SECTION DRY-PIPE SPRINKLER SYSTEMS

Similar documents
SECTION SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS

THE JAMES RUSHTON EARLY LEARNING AND FAMILY SUCCESS CENTER #2616 ISSUE FOR CONSTRUCTION

B. Related Sections: The following Sections contain requirements that relate to this Section.

SPRINKLERS TABLE OF CONTENTS

DARTMOUTH COLLEGE DESIGN November 15, 2007 & CONSTRUCTION GUIDELINES

SECTION FIRE PROTECTION. A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section

SECTION WET-PIPE SPRINKLER SYSTEMS

1.2 CODES AND REGULATIONS A. Sprinkler system design, equipment, materials, devices, and installation shall conform to the following:

SECTION FIRE-SUPPRESSION SYSTEMS

WET-PIPE SPRINKLER SYSTEMS

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

North Hanover Township School District North Hanover Township, New Jersey

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

A. This Section includes the following fire-suppression piping inside the building:

A. Section includes wet-pipe sprinkler system, system design, installation, and certification.

ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1. The Curators of the University of Missouri

SECTION SPRINKLER SYSTEMS

SECTION DRY-PIPE SPRINKLER SYSTEMS

B. Standard-Pressure Standpipe Piping: Fire-suppression standpipe piping designed to operate at working pressure 175 psig (1200 kpa) maximum.

B. The sprinkler system shall be designed to meet the more stringent of the requirements of NFPA 13 and FM Global requirements.

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE

B. Galvanized-Steel-Sheet Sleeves: inch minimum thickness; round tube closed with welded longitudinal joint.

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

SECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM

A. Standard-Pressure Piping System Component: Listed for 175-psig minimum working pressure.

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University.

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL

Gas Station & C Store SECTION CWM Job No

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

SECTION FIRE-SUPPRESSION PIPING

West District Library Section Campeau Drive, Ottawa SPRINKLER SYSTEMS City of Ottawa Project No. CR Page 1 of 8

DIVISION 21 FIRE SUPPRESSION SECTION FIRE PROTECTION SPECIALTIES

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements.

B. Section Identification for Fire Suppression Piping and Equipment.

SECTION PREACTION SPRINKLER SYSTEMS

ADDENDUM NO. 3 March 19, 2018

FIRE SUPPRESSION SPRINKLER SYSTEM

MLA Architects Pierz Public Schools ISD #484 Healy High School Multi-Purpose & Choir Additions Pioneer Elementary School Class Room Addition Pierz, MN

SECTION FIRE-SUPPRESSION STANDPIPES

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 21 FIRE SUPPRESSION

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

SECTION AUTOMATIC SPRINKLER PIPING

Council Bluffs, Iowa Division TOC 1 TABLE OF CONTENTS DIVISION 21 FIRE SUPPRESSION

Wayne State University WSU Project No Chatsworth Tower Apts. Misc. Bldg. Upgrades DSD Project No

Facility Fire-Suppression Water-Service Piping

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION FIRE SUPPRESSION SYSTEMS

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1

SECTION WET-PIPE FIRE-SUPPRESSION SPRINKLERS

SECTION DRY-PIPE FIRE-SUPPRESSION SPRINKLERS

Copyright 2016 AIA MasterSpec Full Length 09/16 PRODUCT MASTERSPEC LICENSED BY AVITRU, LLC TO VICTAULIC COMPANY.

Copyright 2016 AIA MasterSpec Full Length 09/16 PRODUCT MASTERSPEC LICENSED BY AVITRU, LLC TO VICTAULIC COMPANY.

Essex County College - West Essex Campus Addition And Renovations dlb # / 11-14

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 21 FIRE SUPPRESSION

TECHNICAL SPECIFICATIONS SECTION DRY PIPE SPRINKLER SYSTEM PLAISTOW PUBLIC LIBRARY 85 MAIN STREET PLAISTOW, NEW HAMPSHIRE 100%CD.

A. This section includes design and performance information for fire protection and suppression systems.

TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION WATER BASED FIRE PROTECTION SYSTEMS... 5

SECTION FIRE PROTECTION

Addendum No. 2 to the Contract Documents

2016 CDM Smith All Rights Reserved July 2016 SECTION FIRE PROTECTION - SPRINKLER AND STANDPIPE SYSTEMS

A. This Section includes the following domestic water piping specialties:

DIVISION 21: FIRE SUPPRESSION WATER BASED FIRE SUPRESSION SYSTEMS

DIVISION 21 FIRE PROTECTION ISSUE DATE REVISION

A. All Fire Suppression System design and installation shall comply with the most current and adopted version of NFPA 13.

DIVISION 21 - FIRE SUPPRESSION

Port of St Helens SIA Aircraft Hanger Scappoose, OR

ACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO

END OF SECTION

SECTION WET FIRE SPRINKLER SYSTEMS

SECTION WET AUTOMATIC FIRE SPRINKLER SYSTEMS

DIVISION 21 - FIRE SUPPRESSION

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM

2. Welding Materials and Procedures shall conform to the ASME Code.

SECTION ADDENDUM NO. 1 FIRE SPRINKLER SYSTEM

SECTION SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING

UC Santa Cruz Campus Design Guide. Includes the following sections: None DESIGN REQUIREMENTS

Environmental Health & Safety

Mercy Hospital of Buffalo Catholic Health System 2 nd Floor Patient Holding Center 3 rd Floor Locker Rooms Shaflucas Architects, PC Project No.

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION

University of Missouri St. Louis September 9, 2013 Recreation and Wellness Center #S

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION

PART 1 - GENERAL SECTION FIRE PROTECTION BASIC MATERIALS AND METHODS

SECTION FIRE PROTECTION

SECTION COMPRESSED AIR SYSTEM. A. Pipe and pipe fittings, including valves, unions and couplings.

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION GENERAL-SERVICE COMPRESSED-AIR SYSTEMS

C. ASSE 1013: Performance Requirements for Reduced Pressure Principle Backflow Preventers.

SECTION FIRE SUPRESSION

DIVISION 21 FIRE SUPPRESSION FIRE SUPRESSION

NITROGEN-GENERATING SPRINKLER CORROSION INHIBITING SYSTEM

SECTION WET-PIPE FIRE SUPPRESSION SPRINKLERS

WET AUTOMATIC FIRE SPRINKLER SYSTEMS

PROJ. NO SECTION REFRIGERANT PIPING

Mercury Plastics New Building February TABLE OF CONTENTS

SECTION DOMESTIC WATER PIPING SPECIALTIES

Transcription:

SECTION 21 1300 S PART 1 -GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.02 SUMMARY A. This Section is a performance specification for the design and installation of sprinkler systems for buildings and structures. The Contractor is responsible for obtaining the services of a qualified Registered Engineer in the State of Missouri for the purpose of designing a dry-pipe sprinkler in accordance with the requirements herein and included in the latest edition of NFPA 13. B. Products specified in this Section with installation not in Contract include sprinkler cabinets with spare sprinklers and sprinkler wrenches. Deliver to the Owner's maintenance personnel. C. Related Sections: The following Sections contain requirements that relate to this Section: 1. Division 07 Section "Firestopping" for fire barrier sealers. D. Project Scope: Sprinkle all rooms and spaces within the building, including attics in accordance with NFPA 13, except as indicated below: 1. Call Center Room 103, Radio Room 104 and Server Room 105 are not to be sprinkled; however, the attic spaces above each of these rooms is to be sprinkled. 1.03 DEFINITIONS A. Pipe sizes used in this Section are nominal pipe size (NPS) specified in inches. Tube sizes are standard tube size specified in inches. Equivalent or approximate Sl (metric) sizes are indicated in millimeters (mm) in parentheses. B. Other definitions for fire protection systems are included in referenced NFPA standards. 1.04 SYSTEM DESCRIPTION A. Dry-Pipe Sprinkler System: System with automatic sprinklers attached to piping system containing air under pressure. Release of pressure (opening of sprinklers) permits water pressure to open dry-pipe valve. Water then flows into piping and discharges through open sprinklers. 1. Pressurizing Gas: Compressed air, from sprinkler system air compressors. B. Sprinkler System Protection Limits: All spaces within entire building. Include closets, toilets, attics and outdoor soffits, each landing of each stair, and special applications areas. PWA 201130 21 1300/1

1.05 SYSTEM PERFORMANCE REQUIREMENTS A. Design and obtain approval from authority having jurisdiction for fire protection systems specified. B. Conduct or otherwise obtain fire hydrant flow tests as required to obtain hydraulic data needed to prepare design for hydraulically calculated systems. C. Hydraulically design sprinkler systems according to: 1. Sprinkler System Occupancy Hazard Classifications: As follows: a. Office and Public Areas: Light hazard. b. Storage Areas: Ordinary hazard. c. Equipment Rooms: Ordinary hazard. d. Service Areas: Ordinary hazard. 2. Minimum Density Requirements for Automatic Sprinkler System Hydraulic Design: As follows: a. Light Hazard Occupancy: 0.10 GPM over 1500 sq. ft. (6.3 ml/s over 140 sq. m) area. b. Ordinary Hazard, Group 1 Occupancy: 0.15 GPM over 1500 sq. ft. (9.5 ml!s over 140 sq. m) area. c. Ordinary Hazard, Group 2 Occupancy: 0.20 GPM over 1500 sq. ft. (12.6 ml!s over 140 sq. m) area. 3. Maximum Sprinkler Spacing: As follows: a. Office Space: 120 sq. ft./sprinkler (11 sq. m/sprinkler). b. Storage Areas: 130 sq. ft./sprinkler (12 sq. m/sprinkler). c. Mechanical Equipment Rooms: 130 sq. ft./sprinkler (12 sq. m/sprinkler). d. Electrical Equipment Rooms: 130 sq. ft./sprinkler (12 sq. m/sprinkler). e. Other Areas: According to NFPA 13. D. Components and Installation: Capable of producing piping systems with the following minimum working pressure ratings except where indicated otherwise. 1. Sprinkler Systems: 175 psig (1200 kpa). 1.06 SUBMITTALS A. Product data for fire protection system components. Include the following: 1. Fire department connections. Include type of fire department connection; number, size, type, and arrangement of inlets; size and direction of outlet; and finish. 2. Dry pipe system air compressors. 3. Sprinklers, escutcheons, and guards. Include sprinkler flow characteristics, mounting, finish, and other data. B. Sprinkler system drawings identified as "working plans," prepared according to NFPA 13. Submit required number of sets to authority having jurisdiction for review, comment, and approval. Include system hydraulic calculations where applicable. PWA 201130 21 1300/2

C. Maintenance data for each type of fire protection specialty specified, for inclusion in "Operating and Maintenance Manual" specified in Division 01 Section "Project Closeout." 1.07 QUALITY ASSURANCE A. Manufacturer Qualifications: Firms whose equipment, specialties, and accessories are listed by product name and manufacturer in UL Fire Protection Equipment Directory and FM Approval Guide and that conform to other requirements indicated. B. Listing/Approval Stamp, Label, or Other Marking: On equipment, specialties, and accessories made to specified standards. C. Listing and Labeling: Equipment, specialties, and accessories that are listed and labeled. 1. The Terms "Listed" and "Labeled": As defined in "National Electrical Code," Article 100. D. Comply with requirements of authority having jurisdiction for submittals, approvals, materials, hose threads, installation, inspections, and testing. E. Comply with requirements of Owner's insurance underwriter for submittals, approvals, materials, installation, inspections, and testing. F. Licensed Engineer: Submit design drawings, design calculations, and installation inspection reports. Include seal and signature of registered engineer licensed in jurisdiction where Project is located, certifying compliance with specifications. G. Installer's Qualifications: Firms qualified to install and alter fire protection piping, equipment, specialties, and accessories, and repair and service equipment. A qualified firm is one that is experienced (minimum of 5 previous projects similar in size and scope to this Project) in such work, familiar with precautions required, and in compliance with the requirements of the authority having jurisdiction. Submit evidence of qualifications to the Architect upon request. Refer to Division 01 Section "Reference Standards and Definitions" for definition of "Installer." H. NFPA Standards: Equipment, specialties, accessories, installation, and testing complying with the following: 1. NFPA 13 "Standard for the Installation of Sprinkler Systems." 2. NFPA 26 "Recommended Practice for the Supervision of Valves Controlling Water Supplies for Fire Protection." 3. NFPA 70 "National Electrical Code." PART 2 - PRODUCTS 2.01 MANUFACTURERS A. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated in the Work include, but are not limited to, the following: 1. Sprinklers: a. ASCOA Fire Systems, Figgie International Co. b. Central Sprinkler Corp. c. Firematic Sprinkler Devices, Inc. d. Gem Sprinkler Co. Div., Grinnell Corp. e. Globe Fire Sprinkler Corp. f. Reliable Automatic Sprinkler Co., Inc. PWA 201130 21 1300/3

g. Star Sprinkler Corp. h. Viking Corp. 2. Grooved Couplings for Steel Piping: a. Grinnell Supply Sales Co., Grinnell Corp. b. Gustin-Bacon Div., Tyler Pipe Subsid., Tyler Corp. c. Sprink-Line by Sprink, Inc. d. Stockham Valves and Fittings, Inc. e. Victaulic Company of America. 3. Fire Department Connections: 2.02 PIPES AND TUBES a. Guardian Fire Equipment, Inc. A. Refer to Part 3 Articles "Sprinkler System Piping Applications" and "Standpipe System Piping Applications" for identification of systems where pipe and fitting materials specified below are used. B. Steel Pipe: ASTM A 53, Schedule 40 in sizes 6 inches (150 mm) and smaller, black and galvanized, plain and threaded ends, for welded, threaded, cut-groove, and rolled-groove joints. 2.03 PIPE AND TUBE FITTINGS A. Malleable-Iron Threaded Fittings: ASME B16.3, Class 300, standard pattern, with threads according to ASME B1.20.1. B. Grooved-End Fittings for Steel Pipe: UL-Iisted and FM-approved, ASTM A 536, Grade 65-45- 12 ductile iron or ASTM A 47 Grade 32510 malleable iron, with grooves or shoulders designed to accept grooved couplings. 2.04 JOINING MATERIALS A. Refer to Division 22 Section "Basic Plumbibng Materials and Methods" for joining materials not included in this Section. B. Couplings for Grooved-End Steel Pipe and Grooved-End Ferrous Fittings: UL 213, AWWA C606, ASTM A 536 ductile-iron or ASTM A 47 malleable-iron housing, with enamel finish. Include synthetic-rubber gasket with central-cavity, pressure-responsive design; ASTM A 183 carbon-steel bolts and nuts; and locking pin, toggle, or lugs to secure grooved pipe and fittings. 1. Dry-Pipe-Systems Couplings: UL-Iisted for dry-pipe service. 2.05 SPRINKLERS A. Automatic Sprinklers: With heat-responsive element conforming to: 1. UL 199, for applications except residential. B. Sprinkler types and categories are as indicated and as required by application. Furnish automatic sprinklers with nominal 1/2-inch (12.7 mm) orifice for "Ordinary" temperature classification rating except where otherwise indicated and required by application. PWA 201130 21 1300/4

C. Sprinkler types, features, and options include: 1. Coated, painted, or plated sprinklers. 2. Extended coverage sprinklers. 3. Flush ceiling sprinklers, including escutcheon. 4. Recessed sprinklers, including escutcheon. 5. Upright sprinklers. D. Sprinkler Finishes: Bronze or painted. E. Sprinkler Escutcheons: Materials, types, and finishes for following sprinkler mounting applications. Escutcheons for concealed, flush, and recessed-type sprinklers are specified with sprinklers. 1. Ceiling Mounting: White painted cold rolled steel, 2-piece, with 1-inch vertical adjustment. 2.06 FIRE PROTECTION SERVICE VALVES A. General: UL-Iisted and FM-approved, with 175 psig (1200 kpa) non-shock minimum working pressure rating. 1. Option: Valves for use with grooved piping may be grooved type. B. Gate Valves, 2 Inches (50 mm) and Smaller: UL 262, cast-bronze, threaded ends, solid wedge, outside screw and yoke, rising stem. C. Indicating Valves, 2-1/2 Inches (65 mm) and Smaller: Butterfly or ball type, bronze body with threaded ends, and integral indicating device. 1. Indicator: Visual. 2. Indicator: Electrical115 volts a.c., prewired, single-circuit, supervisory switch. 3. Indicator: Electrical115 volts a.c., prewired, 2-circuit, supervisory switch. D. Gate Valves, 2-1/2 Inches (65 mm) and Larger: UL 262, iron body, bronze mounted, taper wedge, outside screw and yoke, rising stem. Include replaceable, bronze, wedge facing rings and flanged ends. E. Swing Check Valves, 2-1/2 Inches (65 mm) and Larger: UL 312, cast-iron body and bolted cap, with bronze disc or cast-iron disc with bronze disc ring and flanged ends. 2.07 SPECIALTY VALVES A. Dry-Pipe Valves: UL 260, differential type, 175 psig (1200 kpa) working pressure, with castiron flanged inlet and outlet, bronze seat with 0-ring seals, and single-hinge pin and latch design. Include UL 1486, quick-opening devices, trim sets for air supply, drain, priming level, alarm connections, ball drip valves, pressure gages, priming chamber attachment, and fill line attachment. 1. Option: Grooved-end connections for use with grooved-end piping. B. Air-Pressure Maintenance Devices for Dry-Pipe Systems: Automatic device to maintain correct air pressure in dry-pipe system or deluge system. Include shutoff valves to permit servicing without shutting down sprinkler system, bypass valve for quick system filling, pressure regulator or switch to maintain system pressure, strainer, pressure ratings 14 psig (95 kpa) to 60 psig (41 0 kpa) adjustable range, and 175 psig (1200 kpa) maximum inlet pressure. PWA 201130 21 1300/5

1. Air Compressor: Fractional horsepower, 120 volts a.c., 60Hz, single phase. 2. Compressed Air or Nitrogen Supply: 1 cylinder with valves. 2.08 FIRE DEPARTMENT CONNECTIONS A. Flush, Wall-Type Fire Department Connections: UL 405, cast-brass body; NH-standard thread inlets according to NFPA 1963 and matching local fire department threads; and threaded NPS outlet. Include lugged cap, gasket, and chain; lugged swivel connection, extension pipe nipples, and clappers for each hose connection inlet; and wall escutcheon plate with marking "AUTO SPKR". 1. Connections: 4" NPT x 4" Storz. 2. Inlet Alignment: In line, horizontal. 3. Non-clapper Type. 4. Direction of Outlet: Back. 5 Escutcheon Plate: Round. 6. Finish: Rough chrome plated. 7. Cap: KNOX locking FDC plug matching fire department connection size 2.09 ALARM DEVICES A. Alarm Devices: Types and sizes that will match piping and equipment connections. B. Water-Motor-Operated Alarms: UL 753, mechanical operation type, 1 0-inch (250 mm) diameter, cast-aluminum alarm gong, with red enamel factory finish. Include Pelton-wheel-type operator with nylon shaft bearings, and shaft length and sleeve to suit wall thickness and construction; 3/4-inch (20 mm) inlet and 1-inch (25 mm) drain. C. Waterflow Indicators: UL 346, electrical-supervision type, vane-type waterflow detector, rated to 250 psig (1725 kpa), and designed for horizontal or vertical installation. Include 2 SPOT (single-pole, double-throw) circuit switches to provide isolated alarm and auxiliary contacts, 7 ampere, 125 volts a.c. (7 A, 125 V a.c.) and 0.25 ampere, 24 volts d.c. (0.25 A, 24 V d.c.); complete with factory-set, field-adjustable retard element to prevent false signals and tamperproof cover that sends a signal when cover is removed. D. Pressure Switches: UL 753, waterflow switch with retard, electrical-supervision type, SPOT (single-pole, double-throw), normally closed contacts, designed to operate on rising pressure and signal water flow. E. Supervisory Switches: UL 753, for valves, electrical-supervision type, SPOT (single-pole, double-throw), normally closed contacts, designed to signal controlled valve in other than full open position. 2.10 PRESSURE GAGES A. Pressure Gages: UL 393, 3-1/2 to 4-1/2 inches (90 to 115 mm) diameter dial with dial range of 0-250 psig (0-1600 kpa). PART 3 - EXECUTION 3.01 EXAMINATION A. Examine walls and partitions for suitable thickness, fire- and smoke-rated construction, framing for cabinets, and other conditions where cabinets are to be installed. PWA 201130 21 1300/6

