Heat Pumps COMFORT NEED IT. When You

Similar documents
Product Information Guide

MODEL SCM INSTALLATION, OPERATION & MAINTENANCE MANUAL

PRODUCT GUIDE EARTHLINKED TECHNOLOGIES GEOTHERMAL RENEWABLE ENERGY SYSTEMS SIMPLE. EFFICIENT. EFFECTIVE.

MODEL LAHP48 INSTALLATION, OPERATION & MAINTENANCE MANUAL

MAC N-407 Air-Cooled Chiller

MODEL SCM INSTALLATION, OPERATION & MAINTENANCE MANUAL

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

MACH N-407 Heat Pump Air-Cooled Chiller

Call us today! (800)

Mascot. Gas-Fired Residential and Commercial Wall-Mounted Boiler. Easy Installation, 96% Efficiency, Fully Condensing

Call us today! (800)

60 TON AIR-COOLED CHILLER. Call us today! (800) PA-ACCTR-60 GENERAL DIMENSIONS ELECTRICAL DATA 60 TON AIR-COOLED CHILLER FEATURES

Commercial High-Efficiency Condensing Units

EREBA ACCESS. Easy and fast installation Hydronic module available Compact, reliable and efficient USE RANGE CONFORMITY

PRODUCT GUIDE

BLUEWAY DC INVERTER AIR TO WATER HEAT PUMP

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

50TM TFF COMBINATION HEATING/COOLING UNITS

Performance and rugged durability. Commercial Split Systems Up to 20-Ton TSA/TPA Models

MAC-120HE-03 Air-Cooled Chiller

50TM COMBINATION HEATING/COOLING UNITS

Call us today! (800)

Heat Pump Water Heater

ENGINEERING SPECIFICATIONS

T-CLASS Commercial Split Systems Up to 20-Ton TSA/TPA Models

Eco ULTRA - Heat Pump Buffer Tanks - Arctic Heat Pumps

Rooftop Units 60HZ. PACKAGED HEAT PUMPS 13HPP / rhp13 PRODUCT SPECIFICATIONS 13 HPP 36 A P - 1 A RHP 13 A 36 T - 1 A MODEL NUMBER IDENTIFICATION

AQUASNAP JUNIOR 30RHV

precision controlled industrial process chillers cooling capacity: ,255,668 BTU /hr ( tons) improved productivity & reduced costs

Hydronic Air Handler Powered by Tankless Technology

ENGINEERING SPECIFICATIONS

water to water heat pumps

Split Type System. Air to Water Heat Pump

Compact, Self-Contained unit that offer low installation cost plus dependable performance.

LIGHT COMMERCIAL. Packaged Units and Split Systems APPLICATIONS: OFFICES RETAIL STORES RESTAURANTS CLINICS

Series PIN. New Construction or Renovation. Application Flexible Quiet Comfort Damage Protection

Rheem High Efficiency Modulating EcoNet Enabled Air Handler

CB/CF. Series CONDENSERS AND CONDENSING UNITS. Features:

CZT CZT. High efficiency air to water heat pumps with E.V.I. compressors E.V.I. HP OTHER VERSIONS ACCESSORIES

LZT High efficiency air to water heat pumps with E.V.I. compressors

PACKAGED TERMINAL AIR CONDITIONER SOLUTIONS. New Construction Model. Model EGN Superior Sound Performance. High Efficiency

Now Available with PVC & Polypropylene Vent Configurations

Air-to-Water Heat Pumps + Boilers A Dynamic Duo

AC, HP and Air Handler Units Up to 20 Tons. Commercial Split Systems. Reliable, cost-effective and servicefriendly split systems inside and out

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

E Z S E R I E S " W X 16" H

Series PIC. New Construction and Renovation; Replaces RetroAire VPAC and First Company DPU Application Flexible Quiet Comfort Damage Protection

TECHNICAL SPECIFICATIONS

BRIZA EC 12 HYBRID. Low Water-Temperature system LOW TEMPERATURE SYSTEM / HEATING AND COOLING

Dunkirk H 2 O. Innovative. Efficient. Dependable. Dunkirk.

