Table of Contents. 1. Mounting Tips... 2

Similar documents
Reflective Optical Beam Smoke Detector User Guide

BL 200 Strobes. Page F.01U A1.en/ 6/2/2004 ST / PMF1 / zab

Fireray 2000 Linear Smoke Detector

PRODUCT INFORMATION. Sounder SG 200. BDL F.01U A3.en / ST FIR/ PRM1 / zab. Page 1 of 10

PRODUCT INFORMATION. GLT - Non-Automatic Fire Detector Series 120

Line Smoke Detector LRMX

Manual call point SM 210 LSN RW

TITLE SLIDE. FIRERAY2000 EExd OPTICAL BEAM SMOKE DETECTOR. Doc. No: Copyright Fire Fighting Enterprises Ltd.

Fireray Application and. Installation Guide FEATURES. Range metres. 12V to 24V dc operation. Selectable alarm thresholds

Motorised Infrared Optical Beam Smoke Detector. User Guide

Manual call points DM 210 LSN / SM 210 LSN

IMPORTANT. PLEASE NOTE: The infrared beam path MUST be kept clear of obstructions at all times!

Motorised Infrared Optical Beam Smoke Detector. User Guide

TITLE SLIDE FIRERAY50/100R OPTICAL BEAM SMOKE DETECTOR. Doc. No: Copyright Fire Fighting Enterprises Ltd.

C-9105R Conventional Reflective Beam Detector Installation and Operation Manual. (Issue 2.01, February 2006)

FIRERAY 5000 range USER GUIDE

Installation and Operation Manual

Fireray5000-EN. Fire Alarm Systems Fireray5000-EN. Extended monitoring range. Up to 2 detectors per system controller

INFRARED PERIMETRAL BARRIER DOUBLE BEAMS

INFRARED PERIMETRAL BARRIER DOUBLE BEAMS

English. Series. Installation and Use Manual

FCS-320-TM Series Conventional Aspirating Smoke Detectors

Retroreflective sensor with polarization filter

TX7130. Conventional Reflective Beam Detector Installation and Operation Manual. TANDA UK Technology Copyright 2015, All right reserved.

Pioneer-R16 Gas Monitor Operator s Manual

CONFIGURATION OF THE OPTICALS

CAUTIONS ON INSTALLATION

UEZ 2000/1 LSN, UEZ 2000 LSN, Intrusion Control Centers

I-9105R Intelligent Reflective Beam Detector Installation and Operation Manual. The Intelligent Solution CONTENTS

Color Mark Sensor. Sensing gdsa distance Spot diameter e. Possible to switch between vertical or horizontal connection using the M12 rotary connector.

Retroreflective sensor with polarization filter

Operating instructions

DS9370-BEL. Installation Instructions TriTech Ceiling Mount PIR/Microwave Intrusion Detector

INSTALLATION AND MAINTENANCE INSTRUCTIONS 6500R AND 6500RS REFLECTIVE TYPE PROJECTED BEAM SMOKE DETECTOR

Instruction manual. Digital Radar Motion Detector with Infrared Remote Control MWD BF. FEIG ELECTRONIC GmbH Lange Straße Weilburg/Lahn

E3M-V. Mark Sensor. Applications

Apollo Intelligent Auto Aligning Beam Detector. User Guide

INSTALLATION AND MAINTENANCE INSTRUCTIONS 6500R AND 6500RS REFLECTIVE TYPE PROJECTED BEAM SMOKE DETECTOR

1 PRODUCT COMPONENTS This section describes the contents of the product package and the names and functions of

I-9105R Intelligent Reflective Beam Detector Installation and Operation Manual. (Issue 2.03 February 2006)

DUAL OPTIC. Installation manual

OPERATING AND MAINTENANCE MANUAL. for the G30 CARBON DIOXIDE MONITOR

Interface and EOL Modules 8

ANALOX 5001 Carbon Dioxide Monitor. User Manual ANALOX Analox 5001 Carbon Dioxide Monitor User Manual

2 General Application Photoelectric Sensors

Twin Photobeam Detectors Manual

INDEX. Installation recommendation

Laser Distance Sensor Type M Analog-Output

HANDBUCH / MANUAL / MANUEL / MANUALE TopScan-S

MODEL 6200 ANALOGUE ADDRESSABLE OPTICAL BEAM SMOKE DETECTOR

02/11/2015

INDEX. Installation recommendation

FAS-420-TM Aspirating Smoke Detector FAS-420-TM. Operation Guide

LaserGuard2. Laser Collision Avoidance System. Part Number: R1 April 2015 Copyright 2015 Magnetek Material Handling

Product Documentation

FDL241-9 Linear smoke detector Mounting Commissioning

Why choose Fireray? Why use a Beam Smoke Detector? Product Range.

INDICE. Installation recommendation

CM-RQE70 PIR REQUEST TO EXIT DETECTOR

LZR -WIDESCAN OPENING, PRESENCE & SAFETY SENSOR FOR INDUSTRIAL DOORS

D-Tect 2 GJD300 Quad PIR Movement Detector

Table of Contents. Page Quick Set-up Instructions 1. Theory of Operation 2. Specifications 3. TM 1003W Controls and Connections 4

Heat Sensor Cable Alarm Units DT650L / DT950L

GSM RFID VOICE Alarm System

Photobeam 5000 ISC-FPB1-W60QS, ISC-FPB1-W120QS, ISC-FPB1-W200QS. en Installation and Operation Guide

Siemens aspirating smoke detector (ASD) for the addressed FDnet/C-NET detector line or for standalone operation

Microwave/PIR Intrusion Detector with POPIT Interface ZX970

Automatic Self-Adjusting General Purpose Sensor

Range brochure. Beam detection. others look up to.

Xenex Conventional Fire Detection & Alarm System

FCS-320-TM Aspirating Smoke Detector FCS-320-TM FCS-320-TM-R. Operation Guide

Section 1: General Description. Section 2: Features. Section 3: Operation. CM-RQE70 PIR REQUEST TO EXIT DETECTOR Installation Instructions.

Operations Manual GMA 313 CO 2. Gas Monitor for one detection point

INSTALLATION AND MAINTENANCE INSTRUCTIONS NFXI-BEAM AND NFXI-BEAM-T REFLECTED TYPE PROJECTED BEAM SMOKE DETECTOR

COMPACT FLAME CONTROLLER CFC 2000

Photobeam 5000 ISC-FPB1-W60QF, ISC-FPB1-W120QF, ISC-FPB1-W200QF. en Installation and Operation Guide

Operating Manual MS220KA and MSR220KA

KNX module for smoke alarm devices Dual/VdS and Q-Label (Order no )

Signaling Devices. Acoustic Signaling Devices 298. Optical Signaling Devices 309. Bosch Security Systems B.V.

Open-area Smoke Imaging Detection (OSID)

Detailed operating instructions

PHOTOELECTRIC BEAM SENSOR PB- 50HFA-KH PB-100HFA-KH PB-200HFA-KH

D-TECT Introduction. Connecting the Unit. Quick Installation. Multi Beam Alignment & Masking. Mounting the Unit

02/11/2015

PHOTOELECTRIC BEAM SENSOR PR-11BE : OUTDOOR 3.3 to 36ft. (1 to 11m) : INDOOR 3.3 to 49ft. (1 to 15m)

MOBILE CALL GSM Alarm System User s Manual

English. Italiano. Português. Françias. Español

Dräger Polytron Pulsar 2 Open Path Gas Detector

>WIRELESS> ALARM SYSTEM CR200

CM-RQE70A PIR REQUEST TO EXIT DETECTOR

GS100-ATEX. Hazardous Areas Infra-Red Beam PULSE MODULATED ACTIVE INFRA-RED BEAM FOR HAZARDOUS AREAS ZONE 1 OR ZONE 2 GENERAL

Leuze electronic. Dimensioned drawing. Electrical connection. Accessories: 150m ISO 9001

GS100-ATEX. Hazardous Areas Infra-Red Beam PULSE MODULATED ACTIVE INFRA-RED BEAM FOR HAZARDOUS AREAS ZONE 1 OR ZONE 2 GENERAL

INSTALLATION MANUAL. Operating Unit BE 500

PHOTOELECTRIC AMPLIFIER SERIES

RS Pro Infrared Temperature Sensor

D296/D297. Installation Instructions Long-Range Beam Smoke Detectors

HOTSPOT-1000 HOTSPOT Thermographic Surface Temperature Detector. Installation - Operation - Maintenance EN11

COMPACT FLAME CONTROLLER CFC 1000

Operations Manual TS400. Test Station for G450/G460 Gas Detector

Transcription:

Table of Contents 1. Mounting Tips............................................. 2 1.1. Connections and DIP switch settings................................... 3 1.2. Mounting the Fireray 50/100RV........................................ 4 1.3. Mounting the prism reflector.......................................... 4 1.4. Connection.......................................................... 5 2. Start-Up.................................................. 7 2.1. Setting up the detector............................................... 7 2.2. Aligning the detector.................................................. 7 2.3. System test......................................................... 9 3. Tips on Maintenance and Service........................... 9 4. Technical Data............................................. 10 5. Additional Documentation.................................. 10 6. Appendices............................................... 11 6.1. Installation protocol................................................... 11 6.2. Fault diagnosis...................................................... 12 6.3. Notes............................................................... 13 Page 1 of 14

1. Mounting Tips Usually, the detector and the reflector are installed at the same height and oriented towards each other. The relatively broad angle of the IR beam eases adjustment and guarantees reliable long- term stability. The mounting surface for the detector must be firm and vibration-free. Metal supports that can be influenced by heat or cold are not suitable for installation. The detector must be installed such that sunlight and artificial light do not beam directly into the detector s lenses. Normal environmental light conditions have no effect on the IR beam and the evaluation. Mount the reflector on a solid surface at the permissible distance. Ensure that the light beam meets the reflector on the vertical. The reflectors must not be mounted on reflective surfaces such as glass or plain sheet surfaces. Additional reflections lead to malfunctions. For protection against radio interference, use a shielded cable. When you are installing the cable, possible sources of disturbance must be circumvented and the cable must be protected against mechanical damage. A 6 DA mini distributor (product ID 2.798.400.302) is required for wiring. There must be a free visual line between the detector and reflector. The IR light beam must not be blocked by moved objects! 120 mm Detector baseplate Operating mode switch Gimbal bearing Receiver window Knurled screw for horizontal adjustment (on right of detector) Knurled screw for vertical adjustment 210 mm Detector cover Transmitter window Operating indicator LEDs Fig. 1.: Detector side view Page 2 of 14

1.1. Connections and DIP switch settings Mounting slots on off DIP switch Operating mode switch Plug connector 2-pin output for key switch (optional) Fig. 2.: Reverse side of detector with plug connector, operating mode switch and DIP switch DIP switch The DIP switches can be accessed through the round recess in the detector base plate. Table 1.: Functions of the DIP switch settings * Function DIP switch settings 1 2 3 4 50% threshold X X OFF OFF 35% threshold X X OFF ON 25% threshold X X ON OFF 12% threshold X X ON ON (extremely sensitive, only for special applications!) X Alarm relay saves the alarm OFF X X X Automatic reset 5 s after the end of the alarm criterion ON X X X Alarm relay after end of readjustment X OFF X X X Fault relay at end of readjustment, no alarm X ON X X The factory presets are shaded in gray. * The recommended settings for connection to a fire panel are marked with X. Use DIP switches 3 and 4 to set the required alarm threshold. The factory setting is moderate sensitivity (35%) for normal environmental conditions. Select a threshold of 50% in very dirty environments. Use DIP switch 1 to select the «Save alarm» or «Auto Reset» function (recommended setting for connection to fire panel = «Save alarm»). Page 3 of 14

Plug connector The plug connector can be accessed through the oval recess on the detector base plate. Table 2.: Pin assignment of the 8-pin connector (from left to right) PIN number Wire color Function 1 Not assigned 2 blue Alarm relay, center contact (COM) 3 yellow Alarm relay, work contact (NO) 4 red Power supply +10 to +30 V DC 5 black Power supply - 6 green Fault relay, normally closed contact (NC) 7 white Fault relay, center contact (COM) 8 Not assigned 1.2. Mounting the Fireray 50/100RV To make mounting easier, you can remove the detector cover by gently raising the upper and lower edges. The mounting slots (see Fig. 2.), which are positioned at a 90 angle, enable vertical or horizontal mounting of the detector. Locate the four bore holes at the mounting location using the detector base plate. Observe the planning notes and mounting tips! Check the plug connector and the DIP switch settings (see Section 1.1.). Secure the detector using four screws. Refit the detector cover. If a key switch is required, a two-wire cable should be routed from the detector to the desired location during installation. 1.3. Mounting the prism reflector Select the mounting location in line with the mounting tips (Section 1.). A prism reflector must be used for the Fireray 50RV, and four prism reflectors arranged in a square for the Fireray 100RV. Fireray 50RV ÌÌÌ ÌÌÌ ÌÌÌ Fig. 3.: Prism reflectors Fireray 100RV ÌÌÌÌ ÌÌÌÌ ÌÌÌÌ ÌÌÌÌ ÌÌÌÌ ÌÌÌÌ ÌÌÌÌ ÌÌÌÌ ÌÌÌÌ ÌÌÌÌ ÌÌÌÌ ÌÌÌÌ Each reflector is secured using two mounting bores ( 3 mm). Arrange the four reflectors for the Fireray 100RV such that there are no mounting holes in the center (see Fig. 3.). Page 4 of 14

1.4. Connection Connection of a Fireray 50/100RV using a NSB100 LSN at the fire panel 1 Bridges Br1, Br2 in position 2-3 2 Contacts in open position Configuration for LSN: Parameterize the NSB in the control panel to control output KA1-KA2/KR-R-RR and Control with Fireray. Fireray 50/100 RV on off Operating mode switch Output for key switch (optional) bl DIP switch (recommended settings) ALARM NO COM 680 Ω rd ye Power supply 10-30 V + - RE gn blk NC FAULT 3K3 COM 2 wh LSN I1 NLT1 I2 I3 -U I4 +U II1 NLT2 II2 II3 -U II4 +U III1 III2 IV1 RR IV2 R V1 KR V2 KA1 V3 KA2 NSB 100 LSN SB VII1 VI1 UEB SA VII2 Br 1 1 Br 2 1 2 3 1 2 3 VI2 UEA Operating mode switches: Prism Targeting Alignment Mode Operating Mode DIP switch: Functions, see table 1. (page 3) 6 DA mini distributor -U +U -U +U I3 I4 NSB 100 (if voltage drop < 6V) EV 24 V - 24 V (if voltage drop > 6V) Select the following DIP switch settings for connection to a fire panel (see table 1. on page 3): - «Alarm relay saves the alarm» - «Fault relay at end of readjustment, no alarm». Page 5 of 14

- - Installation Instructions Connection of two Fireray 50/100RV to fire panel with cross zoning via an NBK 100 LSN and two NSB100 LSNs 1 Bridges Br1, Br2 on the NSB 100 in position 2-3 (see connection of one Fireray 50/100RV) 2 Contacts in open position Configuration for LSN: Parameterize the NSB in the control panel to control output KA1-KA2/KR-R-RR and Control with Fireray. Observe assignment to detector groups/detectors (see example). Operating mode switch Fireray 50/100 RV DIP switch (recommended settings) ALARM Power supply 10-30 V FAULT 2 VI1 VI2 V1 V2 NBK 100 LSN Parameterize, e.g. to 127/1 Line 1 Line 2 150/1 cross zoning with 500, current trigger criterion 500/1 cross zoning with 150, current trigger criterion Output for key switch (optional) bl NO COM 820 ye rd + blk gn Fireray 50/100 RV COM NC 3k92 wh 6 DA mini distributor NSB 100 LSN Parameterize, e.g. to 127/2 V1 KR V2 KA1 Parameterize, e.g. to V3 KA2 KA1-KA2-KR-150/2 1 Operating mode switch Output for key switch (optional) DIP switch (recommended settings) ALARM NO COM 820 Power supply 10-30 V + FAULT COM NC 3k92 rd blk bl ye gn wh 2 NSB 100 LSN Parameterize, e.g. to 127/3 V1 KR V2 KA1 Parameterize, e.g. to V3 KA2 KA1-KA2-KR-500/2 1 6 DA mini distributor -U +U -U +U I3 I4 NSB 100 (if voltage drop < 6V) EV 24 V - 24 V Page 6 of 14

2. Start- Up 2.1. Setting up the detector Start the «Prism Targeting»mode by moving the operating mode switch (see Fig. 2.) up (if the detector is mounted vertically) or to the right (if the detector is mounted horizontally). Connect the power supply. The detector runs in initialization mode for approx. 5 s. The red LED flashes if the detector is operational: 1 x for Fireray 50RV, 2 x for Fireray 100RV. Now direct the detector at the prism, using the two knurled screws, until optimum adjustment is confirmed by a steady yellow LED light. The following LED displays support detector set- up: Yellow LED display off Flashes - > Flashing frequency increasing Steady light Detector status in «Prism Targeting» operating mode No signal at receiver Signal is received -> The faster the flashing, the stronger the signal! Optimum alignment achieved The signal must only move from the reflector to the receiver, under no circumstances must it move to other light sources or reflective surfaces! Cover the prism reflector with a non-reflective material to check. The LED must not be lit. If the yellow LED does not go out, this indicates that a reflector is incorrectly aligned. 2.2. Calibrating the detector Once the optimum detector set-up has been achieved, set the operating mode switch to the center position without displacing the detector. The detector is now in («Alignment Mode»). The detector runs through an automatic configuration procedure to optimize the transmission power and the receiver sensitivity. The following detector statuses may be displayed by the LEDs during this procedure: LED displays Flashing red Steady yellow light Flashing yellow off Flashing red and yellow Detector statuses in «Alignment Mode» Receiver input signal too strong, the transmission power will be reduced. Wait until the LED goes out (max. 20 s). No signal is being received. Switch back to «Prism Targeting» mode and repeat the detector set- up. The receiver is receiving a weak signal, the transmission power will automatically be increased. Transmission power and receiver gain are optimum. Automatic calibration in progress. Page 7 of 14

Follow the flow chart to perform the calibration process: Switch center Alignment Mode Yellow LED lights up for approx. 5 s No signal: back to detector set-up (Section 2.1.) Steady yellow LED Wait until both LEDs have stopped flashing Turn the knurled screws in one direction and monitor the LED status yellow LED Which LED lights up? red LED Stop turning the knurled screw and wait until the red LED stops flashing Turn the knurled screw in the other direction Turn the knurled screw slowly in the same direction yellow LED Which LED lights up? red LED Repeat the procedure for the other detector axis with the second knurled screw no Both axes adjusted? No LED Do not turn the knurled screw any further y e Check optimum setting: s Yellow LED lights up: 1. With gentle pressure from top/bottom/left/right on the detector housing. 2. Each time the knurled screws are moved. Exit the Alignment Mode Switch at bottom: Operating Mode Page 8 of 14

When the calibration procedure is complete, move the operating mode switch to the bottom (if the detector is mounted vertically) or to the left (if the detector is mounted horizontally). The detector is now in «Operating Mode». The detector runs a calibration test for approx. 60 s. If the yellow LED lights up as a steady light after the test, you must repeat the detector alignment and calibration procedures (see Sections 2.1. and 2.2.). If a detector alarm is reset in normal mode by a disruption of the power supply, the detector automatically runs a calibration test. If the test is failed, the detector remains in the alarm position. If the test is positive, the yellow LED goes out, the fault relay is reset and the detector is returned to normal mode. In normal mode, the yellow LED flashes every 10 s. 2.3. System test The «Alarm» and «Malfunction» functions must be checked before final start-up. Alarm test Hold the test filter in front of the receiver lens (upper or right-hand part of detector). Select a volume of smoke slightly greater than the threshold set for the detector (see Section 1.1.). Make sure that you do not also cover the transmitter -lens. After approx.10 s, the red LED must light up and the alarm relay must close. With the «Save alarm» detector setting (DIP switch 1 «off»), there must be a reset at the control panel or the power supply must be disrupted for at least 5 s. With the setting «Auto Reset» setting (DIP switch 1 «on»), the alarm is reset automatically if the volume of smoke falls below the selected alarm threshold for at least 5 s. Fault test Cover the reflector with a non-reflective material. After approx. 10 s, the yellow LED must light up and the fault relay must open. As soon as the obstruction is removed, the detector returns to normal mode automatically after approx. 2 s. 3. Tips on Maintenance and Service For maintenance and inspection work on danger detector systems, in Germany the regulations of DIN VDE 0833 apply, which refer to the maintenance interval according to the manufacturer s instructions. Bosch ST recommends a functional and visual inspection at least once a year. Maintenance and inspection work should be carried out regularly and by trained personnel. Page 9 of 14

4. Technical Data Operating voltage 10 V DC... 30 V DC Current consumption: - in standby mode < 4 ma @ 24 V - in alarm/malfunction < 15 ma Reset control by power disruption Alarm relay Fault relay Permissible distance between Fireray and the reflector: - Fireray 50RV - Fireray 100RV Optical wavelength > 5 s Normally open; dry contact (2 A @ 30 V DC) Normally close; dry contact (2 A @ 30 V DC) 5 m to 50 m 50 m to 100m 880 nm Adjustable alarm threshold values 2.50 db (25%) 3.74 db (35%) 6.02 db (55%) Axial deviation tolerance (at 35% sensitivity) Operating temperature Detector 0.8 Prism reflector 5.0-30 C... +55 C Protection type IP 50 Dimensions (W x H x D) 126 x 210 x 120 mm Weight Housing: - Color - Material 670 g light gray/black ABS, non- flammable VdS ID number G 203070 5. Additional Documentation For those with access authorization, on the Bosch ST ExtraNet at www.boschbest.de the current information for each product, as well as the installation instructions supplied with the device, are available for download as a PDF file. Page 10 of 14

6. Appendices 6.1. Installation protocol Installation company: Type of object: Installation location: Installation date: Total number of all linear detectors: Detector version: Fireray 50RV Fireray 100RV Detector reflector distance: Distance of the detector axes to one another Mounting height m m m Mounting surface (e.g. masonry/reinforced concrete/steel beams/wood/etc.) Serial number(s) Reflector size: 1 x (10 x 10 cm) 4 x (20 x 20 cm) Supply voltage: V Correct mechanical adjustment of transmitter (when gentle pressure is applied to the detector housing from the left/right/top/ bottom, the yellow LED lights up initially): Alarm triggered with absorption film 35% - 50% tested: Fault triggered by disruption of IR beam tested: yes no yes no yes no DIP switch settings: on off 1 2 3 4 Comments (environmental conditions, e.g. dust, humidity, temperature etc.) Installation tested on: by: Page 11 of 14

6.2. Fault diagnosis Fault indicator Possible cause Action Fault LED illumi- nated permanently Fault LED flashes Alarm LED illuminated permanently No fault message when IR beam is disrupted Alarm triggered when IR beam is disrupted Triggering of false alarms Beam path blocked by an obstacle Reflector is contaminated/covered/ has fallen down. Supply voltage too low. Mode sliding switch in upper position («Direct») Detector set- up changed on switching to «Operation». The limit of automatic gain control has been reached «MODE Switch» sliding switch in upper position («Direct») and incomplete detector set- up DIP switch 1 at OFF («Save alarm»), the alarm display remains saved Beam path (partially) blocked by an obstacle Detector receives partial IR signal, e.g. via reflective surfaces near the beam axis. An object placed in the beam path for testing has acted as the reflector. Sensitivity to existing environmental conditions set too high Check and/or ensure free visual line in the area between the detector and the reflector. Check the status of the reflector and clean it if necessary. Measure supply voltage directly at detector. Set the switch to «Operation» and wait until the 60 s activation routine is complete. When operating the sliding switch following the correct adjustment, make sure that the setting is not changed. Clean detector lens and reflector and correct mechanical adjustment! Align detector vertically and horizontally until the fault LED is permanently illuminated. Then continue using fine adjustment (switch in center position)! Reset the detector by disrupting the supply voltage for at least 5 s or select «Reset» on the fire panel Ensure a free visual line in the area between the detector and the reflector! Cover reflector with a dark material to test! Check detector s range of vision for reflective objects! For testing, use a non- reflective material, maintain a greater distance to the detector, cover the reflector as directly as possible. Select a less sensitive alarm threshold (DIP switches 3 and 4): normal= 35%, less sensitive= 50% Page 12 of 14

6.3. Notes Page 13 of 14

Bosch Security Systems Robert-Koch-Str. 100 D- 85521 Ottobrunn Info - Service Telephone: +49 89 6290-1039 Fax: +49 89 6290-1039 www.bosch - sicherheitssysteme.de info.service@de.bosch.com