharge pipe is mm. Accessories and Controls See pages 8 -.

version Dimensions, Weight, Water content Coil connections on the left Vertical Installation D G 0 F Ø ext. 7 9* D 7 O WATER OUTLET S WATER OUTLET 7 N U R 7 9* H G 0 7 00 9 D H E* * Supply frame dimension = E x 9 mm Auxiliary condensate tray (optional) Horizontal Installation E* 0 Ø ext. 0 F 0 * Supply frame dimension = E x 9 mm COIL CONNECTIONS U or row coils Heating additional coil ( or rows) G H M 0 Ø ext. Ø /" F WATER INLET G H P 0 Ø ext. Ø /" F WATER INLET

version 600 X Y,, 0,9,9,8 0,6,,6, 0,,0 0,9, 0, 0,6 Rows Rows 6, 7,6 8, 7, 8,9 9, 0,,0 0,, 7,7 0,0 9,,8 0,,,,9,7,,6, 7, 7, 9, 0, 8,8 0,6,,0,9,8 6, 7, 8, 9, 8, 9, 689 6 669 8 0 60 60 8 0 7 6 60 80 70 6 0 8 70 70 0 0 0 6 9 90 790 9 07 099 8 70 70 0 0 0 6 9 90 0 90 860 88 8 70 70 0 0 0 6 9 90 0 + + Model Weight without packaging Weight with packaging + + + Model D E F G H M N O P R S U X Y Model PACKAGING Dimension, Weight, Water content Dimension (mm) Weight (kg) Water content (litres)

version EUROVENT Certification www.eurovent-certification.com www.certiflash.com pipe units. ˆ ˆ COOLING ˆ Œ Ž ŒŽ Œ Ž Œ Ž HEATING ˆ Œ Ž ˆ ŒŽ ˆ (E) (E) Model (E) ˆ (E) ˆ (E) ˆ (E) Š ˆ (E) Š ˆ (E) (E) (E) Œ (E) ( * ) Œ ( * ) ƒ (E) (E) (E) Model (E) ˆ (E) ˆ (E) ˆ (E) Š ˆ (E) Š ˆ (E) (E) (E) Œ (E) ( * ) Œ ( * ) ƒ (E) ƒ ƒ ƒ ƒ ƒ ƒ pipe units. ˆ ˆ COOLING ˆ Œ Ž ŒŽ Œ Ž Œ Ž HEATING ˆ Œ Ž Water temperature + 70 C E.W.T. + 60 C L.W.T. (E) (E) Model (E) ˆ (E) ˆ (E) ˆ (E) Š ˆ (E) Š ˆ (E) (E) (E) Œ (E) ( * ) Œ ( * ) ƒ (E) ƒ ƒ ƒ + + + + (E) ( * )

version Main performance and technical characteristics pipe units. The following standard rating conditions are used: COOLING Entering air temperature + 7 C d.b. + 9 C w.b. Water temperature + 7 C E.W.T. + C L.W.T. AVAILABLE PRESSURE: 0 Pa HEATING Entering air temperature + 0 C Entering water temperature + 0 C Water flow rate as for the cooling conditions Model Speed Air flow Cooling total emission Cooling sensible emission Heating Dp Cooling Dp Heating Fan Sound power Lw Sound pressure ( * ) m /h W db(a) db(a) 7,,6,6 6,6 8,9 7 8 0,6,76,9 8, 0, 6 0 70,9,96,7,8, 0,8,8,89,7, 6 6 7 9,0,,8 8,7 7,6 76 9 0 66,7,86 6, 6, 8,9 9 7 8 76,,9 6,89 9,,0 07 870,8, 7,6,6, 0 80,,7,0,9 7, 88 6 00,0,0 8,76 7,7 6,9 0 9 0 90,6,0 0,8,66 0 6,8,9 8,78 0,,0,9 8,7 8,7, 9 0,9,9 6 6 7,8, 7,9, 6, 97 9 0 6,68,7,0,8, 7 6 000 6,,9 9,90 9,6,0 6 9 0 60 7,69,88,78, 7,9 9 6 70 8,9 7,0, 8,,0 8 60 980 9,8 7,88 7,,0,6 7 6 0 0,9 8,6 8,9, 6,0 6 66 7 Model Speed Air flow Cooling total emission Cooling sensible emission Heating Dp Cooling Dp Heating Fan Sound power Lw Sound pressure ( * ) m /h W db(a) db(a) 0,68,96,,7 6, 6 0 70,96,9,86, 7,7 0,7,6,8 6,8 9, 6 6 7 7,0,8,98 0,, 7 8 9,0,66,9 9,0, 76 9 0 66,7,0 6,8 9,, 9 7 8 76,7,7 7,7,0 9,0 07 870,6,8 8,9,,0 0 80,8,77 6,06,, 88 6 00,8, 9,97, 0, 0 9 0 90,6, 0 6,,9 0 7,06,7 9,,08,,0 7, 6, 9,8 9 0 9,,0 6 6 7,7,7 7,6 9,,0 97 9 0 7,0,78,,, 7 6 70 980 0 000 6,8,9 0,0,9 7,0 6 9 0 60 8,6 6,,7 9,, 9 6 0,07 7,6 6, 6,0 6, 8 60,6 8,9 8,6, 0, 7 6,0 9, 0,0,9,7 6 66 7 pipe units. The following standard rating conditions are used: COOLING Entering air temperature + 7 C d.b. + 9 C w.b. Water temperature + 7 C E.W.T. + C L.W.T. AVAILABLE PRESSURE: 0 Pa HEATING Entering air temperature + 0 C Water temperature + 70 C E.W.T. + 60 C L.W.T. Model Speed Air flow Cooling total emission Cooling sensible emission Heating Dp Cooling Dp Heating Fan Sound power Lw Sound pressure ( * ) m /h W db(a) db(a) 7,,6, 6,6 9, 7 8 + + + + 0,6,76,9 8, 0, 6 0 70,9,96,6,8,0 0,8,8,8,7, 6 6 7 9,0,,0 8,7,8 76 9 0 66,7,86,8 6,,7 9 7 8 76,,9,9 9, 6,7 07 870,8,,,6 7,7 0 80,,7,8,9,8 88 6 00,0,0,76 7,7 9, 0 9 0 90,6,0,79,9 8,0 0,8,66,0 8,7 0,0 9 0 0 6,8,9,89,9,7 6 6 7,8,,08, 6,0 97 9 0 6,68,7 6,6,8,7 7 6 60 7,69,88 7,0, 0,8 9 6 70 8,9 7,0 8, 8, 7,0 8 60 980 9,8 7,88 8,9,0,0 7 6 000 6,,9,76 9,6, 6 9 0 0 0,9 8,6 9,6, 6,6 6 66 7 ( * ) = The sound pressure levels are 9 db(a) lower than the sound power levels and apply to the reverberant field of a 00 m room and a reverberation time of 0. sec.. 7

version Cooling emission of row coil Entering air temperature: 7 C R. H.: 0% Available pressure: 0 Pa WT: 7/ C WT: 8/ C WT: 0/ C WT: /7 C Mod. Speed Qv m /h 9 0 70 0 7 00 870 76 66 80 0 0 90 7 0 980 70 60 000,,0,78,,8,,8,,0,68 7, 6,9 6,,9,7, 0,6 9,66 8, 6,69,,6,9,7,6,96,7,,8,,,06,7,96,8 8,0 7,7 6,9,8,7 9 79 7 0 9 8 76 696 6 0 88 089 96 8 966 89 66 0,8 9,,9,0 8,8,8 6,0, 8,8,9 7,,,6 7,,8 8,8,, 6,,0,9,7,,9,,8,,98,6, 6, 6,7,66,99, 0, 9, 8,6 7, 6,0,9,0,8,6,,78,0,99,68,0,,8,6,76,0 8,0 7,6 6,6,0,0 0 7 9 70 8 7 68 6 69 08 06 97 89 78 76 66 87 8 0 6,9, 0, 7,,,9, 8,,,0, 0, 7,,0 0,, 0,6 7,, 9,0,6,,9,76,6,77,6,08,80,,0,80,8,8,6 7,9 7,8 6,68,7,6,0,86,67,9,8,8,0,7,,6,7,6,98,0,78 7, 6,76,98,96,8 89 6 0 8 69 77 0 8 8 86 8 7 66 60 68 70 9 98 79 6,8,0,7 0,7 9,6 6,,, 9,6 8,,0,9,0 8,7 6,,8,9 0,8 8,,,70,9,,0,,8,,9,07,88,79,6,8,86,0 6,00,,99,,8,70,9,,0,,8,,9,07,88,79,6,8,86,0 6,00,,99,,8 9 7 7 0 89 9 7 6 6 6 9 0 9 88 79 8 0,0 8,8 7, 6,, 9,8 7,8 6,6,,6 8, 7,7 6,,,7 8,8 7,6 6,,7, Cooling emission of row coil Entering air temperature: 6 C R. H.: 0% Available pressure: 0 Pa WT: 7/ C WT: 8/ C WT: 0/ C WT: /7 C Mod. Speed Qv m /h 9 0 70 0 7 00 870 76 66 80 0 0 90 7 0 980 70 60 000,90,7,9,7,,8,,96,6,9 6, 6,,6,97, 0,7 9,6 8,60 7,0,98,0,0,8,6,,78,0,99,68,,,8,6,76, 8,0 7,7 6,7,, 99 69 8 9 68 89 7 68 6 66 0 06 968 8 7 79 68 79 7 08 6,8,0 0, 7,,,8, 8,,,0, 0, 7,,9 0,, 0, 7,, 9,0,7,,0,0,89,8,8,,9,9,69,,98,9,7 9,0 8,8 7,6 6,,7,0,9,7,7,6,6,,8,,8,90,6,6,7,9 7,70 7,0 6,6,,07 79 6 76 67 60 9 00 979 96 86 7 60 09 907, 9, 6,,8, 0,7 6,9,, 0, 7,7 6,,9, 8, 8,7 6,,8 0, 7,,97,8,67,,,9,9,67,,0,8,8,8,,8 6,9 6,,80,96,97,9,78,8,,,9,88,8,0,0,8,8,80,,6 6,9 6,,69,7,6 9 7 88 6 6 66 0 60 7 78 7 79 6 7 8 9 0 998 8 68,,7 9,8 8, 7,,8 0, 8,8 7, 6,,0 0, 8, 6,7,9,6 0, 8, 6,,,6,6,,,0,,6,96,77,60,7,,8,,0,7,76,7,6,86,6,6,,,0,,6,96,77,60,7,,8,,0,7,76,7,6,86 9 78 7 8 0 7 6 8 889 89 7 6 9 7,6 6,7,6,6, 7,,9,0,, 6,,9,9,8,7 6,7,8,8,, Correction factors for different R.H. Legend R.H. 8% 6% WT: Pc Ps Pc Ps 7/ C 0,9 0,90 8/ C 0,9 0,88 0/ C /7 C WT = Water temperature Pc = Cooling total emission Ps = Cooling sensible emission = Water flow = Water pressure drop Speed = Fan speed = High speed = Medium speed = Low speed Qv = Air flow 8

version Cooling emission of row coil Entering air temperature: C R. H.: 0% Available pressure: 0 Pa WT: 7/ C WT: 8/ C WT: 0/ C WT: /7 C Mod. Speed Qv m /h 9 0 70 0 7 00 870 76 66 80 0 0 90 7 0 980 70 60 000,6,,9,00,88,7,8,9,8,90,68,,96,8,7 9,00 8,6 7,8 6,,,0,9,7,7,6,6,,8,,8,90,6,6,8,9 7,70 7,0 6,6,,07 78 7 6 60 7 98 976 9 8 7 68 8 7 0 0 90, 9, 6,,7, 0,7 6,9,, 0, 7,7 6,,9, 8, 8,7 6,,8 0, 7,,6,,9,76,6,76,,07,79,,0,78,7,8, 7,9 7,6 6,67,7,60,0,86,66,9,8,7,00,7,,6,69,,97,0,78 7,8 6,7,96,9,8 88 6 0 8 67 76 8 80 6 86 8 7 66 8 6 66 7 98 790 6,9,,8 0,8 9,6 6,,, 9,6 8,,,0,0 8,8 6,,9,0 0,9 8,,6,7,60,,,,86,,,09,89,8,6,0,88, 6,0,7,0,7,0,7,60,,,,86,,,09,89,8,6,0,88, 6,0,7,0,7,0 9 7 9 9 97 9 66 6 67 96 6 08 99 86 7 8 0, 9,0 7, 6,,6 0,0 8,0 6,8,7,7 8, 7,8 6,6,,8 9,0 7,8 6,,8,,,6,0 0,9 0,87,,88,67,0,,7,96,9,6,7,88,7,78,0,0,,6,0 0,9 0,87,,88,67,0,,7,96,9,6,7,88,7,78,0,0 99 79 6 0 8 87 7 0 6 7 96 80 7 60,7,0,,,0 6,,6,7,, 6,,,,0,0 6,,0,8,6,7 Correction factors for different R.H. Legend R.H. 8% 6% WT: Pc Ps Pc Ps 7/ C 0,9 0,90 8/ C 0,9 0,88 0/ C /7 C WT = Water temperature Pc = Cooling total emission Ps = Cooling sensible emission = Water flow = Water pressure drop Speed = Fan speed = High speed = Medium speed = Low speed Qv = Air flow 9

version Cooling emission of row coil Entering air temperature: 7 C R. H.: 0% Available pressure: 0 Pa WT: 7/ C WT: 8/ C WT: 0/ C WT: /7 C Mod. Speed Qv m /h 9 0 70 0 7 00 870 76 66 80 0 0 90 7 0 980 70 60 000,78,,9,88,69 6,7,,06,7, 8,00 7,6 6,96 6,09,0,06,08 0,89 9, 7,,6,,8,9,8,9,8,,09,77,69,0,86,9, 9,7 8,9 7,6 6,,90 6 607 9 96 6 078 9 870 786 709 76 97 07 876 6 078 87 9 9,9 9, 6,,,8 8, 6,7 9,7,0 7,,, 9,0,9 0,8, 6,0 9,9,,6,9,7,87,60,,6,00,7,,7 7, 6,8 6,,6,8,67 0,80 9,7 8,0 6,60,9,0,0,8,70,,60,,9,60,0,,9,9, 8,80 8,0 7,,9,60 8 9 6 8 970 86 787 7 6 0 7 070 98 789 007 88 677 8 6 7,8,8,,0 9,8 8,0 8,7,9 7,,8 9,8 8,,, 8,9,7 9,, 8,,,6,,0,99,86,7,86,,8,88,,6,78,9,0 9,0 8, 7,9 6,7,0,,0,8,6,0,7,,90,8,0,9,6,,,88 7,97 7, 6,0,8,0 8 8 78 0 7 66 606 8 9 98 90 8 70 60 9 89 09 869,0 9,7 8, 6,8 6,0 0,0,0 0, 7,0,,, 9, 7,, 0,9 8,,0, 7,,9,79,6,,,,8,9,,0,,9,,07,6 6,70 6,7,,66,67,9,79,6,,,,8,9,0,0,,9,,07,6 6,70 6,7,,66,7 08 77 0 9 9 6 0 6 707 67 609 9 0 06 90 80 6 6,,6,6,8, 7,,8,6 9,6 8,0 7, 6,6,,,, 0, 8,6 6,, Cooling emission of row coil Entering air temperature: 6 C R. H.: 0% Available pressure: 0 Pa WT: 7/ C WT: 8/ C WT: 0/ C WT: /7 C Mod. Speed Qv m /h 9 0 70 0 7 00 870 76 66 80 0 0 90 7 0 980 70 60 000,7,,8,8,,6,98,,0,7 7, 6,80 6,9,,6,6 0,7 9,70 8,6 6,6,9,0,06,8,7,,6,6,9,6,,,60,96, 8,8 8,0 7,,96,6 80 90 966 86 78 706 67 69 06 9 78 996 88 668 0 8 7,8,7,,0 9,7 7,9 8,,7 7,,6 9,8 8,,, 8,9, 9,, 8,,0,98,78,,8,,97,0,0,6,9 6,9 6,00,6,79,0 0,7 9,0 8,7 7,9,79,6,8,9,7,6,9,,08,7,,,88,7,7,06 8,8 7,6 6,76,6, 79 9 67 86 77 69 66 66 08 0 90 8 69 767 6 7 996,, 0, 8,7 7,7 8, 0,7 6,,8 8,,7,, 9,6 7,0 6,8, 9,, 9,,,0,90,7,60,79,,0,7,8,79,6,,6,0 7,8 7, 6,8,8,,,9,7,,,7,07,7,,7,70,,9,,7 7,8 6,88 6,06,98,8 88 6 6 9 7 6 7 7 6 8 78 7 6 9 0 9 76 8, 7, 6,,,6, 8,,7,0 0,8 9, 8,8 7,,7, 6,,0,6 8,6,6,6,,6,,,78,,0,97,77,,,0,6,6,7,6,70,9,09,6,,6,,,78,,0,97,77,,,0,6,6,7,6,70,9,09 8 6 96 78 8 79 0 0 606 76 0 9 7 986 90 808 678,7,,,8,, 0, 8,7 7,,9,,0,,, 9, 7,9 6,,7,0 Correction factors for different R.H. Legend R.H. 8% 6% WT: Pc Ps Pc Ps 7/ C 0,9 0,90 8/ C 0,9 0,88 0/ C /7 C WT = Water temperature Pc = Cooling total emission Ps = Cooling sensible emission = Water flow = Water pressure drop Speed = Fan speed = High speed = Medium speed = Low speed Qv = Air flow 0

version Cooling emission of row coil Entering air temperature: C R. H.: 0% Available pressure: 0 Pa WT: 7/ C WT: 8/ C WT: 0/ C WT: /7 C Mod. Speed Qv m /h 9 0 70 0 7 00 870 76 66 80 0 0 90 7 0 980 70 60 000,97,77,,7,,96,9,0,6,8 6,7,98,,77,00 0, 9,7 8, 7,6,77,6,8,9,7,6,9,,08,7,,6,88,7,7,07 8,7 7,6 6,77,6, 0 77 90 6 8 7 690 6 6 078 08 97 80 688 79 69 67 8 99,, 0, 8,7 7,7 8, 0,7 6,,8 8,,7,, 9,6 7,0 6,7, 9,, 9,,60,,9,98,8,6,8,,7,87,0,,77,7,9 8,99 8,0 7,8 6,,0,,06,8,6,,7,,9,9,,9,6,,,89 7,96 7, 6,0,9,07 7 8 77 9 79 66 60 6 9 96 90 8 77 60 6 8 86 09 866, 9,8 8, 6,8 6,0 0,, 0, 7,,,, 9,6 7,,,0 8,,, 7,,9,80,6,6,6,7,87,6,,,,9,7,0,8 6,7 6,,7,70,70,9,80,6,,,7,87,60,0,0,,9,7,0,6 6,7 6,,7,69,7 0 79 6 9 0 0 6 7 678 6 6 068 97 808 66 6,,7,7,9, 7,9,,9 9,9 8, 7, 6,7,6,,, 0,7 8,8 6,,,8,8,,0 0,9,,0,8,6,8,,9,8,0,8,07,,9,0,6,8,8,,0 0,9,,0,8,6,8,,9,8,0,8,07,,9,0,6 7 0 96 76 6 0 8 8 06 78 87 78 680 68 0,,0,,0,8 9,8 7,6 6,,,,,9,,,6 7, 6,0,7,, Correction factors for different R.H. Legend R.H. 8% 6% WT: Pc Ps Pc Ps 7/ C 0,9 0,90 8/ C 0,9 0,88 0/ C /7 C WT = Water temperature Pc = Cooling total emission Ps = Cooling sensible emission = Water flow = Water pressure drop Speed = Fan speed = High speed = Medium speed = Low speed Qv = Air flow

version 9 0 70 0 7 00 870 76 66 80 0 0 90 7 0 980 70 60 000 9 0 70 0 7 00 870 76 66 80 0 0 90 7 0 980 70 60 000 6,89 6,7,69,09,7, 9,9 8,99 8,0 7,6,7,90,6,7 9,6,70,6 0,09 6,69,90 9 8 89 7 0 98 86 77 689 6 8 9 987 80 9 77 09 7,,9 9,,9,9 6, 0,6 7,,9,,,8 7,9,6 9,,9, 7,, 7,7,8,89,7,9,6 8,76 7,6 6,89 6,,0,0,0 0, 8,78 7,9 8,9 7,,,78 9,90 76 6 7 66 9 8 7 0 980 880 7 68 66 89 0 099 8 7,6,, 0, 8,9 6,9,,0 8,9 7,,,9, 8,7 6, 6,0,6,0 7,9,0,8,,7,,08 7, 6,6,8,,66 0,7 9,6 8,66 7, 6,09 6,0,6,0 0,8 8,8 86 6 9 8 6 68 0 8 0 87 89 7 60 77 9 0 9 7,,6 9, 7,8 6,8,8 9,9 8, 6,8,,6 0, 8,7 6,6,6,0 0, 8, 6,0,8,68,0,0,7, 6,08,9,79,8,8 8, 7,89 7,09 6,0,00,09,99 0,68 8,89 6,89 6 9 6 7 68 9 7 678 609 0 6 0 98 76 9 9, 8, 6,8,,9 9, 7,,9,8,9 8, 7, 6,,7, 8, 7,,9,,7,,90,9,,89 7,00 6,0,0,9,9 9,6 9, 8,9 7,0,7,,8,9 0, 7,90 7 67 600 6 97 0 09 96 8 7 68 69 08 06 986 60 80 79 8,0 6, 9,9,, 0,, 6,, 7, 6,8, 7, 0,8, 8,, 6, 8,9,8,,6,8,,,67,9,6,98,6 7,80 7,9 6,6,69,66 88 87 0 976 80 766 68 6 70 9 979 80 9,, 0,9 7,0,9 8,,0 8,,9,,6, 9,, 0, 7,7 7, 6,,60,7,97,6 0,0 8,86 7,86 7, 6,0,,8 9,9 6,66,, 7,67, 667 6 8 960 86 76 676 7 9 06 86 9 08 8 0 6 7,,8,9 9,6 8, 6,7,7 9,, 9,0 0,8 8,8,, 7,8 7,,,0 7,7 0,9,9,8,86,,98 9,97 8,9 7,7 6,8 6,06,,,08 9, 7,6 0,0 8,6 6,,7 0,0 7 8 70 87 79 66 87 9 067 9 8 67 7 600 67 89, 9, 7,7 6,, 0,,0 9,0,,,,0 9,8 7,,0,7 0, 6,, 7,0,06,6,,6,8 8,8 7,0 6,,80,6, 0, 9,8 7,99 6,9 7,9,76,9, 8,8 00 90 79 68 6 99 96 90 806 687 8 87 99 99 79 8, 7,,8,7,,9 7,,,6 9, 0,0 9, 7,,,8 7,9,, 8,6,,,8,9,0,78 6,96 6,0,9,78, 9, 8,60 7,68 6,,,6,90, 9, 7, 7 8 9 9 9 99 7 6 6 78 70 660 6 8 8 0 98 8 6 6,0,,,,9 6,,6 0, 8, 6,7 7, 6,,,9,7,7 0,8 8,6 6,,8,7,7,87,,7 7,9 6,8 6,,,8 0,0 9,9 8,8 7, 6,09 6,0,8, 0,8 8,7 86 7 66 90 67 76 0 9 87 807 708 9 07 80 8 86 6,,7 8,,7,7 7,6,6,9 6,0 9,0,9 8,8, 7,,9 6,7 7,9 8, 7, 6,7,86,,,79,7 6,,,98,,9 8,0 8,0 7,7 6,09,9,,0 0,6 8,79 6,7 66 60 0 79 09 9 87 78 67 6 8 08 89 7 070 88 8,,9,7 0, 8,9 0, 8,,, 0,, 0, 6,, 8, 9,6, 6,7 9,0,7 Qv Qv m /h m /h Speed Speed WT: 70/60 C WT: 70/60 C WT: 60/0 C WT: 60/0 C WT: / C WT: / C WT: 0/0 C WT: 0/0 C WT: 0/ C WT: 0/ C WT: /0 C WT: /0 C Heating emission of row coil Heating emission of row coil Entering air temperature: 0 C Available pressure: 0 Pa Entering air temperature: 0 C Available pressure: 0 Pa = High speed = Medium speed = Low speed Legend WT = Water temperature = Emission = Water flow = Water pressure drop Qv = Air flow Speed = Fan speed Mod. Mod.

version Mod. Speed Qv m /h 9 0 70 0 7 00 870 76 66 80 0 0 90 7 0 980 70 60 000,77,,,96,79,96,,90,8,09 7,68 7, 6,7,9,08,9, 0,07 8,7 7, 0 79 0 7 8 660 6 78 7 06 96 866 7 6,6 0, 7,,6,,7, 9,6 8, 7,0 8, 6,8,, 8,7,0,8 8, 9,6 0,6 Heating emission of row additional coil Entering air temperature: 0 C Available pressure: 0 Pa WT: 80/70 C WT: 7/6 C WT: 70/60 C WT: 6/ C WT: 60/0 C WT: / C,0,0,9,68,,7,79,,0,68 6,9 6,6 6,06,7,9 0,78 0,0 9, 7,88 6, 9 7 0 7 6 79 7 7 9 70 6 9 97 86 78 678 9, 7,,,,, 9, 8, 6,9,8,,, 9,7 7,,0 8,6,,0 7,,0,8,6,9,,76,,9,8,8 6,6,89,0,79,08 9,6 8,9 8, 7,0,76 6 0 9 09 66 7 08 8 0 07 6 89 770 700 60 9,8,,0 0, 9, 9, 7,7 6,7,7,8,7,7 0,0 8,0 6,0 6,6,0 7,0 0,8,,67,,9,0,98,7,7,,,87,0,8,7,9,9 8,7 7,88 7,6 6,,08 0 6 97 80 70 9 0 9 70 7 6 07 6 08 79 678 66 7,8, 9,7 8, 7, 7, 6,,,,9 0, 9, 8,0 6,,9 9,,9,8 6,8,7,0,6,98,8,7,7,9,9,69,7,6,,08,6,09 7, 6,8 6,9,6,8 97 86 70 6 7 07 7 99 8 66 69 86 6 77 9,9 8,9 7,6 6,,8,8,7,,,0 7,9 7, 6,,0,8,0 0, 7,0, 9,,9,8,66,,,97,66,6,,06,89,7,,0,9 6,7,7,,,70 66 6 6 9 9 77 9 6 9 8 88 8 7, 6,6,6,8,,,,0,6,,8,,6,7,8 7,,,7 9,8 6,9 Mod. Speed Qv m /h 9 0 70 0 7 00 870 76 66 80 0 0 90 7,9,9,88,,9 7,60 6,7 6,,6,0 0,6 9,79 8,9 7,79 6, 9 69 0 8 6 79 9 78 88 8 767 670 6 6,0,,,7, 0, 6,,8, 9,6 6,,,9 8, 0, Heating emission of row additional coil Entering air temperature: 0 C Available pressure: 0 Pa WT: 6/ C WT: 60/0 C WT: / C WT: 0/0 C WT: /0 C WT: / C,96,70,,0,8 6,8,8,,8, 8,90 8,9 7,7 6,76,66 8 88 6 66 0 8 7 76 70 66 8 87,7,,,9,6,8,7 0,8 9,0 7, 6,, 8,, 6,,,,8,,9,,9,0,06,68 7, 7,9 6,,7,79 86 68 9 06 78 87 9 7 67 68 6 9,,,6,,9,9 9, 8, 6,8,7 7,,, 6,7,,69,,9,07,9,,0,67,,00 6,6,87,,68,9 7 97 78 67 89 8 8 0 0 60 0 7,,,8,, 8, 6,7,7,8,0 9, 7,9,,8 8,6,7,,7,97,8,7,78,,,8,77,0,00,8,67 7 9 7 7 6 9 7 86 99 96 860 7 6 7,9 7,0,8,9, 6,, 8,,,6 60,8,8 7,0 7,0 6,9,06,9,7,9,9,9,0,8,7,,77,6,,6,06 78 66 7 8 00 66 00 0 9 7 6,,,,0 0,9,,,7,,6,, 9,7 7,7,6 Legend WT = Water temperature = Emission = Water flow = Water pressure drop Qv = Air flow Speed = Fan speed = High speed = Medium speed = Low speed

version Air flow (m /h) depending on speed and requested available pressure Mod. Speed Available pressure (Pa) 0 0 0 0 0 0 60 70 80 9 0 70 0 7 00 870 76 66 80 0 0 90 7 0 980 70 60 000 6 07 7 78 0 99 8 70 60 7 80 90 68 0 900 60 0 98 0 7 0 0 90 780 66 60 9 0 070 860 60 00 80 8 00 97 9 6 0 60 900 70 60 70 70 00 80 600 90 70 0 60 9 9 7 6 0 8 680 7 70 0 00 0 960 760 0 8 60 0 9 0 8 8 78 78 60 0 0 70 0 00 890 700 0 70 0 80 60 900 00 7 80 7 70 7 80 80 0 00 90 80 60 60 600 0 9 090 870 97 87 60 0 0 70 9 860 70 70 00 9 0 00 000 80 0 8 0 7 0 60 8 780 60 00 0 7 0 00 90 70 Power absorption (Watt) depending on air flow and available pressure Mod. Speed Available pressure (Pa) 0 0 0 0 0 0 60 70 80 76 6 6 0 0 07 9 88 7 6 97 6 7 9 9 6 7 6 0 7 7 0 9 8 7 6 8 9 8 08 8 6 7 6 9 0 89 8 67 7 7 9 8 97 7 7 60 9 8 9 0 97 86 80 6 0 88 7 0 87 6 70 8 8 6 0 9 8 76 6 6 8 06 8 6 90 77 7 6 68 6 6 9 9 0 90 79 7 0 0 0 8 0 79 68 8 7 6 8 97 86 7 69 96 77 9 70 8 9 6 6 09 9 8 70 6 08 9 7 8 6 8 0 60 0 0 0 86 76 7 9 0 8 68 7 9 08

version 0,97 0,97 0,96 0,96 0,9 0,98 0,97 0,96 0,96 0,96 0,98 0,98 0,98 0,97 0,96 0,98 0,98 0,98 0,99 0,99 0,9 0,9 0,9 0,9 0,89 0,9 0,9 0,9 0,9 0,9 0,97 0,96 0,96 0,9 0,9 0,9 0,96 0,96 0,98 0,99 0,9 0,89 0,87 0,8 0,8 0,9 0,9 0,89 0,87 0,88 0,9 0,9 0,9 0,9 0,89 0,9 0,9 0,9 0,96 0,98 0,86 0,8 0,8 0,78 0,7 0,89 0,87 0,8 0,8 0,8 0,9 0,9 0,9 0,89 0,8 0,90 0,9 0,9 0,9 0,96 0,8 0,78 0,7 0,70 0,6 0,8 0,8 0,8 0,78 0,77 0,88 0,87 0,87 0,8 0,80 0,87 0,88 0,89 0,9 0,9 0,7 0,7 0,66 0,6 0, 0,8 0,79 0,76 0,7 0,70 0,8 0,8 0,8 0,80 0,76 0,8 0,8 0,86 0,89 0,9 0,66 0,6 0,7 0,0 0,76 0,7 0,7 0,66 0,6 0,80 0,78 0,77 0,7 0,69 0,80 0,80 0,8 0,8 0,90 0,6 0, 0, 0,70 0,67 0,6 0,7 0,7 0,7 0,68 0,6 0,76 0,76 0,78 0,80 0,8 0,96 0,96 0,9 0,9 0,9 0,97 0,96 0,9 0,9 0,9 0,98 0,98 0,98 0,97 0,9 0,97 0,97 0,98 0,98 0,99 0,9 0,9 0,90 0,88 0,86 0,9 0,9 0,9 0,89 0,89 0,9 0,9 0,9 0,9 0,90 0,9 0,9 0,9 0,97 0,98 0,88 0,86 0,8 0,8 0,77 0,90 0,88 0,86 0,8 0,8 0,9 0,9 0,9 0,89 0,86 0,9 0,9 0,9 0,9 0,97 0,8 0,80 0,77 0,7 0,68 0,86 0,8 0,8 0,78 0,78 0,89 0,88 0,88 0,8 0,80 0,87 0,88 0,89 0,9 0,9 0,76 0,7 0,69 0,6 0,7 0,8 0,79 0,77 0,7 0,7 0,8 0,8 0,8 0,80 0,7 0,8 0,8 0,86 0,89 0,9 0,68 0,6 0,60 0, 0,7 0,77 0,7 0,7 0,66 0,6 0,80 0,79 0,78 0,7 0,70 0,79 0,80 0,8 0,8 0,9 0,60 0, 0,0 0, 0,7 0,68 0,6 0,9 0,7 0,7 0,7 0,7 0,69 0,6 0,7 0,7 0,78 0,80 0,87 0,9 0, 0,8 0,6 0,6 0,7 0,69 0,68 0,66 0,6 0,6 0,70 0,70 0,7 0,7 0,8 0 0 0 0 0 0 60 70 80 0 0 0 0 0 0 60 70 80 Speed Speed Available pressure (Pa) Available pressure (Pa) Mod. Mod. Correction factors for Total cooling emission Correction factors for Sensible cooling emission and Heating emission

version Operation limits Highest water inlet temperature... + 8 C Lowest water inlet temperature... + C for entering water temperatures below + C, contact SABIANA technical department Highest working pressure... 000 (0 bars) Water flow limits for row coil () Model Lowest 00 0 00 00 Highest 70 000 000 000 Water flow limits for row coil () Model Lowest 0 0 00 00 Highest 000 00 0 00 Water flow limits for row additional coil () Model Lowest 0 00 00 00 Highest 0 00 70 70 Water flow limits for row additional coil () Model Lowest 00 00 00 Highest 0 00 70 Motor electrical data (max. absorption) Model 0/ 0Hz W A 76 0 7 6 0, 0,6 0,8, 6

version Water pressure drop Dp - 0 0 row coil row coil Dp - 0 0 0 0 0 0 0 9 8 7 6 0 9 8 7 6 00 00 00 00 600 800 000 00 000 Water flow () The water pressure drop figures refer to a mean water temperature of 0 C; for different temperatures, multiply the pressure drop figures by the correction factors K. 00 00 00 00 600 800 000 00 000 Water flow () C 0 0 0 0 60 70 80 K 0,9 0,90 0,86 0,8 0,78 0,7 0,70 Dp - 60 0 0 row additional coil row additional coil Dp - 60 0 0 0 0 0 0 0 9 8 7 6 0 9 8 7 6 0 60 80 00 00 00 00 600 800 000 Water flow () 0 60 80 00 00 00 00 600 800 000 Water flow () The water pressure drop figures refer to a mean water temperature of 6 C; for different temperatures, multiply the pressure drop figures by the correction factors K. C 0 0 60 70 80 K,,08,0 0,96 0,90 7

Accessories for version VBP main coil way valve Control valve kit: way valve, ON-OFF, with electric motor and mounting kit with micrometric lockshield valve. Dimensions ± 0 mm Mod. Dimensions (mm) Valve A B C D E DN (Ø) Kvs 0 0 8 8 0 0 90 90 8 8 90 90 90 90 0 0 0 0 0 0 0 / / / /,6,, Micrometric lockshield valve DN (Ø) Kvs 0 / F / F / F / F, FITTED 90666H 90607H 90607H 90690H NOT FITTED 906660H 90607H 90607H 906900H VBA additional coil way valve Control valve kit: way valve, ON-OFF, with electric motor and mounting kit with micrometric lockshield valve. Dimensions ± 0 mm Mod. Dimensions (mm) Valve A B C D DN (Ø) Kvs 0 9 00 00 0 0 0 0 / / /,6,6,6 Micrometric lockshield valve DN (Ø) Kvs / F / F / F FITTED 90607H 90607H 90607H NOT FITTED 90607H 90607H 90607H Dp - 0 0 Kvs,6 Kvs Kvs, Kvs, Kvs 0 0 98 7 6 Water flow () 00 00 00 00 600 800 000 000 000 000 8

Accessories for version VS simplified kit for way valve way valve, (ON-OFF) with electric motor and mounting kit. Valve with flat connection without micrometric lockshield valve. Dimensions ± 0 mm Mod. Dimensions (mm) Main Additional Main Additional A A B B 77 77 70 68 70 70 8 8 0 0 0 0 7 9 C 6 DN 0 0 0 Valve Valve (Ø) Kvs FITTED NOT FITTED DN (Ø) Kvs FITTED NOT FITTED /,6 90667H 906670H /, 90608H 90608H /,6 90608H 906080H /, 90608H 90608H / 90690H 90690H V way valve for main and additional coil Control valve kit: way valve, ON-OFF, with electric motor and mounting kit. Dimensions ± 0 mm Dimensions (mm) Main Additional Mod. Main Additional A C D E H 9 80 8 86 6 0 8 8 86 6 76 7 0 0 76 7 0 0 Valve DN (Ø) Kvs 0 0 / / /,7,8,8 FITTED 906076H 906077H 906077H 90690H NOT FITTED 906078H 906079H 906079H 90690H Valve DN (Ø) Kvs /,7 FITTED 906076H NOT FITTED 906078H Dp - 0 Kvs, Kvs,7 Kvs,8 Kvs,6 Kvs 0 0 0 98 7 6 Water flow () 00 00 00 00 600 800 000 000 000 000 9

Accessories for version BEL electric heater PHASE 0V Electric heater with integral: safety thermostat and relay control. Size Watt 00 900 600 000 0 70 00 00 000 00 90666 906660 90669 90666 906660 90669 906667 9066607 906697 90806 BSV extension condensate collection tray to cover valve assembly (for vertical units) 90 606000 00 BSO extension condensate collection tray to cover valve assembly (for horizontal units) Connection side Type LEFT BSO-SX 60600 RIGHT BSO-DX 60600 DRPV-C condensate pump (for vertical units) Type Fitted Not Fitted DRPV-C-M DRPV-C-S 906697 906696 Height Water flow () depending on the length of horizontal flow for vertical flow (m) m 0 m 7,6,6,0, 7,,,7,9 0

Accessories for version DRPO-C fitted condensate pump (for horizontal units) Type DRPO-C 90669 Height Water flow () depending on the length of horizontal flow for vertical flow (m) m 0 m 7,6,6,0, 7,,,7,9 SCR plastic condensate drain pipe with fast connection (allows correct condensate drain) 60600 KAF frontal intake kit Bottom closing panel and filter sliding guides. Size 906907 906907 906907 906907 FRD straight inlet flange Can be used together with GRAG air inlet grid. Made of galvanized steel. Size Type A B C D G FRD - / FRD - S FRD - 8/9 FRD - 8S 669 88 099 9 90 790 990 0 9, 7,, 6 6 6 6 6 6 6 6 90607 90800 90607 908007

Accessories for version FR 90 90 inlet flange Can be used together with GRAP air inlet grid. Made of galvanized steel. Size Type FR90 - / FR90 - S FR90-8/9 FR90-8S A B C D G 669 90 9, 6 88 790 7 6 099 990, 6 9 0, 6 90607 90800 90607 908006 GRAP air inlet grid To be used with FR 90 90 inlet flange. Made of anodized aluminium. Size Type GRAP - / GRAP - /6 GRAP - 7/9 GRAP - S Description Grid 600x0 Grid 800x0 Grid 000x0 Grid 0x0 B 7 77 97 906076 906076 906076 9080 GRAG air inlet grid To be used with FRD straight inlet flange. Made of anodized aluminium. Size Type GRAG - / GRAG - /6 GRAG - 7/9 GRAG - S Description Grid 600x00 Grid 800x00 Grid 000x00 Grid 0x00 B 7 77 97 906076 9060766 9060767 9080 FMD straight outlet flange Made of galvanized steel. Size Type FMD - / FMD - S FMD - 8/9 FMD - 8S A B C D 667 90 8, 88 790 6 79 097 990, 79 7 0, E - - - 8 90667 9069 906678 9069

Accessories for version FM 90 90 outlet flange Made of galvanized steel insulated with polyethylene lining. Size Type FM90 - / FM90 - S FM90-8/9 FM90-8S A B C D 667 90 8, 88 790 6 79 097 990, 79 7 0, E - - - 8 90668 9069 906688 9069 BMA air outlet grid Double louvre grid to be fitted to the duct, to the FMD straight outlet flange or to the FM 90 90 outlet flange. Made of anodized aluminium. Size Type BMA - / BMA - /6 BMA - 7/9 BMA - 8S B 7 77 97 90607 90607 90607 90800 PRC air inlet spigot plenum Made of galvanized steel insulated with polyethylene lining. All the plenums are supplied with spigots for the connection of flexible ducts. Size Type PRC - / PRC - S PRC - 8/9 PRC - 8S A 6 860 07 B 66 60 90 C 8 8 8 8 D 70 7, 60 Spigots N N N N 90666 90800 906668 9080 PMC spigot diffuser Made of galvanized steel insulated with polyethylene lining. All the plenums are supplied with spigots for the connection of flexible ducts. Size Type PMC - / PMC - S PMC - 8/9 PMC - 8S A 6 860 07 B 66 60 90 C 8 8 8 8 D 70 7, 60 Spigots N N N N 90666 9069 906668 9069

Control functions Electrical diagrams are shown on the installation, use and maintenance manual TMO-T-AU-IAQ 9060 TMO-T-IAQ 9060 TT 90607 TMO-DI 90606 TMO-0-SV 90607 TMO-T-AU 90606 TMO-T 90606 CR-T 90660 MO-V 906060 CONTROL OPERATIONS CONTROL IDENTIFICATION ON-OFF switch ON-OFF switch for electric heater Manual speed switch Manual/Automatic speed selection Summer/Winter switch Remote centralized Summer/Winter switch or by an automatic change-over fitted on the water pipe Automatic Summer/Winter switch with neutral zone for pipe installation with valves Room thermostat for fan control (ON-OFF) Room thermostat for valve control ( pipe installation) Room thermostat for valve control ( pipe installation) Simultaneous thermostatic control of the valves and fan Room thermostat for chilled water valve (SUMMER) and electric heater (WINTER) control (in winter only the heater is working) Room thermostat for fan and electric heater control Installation of electronic low temperature CUT-OUT thermostat (TME) Installation of bimetallic low temperature CUT-OUT thermostat (TMM) CONTROL CODES Electronic controls The units can be controlled using the remote controls above; in the standard version, the motor speeds connected to the main terminal block, are: - for sizes, and motor speeds, and are connected while the wires for speeds and are connected to a two-pole support terminal block. - for size motor speeds, and are connected while the wires for speeds and are connected to a two-pole support terminal block.

Wall electronic controls Identification MO-V 906060 ON-OFF switch and speed switch. Without thermostatic control. It allows to control the low temperature cut-out thermostat (TMM). Dimensions: x9x7 mm Identification CR-T 90660 ON-OFF switch. Manual speed switch. Manual Summer/Winter switch. Electronic room thermostat for fan or valve control (ON-OFF). It allows to control the low temperature cut-out thermostat (TMM). It allows to control the chilled water valve (ON-OFF) and the electric heater (BEL) only in case that hot water is not used in winter (otherwise please use TMO-T-IAQ control with on/off switch for the electric heater). Dimensions: x9x7 mm Identification TMO-T 90606 ON-OFF switch. Manual speed switch. Summer/Winter switch. Electronic room thermostat for fan or valve control (ON-OFF). It allows to control the low temperature cut-out thermostat (TME). It allows to control the chilled water valve (ON-OFF) and the electric heater (BEL) only in case that hot water is not used in winter (otherwise please use TMO-T-IAQ control with on/off switch for the electric heater). It allows to control the summer/winter cycle with a centralized and remote switch or with an automatic change-over fitted on the water pipe (for -tube installations only). Dimensions: x9x7 mm Identification TMO-T-AU 90606 ON-OFF switch. Manual or automatic speed switch. Summer/Winter switch. Electronic room thermostat for fan or valve control (ON-OFF). Simultaneus thermostatic control of the valves and fan. It allows to control the low temperature cut-out thermostat (TME). It allows to control the chilled water valve (ON-OFF) and the electric heater (BEL) only in case that hot water is not used in winter (otherwise please use TMO-T-AU-IAQ control with on/off switch for the electric heater). It allows to control the summer/winter cycle with a centralized and remote switch or with an automatic change-over fitted on the water pipe (for -tube installations only). N.B.: with pipe installations and continuous chilled and hot water supply, it allows the automatic summer winter change-over in accordance to the room temperature (- C = Winter, + C = Summer, Neutral Zone C). Dimensions: x9x7 mm

Wall electronic controls Identification TMO-0-SV 90607 The TMO-0-SV control for fan coils with valves, is designed to be installed in a DIN 0 wall box. It is easy to use, it has a big and clear display, and a great precision. The control is supplied integral with the external frame, but it is possible to use frames of the most known brand on the market (BTicino, Vimar, AVE, Gewiss). The highest working electric absorbtion is 00 W. If the fan coil has an higher absorbtion or more units are connected to the same control, the speed switch SEL-CR must be installed (on size the SEL-CR switch must be installed). Manual or automatic speed switch. Manual Summer/Winter switch. Electronic thermostat for valves control (ON-OFF). Simultaneus thermostatic control of the valves and fan. It allows to control the low temperature cut-out thermostat, included with the control. Dimensions: 8x87x8 mm N.B.: with pipe installations and continuous chilled and hot water supply, it allows the automatic summer/ winter change-over in accordance to the room temperature (- C = Winter, + C = Summer, Neutral Zone C). Identification TMO-DI 90606 Dimensions on the wall: x9x7 mm Dimensions in the DIN 0 box: x9x8 mm To be installed on the wall or in the DIN 0 box. Manual or automatic speed switch. Manual or centralized Summer/Winter switch. Electronic thermostat for fan control (ON-OFF). Electronic thermostat for valve control (ON-OFF). Simultaneus thermostatic control of the valves and fan. It allows to control the low temperature cut-out thermostat (TME). It allows to control the chilled water valve (ON-OFF) and the electric heater (BEL) only in case that hot water is not used in winter. It allows to control the fan and the electric heater. It allows to control up to 0 units with SEL-DI speed switch. N.B.: with pipe installations and continuous chilled and hot water supply, it allows the automatic summer/ winter change-over in accordance to the room temperature (- C = Winter, + C = Summer, Neutral Zone C). Identification TT 90607 pipes units only. ON-OFF switch. speed switch. Manual Summer/Winter switch. Thermostatic control on the fan. Thermostatic control on the valve and continuous fan operation. Simultaneous thermostatic control of the valve and fan. Cannot be used with speed switch (master-slave). Dimensions: 8x7x mm 6

