Saffire User & Installation Manual. IMPORTANT This manual should be left with the panel after installation.

Similar documents
Installation, Operating and Maintenance Manual

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

Operation and Maintenance Manual

Intelligent Security & Fire Ltd

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

Surveyor Envoy-MINI 4

OPERATION AND INSTALLATION MANUAL

Excel-EN Conventional Fire Control Panel

Intelligent Security & Fire Ltd

Precept Marine Control Panel Application Guide

Conventional Fire Control Panel (FKEP2, FKEP4, FKEP8) Operation and Maintenance Manual. Man-1078EL Issue 01 February 2014

Application, Installation, Operation & Maintenance Manual

Fire Control Panel. Installation & Programming Manual TABLE OF CONTENTS

BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL

ED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR

Conventional Fire Alarm System 2014 V1.2

CONVENTIONAL CONTROL PANEL FL2/4/8/12 LT-XP

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL

NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

FEC400 Series. Installation Manual

Sigma CP (K and T Series)

USER MANUAL & MAINTENANCE GUIDE OG OO

FSTP4-2-wire 4 Zone Conventional Fire Control Panel Operation and Maintenance Manual. Man-1078FS4 Issue 01 April 2012

Conventional Fire Control Panel

Installation and Operating Instructions

Control Panel Engineering and Commissioning Instructions

Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

Smoke Vent Control Panel PCB4 V4 Installation Manual

FSTP2-2-wire 2 Zone Conventional Fire Control Panel Operation and Maintenance Manual. Man-1078FS2 Issue 01 April 2012

MAG2/4. AL MAG2 Soft. Version 2.1 MAG4 Soft.Version 2.0 USER MANUAL

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3

SECURIT 700L PLUS ENGINEERING MANUAL

User Operation Manual

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

FIRE DETECTOR TYPE ED816 ZONE 5 ZONE 4 ZONE 6 ZONE 7 FIRE FIRE FIRE FIRE FAULT FAULT FAULT FAULT DISABLED DISABLED DISABLED DISABLED OFF OFF OFF OFF

FIRE ALARM CONTROL PANEL FVC01-08

FIREPRO INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL. Approved Document No. GLT Issue: 1. 8 Author: NRPJ Date: 7/ 3/201 4

909e Series 2/4 Zone Panel. Operating and Configuration. Manual Version V01

VSN PLUS VSN 4 PLUS ; VSN 8 PLUS ; VSN 12 PLUS

INSTALLATION INSTRUCTIONS

Conventional & Twin-wire Fire System

SOLO Single Loop Addressable Fire Control Panel

Matrix2000. User Guide - CPD Advanced Analog Fire Alarm Control Panel 4 24 Zones. Version: 2.0 Revision: 1

Fire Control Panel. Installation & Programming Manual TABLE OF CONTENTS

PAT E N T System 88. COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00

Noby-448 User Operating Manual & Log Book Page 1 of 12. Fire Control Panel. User Operating Manual & Log Book

FIRE ALARM CONTROL PANEL. COMPLIES WITH EN54 part 2 & part 4 MEETS THE FUNCTIONAL REQUIREMENT OF BS:EN 5839 part 1 INSTALLATION MANUAL

EX8. Instruction Manual: COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 AND EN54 PARTS 2 & 4

Conventional Leaflets

Sigma XT+ Extinguishant Control Panel. Operation and Maintenance Manual

USER MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 & EN54 PARTS 2 & 4

VoCALL - CFVCC5. Compact 5 Line Exchange Unit. Installation & Commissioning Manual

Hydrosense. Vimpex Limited. Star Lane. Great Wakering. Essex SS3 0PJ. Tel: +44 (0) Fax +44 (0)

Doc. No.: OMPII.DOC Rev. 2 Written By: Raj Patel Checked By: AJC Approved By: JBJ Date: 03/05/05

General Routing Interface

GAS SUPRESSION CONTROL PANEL:

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER

Conventional Fire Control Panel with Extinguishant Control Unit. Operation and Maintenance Manual SIGMA-2-M3-ECU SIGMA-4-M3-ECU SIGMA-8-M3-ECU

2018 Johnson Controls. Tyco Fire & Security GmbH, Victor von Bruns-Strasse 21, 8212 Neuhausen am Rheinfall, Switzerland DUO-CEL

INSTALLATION MANUAL SECURIT 802 CONTROL PANEL

Menvier Fire System MF9300

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK

ANALOGUE ADDRESSABLE FIRE CONTROL PANELS FIREQUEST FAMILY. Section 6 Trouble Shooting Issue 1.1

PREMIER EX8 INSTALLATION MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 & EN54 PARTS 2 & 4 INSTALLATION MANUAL

NFS Supra / VSN-2Plus / ESS-2Plus Conventional Fire Alarm Control Panel. Installation and Operating Manual

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK

