SUBMITTAL DATA for STOCK ROOFTOP UNIT AS ORDERED - PLEASE CHECK AND SIGN AS APPROVED Prepared for Stuart Mc Munn Company 137 North Sixth Street Clarksburg, WV 6301 Customer PO#: 38 Prepared by Mason and Barry Inc 301 Smiley Drive Saint Albans, WV 5177 1 of 13
Job Information Technical Data Sheet STOCK UNIT ADD Medbrooke Matt Duncan 04.50 RTU CO#1 Job Name Date Submitted By Software Version Unit Tag Unit Overview Model Number Voltage Design Cooling Capacity MPS010B 460/60/3 15738 Btu/hr AHRI 360 Standard EER IEER 11. 11.9 ASHRAE 90.1 010 Compliant Unit MPS010B Cooling, Standard Natural gas heat Hot Gas Reheat Constant volume 0 ft culus Model Number: Model : Heat : Hot Gas Reheat: Application: Altitude: Approval Physical Unit Dimensions and Weights Unit Length Unit Height Unit Width Unit Weight 93.7 in 44.0 in 58.7 in 1165 lb Unit Construction Powder Coat Galvanized Exterior: Doors: 3/4" foil face with mechanical fasteners, R value of 3.6 Single wall construction Insulation: Liners: Drain Pan Material Fan, Filter, Coil, Control Panel, and Economizer section Polymer Unit Electrical Data Voltage SCCR MCA MROPD 460/60/3 V 5 kaic 8.0 A 35A Return/Outside/Exhaust Air Outside Air Option : Factory Installed Econ, vertical return, DDC Controls Draw Through Filters ft² Face Velocity ft/min Air Pressure Drop inh₂o " Disposable 13.5 96 Included In Fan Performance 9 of 13
Cooling Coil Fins per Inch Rows ft² Face Velocity ft/min Air Pressure drop inh₂o 18 3 13.5 96 Included In Fan Performance Cooling Performance Btu/hr Sensible Capacity Btu/hr 15738 96908 Entering Air Temperature Dry Bulb Wet Bulb 80.0 Leaving Air Temperature Dry Bulb Wet Bulb 67.0 57.6 Ambient Air Temp 57.0 95.0 Hot Gas Reheat Coil Section Air Pressure Drop Entering DB Leaving DB Aluminum Tube Micro channel 5.9 ft² 0.4 inh₂o 4577 Btu/hr 57.6 68.0 Control : On Off Control Fan Section Fan Wheel Diameter Quantity Vibration Isolation FC 15 in 1 Rigid Fan Performance Air Flow External Static Pressure Design Fan Speed Drive Package Speed Brake Horsepower Altitude 4000 CFM 1.00 inh₂o 1043 RPM 894.9 HP 0 ft Motor Horsepower Full Load Current 3.0 HP Open drip proof, EPAct 80.0 7.0 A Drives Service Factor Adjustable Sheave 10% Gas Heat Section Material Gas Ignition Combustion Blower Heat Stages Tubular Heat exchanger with in shot burner manifold Aluminized steel Natural Gas Electric Induced draft blower Stage Heating Performance Input Size Steady State Entering Air Dry Bulb Leaving Air Dry Bulb 5 MBH 1850 Btu/hr 81% 60.0 10.0 10 of 13
Condensing Section Compressor Quantity Total Power Capacity Control Refrigerant Scroll 9.1 kw steps R410A Compressor Amps: Compressor 1 Compressor 8.6 A 8.6 A LP, HP switch Compressor Options: Condenser Coil Fins Per Inch Rows Fin Material Refrigerant Valves Copper tube Aluminum None Condenser Fan Motors Number of Motors Full Load Current 0.7 A AHRI 360 Certified Data at AHRI 360 Standard Conditions Net Capacity 118000 Btu/hr 11. EER ASHRAE 90.1 11.9 IEER 010 Compliant Internal Static Pressure Drop Calculation 1.00 0.35 External Static Pressure: Internal Static Pressure: 1.35 inh₂o Total Static Pressure: Options Electrical Field Connection: Power Options: Power Block None Controls Temperature Controls: DDC controls, no BAS communication card Warranty Parts Warranty: Compressor Warranty: Heat Exchanger Warranty: Standard one year Standard five year Standard ten year AHRI Certification All equipment is rated and certified in accordance with AHRI 340/360 Notes As a standalone component, unit meets or exceeds the requirements of ASHRAE 90.1.010. The approving authority is responsible for compliance of multi component building systems. 11 of 13
M MPS 006 01 1 gas heat Drawing fo or RTU CO#1 1 MPS 0006 01 gas heat_drawing for RTU CO#1 Product Draw wing Unit Tag: RTU U CO#1 Product: Model: MPS010 0B Project Name: D Sales Engineer: Jan. 06, 015 Sales Office: Masson & Barry, Inc. Ver/Rev: Sheet 1 of 1 13600 Industrial Park Blvd. Minneap polis, MN 55441 Softwaare Version: 04.50 www.daikinapplieed.com Scale: NTS Toleerance: +/ 0.5 Dwg Units: in [mm] No change to this drawing may be made unless approve ed in writing by Daikkin Applied. Purchaaser must determinne that the equipment is fit and sufficient for the job specifications. J J 1 1 of 13 Prrepared Date: