MISSION CRITICAL Air Conditioning Systems. Maintenance Guide. ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4

Similar documents
Series 9. Commissioning Checklist. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

Mission Critical. Series 6, 8 & 9. vertical floor mount Ton Units. Air Conditioning Systems

Series 8. Guide Specification 60 Hz. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

Series 6. Guide Specification 60 Hz. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

Preventative Maintenance Tables

Mission Critical Air Conditioning Systems

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Service Step by Step Trouble-Shooting Check-List

NetworkAIR AFX. Operation and Maintenance AFX65 AFX18

User s Information Manual

Air Conditioning Components

RTU. Roof Top Units 8 30 Ton. Maxi-Kool.

40 RM/RMS Packaged Air-Handling Units

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

VertiCool CLASSIC. Engineering Guide. Effective March Air-Cooled, Water-Cooled, Chilled Water and Water Source Heat Pump

Advance Release September 2009

Liebert Challenger 3000/Liebert Challenger ITR with Liebert icom Control. Operation & Maintenance Manual - 50 & 60Hz

Equipment Maintenance Checklist

KCC Centrifugal Fan Air Cooled Condensers

System Floor Mount Systems DX / Glycol / Chilled Water 6-12 Tons. High Density Presicion Cooling. Kompact.

Technical instructions

TECAM S.A. harmony. 5PZA Direct Expansion. Air Conditioning Equipment Manufacturer. R-410A PRECISION UNIT 2 Ton 6 Ton / 60 Hz. Tecnología Ambiental

OPERATING & MAINTENANCE MANUAL HORIZONTAL WATER SOURCE HEAT PUMP. World class comfort.

C13-Series Engineering Guide

SIMPLICITY BY DESIGN M52 CONTROLLER

DSH Model Air Cooled Self Contained Indoor Packaged Units 2-5 Tons Preliminary Application Data

12 In Row. Installation Manual. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

Operation Manual. Instructions for Installation, Operation & Maintenance. PortaPac 5-, 8 and 10-ton Portable Air Conditioners

Fig. 1 - Unit PHD4 and WPH4

RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW

City of Duluth Festival Center 04/25

Rooftop Ventilator. Models RV and RVE. with Packaged Cooling & Heating

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

USER'S MANUAL PGE Single Package Rooftop

Evaporative Cooling products

Shelf Units R-407C. 2, 3, and 4 ton. ISO 9001 Certified

Climate control precision in Hi-tech environments Jupiter and Mercury Close Control Units

User s Information Manual

Packaged Heat Pumps. Owner s Guide to Operating and Maintaining Your Heat Pump

Owner s Information Manual

SECTION WATER-SOURCE UNITARY HEAT PUMPS

Construction Electrical

T-SERIES Air Conditioner. T29 Model INSTRUCTION MANUAL nvent Rev. I P/N

Operation Manual. AvantAC Classic Bus Air Conditioning Units. Carrier Transicold China

Electrical. Bi-Metallic Thermal Cutouts. Linear Thermal Cutouts

OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER

Series 11, Ceiling Units

User s Information Manual

Series 6, Vertical Floor-Mount Units

How about Savings in Time, Money, Energy and Longer Life?

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N

50BY, BL. Ÿà Õ µ µ Èß ËÕߪ Õ» å Single-Package Cooling Units 50BY, BL 50BY, BL

DATA TEMP Installation, Operation and Maintenance Manual

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N

T-Series Air Conditioner T15 Model

VertiCool Space Saver

T-Series Air Conditioner T20 Model

Fig. 1 - Unit PGD4, PGS4, WPG4

VertiCool Aurora Engineering Guide

Stanford University Facilities Design Guidelines SECTION DECENTRALIZED UNITARY HVAC EQUIPMENT

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

READ AND SAVE THESE INSTRUCTIONS OWNER S MANUAL FOR BYPASS AND FAN POWERED HUMIDIFIERS. Small or Large Bypass 12 Water Saver Bypass 13 Fan Powered 14

V-SERIES Air Conditioner. VA08 Model INSTRUCTION MANUAL nvent Rev. F P/N

DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

VERTICOOL TECHNICAL DATA MANUAL. Vertical Air/Water Cooled 3-25 Tons

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

CoolSpot Engineering Guide

INSTALLATION INSTRUCTIONS

442 Chapter 16. Figure 16-5 Gas leak detection

Mortex INSTALLATION INSTRUCTIONS AIR CONDITIONING & HEAT PUMP INDOOR COILS

Plant Growth Cabinets

INSTALLATION, OPERATION AND MAINTENANCE MANUAL AIR HANDLERS

User s Information and Installation Instructions

Diocese of Cleveland Facilities Services Corporation

C13-Series. Installation, Operation and Maintenance Manual Effective April Horizontal Air-Cooled, Water-Cooled, Chilled Water and Heat Pump

"This is only the scope of work for the project. For more information, interested parties should contact Procurement at

SECTION REFRIGERATION EQUIPMENT. A. Section Includes: Refrigeration equipment for insulated cold storage rooms including necessary accessories.

