A. Introduction 1. Title: Transmission and Generation Protection System Maintenance and Testing

Similar documents
A. Introduction 1. Title: Transmission and Generation Protection System Maintenance and Testing

A. Introduction 1. Title: Transmission and Generation Protection System Maintenance and Testing

4. Applicability: 4.1. Functional Entities: 4.2. Facilities: 5. Effective Date: See Implementation Plan

The North American Electric Reliability Corporation ( NERC ) hereby submits

Standard PRC Protection System, Automatic Reclosing, and Sudden Pressure Relaying Maintenance

4. Applicability: 4.1. Functional Entities: 4.2. Facilities: 5. Effective Date: See Implementation Plan

4. Applicability: 4.1. Functional Entities: 4.2. Facilities:

Standard PRC-005-3(i) Protection System and Automatic Reclosing Maintenance

Standard PRC-005-3(X) Protection System and Automatic Reclosing Maintenance

Standard PRC Protection System, Automatic Reclosing, and Sudden Pressure Relaying Maintenance

Standard PRC-005-4(X) Protection System, Automatic Reclosing, and Sudden Pressure Relaying Maintenance

Standard PRC-005-X Protection System, Automatic Reclosing, and Sudden Pressure Relaying Maintenance

June 4, 2014 VIA ELECTRONIC FILING. Ms. Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, NE Washington, D.C.

Standard PRC Disturbance Monitoring Equipment Installation and Data Reporting

Standard Development Roadmap

Standard PRC Transmission Relay Loadability

Standard Development Timeline

Standard PRC Protection System and Automatic Reclosing Maintenance. Standard Development Roadmap

Standard PRC 004 5(i) Protection System Misoperation Identification and Correction

Standard PRC Protection System Misoperation Identification and Correction

Standard PRC Protection System Misoperation Identification and Correction

IRO Reliability Coordinator Real-time Reliability Monitoring and Analysis Capabilities

PRC-005. Tips and Updates. February 25th, Jonathan Hayes

PRC (I) August 9, Authored by

Sudden Pressure Relays and Other Devices that Respond to Non-Electrical Quantities

Supplementary Reference & FAQ. Draft

Appendix B. FRCC regional application of the term transmission Protection Systems

Supplementary Reference and FAQ - Draft

Supplementary Reference and FAQ

Supplementary Reference and FAQ - Draft

TOP R4 Unknown Operating State

Protection System Maintenance

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION. North American Electric Reliability ) Docket No. RC Corporation )

NERC s Compliance Enforcement Initiative Find, Fix, Track and Report Implementation

TRANSMISSION ENGINEERING STANDARDS SUBSTATIONS

Airworthiness Directives; Kidde Aerospace Part Number (P/N) Hand-Held Halon Fire Extinguishers

Classifying Forced Outages Transmission Maintenance Procedure No. 5

TRANSMISSION ENGINEERING STANDARDS SUBSTATIONS

NERC PRC Compliance Guide

FACILITY CONNECTION STANDARD

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION ) )

CAN/ULC-S561. To comply, or not to comply. actually it s not even a question! Underwriters Laboratories of Canada. By Alan Cavers & Brian McBain

M2500 Engine Controller Installation Manual

Alarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN)

POLICY. Carbon Monoxide (CO) is an odorless, colorless gas that can cause sudden illness and death. 1

SECTION AUTOMATIC TRANSFER SWITCHES

Safety Function: Single-beam Area Access Control (AAC)

CIRCUIT BREAKER FAIL PROTECTION

AS/NZS :2011. Household and similar electrical appliances Safety AS/NZS :2011. Part 1: General requirements

NERC Requirements for Setting Load-Dependent Power Plant Protection: PRC-025-1

AS/NZS IEC :2013

CERTIFICATION BULLETIN

2012 Edition. Tech Topics: Standards & Codes. Note 4, Issue 1. Points of Interest: Introduction. Background. Changes to Definitions in Article 100

CERTIFICATION BULLETIN

Australian Standard. Smoke alarms. AS (Incorporating Amendment Nos 1, 2, 3 and 4) AS 3786

La Marche Manufacturing Company Option 46 Series. Digital Combined Accessory Package. Installation and Operation Manual

Preliminary Operations and Maintenance Plan Baron Winds Project

GRADE CROSSING SIGNAL SYSTEM SAFETY REGULATIONS

La Marche Manufacturing Company Option 16 Series. Digital Combined Accessory Package. Installation and Operation Manual

IEEE Transformer Committee PC Distribution Transformer Monitoring - User

Distribution Control Center Operator Training

Fact File 48 Guide to BS EN 54-13:2017 Fire Detection and alarm systems:

UNDERSTANDING ELECTRICAL SAFETY RISKS

CHAPTER 4 POLICE DEPARTMENT PAGE NO.

Relay Performance Index for a Sustainable Relay Replacement Program

AS/NZS :2016

National Grid Requirements for Interconnection of Parallel Generation

[Docket No. FAA ; Product Identifier 2017-NE-02-AD; Amendment ; AD ]

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection

NZQA unit standard version 2 Page 1 of 6. Perform installation and maintenance of telecommunications radio systems and services

PS1240x Series Dual Voltage Access Control Power Supply Systems Operating and Installation Instructions Rev D.01

ELECTRIC SERVICE RELIABILITY IN PENNSYLVANIA 2008

Molded Case Circuit Breakers, Bulletin 140G

NFPA Updates (c) 2015 SSR, Inc. All rights reserved Florida AHCA Conf

DEPARTMENT OF PUBLIC SAFETY DIVISION OF FIRE PREVENTION AND CONTROL

This is a preview - click here to buy the full publication. IEC Quality Assessment System for Electronic Components (IECQ System)

SAFETY INFORMATION AND WARNINGS

[Docket No. FAA ; Directorate Identifier 2004-CE-25-AD; Amendment ; AD ]

Carbon Monoxide Detectors in New and Existing Buildings

SUMMARY: Policy Title: Electrical Safety Work Practice Program. Policy Number: UNIV-EHS 430 Policy Approved: January 2014

PRC NERC Protection System Maintenance Standard PRC-005-2

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL

AS/NZS :1995. Emergency escape lighting and exit signs for buildings AS/NZS :1995. Part 2: Inspection and maintenance

National Grid / Supplement to Specifications for Electrical Installations / ESB ver Doc. File: ESB _ver3_

Changes in NFPA

Australian Standard. Emergency escape lighting and exit signs for buildings. Part 1: System design, installation and operation AS 2293.

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER

MEMORANDUM. TERESA McCLISH, COMMUNITY DEVELOPMENT DIRECTOR

Winthrop University Police Department. Daily Fire Log. Month of January, 2013

Power System Protection Part 2 Dr.Prof. Mohammed Tawfeeq. Zones of Protection

NEW YORK CITY FIRE DEPARTMENT. Notice of Public Hearing and Opportunity to Comment on Proposed Rule

PLUMBING & CARBON MONOXIDE

Clarification. Summary of Changes. Summary of Changes. Alan Cavers Area Manager Fire & Security Systems Group

LEE COUNTY ORDINANCE NO

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

NECA. Standard for Electrical Safety in the Workplace

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

This chapter shall be known as the "City of Bayfield Alarm Systems Ordinance."

MODEL B2 INSTALLATION MANUAL

CALIFORNIA DEPARTMENT of FORESTRY and FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL UL 300

Transcription:

A. Introduction 1. Title: Transmission and Generation Protection System Maintenance and 2. Number: PRC-005-1.1b 3. Purpose: To ensure all transmission and generation Protection Systems affecting the reliability of the Bulk Electric System (BES) are maintained and tested. 4. Applicability 4.1. Transmission Owner. 4.2. Generator Owner. 4.3. Distribution Provider that owns a transmission Protection System. 5. Effective Date: To be determined B. Requirements 5. R1. Effective Date: In those jurisdictions where regulatory approval is required, all requirements become effective upon approval. In those jurisdictions where no regulatory approval is required, all requirements become effective upon Board of Trustee s adoption or as otherwise made effective pursuant to the laws applicable to such ERO governmental authorities. B. Requirements R1. Each Transmission Owner and any Distribution Provider that owns a transmission Protection System and each Generator Owner that owns a generation or generator interconnection Facility Protection System shall have a Protection System maintenance and testing program for Protection Systems that affect the reliability of the BES. The program shall include: R1.1. R1.2. Maintenance and testing intervals and their basis. Summary of maintenance and testing procedures. R2. Each Transmission Owner and any Distribution Provider that owns a transmission Protection System and each Generator Owner that owns a generation or generator interconnection Facility Protection System shall provide documentation of its Protection System maintenance and testing program and the implementation of that program to its Regional Reliability OrganizationEntity on request (within 30 calendar days). The documentation of the program implementation shall include: R2.1. Evidence Protection System devices were maintained and tested within the defined intervals. R2.2. C. Measures Date each Protection System device was last tested/maintained. M1. Each Transmission Owner and any Distribution Provider that owns a transmission Protection System and each Generator Owner that owns a generation or generator interconnection Facility Protection System that affects the reliability of the BES, shall have an associated Protection System maintenance and testing program as defined in Requirement 1. Page 1 of 9