B. Do not proceed until unsatisfactory conditions have been corrected. 3.02 SPRINKLER SYSTEM PIPING APPLICATIONS A. Refer to Part 2 of this Section for detailed specifications on pipe and fittings products listed below. Use pipe, tube, fittings, and joining methods according to the following applications. Piping may be joined with flanges instead of indicated joints. Use grooved-end fittings with grooved couplings that are made by the same manufacturer and that comply with listing when used together for grooved-coupling joints. B. Sizes 2 Inches (50 mm) and Smaller: ASTM A 53, A 135, or A 795; Schedule 40 steel pipe with threaded ends, cast-iron or malleable-iron threaded fittings, and threaded joints. 3.03 JOINT CONSTRUCTION A. Refer to Division 22 Section "Basic Plumbing Materials and Methods" for basic piping joint construction. B. Grooved-End Pipe and Grooved-End Fitting Joints: Use grooved-end fittings and grooved couplings that are made by the same manufacturer and that are listed for use together. Groove pipe and assemble joints with grooved coupling, gasket, lubricant, and bolts according to coupling and fitting manufacturer's written instructions. 1. Groove Type: Rolled. 3.04 PIPING INSTALLATIONS A. Refer to Division 22 Section "Basic Plumbing Materials and Methods" for basic piping installation. B. Locations and Arrangements: Drawings (plans, schematics, and diagrams) indicate general location and arrangement of piping. Install piping as indicated, as far as practical. 1. Deviations from approved "working plans" for sprinkler piping require written approval from authority with jurisdiction. File written approval with the Architect prior to deviating from approved "working plans." C. Use approved fittings to make changes in direction, branch takeoffs from mains, and reductions in pipe sizes. D. Hangers and Supports: Comply with NFPA 13. Install according to NFPA 13 and NFPA 14. 1. Install hanger and support spacing and locations for steel piping joined with grooved mechanical couplings according to manufacturer's written instructions for rigid systems. 2. Earthquake Protection: Install piping according to NFPA 13 to protect from earthquake damage. 3.05 SPRINKLER APPLICATIONS A. Rooms without Ceilings: Upright sprinklers. B. Rooms with Suspended Ceilings: Recessed sprinklers. C. Wall Mounting: Sidewall sprinklers. D. Sprinkler Finishes: Use sprinklers with following finishes: PWA 201130 21 1300/7

1. Upright Sprinklers in Areas not exposed to view: Brass. 2. Recessed Sprinklers: White polyester, with white escutcheons. E. All sprinklers suitable for dry pipe systems in accordance with the latest edition of NFPA 13. END OF SECTION PWA 201130 21 1300/8