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: INDOOR UNIT:

User Manual Box Exhaust Fan Series (Belt Drive)

UNDERCOUNTER LABORATORY REFRIGERATORS and FREEZERS Installation, Operation and Maintenance Instructions

Owner s Information Manual

FILTERS MANIFOLD CABINET REFRIGERANT CONNECTION LOCATION

"SWVP - SWHP" COMMERCIAL WATER SOURCE HEAT PUMPS & AIR CONDITIONERS

INSTALLATION INSTRUCTIONS

PDF Created with deskpdf PDF Writer - Trial ::

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT

Series PS6, Vertical Floor-Mount Units

USERS INFORMATION MANUAL

PROAIR Air Conditioner. CR23 Model INSTRUCTION MANUAL nvent Rev. D P/N

Maintain. a TOWER of POWER. Part One How to. Don t let out of site, out of mind prevent you from keeping cooling towers running efficiently

T-SERIES Air Conditioner. T43 Model INSTRUCTION MANUAL nvent Rev. I P/N

INSTALLATION MANUAL FOR ROTARY TWIN LOBE (ROOTS) BLOWERS / COMPRESSORS

Aprilaire Dehumidifier Troubleshooting Manual Models 1830, 1850, 1870

Tuning up ventilation systems

Operator Preventive Maintenance

RHEEM PACKAGE GAS/ELECTRIC

OPERATING AND MAINTENANCE MANUAL

A Fläkt Woods Company 2933 Symmes Road, Fairfield, Ohio Phone: (513) Fax: (513)

MECHANICAL ENGINEERING ME.2017 FUNDAMENTAL OF REFRIGERATION AND AIR CONDITIONING. Sample Questions and Answers

Transcription:

MISSION CRITICAL Air Conditioning Systems Maintenance Guide ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4

Vertical Floor /Wall /Ceiling Mount - Maintenance Manual 2

Vertical Floor /Wall/Ceiling Mount - Maintenance Manual TABLE OF CONTENTS MAINTENANCE 4 GENERAL SERVICE AND INSPECTION 4 REGULAR INSPECTION 4 SENSOR CALIBRATION CHECK 4 PREVENTIVE MAINTENANCE: QUARTERLY 5 REPLACEMENT OF AIR FILTERS 5 MICROPROCESSOR CONTROLLER 6 POWER PANEL 6 COMPRESSOR LUBRICATION 6 COOLING COIL AND REFRIGERATION SYSTEM 7 CONDENSER 7 ELECTRIC MOTOR 7 BLOWER FAN 8 ELECTRIC HEATER 8 HUMIDIFIER 8 3

Vertical Floor /Wall /Ceiling Mount - Maintenance Manual MAINTENANCE The ClimateWorx Series Vertical Floor Mount family computer room air-conditioning unit employs carefully selected components of proven quality to ensure prolonged trouble-free operations. Maintenance-free solid state controllers also enhance the reliability of the whole system. ClimateWorx uses one microprocessor controller to centralize all control and monitoring functions which makes the machine user friendly and simplifies maintenance routine and fault finding procedure. The maintenance practice which are given below are for guidance only and are for general service and maintenance to minimize wear and tear resulting from normal operation and for insurance that the machine will be operating under the most efficient condition. Maintenance is classified into two categories, i.e. general service and preventive maintenance. General service, including regular inspection may be carried out by unskilled personnel of the client. Preventive maintenance however must be performed by competent service personnel familiar with the servicing of air-conditioning, electrical and electronic engineering equipment. Our authorized service agents have been carefully chosen to provide efficient and quality service to our clients. GENERAL SERVICE AND INSPECTION Although the status of the machine and the environmental conditions are under the constant surveillance of the controller and any abnormality will be announced either as out-of-limit warning or alarm, there is, however no place for complacency if efficient and reliable service is demanded from these well engineered machines. We recommend that the following procedures should be followed. REGULAR INSPECTION The machine should be inspected periodically to ensure that no unusual noise or changes in operation are present. Any abnormalities should be investigated immediately by qualified air-conditioning personnel. SENSOR CALIBRATION CHECK This procedure should be followed if sensor is found to be out of calibration. Advanced M52 Sensor Calibration 1. Go to setting tab on page 6 and scroll down to the bottom of the page where you will find Temperature and Humidity offset settings. While measuring the actual temperature and humidity in the space you can make adjustments to these settings to have the sensor read the space temperature and humidity more accurately. This is the only calibration function available. If the sensor is still reading out of specification sensor should be replaced. M52 Sensor Calibration Temperature 2. Power off unit, locate temperature/humidity sensor board and set the jumper, JP1, to points 1 and 2 for zero setting. The pin 1 and 2 of the sensor board should read approximately 1000 ohms which corresponds to 0 C for the Hycal PT100 sensor. 4

