TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

Similar documents
TECHNICAL GUIDE MODELS: H5CE090, H3CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS EER DESCRIPTION

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

SPLIT-SYSTEM HEAT PUMPS 50 AND 60 HZ DESCRIPTION

TECHNICAL GUIDE DESCRIPTION EA090/FA090 SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNIT INDOOR UNIT

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: INDOOR UNIT:

Commercial High-Efficiency Condensing Units

Commercial High-Efficiency Condensing Units

PACKAGE AIR CONDITIONER

EMBASSY SERIES SINGLE PACKAGE AIR CONDITIONERS (WATER-COOLED) C2ED060, 090, 120 & 180 5, 7-1/2, 10 & 15 Nominal Tons

MIN. CCT. QTY RLA LRA HP FLA AMPACITY /1/ /3/

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

MACH N-407 Heat Pump Air-Cooled Chiller

MAC N-407 Air-Cooled Chiller

CHS. Product Specifications COMMERCIAL SPLIT SYSTEMS HEAT PUMP UNITS R 410A, 6 10 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

Air-Cooled Split System Condensing Unit for Rooftop Systems and Air Handlers

FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 3 of 13

Catalog Air Cooled Split System Condensing Units for Rooftop Systems and Air Handlers

MAC-120HE-03 Air-Cooled Chiller

INSTALLATION MANUAL COMMERCIAL SPLIT SYSTEM COOLING UNITS 4 PIPE SYSTEMS 15 THROUGH 20 NOMINAL TON HB B-0804

DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING

High Ambient / High Efficiency Series. R - 410a. 50Hz. Ducted Split Air Conditioners (5.0 kw kw)

TECHNICAL GUIDE LISTED. SPLIT-SYSTEM AIR CONDITIONERS 10 SEER R22 60Hz MODELS: AC036X10(3,4) THRU 060 (3 THRU 5 NOMINAL TONS, 3 PH) DESCRIPTION

SUBMITTAL DATA SHEET FEATURES. SPLIT-SYSTEM EVAPORATOR BLOWERS 7.5, 10, 15 & 20 TONS MODELS: NH-07 thru -20, 2-PIPE NJ-10 thru -20, 4-PIPE

TECHNICAL GUIDE LISTED. SPLIT-SYSTEM AIR CONDITIONERS 10 SEER R22 60Hz MODELS: H*BA-(T,W)036 THRU 076 (3 THRU 6.3 NOMINAL TONS, 3 PH) DESCRIPTION

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MODELS E1FB180 & E1FB240

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MODELS B1PA024, 030 AND 036

DSH Model Air Cooled Self Contained Indoor Packaged Units 2-5 Tons Preliminary Application Data

SKYPAK II, 3 Ton Series, gives you a

MHCCW Chilled Water Ceiling Concealed With 5kW Electric Heat 2-Pipe Heat / Cool Fan Coil 30,000 BTUH

SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNITS. INSTALLATION INSTRUCTION Supersedes: N1Y (497) N1Y (998) MODELS E2FB090 & E1FB120 GENERAL

MHCCW Chilled Water Ceiling Concealed Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000 BTUH

JOB NAME: LOCATION: PURCHASER: ENGINEER: SUBMITTED TO: FOR: REFERENCE [ ] APPROVAL [ ] CONSTRUCTION [ ] SUBMITTED BY: DATE:

SKYPAK II, 3 Ton Series, gives you a

CONDENSING UNITS. Equipped with the Award Winning Comfort Control System UARL- JEZ. Four Models

TECHNICAL SPECIFICATIONS

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L4EU NOMINAL TONS

INSTALLATION MANUAL COMMERCIAL SPLIT SYSTEM COOLING UNITS 4 PIPE SYSTEMS. HB 180 & thru 20 Nominal Tons NOTES, CAUTIONS AND WARNINGS

Technical Guide DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWERS. 7-1/2 and 10 NOMINAL TONS LA090 & LA120 SUPPLY AIR PLENUMS

Advance Release September 2009

MODELS W1LC220, 260 AND 320 STYLE B

TECHNICAL SPECIFICATIONS

PGF SERIES 7-1/2 Ton. Belt Drive CONVERTIBLE SINGLE PACKAGE GAS/ELECTRIC UNIT

Technical Guide DESCRIPTION CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) FEATURES XTG-A-0307

INSTALLATION MANUAL SPLIT-SYSTEM CONDENSING UNITS (AIR COOLED) HB Ton HB Ton HB Ton NOTES, CAUTIONS AND WARNINGS

Product Data. Features/Benefits. 50TJ S Side Discharge Single-Package Rooftop Units 50/60 Hz 15 to 30 Nominal Tons

Concealed Ducted Split Series R-407C MBH

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 PROVEN PERFORMANCE GENERAL FEATURING

Compact, Self-Contained unit that offer low installation cost plus dependable performance.

ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical

MHNCCW (4-Pipe) Chilled/Hot Water Ceiling Concealed 208/230V 4-Pipe Heating & Cooling Fan Coil 12,000 BTUH

UP to 14.5 SEER, PACKAGE AIR CONDITIONER UNIT, 2 to 5 TONS 208/230 Volt, 1 phase, 60 Hz REFRIGERATION CIRCUIT

60 TON AIR-COOLED CHILLER. Call us today! (800) PA-ACCTR-60 GENERAL DIMENSIONS ELECTRICAL DATA 60 TON AIR-COOLED CHILLER FEATURES

PAJ3. Product Specifications

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

Technical Guide SUNLINE 2000 DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWER K4EU NOMINAL TONS (WORLD 50 HZ)

Condensing Units CUS 15-60

INSTALLATION MANUAL AFFINITY SERIES SINGLE PACKAGE AIR CONDITIONERS ELECTRIC/ELECTRIC, AIR-COOLED. MODELS: D1EB036 thru Thru 5 Ton (10 SEER)

SKYPAK II Heating & Cooling Self Contained Packages

TECHNICAL SPECIFICATIONS

INSTALLATION MANUAL - 50 Hz

SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNITS. INSTALLATION INSTRUCTION Supersedes: Nothing N1Y (692) MODELS E1FB090 & 120 (50 & 60 HZ) GENERAL

VariCool VAV Engineering Guide

DESCRIPTION TECHNICAL GUIDE SINGLE PACKAGE GAS/ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERS D(HE, HG) 036, 048 & YTG-A-0506

CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L2EU NOMINAL TONS

WCH5**4. Product Specifications

Advance Product Data. Features/Benefits. 42WKN Hydronic Fan Coil Units

50TM TFF COMBINATION HEATING/COOLING UNITS

DT5BD Series High Efficiency Heat Pumps 13+ SEER Residential System Ton Capacity

THE WALL-MOUNT ONE TON AIR CONDITIONER. Green Refrigerant. 12,000 Btuh EER Right Side Control Panel. Engineered Features

50TM COMBINATION HEATING/COOLING UNITS

CHAMPION SPLIT-SYSTEM CONDENSING UNITS (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: N4 (778) N4Y (492)

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw)

Supersedes: N2Y (498) N2Y (799) MODELS B1HH018 THRU THRU 5 TON (12 SEER)

RetroAire Model Number: 9,000 to 36,000 Btuh (2.6 to 10.5 kw)

SPLIT-SYSTEM EVAPORATOR BLOWERS K2EU060, K4EU090, K3EU120 & K1EU180 5 Thru 15 Nominal Tons DESCRIPTION ACCESSORIES FIELD INSTALLED

Product Data. 50HS Single-Package Heat Pumps to 5 Nominal Tons

072, 090, 120, 180 & 240 MODELS C SERIES CONDENSING UNITS P SERIES HEAT PUMPS

30GT FLOTRONIC AIR-COOLED CHILLERS

Split System Heat Pump Product Data

NH4H4. Product Specifications 14 SEER HORIZONTAL DISCHARGE HEAT PUMP FOR USE WITH DUCTED INDOOR UNIT

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM

VERTICOOL TECHNICAL DATA MANUAL. Vertical Air/Water Cooled 3-25 Tons

SPLIT SYSTEM HEAT PUMP 1½ 5 TON HERITAGE 13 MODELS 2A6H A American Standard Heating & Air Conditioning

PC SERIES 50 Hertz PRODUCT SPECIFICATIONS. Self-Contained Packaged Air Conditioners. 4 and 5 Ton [14.1 kw to 17.6 kw]

Split System Cooling Product & Performance Data

T-SERIES SPLIT SYSTEM UNITS R-410A - 60 HZ. EER up to to 20 Tons Cooling Capacity - 71,000 to 236,000 Btuh AIR CONDITIONERS TS

technical guide Water-Cooled Self-Contained Units

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION ACCESSORIES - FIELD INSTALLED. K5EU090 and K4EU Hz 7.5 and 10 NOMINAL TONS SUNLINE 2000 (WORLD 50 HZ)

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

PAR5. Product Specifications

C13-Series Engineering Guide

Nominal Capacity 024 = 7 kw (2 tons) 036 = 10.5 kw (3 tons) 048 = 14 kw (4 tons) 060 = 17.5 kw (5 tons)

Transcription:

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 DESCRIPTION These Sunline 2000 units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging. Each unit is pressurized with a holding charge of Refrigerant-22 for storage and/or shipping. The compact design, clean styling, low silhouette, and quiet operation make these condensing units suitable for almost any outdoor location. On rooftops, because they weigh much less than a single package unit of similar capacity and are much easier to rig and support. At ground level, because their ample sub-cooling capacity allows them to be located 60 feet below the evaporator coil. All sheet metal parts are constructed of commercial grade (G90) galvanized steel. After fabrication, each part is thoroughly cleaned to remove any grease or dirt from its surfaces. The external parts are coated with a powder paint to assure a quality finish for many years. This UL approved coating system has passed the 750 hour, 20% salt spray test per ASTM Standard B117. All models include a 1-year limited warranty on the complete unit. The compressor carries an additional 4-year warranty. A complete line of Evaporator Blower units is also offered to meet your precise capacity and air handling requirements. Refer to Form 036-21300-001 for more information on this air side equipment. FEATURES 208/230/460 VOLT ONLY 208/230/575 VOLT ONLY Condenser coil constructed of copper tubes and aluminum fins for durability and long lasting efficient operation. Permanently attached base rails with fork-lift slots and lifting holes. This design allows for 3-way fork-lift access and overhead rigging. Both high and low pressure controls. Since these controls are self-contained, there are no capillary lines to be damaged. Compressor line-break motor protection and crankcase heaters. Anti-short cycle timer to protect the compressor. A lockout circuit to prevent the unit from cycling on safety control. A 24-volt temperature control circuit. Low ambient operation to 45 F accessories for 0 F low ambient operation are available. A filter-drier (shipped in the unit's compressor compartment for field installation near the evaporator coil). Service valves with a back-seating access port for pressure testing the system. Copper stub-outs are factory mounted on the suction and liquid service valves to simplify the field piping connections. Separate panel for easy access to the control box without affecting air flow across the condenser coil. Gauge lines extend out from cabinet to facilitate servicing. Packaging suitable for outdoor storage Optional coil guard accessory protect coils with a decorative grille. FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

TABLE OF CONTENTS DESCRIPTION............................. 1 FEATURES................................ 1 SEQUENCE OF OPERATION................. 7 GUIDE SPECIFICATIONS................... 11 LIST OF FIGURES Fig. # Pg. # 1 TYPICAL FIELD WIRING WITH AIR HANDLER..... 8 2 4 POINT LOADS.............................. 8 3 TYPICAL FIELD WIRING WITH 7-1/2 TON FURNACE................................... 9 4 CENTER OF GRAVITY....................... 10 5 UNIT DIMENSIONS & CLEARANCES HF-07...... 10 LIST OF TABLES Tbl. # Pg. # 1 ARI RATINGS............................... 3 2 APPLICATION DATA.......................... 3 3 PHYSICAL DATA............................. 3 4 ELECTRICAL DATA........................... 4 5 UNIT COOLING CAPACITIES AND POWER REQUIREMENTS............................ 4 6 SYSTEM COOLING CAPACITIES AND POWER REQUIREMENTS (HF-07/LF-07)................. 5 7 HF-07 CHARGING CURVE..................... 6 8 MINIMUM CLEARANCES...................... 9 2 Unitary Products Group

TABLE 1: ARI RATINGS * CONDENSING UNIT MODEL INDOOR BLOWER UNIT MODEL SYSTEM MBH SYSTEM EER CONDENSING UNIT SOUND LEVEL(bels) HF-07 LF-07 90 10.7 8.9 *. Certified in accordance with Unitary Large Equipment certification program, which is based on ARI Standard 340/360. TABLE 2: APPLICATION DATA LIMITATION MIN. MAX. 208/230-3-60 187V 252V Voltage Variation * 460-3-60 432V 504V 575-3-60 540V 630V Ambient Air on Condenser Coil 45 F 125 F *. Rated in accordance with ARI Standard 110, utilization range A.. Low Ambient accessories are available to permit stable system operation at ambient temperatures down to 0 F. Note: Refer to Form 035-15407-001 for refrigerant piping limitations. TABLE 3: PHYSICAL DATA Model HF Compressor Condenser Fan (Propeller) Fan Motor * Coils Unit Weight (Lbs.) Charge, Lbs,-Oz. (Refrigerant-22) Rating Cap. (Tons) (Stages) Qty. Dia. Norm Blades Qty. RPM HP (in.) CFM Rotation Face Finned Rows Pitch Length Qty Area High Ship. Oper. Holding Oper. ** (Deg.) (in.) -07 7-1/2 1 2 24 7800 3 26 2 1110 3/4 CW 23.8 96 36 388 383 1-12 14.95 *. These PSC motors are directly connected to the condenser fans and have inherent protection, ball bearings and a 48 frame.. These condenser coils have 2 rows of 3/8 OD copper tubes and 16 aluminum fins per inch.. When viewing the shaft end of the motor. **. Includes matched indoor blower unit but no piping. Unitary Products Group 3

TABLE 4: ELECTRICAL DATA MODEL HF VOLTAGE CODE POWER SUPPLY COMPRESSOR RLA LRA CONDENSER FAN MOTOR POWER SUPPLY HP QTY FLA UNIT AMPACITY (AMPS) MAX. FUSE SIZE * (AMPS) 2 208/230-3-60 25.6 190 208/230-1-60 3/4 2 3.03 38.1 60 8-07 4 460-3-60 12.8 95 460-1-60 3/4 2 1.60 19.2 30 10 5 575-3-60 10.2 75 575-1-60 3/4 2 1.35 15.5 25 10 *. Dual element.. Based on three, 60 C insulated copper conductors in steel conduit. MIN. WIRE SIZE (AWG) TABLE 5: UNIT COOLING CAPACITIES AND POWER REQUIREMENTS Model HF Suction Press. & Temperature of Air on Condenser Coil, F Corresponding Temp. @ 65 75 85 95 105 115 Saturation PSIG F MBH KW* MBH KW * MBH KW* MBH KW* MBH KW* MBH KW* -07 61.6 35 94 6.7 90 7.2 85 7.8 80 8.3 75 9.1 70 9.8 68.5 40 104 6.8 99 7.3 94 7.9 89 8.5 84 9.2 78 9.9 76.0 45 114 6.8 109 7.4 103 8 98 8.6 93 9.3 87 10 84.0 50 124 6.9 119 7.5 113 8.1 108 8.7 102 9.4 96 10.2 *. Includes compressor and condenser fan motor(s). 4 Unitary Products Group

TABLE 6: SYSTEM COOLING CAPACITIES AND POWER REQUIREMENTS (HF-07/LF-07) Temperature of on Air Condenser Coil 85 F 95 F Air On Evaporator Coil Total Total Sensible Capacity (MBh) Total Total Sensible Capacity (MBh) Capacity Input Capacity Input (MBh) (kw) Return Dry Bulb ( F) (MBh) (kw) Return Dry Bulb ( F) CFM WB( F) 86 83 80 77 74 71 68 86 83 80 77 74 71 68 2250 72 99 7.1 58 51 45 38 32 - - 95 7.7 56 49 43 37 30 - - 67 90 6.9 70 63 57 50 44 38 31 87 7.6 68 62 55 49 43 36 30 62 83 6.7 80 74 68 61 55 48 42 80 7.4 78 72 65 59 52 46 40 57 79 6.6 79 79 72 66 59 53 47 76 7.3 76 76 69 63 56 50 44 2625 72 102 7.1 63 55 48 40 32 - - 98 7.8 61 54 46 39 31 - - 67 93 7.0 76 68 60 53 45 38 30 90 7.6 75 67 60 52 44 37 29 62 85 6.8 84 79 72 64 57 49 42 82 7.5 82 78 70 63 55 47 40 57 81 6.7 81 81 77 69 62 54 47 79 7.4 79 79 74 67 59 52 44 3000 72 105 7.2 68 59 51 42 33 - - 101 7.8 67 58 50 41 32 - - 67 96 7.0 82 73 64 55 47 38 29 93 7.6 81 73 64 55 46 38 29 62 88 6.8 88 85 76 68 59 50 41 85 7.5 85 84 75 66 58 49 40 57 84 6.7 84 84 82 73 64 55 47 81 7.4 81 81 80 71 62 53 45 3300 72 106 7.2 72 63 53 43 33 - - 103 7.8 71 62 52 42 32 - - 67 97 7.0 87 77 67 57 48 38 28 95 7.7 86 76 67 57 47 37 28 62 89 6.9 89 88 80 70 60 51 41 87 7.5 87 86 79 69 59 49 40 57 85 6.7 85 85 84 74 65 55 45 83 7.4 83 83 82 72 63 53 43 3600 72 108 7.2 77 66 55 45 34 - - 105 7.9 76 65 54 43 33 - - 67 99 7.0 92 81 70 59 49 38 27 97 7.7 91 80 70 59 48 37 27 62 91 6.9 91 91 84 73 62 51 41 88 7.6 88 88 82 71 61 50 39 57 87 6.7 87 87 87 76 65 54 44 84 7.5 84 84 84 74 63 52 41 Temperature of Air on Condenser Coil 105 F 115 F Air On Evaporator Coil Total Total Sensible Capacity (MBh) Total Total Sensible Capacity (MBh) Capacity Input Return Dry Bulb ( F) Capacity Input Return Dry Bulb ( F) (MBh) (kw) (MBh) (kw) CFM WB( F) 86 83 80 77 74 71 68 86 83 80 77 74 71 68 2250 2625 3000 3300 3600 72 91 8.5 63 56 50 44 37 - - 88 9.4 70 63 57 50 44 - - 67 84 8.4 67 60 54 48 41 35 28 81 9.2 65 59 52 46 40 33 27 62 77 8.2 70 63 57 50 44 38 31 74 9.0 61 55 48 42 35 29 23 57 74 8.1 74 74 68 61 55 49 42 72 8.9 72 72 66 60 54 47 41 72 94 8.6 69 61 54 46 38 - - 91 9.4 76 68 61 53 46 - - 67 87 8.4 73 65 58 50 43 35 28 84 9.3 71 64 56 48 41 33 26 62 80 8.3 74 69 61 53 46 38 31 77 9.1 67 59 52 44 36 29 21 57 77 8.2 77 76 73 65 58 50 42 74 9.0 74 74 71 63 56 48 41 72 98 8.7 75 66 57 48 40 - - 94 9.5 82 73 65 56 47 - - 67 90 8.5 79 70 62 53 44 35 27 87 9.3 77 68 60 51 42 33 25 62 82 8.3 79 74 65 56 48 39 30 80 9.2 72 64 55 46 37 29 20 57 79 8.2 79 79 78 69 60 51 43 77 9.0 77 77 75 67 58 49 40 72 99 8.7 80 70 60 50 41 - - 95 9.5 88 78 69 59 49 - - 67 92 8.5 85 75 65 55 46 36 26 88 9.4 83 73 63 54 44 34 24 62 84 8.4 82 77 68 59 49 39 29 81 9.2 77 68 58 49 39 29 19 57 81 8.3 81 81 80 70 60 51 41 78 9.1 78 78 77 68 58 48 39 72 101 8.7 85 74 63 53 42 - - 97 9.5 94 83 73 62 51 - - 67 93 8.6 90 79 68 58 47 36 25 89 9.4 89 78 67 56 46 35 24 62 85 8.4 85 80 72 61 50 40 29 82 9.2 82 72 62 51 40 30 19 57 82 8.3 82 82 82 71 60 50 39 80 9.1 80 80 80 69 58 47 37 Unitary Products Group 5

TABLE 6: SYSTEM COOLING CAPACITIES AND POWER REQUIREMENTS (HF-07/LF-07) (CONTINUED) Temperature of Air on Condenser Coil 125 F Air On Evaporator Coil Total Total Input Sensible Capacity (MBh) Capacity (kw) (MBh) Return Dry Bulb ( F) CFM WB( F) 86 83 80 77 74 71 68 72 84 10.2 77 70 64 57 51 - - 2250 67 77 10.0 64 57 51 45 38 32 25 62 72 9.8 53 46 40 33 27 21 14 57 70 9.7 70 70 65 59 52 46 39 72 87 10.2 83 76 68 60 53 - - 2625 67 80 10.1 69 62 54 47 39 32 24 62 74 9.9 59 50 42 35 27 20 12 57 72 9.8 72 72 69 62 54 46 39 72 90 10.3 90 81 72 63 55 - - 3000 67 83 10.2 75 66 58 49 40 31 23 62 77 10.0 66 54 45 36 27 19 10 57 75 9.9 75 75 73 65 56 47 38 72 92 10.4 92 87 77 67 58 - - 3300 67 84 10.2 81 71 62 52 42 32 23 62 78 10.0 73 59 48 38 29 19 9 57 76 9.9 76 76 75 65 56 46 36 72 93 10.4 93 93 82 71 61 - - 3600 67 86 10.2 86 77 66 55 44 34 23 62 79 10.0 79 65 52 41 30 19 9 57 77 9.9 77 77 77 66 56 45 34 TABLE 7: HF-07 CHARGING CURVE Charging Curve HF-07 330 Discharge Pressure 310 290 270 250 230 210 115ºF Ambient 105ºF Ambient 95ºF Ambient 85ºF Ambient 190 170 75ºF Ambient 60 70 80 90 100 Suction Pressure 6 Unitary Products Group

SEQUENCE OF OPERATION UNIT OPERATION - 7-1/2 TON When the external control calls for cooling at terminal Y1: The system controller (SC) is energized. The system controller starts the tandem compressors and enables the condenser fans by energizing contactor 1M (2M on the 208/230 volt models). Condenser fan motor #1 is energized with the compressor. Fan motor #2 operation is controlled through the Pressure Switch (PS) which will de-energize the motor when the discharge pressure falls below 180 psi. Safety Lockout: The system controller (SC) has a lockout circuit to prevent compressor short-cycling on a safety control with automatic reset. If the high or low refrigerant pressure switches (HP or LP) open, the SC will enter lockout mode. SC provides a 90 second bypass of the low pressure switch LP to prevent nuisance lockouts during unit start-up. A malfunction light (24V, 2 A max. resistive load) can be energized through SC, by connecting the light between terminals X and B on TB1. NOTE: To reset the unit after a lockout: a. Turn the system switch on the thermostat to the OFF position and back to the COOL position. OR b. Increase the set point of the room thermostat above the temperature in the conditioned space and return it to its original setting. If the unit continues to be shut down by one of its safety controls, a service man should be called to determine the cause of the problem. Repeated resetting of the lockout circuit may damage the unit. Unitary Products Group 7

GROUND LUG 3-PHASE LINE VOLTAGE POWER SUPPLY SIZE POWERWIRING, DISCONNECT SWITCH, AND FUSING PER ELECTIRICAL DATA TABLE NOTE: USE COPPER CONDUCTORS ONLY TB2 R B Y1 FACTORY MOUNTED PIGTAILS ON TERMINALS OF COMPRESSOR CONTACTOR 1M TERMINALS ON BLOCK TB1 OF BLOWER UNIT 24 VOLT R B Y O W X 53 G 60 66 WIRE IN ACCORDANCE WITH ALL LOCAL AND NATIONAL ELECTRICAL CODES R Y G THERMOSTAT The field wiring connected to these dummy terminals on TB2 can be routed directly from the condensing unit to the thermostat if desired. NOTE: SEE PN# 036-13335-002 FOR APPLICABLE THERMOSTATS. FIGURE 1 - TYPICAL FIELD WIRING WITH AIR HANDLER * ) + HF-07, UNIT 4-POINT LOAD (lbs) Total A B C D HF-07 383 83 115 107 78 FIGURE 2-4 POINT LOADS 8 Unitary Products Group

TERMINAL STRIP TB1 ON HF-07 R Y1 B TERMINAL STRIP ON FURNACE R Y G W C THERMOSTAT* TERMINALS R Y G W COIL *24-volt thermostat 24-VOLT ISOLATION RELAY (FIELD SUPPLIED) FIELD-INSTALLED ACCESSORIES - 0 F LOW AMBIENT KITS - An auto-transformer and temperature control maintain stable system operation by reducing the speed of the condenser fan motor. FIGURE 3- TYPICAL FIELD WIRING WITH 7-1/2 TON FURNACE CLEARANCES All units require certain minimum clearances for proper operation and service. Refer to Figure 5 for these clearances. TABLE 8: MINIMUM CLEARANCES DISTANCE CLEARANCE DESCRIPTION IN INCHES Overhead (Top) 120 Front (Access Cover) 36 Rear 24 Left Side 30 Right Side 30 Do not permit overhanging structures or shrubs to obstruct condenser air discharge. Additional height may be required for snow clearance if winter operation is expected. Unitary Products Group 9

UNIT 7-1/2 Ton. A B DIM (In.) C D 70-1/8 32 29-5/8 16-1/12 All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request. FIGURE 4- CENTER OF GRAVITY AIR OUT AIR OUT CONTROL BOX ACCESS AIR IN SERVICE PORT LOCATION 39 15-3/4 1-1/8 SUCTION LINE 5/8 OD LIQUID LINE HF-07 2-3/4 32 7/8" KNOCKOUT ACCESSORY WIRING ENTRY 2-1/4 5-7/8 8-3/4 5-3/8 32-1/2 70-1/2 CONDENSER FAN MOTOR ACCESS 6-3/4 7-3/4 7/8 DIA CONTROL WIRING ENTRY COMPRESSOR AND CONDENSER FAN MOTOR ACCESS 1-3/8 DIA. POWER WIRING ENTRY All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request. FIGURE 5- UNIT DIMENSIONS & CLEARANCES HF-07 10 Unitary Products Group