Domestic Hot Water Heaters and Boilers FTIIIC-6

Ductless Series Variable Speed Split Systems

FTIIIC-10. Domestic Hot Water Heaters and Boilers

ISERIES VERTICAL AHU ENGINEERING SPECIFICATIONS

PACKAGED TERMINAL AIR CONDITIONER SOLUTIONS. New Construction Model. Model EGN Superior Sound Performance. High Efficiency

13 GEP A L P - 1 A

Rheem High Efficiency Two-Stage EcoNet Enabled Air Handler

AFFORDABLE RENEWABLE CLEAN

AIR COOLED HEAT PUMP FOR OUTDOOR INSTALLATION FROM 4,2 TO 35,1 kw

Product Data. Features/Benefits. OMNIZONE 50BRN,BZN Water-Cooled and Remote Air-Cooled Indoor Self-Contained Systems. 5 to 20 Nominal Tons

Product Data. Features/Benefits. GEMINI 38AKS Commercial Air-Cooled Split Systems 50/60 Hz. 25 to 40 Nominal Tons (82.8 to 127.

ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical

Session: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island

SWIMMING POOL HEAT PUMPS

Water Chiller Solutions. A solution to every water cooling need.

LSA LSA A + Air cooled water chillers with axial fans VERSIONS ACCESSORIES

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

HEATING COOLING HOT WATER PRODUCT LINE

Rheem High Efficiency Two-Stage EcoNet Enabled Air Handler

VERTICAL AHU ENGINEERING SPECIFICATIONS BULLETIN

High Ambient / High Efficiency Series. R - 410a. 50Hz. Ducted Split Air Conditioners (5.0 kw kw)

ULTRATEMP HIGH PERFORMANCE HEAT PUMP

FXLF-9. High Efficiency Water Heaters and Boilers

PROJECT MANUAL GUIDE SPECIFICATIONS FOR: PFANNENBERG SERIES CC COMPACT PACKAGED CHILLERS PART 1 GENERAL

Hydronic Air Handler Powered by Tankless Technology

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

Outstanding Performance; Application Flexibility

Vertical Air Handler Unit

30GT FLOTRONIC AIR-COOLED CHILLERS

A/C Cooling Load calculation and measurement

CFFWA4P-16-1-U Chilled/Hot Water Universal Mount Fan Coil (4-Pipe) 4-Pipe Heat / Cool Fan Coil 48,000 BTUH

CFFWA4P-12-1-U Chilled/Hot Water Universal Mount Fan Coil (4-Pipe) 4-Pipe Heat / Cool Fan Coil 36,000 BTUH

Heating Systems Company LAARS INTRODUCES. The MASCOT LX. A Boiler. An All-in-One Answer to Your Home Heating and Hot Water Needs

Commercial High-Efficiency Condensing Units

Technical Data Manual Model Nos. and pricing: see Price List

CONDENSERS AND CONDENSING UNITS

Dunkirk H 2 O. Innovative. Efficient. Dependable. Dunkirk.

CFFWA4P-08-1-U Chilled/Hot Water Universal Mount Fan Coil (4-Pipe) 4-Pipe Heat / Cool Fan Coil 24,000 BTUH

HEATING & COOLING SUBMITTAL The DuraPac Series Unit 559F/579F180, 216, 240, , 18, 20, and 25 NOMINAL TONS

PACKAGE AIR CONDITIONER

Solstice Air to Water Heat Pump

48PGD/E/F/L/M/N PG20-28

THE WORLD S MOST EFFICIENT HEAT PUMP

Submitted to Reference Approval Construction Unit Designation Schedule #

The most energy-efficient commercial split system* Commercial Air Conditioners and Heat Pumps SSB/SPB Models

Geothermal HIGH EFFICIENCY HEATING & COOLING. the logical choice for energy efficient residential heating and cooling

The Premium Quality Fan Coil Units for Vertical, Horizontal (Left or Right) Application with Direct Expansion, Hydronic or Electric Heat

comfort where it counts Variable Speed Ductless Split Systems Single Zone Air Conditioners / Heat Pumps

Gas Fired Double-Effect Chiller-Heater CH-MG Series: 150 and 200 RT Cooling Capacities

Nordic Heat Pump Product Guide

Transcription:

Heat Pumps COMFORT When You NEED IT

COMFORT When You NEED IT SpacePak s Solstice heat pumps are air-to-water reverse cycle heat pumps that use the comfort of Hydronics as the primary source for both heating and cooling demands. In any season, SpacePak units provide perfectly conditioned air with reliability and efficiency. Solstice heat pumps work similar to conventional heat pumps by circulating refrigerant, which vaporizes at a low temperature in its enclosed evaporator, producing additional energy in the process. Further concentration of the conditioned warm vapor occurs in SpacePak s dual programmable compressor raising it to a temperature where it can be circulated through one of the many SpacePak hydronic air handlers for distribution to the occupied space. Flexible Solutions Heat pumps can be used in many types of applications from small homes with multiple thermostat driven zones, to large homes and light commercial applications. Perfect for zoning, these units can operate in a loop that can provide conditioned air to several individual zones utilizing single or multiple air handlers, allowing total comfort control to the occupied space. Whether radiant heating & cooling, domestic hot water, dehumidification, process cooling, or even conventional with multiple air handlers SpacePak Solstice heat pumps offer application flexibility requiring less equipment outside. Units can be easily installed at ground level, on rooftops or even in remote locations when necessary. High Efficiency Solstice heat pumps utilize a condenser coil that is 30% larger than standard units and operate with a COP of up to 4. Designed for heating in colder climates, SpacePak Solstice produce up to 67,000 BTU/h, and can effectively heat in ambient temperatures as low as 0 F. Perfect Match SpacePak s Solstice allows custom control not obtainable by most traditional refrigerant-based systems. Heat pumps use hydronics (water) to provide unparalleled load matching by utilizing adjustable water flow, water temperature, and airflow settings. 2

Green by Nature An ultra safe and environmentally friendly design keeps all refrigerant sealed in its powder coated galvanized steel cabinet and outside the occupied space. Heat pump high efficiency compressors operate on R-410A but use only a fraction of the refrigerant needed by other systems, while providing superior performance and high COP and EER. Solstice heat pumps run quieter than traditional systems with their dual fan, horizontal discharge configuration and soft start activation. System Layout Solstice Key: = = Return Illustration depicts heating application. In cooling applications chilled water replaces hot water supply lines. 3

EXTREME Solstice Extreme, SpacePak s low ambient heat pump provides primary heating and cooling even in severe weather climates. Its environmentally friendly design uses EVI technology and the clean efficient characteristics of hydronics as its primary energy source to deliver perfectly conditioned air to any occupied space. Standard Features Enhanced Vapor Injection 66,480 BTU/h at 47 F Ambient 3.3 Ton of Cooling at 95 F Ambient Simple Piping & Pumping Installation & Service Friendly Easily Zoned Proven Integrated Control Outdoor Reset Green Hydronic Energy No Refrigerant in Occupied Space Low Ambient Freeze Protection Enhanced Vapor Injection (EVI) The award winning EVI technology and high efficiency condenser used in SpacePak low ambient heat pumps, provides improved efficiency, reliability and heating capacities. EVI increases heating capacity by over 30%, making it the perfect compressor for severe ambient conditions (0 F) in cold climates, while maintaining the ability to cool during the summer months. EVI Tube Dynamic Exhaust Valve Dynamic Scroll Motor 4

EXTREME Specifications Model LAHP - 048 COP Heating Capacity (47 F/8 C Ambient temp. 120 F/50 C Water) 66,480 BTU/h (18.9kW) 3.26 Heating Capacity (17 F/-8 C Ambient temp. 120 F/50 C Water) 46,440 BTU/h (13.6kW) 2.35 Heating Capacity (5 F/-15 C Ambient temp. 120 F/50 C Water) 42,240 BTU/h (12.4kW) 2.12 Cooling Capacity (95 F/35 C Ambient temp. 44 F/6.7 C Water) 40,000 BTU/h (11.7kW) 2.43 Volts 230V/1ph/60Hz Minimum water supply temperature 42 F (5.5 C) Maximum water supply temperature 131 F (55 C) Minimum operating ambient temperature -8 F (-22 C) Maximum operating ambient temperature 105 F (40 C) Minimum water flow 10 GPM (37.9 l/min) Rated water flow 11 GPM (41.6 l/min) Pressure drop at recommended flow 17.1 ft/7.4 PSI (35.8 kpa) Heating current 31A Cooling Current 23.5A Noise level at max fan speed (Heating or Cooling) 62 db (A) Compressor EVI Scroll Installed weight 386 lbs (175 kg) Dimensions 5

EXTREME Performance Water Ambient LAHP Heating Operation Capacity BTU/hr Water DP ft WC Watts COP Water Ambient LAHP Cooling Operation Capacity BTU/hr Water DP ft WC -5 37,500 14.6 3,880 2.30 70 41,100 15.0 4,298 2.80 110 17 44,800 14.6 3,970 2.70 42 82 39,950 15.0 4,414 2.65 47 60,580 14.6 4,263 3.75 95 38,800 15.0 4,897 2.32-5 38,500 14.6 4,513 2.00 70 42,500 15.0 4,190 2.97 120 17 46,440 14.6 5,790 2.35 44 82 41,250 15.0 4,238 2.85 47 66,480 14.6 5,963 3.26 95 40,000 15.0 4,820 2.43-5 40,425 14.6 5,249 1.86 70 44,600 15.0 4,240 3.08 130 17 48,762 14.6 5,371 2.18 47 82 43,200 15.0 4,274 2.96 47 69,804 14.6 5,768 3.04 95 41,800 15.0 4,708 2.60 All data based upon pure water @ 11.0 GPM Watts COP 80,000 LAHP Heating Performance 72,000 64,000 Water 130 HEATING CAPACITY, BTU/hr 56,000 48,000 40,000 32,000 24,000 16,000 1.00-10 -5 0 5 10 15 20 25 30 35 40 45 50 OUTDOOR AMBIENT TEMPERATURE, F All data based upon pure water @11.0 GPM 4.00 3.00 2.00 120 110 Coefficient of Performance 48,000 LAHP LAHP48 Cooling COOLING Performance PERFORMANCE 44,000 Water 42 COOLING CAPACITY, BTU/hr 40,000 36,000 32,000 28,000 24,000 0.0 65 70 75 80 85 90 95 100 OUTDOOR AMBIENT TEMPERATURE, F All data based upon pure water @11.0 GPM 4.0 3.0 2.0 1.0 Coefficient of Performance 44 47 6

SE Standard Features Dual Refrigerant Circuits Simple Piping & Pumping Installation & Service Friendly Easily Zoned Self Diagnostic Control Configurable Low Amp Requirements Quiet Operation Green Hydronic Energy - No Refrigerant in Occupied Space Low Ambient Freeze Protection Sophisticated. but Simple Control Platform Intelligent factory configured control platform, with stateof-the-art self diagnostic microprocessor allow staging of compressors for seamless operation. Amp draw starts low and stays low with no spike at start-up and use a smaller breaker than other heat pump units for even more efficiency benefits. 7

SE Specifications Model SCM - 036 SCM - 060 Heating Capacity 36,840 BTUh (10.8 kw) 52,200 BTUh (15.3 kw) Heating COP 2.65 2.65 Cooling Capacity 36,000 BTUh (10.5 kw) 48,000 BTUh (14.1 kw) Voltage 230v/1ph/60Hz 230v/1ph/60Hz Min Temp 36 F (2.2 C) 36 F (2.2 C) Max Temp 125 F (51.7 C) 125 F (51.7 C) Min Water Flow 7 GPM (26.5 l/min) 10 GPM (37.9 l/min) Rated Water Flow 10 GPM (37.8 l/min) 12 GPM (45.4 l/min) dp @ Rated Flow 15.8 ft (47.7 kpa) 24.2 ft (72.4 kpa) Heating Current 18.0 amps 25.6 amps Cooling Current 16.7 amps 24.8 amps Noise Level 56 db (A) 56 db (A) Compressor Rotary x 2 Rotary x 2 Installed Weight 354 lbs (161 kg) 407 lbs (185 kg) All heating data at 47 F ambient, 120 F supply. All cooling data at 95 F ambient, 44 F supply. Dimensions A B D D1 D2 E F G H J K W W1 W2 Model Leg height Front to return Cabinet depth Mounting lug depth Mounting lug centers Bottom to return Bottom to supply Base to bottom edge of lower fan Overall Height Return connection connection Overall width Mounting lug centers Lug center to edge SCM-036 1" 10" 17 3 /4" 17 3 /8" 15 3 /4" 5 1 /2" 15 1 /4" 25" 53" 1" NPT 1" NPT 43 3 /8" 27 1 /2" 7 15 /16" SCM-060 1" 10" 17 3 /4" 17 3 /8" 15 3 /4" 5 1 /2" 15 1 /4" 25" 53" 1" NPT 1" NPT 43 3 /8" 27 1 /2" 7 15 /16" 8

SE Performance Water SCM-036 Heating Operation Ambient Capacity BTU/hr Water DP ft WC Watts COP Water SCM-036 Cooling Operation Ambient Capacity BTU/hr Water DP ft WC 17 23,397 12.0 2,742 2.50 82 36,225 12.0 3,019 3.20 100 32 33,075 12.0 2,801 3.46 42 95 33,872 12.0 3,528 2.40 47 42,754 12.0 3,008 4.16 105 30,579 12.0 4,497 1.70 17 21,718 12.0 3,190 1.99 82 38,500 12.0 3,208 3.60 110 32 30,703 12.0 3,258 2.76 44 95 36,000 12.0 3,750 2.50 47 39,687 12.0 3,499 3.32 105 32,500 12.0 4,100 1.80 17 20,160 12.0 3,710 1.59 82 42,070 12.0 3,825 3.80 120 32 28,500 12.0 3,790 2.20 47 95 39,338 12.0 4,522 2.80 47 36,840 12.0 4,070 2.65 105 35,514 12.0 5,822 2.00 All data based upon pure water @ 10.0 GPM Watts COP 45,000 SCM-036 Heating Performance 40,000 Water HEATING CAPACITY, BTU/hr 35,000 30,000 25,000 20,000 15,000 10,000 1.00 15 20 25 30 35 40 45 50 OUTDOOR AMBIENT TEMPERATURE, F All data based upon pure water @10.0 GPM 4.00 3.00 2.00 120 110 100 Coefficient of Performance 45,000 40,000 SCM-036 Cooling Performance Water 42 COOLING CAPACITY, BTU/hr 35,000 30,000 25,000 20,000 15,000 1.0 80 85 90 95 100 105 110 OUTDOOR AMBIENT TEMPERATURE, F All data based upon pure water @10.0 GPM 4.0 3.0 2.0 Coefficient of Performance 44 47 9

SE Performance Water SCM-060 Heating Operation Ambient Capacity BTU/hr Water DP ft WC Watts COP Water SCM-060 Cooling Operation Ambient Capacity BTU/hr Water DP ft WC 17 33,075 13.5 3,880 2.50 82 54,102 13.5 5,281 3.00 100 32 46,828 13.5 3,970 3.45 42 95 45,163 13.5 5,510 2.40 47 60,580 13.5 4,263 4.16 105 34,343 13.5 6,285 1.60 17 30,703 13.5 4,513 1.99 82 57,500 13.5 5,262 3.20 110 32 43,468 13.5 4,618 2.76 44 95 48,000 13.5 5,622 2.50 47 56,234 13.5 4,959 3.32 105 36,500 13.5 5,938 1.80 17 28,500 13.5 5,249 1.59 82 62,832 13.5 5,411 3.40 120 32 40,350 13.5 5,371 2.20 47 95 52,451 13.5 5,485 2.80 47 52,200 13.5 5,768 2.65 105 39,885 13.5 5,840 2.00 All data based upon pure water @ 12.0 GPM Watts COP 64,000 56,000 SCM-060 Heating Performance 13.00 Water 120 HEATING CAPACITY, BTU/hr 48,000 40,000 32,000 24,000 16,000 1.00 15 20 25 30 35 40 45 50 OUTDOOR AMBIENT TEMPERATURE, F All data based upon pure water @12.0 GPM 5.00 4.00 3.00 2.00 Coefficient of Performance 110 100 64,000 56,000 SCM-060 Cooling Performance Water 42 10 COOLING CAPACITY, BTU/hr 48,000 40,000 32,000 24,000 16,000 80 85 90 95 100 105 OUTDOOR AMBIENT TEMPERATURE, F All data based upon pure water @12.0 GPM 4.0 3.0 2.0 1.0 0.0 Coefficient of Performance 44 47

Solstice BT Hydronic buffer tanks are used as both hydraulic separators and hydronic buffer tanks. As a hydraulic separator, BT's separate the hydronic from the energy source loop (heat pump / boiler) from the hydronic flow in the distribution system (air handlers / emitters). Hydraulic separation is used primarily in systems where flow rates from the source to the distribution vary or with applications utilizing variable speed pumps. The heating or cooling source can be hydraulically decoupled from the distribution system. HighWall Heating & Cooling HighWall fan coils are the perfect indoor complement to our low ambient heat pumps, providing optimum heating and cooling in one classic design. ThinWall Heating & Cooling ThinWall fan coils are the ultra-sleek alternative to HighWall fan coils or can be used in conjunction with a HighWall unit for optimum flexibility. BT's are used as hydronic buffer tanks in systems having several low BTU cooling or heating loads calling at different times or systems operating below the design load condition. BT's store the additional system volume and energy currently not utilized by the system for use on additional calls for heat leading to more efficient system performance and longer equipment life. There are four connections (1 1/2" NPT on BT26 and BT40, 2" NPT on BT80) built into the BT units. Two connections can be piped to the heat pump / boiler, and two connections can be piped to the distribution system. All tanks are durable stainless steel construction with R12 insulation and offered in 26 and 40 gallons with (2) 3kW electric heating elements. 11

260 North Elm Street Westfield, Ma 01085 (800) 465-8558 Fax (413) 564-5815 www.spacepak.com 7555 Tranmere Drive Mississauga, Ontario L5S 1L4 Canada (905) 670-5888 Fax (905) 670-5782 HPB-3