Vertical Floor /Wall/Ceiling Mount - Maintenance Manual 3. Switch unit on, wait 60-120 seconds, and login to security level 1. Go to the sensor page under the [Test mode] tab, press the Def. and then Set 0 key next to the temp1 reading. The Temp1 reading should now read 0 C 4. Power off the machine and reset the jumper, JP1, to point 3 and 2 on the sensor board. The zeroing of the temperature sensor is now complete. You can further fine tune sensor to what you actually measure by simply entering the measured temperature in C in the Main Temp setting under the [Setting] tab. Relative Humidity There is no zeroing function for the humidity sensor. 1. Login security level 1. Go to the sensor page under the [Test mode] tab and press the Def. Key next to the Humid. 1 reading. 2. If required, fine tune sensor to what you actually measure by simply entering the measured relative humidity in the Main Humidity setting under the [Setting] tab. SERIES V Calibration procedure This procedure should be followed if sensor is found to be out of calibration or changed. Switch unit on and allow room to stabilize. Measure dry bulb temperature and relative humidity using a slingpsychrometer or similar device. Enter top security mode (see user guide) and enter the dry bulb reading into address 44 on the controller 1. Enter relative humidity into address 47 on the controller. This adjusts the correction factor in the controller automatically calibrating the sensor. 1) If the unit is set to display in F enter the actual room temperature in F minus 32. ie: Room temperature is 68 enter 36 in address 44 PREVENTIVE MAINTENANCE: QUARTERLY For the machine s warranty to be valid, regular maintenance comprising four visits per annum should be undertaken by qualified personnel or staff of our appointed agents. REPLACEMENT OF AIR FILTERS Visually check the air filters for cleanliness. If in doubt, use a manometer to measure the pressure differential before and after the filter. If the pressure-drop is more than 0.8 inches w.g., the filters should be replaced. Ensure filters being replaced are being replaced with filter with the same MERV rating. I. Changing filters on down flow machine Switch off the machine and open the side panel(s) of the machine on either (or both) side. The filters are on the upper part of the unit and can be taken out by sliding the filter horizontally out from the machine. After removing all dirty filters, put new clean filters in ensuring that airflow direction arrow points into machine. Restore panels back to the machine. 5

II. Changing filters on up flow machine Vertical Floor /Wall /Ceiling Mount - Maintenance Manual Switch off machine, open the side panel(s) on the rear return air machines or the front panels on standard machines. The air filters can be taken out by sliding horizontally to either end of the machine. Install clean filters and ensure that airflow direction arrows point into machine. Restore plenum panels onto the machine. III. Changing filters on packaged air cooled section only Switch off machine, open the side panel(s) on the condenser section. The air filters can be taken out by sliding horizontally to either end of the machine. Install clean filters and ensure that airflow direction arrows point into the machine. Securely close and latch panels(s) and switch on the machine. MICROPROCESSOR CONTROLLER The state-of-art solid state microprocessor based controller is virtually trouble free and little or no maintenance is needed. Quarterly checks of the following are recommended for efficient operation of the machine. To control individual operations refer to ClimateWorx User Guide pages 34 to 36. Note: The fan must be kept running through individual tests. 1. Check controller display. 2. Check alarm operation and calibrate where necessary. 3. Check accuracy of sensors and calibrate where necessary. 4. Check weekly operation program and real time clock. 5. Check keyboard functions. 6. Check output voltage of controller. POWER PANEL 1. Check operation of all MCBs, and contactors. 2. Check current in each motor and heater circuit. 3. Check operation of overload devices. 4. Check cable terminations for tightness. COMPRESSOR LUBRICATION The refrigeration compressors must have adequate lubrication to ensure trouble-free operation and a long life. On the start-up of any new system, some oil will be lost to coat the inside of the piping, some logged in low velocity areas of the system, and some will be kept in circulation. This lost oil must be made up by adding new oil to the system after the initial start-up. Very low compressor oil levels can cause complete loss of lubrication and may result in an immediate compressor failure if not protected against. The loss of oil can also be caused by flooded starts or refrigerant migrating to the oil during an off period and pulling the oil out of its sump during the sudden pressure drop of a start-up. The level should be observed in the sight glass immediately after the compressor shutdown, while it is still warm. The level observed when the compressor is not running for a long period may be a mixture of oil and refrigerant which would not be a true indication of the oil level when the compressor is running. 6