M2. Each Transmission Owner and any Distribution Provider that owns a transmission Protection System and each Generator Owner that owns a generation or generator interconnection Facility Protection System that affects the reliability of the BES, shall have evidence it provided documentation of its associated Protection System maintenance and testing program and the implementation of its program as defined in Requirement 2. D. Compliance 1. Compliance Monitoring Process 1.1. Compliance Monitoring Responsibility Regional Reliability OrganizationEntity. 1.2. Compliance Monitoring Period and Reset Time Frame One calendar year. 1.3. Data Retention The following evidence retention periods identify the period of time an entity is required to retain specific evidence to demonstrate compliance. For instances where the evidence retention period specified below is shorter than the time since the last audit, the Compliance Enforcement Authority may ask an entity to provide other evidence to show that it was compliant for the full time period since the last audit. The Transmission Owner and any Distribution Provider that owns a transmission Protection System and each Generator Owner that owns a generation or generator interconnection Facility Protection System, shall retain evidence of the implementation of its Protection System maintenance and testing program for three years. The Compliance Monitor shall retain any audit data for three years. 1.4. Additional Compliance Information The Transmission Owner and any Distribution Provider that owns a transmission Protection System and the Generator Owner that owns a generation or generator interconnection Facility Protection System, shall each demonstrate compliance through self-certification or audit (periodic, as part of targeted monitoring or initiated by complaint or event), as determined by the Compliance Monitor. 2. Violation Severity Levels of Non-Compliance(no changes) 2.1. Level 1: Documentation of the maintenance and testing program provided was incomplete as required in R1, but records indicate maintenance and testing did occur within the identified intervals for the portions of the program that were documented. 2.2. Level 2: Documentation of the maintenance and testing program provided was complete as required in R1, but records indicate that maintenance and testing did not occur within the defined intervals. 2.3. Level 3: Documentation of the maintenance and testing program provided was incomplete, and records indicate implementation of the documented portions of the maintenance and testing program did not occur within the identified intervals. 2.4. Level 4: Documentation of the maintenance and testing program, or its implementation, was not provided. Page 2 of 9

E. Regional Differences None identified. Version History Version Date Action Change Tracking 0 April 1, 2005 Effective Date New 1 December 1, 2005 1 February 7, 2006 1a November 5, 2009 1a February 17, 2011 1a February 17, 2011 1a September 26, 2011 1.1a February 1, 2012 1b February 3, 2012 1. Changed incorrect use of certain hyphens (-) to en dash ( ) and em dash ( ). 2. Added periods to items where appropriate. 3. Changed Timeframe to Time Frame in item D, 1.2. Adopted by NERC Board of Trustees Interpretation of R1, R1.1, and R1.2 adopted by the NERC Board of Trustees Added Appendix 1 - Interpretation regarding applicability of standard to protection of radially connected transformers adopted by the NERC Board of Trustees (adopted and filed as - 1a instead of -1b) Adopted by Board of Trustees FERC Order issued approving interpretation regarding applicability of standard to protection of radially connected transformersof R1 and R2 (FERC s Order is effective as of September 26, 2011) Errata change: Clarified inclusion of generator interconnection Facility in Generator Owner s responsibility FERC Order issued approving interpretation of R1, R1.1, and R1.2 (FERC s Order is effective as ofdated March 14, 2012). Updated version from 1a to 1b. 01/20/05 Project 2009-10 Interpretation Project 2009-17 Interpretationinterpretati on Project 2009-17 Interpretation Revision under Project 2010-07 Project 2009-10 Interpretation 1.1b April 23, 2012 Updated standard version to 1.1b to reflect Revision under Project Page 3 of 9

FERC approval of PRC-005-1b. 2010-07 1.1b May 9, 2012 Adopted by Board of Trustees Page 4 of 9

Appendix 1 Requirement Number and Text of Requirement Question: R1. Each Transmission Owner and any Distribution Provider that owns a transmission Protection System and each Generator Owner that owns a generation Protection System shall have a Protection System maintenance and testing program for Protection Systems that affect the reliability of the BES. The program shall include: R1.1. Maintenance and testing intervals and their basis. R1.2. Summary of maintenance and testing procedures. R2. Each Transmission Owner and any Distribution Provider that owns a transmission Protection System and each Generator Owner that owns a generation Protection System shall provide documentation of its Protection System maintenance and testing program and the implementation of that program to its Regional Reliability Organization on request (within 30 calendar days). The documentation of the program implementation shall include: R2.1 Evidence Protection System devices were maintained and tested within the defined intervals. R2.2 Date each Protection System device was last tested/maintained. Is protection for a radially-connected transformer protection system energized from the BES considered a transmission Protection System subject to this standard? Response: The request for interpretation of PRC-005-1 Requirements R1 and R2 focuses on the applicability of the term transmission Protection System. The NERC Glossary of Terms Used in Reliability Standards contains a definition of Protection System but does not contain a definition of transmission Protection System. In these two standards, use of the phrase transmission Protection System indicates that the requirements using this phrase are applicable to any Protection System that is installed for the purpose of detecting faults on transmission elements (lines, buses, transformers, etc.) identified as being included in the Bulk Electric System (BES) and trips an interrupting device that interrupts current supplied directly from the BES. A Protection System for a radially connected transformer energized from the BES would be considered a transmission Protection System and subject to these standards only if the protection trips an interrupting device that interrupts current supplied directly from the BES and the transformer is a BES element. Page 5 of 9