Wall electronic controls for units with electric heater Identification TMO-T-IAQ 9060 ON-OFF switch. Manual speed switch. Summer/Winter switch. Electric heater ON-OFF switch. Electronic room thermostat for fan or valve control (ON-OFF). It allows to control the low temperature cut-out thermostat (TME). It allows to control the chilled water valve (ON-OFF) and the electric heater (BEL) only in case that hot water is not used in winter. It allows to control the summer/winter cycle with a centralized and remote switch or with an automatic change-over fitted on the water pipe (for -tube installations only). Dimensions: x9x7 mm Identification TMO-T-AU-IAQ 9060 ON-OFF switch. Manual or automatic speed switch. Summer/Winter switch. Electric heater ON-OFF switch. Electronic room thermostat for fan or valve control (ON-OFF). Simultaneus thermostatic control on the valves and fan. It allows to control the low temperature cut-out thermostat (TME). It allows to control the chilled water valve (ON-OFF) and the electric heater (BEL) only in case that hot water is not used in winter. It allows to control the summer/winter cycle with a centralized and remote switch or with an automatic change-over fitted on the water pipe (for -tube installations only). N.B.: with pipe installations and continuous chilled and hot water supply, it allows the automatic summer/ winter change-over in accordance to the room temperature (- C = Winter, + C = Summer, Neutral Zone C). Dimensions: x9x7 mm Identification TMO-DI 90606 Dimensions on the wall: x9x7 mm Dimensions in the DIN 0 box: x9x8 mm To be installed on the wall or in the DIN 0 box. Manual or automatic speed switch. Manual or centralized Summer/Winter switch. Electronic thermostat for fan control (ON-OFF). Electronic thermostat for valve control (ON-OFF). Simultaneus thermostatic control of the valves and fan. It allows to control the low temperature cut-out thermostat (TME). It allows to control the chilled water valve (ON-OFF) and the electric heater (BEL) only in case that hot water is not used in winter. It allows to control the fan and the electric heater. It allows to control up to 0 units with SEL-DI speed switch. N.B.: with pipe installations and continuous chilled and hot water supply, it allows the automatic summer/ winter change-over in accordance to the room temperature (- C = Winter, + C = Summer, Neutral Zone C). 7

Speed switches Identification SEL-CR 9066 7 8 9 0 Speed switch (Slave). It allows to control up to 8 units with only one centralized wall control ( speed switch for each unit). For controls CR-T, TMO-T, TMO-T-AU and TMO-0-SV. 6 Identification SEL-DI 90609 Speed switch (Slave) for TMO-DI It allows to control up to 0 units with only one TMO-DI centralized wall control. 8

Wall electronic control accessories for version TME low temperature cut-out thermostat To be fitted between the coil fins; when connecting the control, the TME probe cable must be separated from the power supply wires. To be used with the following controls: TMO-T, TMO-T-AU, TMO-DI and corresponding IAQ controls. It stops the fan when the water temperature is lower than 8 C and it starts the fan when is higher than C. 009 TMM low temperature cut-out thermostat To be installed in contact with the hot water circuit. To eliminate cold air blow. Installed by the installing engineer. To be used with the MO-V and CR-T controls. For units working on heating only. It stops the fan when the water temperature is lower than 0 C and it starts the fan when is higher than 8 C. RED BROWN 9008 Change-Over CH - Automatic summer/winter switch to be installed in contact with the water circuit. For -tube installations only (not to be used with way valve). To be used with the following controls: TMO-T, TMO-T-AU, TMO-DI. RED BLACK 9009 9

FreeSabiana wireless control system FreeSabiana Free Sabiana is an innovative, fully wireless, electronic system for use with fan coil units, based on radio communication. This technology provides installation flexibility and a more accurate measurement of the room temperature. The probe can be moved until the most suitable position is found, without the worry of changes in the room layout and of its furniture and also without mounting it on a wall. If a new fan coil unit is added, no electrical wiring for the control system is required: just define the control unit and the probe which regulates it. The improved measurement accuracy is a result of the possibility to position the probe near the user location: this enables to keep the temperature exactly at the required value with more energy savings compared with a traditional measurement system. Transmission is based on communication protocol IEE80.., the most suitable way to transmit a relatively low amount of information with very low consumption and high reliability. The system has been certified by a leading independent body, officially recognized by the EU authorities and its sale has been authorized in all the EU and EFTA countries. Main components Free Sabiana includes main components: A remote control which features a button panel and LCD display and can be wall-mounted or positioned on a dedicated table support. It enables the control of all the operating variables of the fan coil units in different configurations. The control is battery powered. The temperature and the operating speed of the fan coil unit are set with two large buttons featuring user friendly graphics. Description Remote control Identification Free-Com 90607 Control unit with support A power unit to be installed on the fan coil (fan coil interface). It controls the fan and the valves of the fan coil. The power unit is connected to the electric supply. The power unit receives the information required to control the fan coil both from the remote control and locally, such as the temperature of the coil. Description Power unit fitted on the unit Power unit not fitted on the unit Identification Free-Upm 90607 Free-Ups 906070 Power unit A room temperature probe, which can be wallmounted or positioned on a dedicated table support. It is a battery powered device, able to measure the air temperature in the spot where it is positioned, generating temperature information which is communicated to the other devices. Description Temperature probe Identification Free-Sen 90607 0 Probe with support

FreeSabiana wireless control system Main features of the remote control The control enables: Fan coil on/off switching Fan speed selection (high - medium - low - automatic) Summer/winter operation selection Valve on/off Real time clock setting Temperature setting Daily switch on/off setting (timer function) Enable/disable the timer function Activation of the (optional) electrostatic filter Activation of the (optional) electric heater Main information displayed: 7 6 6 7 On-off status Summer operation Winter operation Automatic season change Electric heater Electrostatic filter Room temperature (with decimal accuracy) 8 9 0 Fan operating speed Required/measured temperature Timer Clock Transmission signal Battery level 9 0 8 Main features of the power unit to be installed on the fan coil The power unit controls the fan and the valves of the fan coil. The power unit receives the information required to control such units both from the remote control and locally. It enables the following main actions: Fan on/off at a set speed Fan speed change (fan on/off) Water valve/s on/off ( valve for tube system - valves for tube system) Fan speed change operating the water valve/s Control of the electric heater as main heating unit or as integration to the battery supplied with hot water Control of the operation of the electrostatic filter (in parallel to the fan) Management of the dead zone function for -tube systems Available functional inputs: Consent for remote on/off Consent for remote Summer/Winter switch (centralized) Consent for the activation of the Energy Saving function with setting change Minimum probe Probe for season change Main features of the temperature probe This device is able to measure the temperature of the air in the spot where it is positioned and to transmit it by means of radio communication to the other devices in the system. It is battery powered and can be freely positioned in the area to be air-conditioned. Display: Measured environment temperature Transmission signal Clock Battery status

Controls and units MB version All the units can be supplied with a wide range of controls, which allows managing one single unit or several units by using the Modbus RTU - RS 8 communication protocol. Units can be managed according to the Master/Slave logic (up to 0 units) or by supervisory components. The system consists in a MB board and a series of controls, such as the T-MB wall control, the RT0 infra-red remote control, the PSM-DI multifunction control and the Sabianet supervisory program. MB electronic board Description MB electronic board fitted on the unit MB electronic board supplied with separate packaging Identification MB-M 9066 MB-S 9066 The MB electronic board, to be mounted on the fan coil internal unit, is set to carry out different functions and adjustment modes, in order to meet the installation requirements. These modes are selected by setting the configuration dip switches on the board. / pipe system. Fan ON/OFF thermostatic control. Valve ON/OFF thermostatic control and continuous ventilation. Valve and simultaneous ventilation ON/OFF thermostatic control. Fan operation control depending on the coil temperature (cut-out T probe fitted), which can be activated only in heating mode or heating and cooling mode. Automatic switch of the operating mode by means of T water probe (optional) applied on the pipe system. Seasonal switch by means of remote contact. ON/OFF of the fan coil by means of the remote contact (window or clock contact). Electric heater control. By activating the cut-out T probe function, the fan is stopped in winter when the coil temperature is lower than C and started when the temperature reaches 6 C. In summer mode, the fan stops when the temperature inside the coil exceeds C and starts when it drops below 8 C. The following connections are located on the power board: Receiver for infra-red remote control. T-MB wall mounted control. RS 8 serial connection to manage several fan coils in Master/Slave configuration or to create a supervisory network.