GUIDE SPECIFICATIONS Furnish and install UPG air-cooled condensing units or equivalent, suitable for ground or roof mounting. Units shall have capacities and efficiencies as outlined in the schedules shown on the plans and shall be installed in accordance with all applicable national and local codes. I. GENERAL a. Units shall be manufactured in a facility registered under the ISO 9002 manufacturing quality standard. b. Units shall be UL and CSA approved. c. Unit shall be packaged to allow outdoor storage. d. Hermetic compressors shall be covered by a five year limited warranty. e. All other unit parts shall be covered by a full year limited warranty. II. UNIT CABINET a. Cabinet shall be constructed of 18 gauge, zinc-coated steel, finished with a powder paint process capable of withstanding a minimum of 750 salt spray hours according to ASTM B117. b. Cabinet screws shall comply with the ASTM B117 salt spray test for a minimum of 750 hours. c. Panels shall be removable for easy access to all internal components during maintenance and service. d. Cabinet shall feature a separate access panel for the controls so that unit airflow need not be disturbed during servicing. e. Permanently attached base rails shall have 3-way fork lift access and lifting holes for ease of installation. III. COMPRESSOR a. Compressor shall be a scroll compressor with integral motor overload protection. b. Compressors shall have an integral crankcase heater to keep refrigerant from diluting the compressor oil in the sump. Crankcase heater shall be field replaceable without removal of the charge. c. Compressor shall be mounted on isolators to limit the transmission of sound and vibration. IV. CONDENSER AND FANS a. Fan motors shall be single phase, direct-drive with propeller-type condenser fans which discharge air vertically upward. b. Units with more than one condenser fan motor shall be wired to distribute the single phase motor loads across the 3 phase power supply, thus minimizing phase imbalance on multiple unit installations. c. Fan motors shall be totally enclosed with permanently lubricated ball-bearings for longer wear during start and stop cycles. d. Fan motors shall have inherent overload protection. e. Coil shall be constructed of rifled copper tubing mechanically expanded and bonded to louvered aluminum fins. Coil shall include an integral subcooler. V. REFRIGERATION COMPONENTS a. Refrigeration system contains both high and low pressure cut-outs. b. Service valves to ease installation and recovery of refrigerant. c. External ports to accommodate gauge lines, allowing for easy servicing of the unit. d. Each unit ships with a filter drier for field installation. e. Holding charge of R-22. VI. CONTROLS a. Each unit is equipped with 24 volt control circuit with terminal blocks. b. Color-coded wiring for easy service and trouble shooting. c. Independent line break thermal protection for the condenser fans. d. 5 minute anti-short cycle timer to protect the compressor from frequent cycling. e. Unit safety lockouts which automatically reset from the thermostat once the anti-short cycle timer is satisfied. Safety lockouts will also generate a 24 volt signal to the "X" terminal, allowing notification to the user via the thermostat fault light (if present). These safety lockouts shall include: High refrigerant pressure. Low refrigerant pressure (low refrigerant pressure shall be bypassed for the first 90 seconds of operation to eliminate nuisance trips). Compressor motor protection to automatically shutdown the unit in the event of motor overcurrent or excessive temperature conditions. Unit shall automatically restart after the line break protector cools. Low ambient operation down to 45 F (7 C) without a low ambient kit. (Operation down to 0 F with the optional low ambient kit.) VII. ELECTRICAL a. Units shall be volts, 3 phase, with a single power point connection. b. Unit control circuit shall have a 24 volt transformer, sized sufficiently to operate the indoor fan. c. All condenser fan motors and the secondary of each transformer shall be grounded. Unitary Products Group 11

VIII. ACCESSORIES AND OPTIONS a. Head Pressure Control b. Shall include a condenser fan motor and an auto transformer to slow the speed of the condenser fan at low ambient temperatures, allowing operation of the condensing unit down to 0 F. IX. COIL GUARD a. Field installed decorative grille shall be placed on the units to provide further coil protection. b. Phenolic Coating on Condenser Coil. c. Condenser coils shall be dipped in a four-coat phenolic coating process to provide longer life in corrosive conditions. Subject to change without notice. Printed in U.S.A. 036-21378-002-B-0703 Copyright by Unitary Products Group 2003. All rights reserved. Supersedes: 036-21378-002-A-1002 Unitary 5005 Norman Products York OK Group Drive 73069