Page 6 of 9

Appendix 2 1 Requirement Number and Text of Requirement R1. Each Transmission Owner and any Distribution Provider that owns a transmission Protection System and each Generator Owner that owns a generation Protection System shall have a Protection System maintenance and testing program for Protection Systems that affect the reliability of the BES. The program shall include: R1.1. Maintenance and testing intervals and their basis. R1.2. Summary of maintenance and testing procedures. Question #1: Does R1 require a maintenance and testing program for the battery chargers for the station batteries that are considered part of the Protection System? Response to Question #1 While battery chargers are vital for ensuring station batteries are available to support Protection System functions, they are not identified within the definition of Protection Systems. Therefore, PRC-005-1 does not require maintenance and testing of battery chargers. Question #2 Does R1 require a maintenance and testing program for auxiliary relays and sensing devices? If so, what types of auxiliary relays and sensing devices? (i.e. transformer sudden pressure relays) Response to Question #2 1. The existing definitiondoes R1 require a maintenance and testing program for the battery chargers for the station batteries that are considered part of the Protection System does not include? 2. Does R1 require a maintenance and testing program for auxiliary relays; therefore, maintenance and testing of such and sensing devices is not explicitly required. Maintenance and testing of such? If so, what types of auxiliary relays and sensing devices is addressed to the degree that an entity s maintenance and testing program for DC control circuits involves? (i.e transformer sudden pressure relays) 3. Does R1 require maintenance and testing of imbedded auxiliarytransmission line re-closing relays. Maintenance? 4. Does R1 require a maintenance and testing program for the DC circuitry that is just the circuitry with relays and devices that control actions on breakers, etc., or does R1 require a program for the entire circuit from the battery charger to the relays to circuit breakers and all associated wiring? 1 According to the FERC Order issued approving a modified definition of Protection System (RD11-13-000), this interpretation will be superseded by the modified definition of Protection System when the modified definition becomes effective. The modified definition of Protection System becomes effective on April 1, 2013. Page 7 of 9

5. For R1, what are examples of "associated communications systems" that are part of Protection Systems that require a maintenance and testing of devices that respond to quantities other than electrical quantities (for example, sudden pressure relays) are not included within Requirement R1.program? Question #3 Does R1 require maintenance and testing of transmission line re-closing relays? Response to Question #3: No. Protective Relays refer to devices that detect and take action for abnormal conditions. Automatic restoration of transmission lines is not a protective function. Question #4 Does R1 require a maintenance and testing program for the DC circuitry that is just the circuitry with relays and devices that control actions on breakers, etc., or does R1 require a program for the entire circuit from the battery charger to the relays to circuit breakers and all associated wiring? Response to Question #4 PRC-005-1 requires that entities 1) address DC control circuitry within their program, 2) have a basis for the way they address this item, and 3) execute the program. PRC-005-1 does not establish specific additional requirements relative to the scope and/or methods included within the program. Question #5 For R1, what are examples of "associated communications systems" that are part of Protection Systems that require a maintenance and testing program? Response to Question #5 1. While battery chargers are vital for ensuring station batteries are available to support Protection System functions, they are not identified within the definition of Protection Systems. Therefore, PRC-005-1 does not require maintenance and testing of battery chargers. 2. The existing definition of Protection System does not include auxiliary relays; therefore, maintenance and testing of such devices is not explicitly required. Maintenance and testing of such devices is addressed to the degree that an entity s maintenance and testing program for 3 DC control circuits involves maintenance and testing of imbedded auxiliary relays. Maintenance and testing of devices that respond to quantities other than electrical quantities (for example, sudden pressure relays) are not included within Requirement R1. 3. No. Protective Relays refer to devices that detect and take action for abnormal conditions. Automatic restoration of transmission lines is not a protective function. 4. PRC-005-1 requires that entities 1) address DC control circuitry within their program, 2) have a basis for the way they address this item, and 3) execute the program. PRC-005-1 does not establish specific additional requirements relative to the scope and/or methods included within the program. Page 8 of 9

Associated communication systems refer to communication systems used to convey essential 5. Protection System tripping logic, sometimes referred to as pilot relaying or teleprotection. Examples include the following: communications equipment involved in power-line-carrier relaying communications equipment involved in various types of permissive protection system applications direct transfer-trip systems digital communication systems (which would include the protection system communications functions of standard IEC 618501 as well as various proprietary systems) Page 9 of 9