Vertical Floor /Wall/Ceiling Mount - Maintenance Manual If the oil level in the sightless of the compressor is less than one-eighth (1/2) up from the bottom of the glass, this indicates a low oil level. If the oil level is up more than one-half (3/4) from the bottom, his indicates a high oil level. Therefore, the oil level should be 1/2 to 3/4 up the sight glass when the compressor is running. Notes: 1. Allow compressor to run for at least 10 minutes before checking sight glass. 2. Unit sizes 6 to 12 tons do not have sight glass. COOLING COIL AND REFRIGERATION SYSTEM The refrigeration circuit shall be inspected each month for proper function and signs of wear and abnormality. In most cases signs of deterioration of component parts give prior warning to system failure. Periodic inspection is essential to detect and prevent failure. The liquid line sight glass should be inspected for the presence of bubbles and moisture. Bubbles in the circuit indicate a shortage of refrigerant in the system and changing of the indicator color from green to yellow denotes presence of moisture. If moisture is detected change filter drier and refrigerant as required. If charge is found to be low, check system for leak using current ODP procedures. 1. Check cleanliness of coil. 2. Check cleanliness of stainless steel drain pan and drain system. 3. Check operation of controls. 4. Check operation of drier filter, sight glass and valves. Once all of the checking and adjusting of the refrigeration circuit is complete make sure that all pipes, distributor tube and capillary lines are not in contact with each other or other objects that will result in premature failure from wear. It is the responsibility of the maintenance personal to assure this step has been followed. CONDENSER a. Air Cooled Condensers 1. Check condition of condenser coil. 2. Check and clean all debris from underside of coil to ensure that airflow is not blocked. 3. Check refrigerant line for leakage or damage. Note: On packaged air cooled Series 6 units there are filters that require maintenance. Please see note above in replacement of air filters section. b. Water Cooled Condensers 1. Check operation of valves. 2. Check pipe work and fittings for leakage. ELECTRIC MOTOR Totally enclosed air cooled electric motor with class F insulation and IP55 is our standard. 1. Check motor current. 2. Check bearing condition and grease or replace where necessary. 7

Vertical Floor /Wall /Ceiling Mount - Maintenance Manual BLOWER FAN Special design blower fans with strengthened bearing and mounting arrangement driven by double belt pulley system is our standard design. Regular maintenance should include: 1. Check motor current and bearing. 2. Check fan belt tension and adjust where necessary. 3. Check fan bearing for noise and wear and tear for twin blower unit. 4. Check blower tightness on shaft. 5. Periodically clean dust and debris from blower wheel, as this can cause an imbalance and lead to further problems. The fan belt shall be checked monthly for signs of wear and proper tension. Depressing the belts midway between pulley and sheaves should produce a displacement of between 10 mm to 20 mm. Tight belts may cause excessive bearing wear and loose belt will cause slippage. Belt tension can be adjusted by turning the adjustment screws on the motor mounting slide. ELECTRIC HEATER 1. Check current of heater. 2. Check mounting bracket. HUMIDIFIER The humidifier consists of an electrode steam boiler for high efficiency and quick response. Automatic flushing of the water using an auto-adaptive process enhances boiler life and maintains full output over the life span of the boiler. 1. Check operation of fill and drain solenoid valves. 2. Check and clean fill valve inlet strainer. 3. Check high water level sensor. (When replacing steam boiler) 4. Check boiler condition and water level. The humidifier is designed to operate on ordinary tap water. Minerals will collect in the disposable bottle and the microprocessor will alarm when the bottle requires replacing. The quantity of such deposits and the life span of the bottle depend on the quality of the city water supply. 8