Controls and units MB version T-MB wall control Wall control (to be used with MB board only) Description Identification T-MB 9066E Wall control with display that allows controlling one or more units in Master/ Slave mode. The control is equipped with internal sensor to detect the room temperature, which can be defined as a priority compared to the return air sensor on the fan coil. The T-MB control features the following functions: Switch the appliance ON and OFF. Temperature set. Modify the set point (when used as a +/- variation of the set point configured from Sabianet supervisory program or PSM-DI). Set the fan speed (low, medium, high or autofan). Set the operation mode (fan only, cooling, heating; auto for pipe systems with mode selection depending on the air temperature). Time setting. Weekly ON/OFF program. Display and change of the fan coil operation parameters. RT0 infra-red remote control Description Identification RT0 infra-red remote control with receiver supplied with separate packaging (to be used with MB board only) RT0 infra-red remote control supplied with separate packaging (to be used with MB board only) Receiver for RT0 infra-red remote control supplied with separate packaging (to be used with MB board only) RS-RT0 90667 RT0 00 RS 90668 The infra-red remote control allows setting by a remote position the fan coil operation parameters. The RT0 infra-red remote control features the following functions: Switch the appliance ON and OFF. Temperature set. Set the fan speed (low, medium, high or autofan). Set the operation mode (fan only, cooling, heating; auto for pipe systems with mode selection depending on the air temperature). Time setting. hours ON/OFF program. Installation example with infra-red remote control

Controls and units MB version A group of units with MB electronic board can be connected via a serial link and can consequently be managed at the same time by just one T-MB wall control or RT0 infra-red remote control. Using the special jumper present on the MB board, one unit must be configured as the master, and all the others as slaves. It is clear that the remote control must be pointed at the receiver on the master unit. To avoid problems, it is recommended to install and connect the receiver only on the master unit. With T-MB wall control One control for each unit (Maximum length of the connection cable = 0 m) One control for more units (0 units max.) (Maximum total length of the connection cable = 800 m) With RT0 infra-red remote control One control for each unit One control for more units (0 units max.) (Maximum total length of the connection cable = 800 m) T accessory for units with MB electronic board Identification T 900 The T sensor can be combined with MB boards to be placed on the water supply pipe upstream way valves (not to be used with way valve). The T sensor must be used as described below: - Change-Over for -pipe system for the automatic switch of the operating mode. If water temperature is lower than 0 C, cooling mode is set; on the other hand, if water temperature exceeds 0 C, heating mode is set. - It can be used on units with electric heater and hot water supply. The T priority probe activates the electric heater or water valve, depending on the water temperature detected. If water temperature exceeds C, the water valve ON-OFF control is activated; on the other hand, if water temperature is lower than 0 C, the electric heater is activated.

Controls and units MB version PSM-DI multifunction control panel Description Multifunction control panel (to be used with MB board only) Identification PSM-DI 09 Another option available for the serial communication between the units is the possibility to connect up to 60 units in series and manage them with just one wall mounted PSM-DI controller. The wall mounted controller can be used to set the operating mode for each individual unit connected, display the operating conditions of each individual unit, and set the ON/OFF time sets for each day of the week (the program can be set for all the units and for a maximum of two groups of units). If more than 60 units need to be connected, two or more controllers must be used. Each unit must have a MB board. The PSM-DI control is used to manage a series of fan coils, up to a maximum of 60 units (the maximum length of the RS 8 connection cable must not exceed 800 m), from one single control point. The PSM-DI control communicates via a serial line with all the units connected, with the possibility of controlling them all together or individually. In fact, the unique address of each individual fan coil means that all the units can be called at the same time, or the individual unit called, to perform the following functions: - display the current operating mode, the fan speed, the set point; - display the room temperature measured on the individual unit; - turn all the units ON and OFF at the same time or alternatively each unit individually; - change the operating mode (fan only, heating, cooling, automatic changeover); - change the set point; - modify the values and operation parameters of the fan speed. Each function can then be sent to all the units connected, or alternatively to each individual unit. Different set points or operating modes can be set for each individual unit. The PSM-DI panel can also be used for the time management of the units over the week. Four ON times and four OFF times can be set on the units for each day of the week. A different Temperature set that will be considered as Operation set for all connected appliances, can be set for each event. If the Temperature set is not entered for the individual event, it must be set during programming for each individual unit or for the entire network. Units without receiver or with receiver can be connected within the network: the former can receive instructions only from the PSM-DI wall mounted panel; while the latter can receive information from both the wall mounted panel (PSM-DI) and infra-red remote control. Use the infra-red remote control to force ON mode of the individual unit, if ON/OFF daily time programming has been set. The unit will regain the settings from the PSM-DI panel during execution of successive start-up program. The PSM-DI panel cannot be used together with the Sabianet management program (see next page). Note: set the configuration Dip Switches of each fan coil as illustrated in the remote control use manual, based on the required solutions. Note: the RS 8 network s overall length must not exceed 700/800 metres.

Management system for a network of fan coils Sabianet program for managing a network of Sabiana MB fan coils Description Hardware/software supervisory system (to be used with MB board only) Identification Sabianet 90798 Sabianet is a centralised control system for networks of Sabiana MB fan coils, based on software that runs on LINUX. The Sabianet software offers a practical and economical solution for managing the units, with the simple click of the mouse. The main characteristics include simplicity of use, an extremely complete and functional weekly program, and the possibility to access the historical operating data for each individual unit connected. The program exploits all the potential of our units with remote controls, representing an addition to the latter. The Sabianet program is a control tool that can be used as a replacement for the remote control, or in parallel, however the settings made using Sabianet can have priority over those made using the remote control. The program can be used to: - Create uniform groups (groups of units on individual floors, in offices or rooms). - Save weekly programs configured for different types of operation (summer, winter, mid seasons, closing periods etc.); these can then be recalled and activated with a simple click of the mouse. Weekly on/off cycles can be set for individual units or groups of units. - Set the operating conditions for each individual unit or groups of units (operating mode, fan speed, temperature setting). - Set the set point limits for each individual unit or groups of units. - Switch each individual unit or groups of units ON or OFF. The main program screen can display and interact with the entire network of units. An individual unit, a group of units or the entire network can be called so as to make modifications to the operating mode and the set point. The user can then check the operating status of each individual unit, read the room temperature, the coil temperature and the operating status of the condensate drain pump or any alarms. MONITORING Screen 6

Management system for a network of fan coils Displaying a unit The MONITORING Screen shows the units that are connected to the network and scanned by the program. The icon of the terminal unit provides the following information: - Unit name ( C000000) - Set temperature ( TSET ) - Room temperature ( TA ) - Unit status: ON or OFF - Mode: Summer Auto Winter Fan only - Fan speed: Low High Medium AutoFan The Weekly Program can be used to set the unit operating parameters for each day of the week. Up to 0 different weekly programs can be set. EVENT MANAGEMENT Screen Time bands are available for each day of the week. The time and the type of operation to be performed by the unit can be set for each band. The time and the operating parameters can then be displayed before being sent to the unit and implemented. 7

Management system for a network of fan coils PC Sabianet Software Power input Outputs for system Power input Outputs for system Power input Outputs for system Connection of a network with MB electronic board unit unit 60 units max. ( * ) unit RS 8 MC Jumper to be closed. End of network. ( * ) In the event of more than 60 units, add one or more Router-S (see below). USB-RS 8 CONVERTER SABIANET RS 8 serial connection cable Shielded cable to be used: Belden 98, RS-8, xx AWG SFTP, 0 Ohm PSM-DI and Sabianet electronic boards for HPO units Identification SIOS 09 SIOS is a board equipped with 8 relays with potential free contact to control the activation or deactivation of remote electric utilities. Moreover, the board has 8 digital inlets to display the actuators or external consents, such as motor or other. The SIOS boards can be connected: - inside a network managed by Sabianet; - to a PSM-DI panel (one SIOS for each PSM-DI panel). Identification Router-S 090 The Router-S is an electronic board that: - allows creating networks with more than 60 units (minimum Router-S are required) or to divide the network (per floor, building, etc.); - it allows creating a Master/Slave sub-network to be controlled as an indipendent group. The Router-S can be used only inside a network managed by Sabianet. The number of Router-S to be used is: - up to 60 units: no Router-S - from 6 to 0 units: Router-S - every 60 subsequent units: additional Router-S 8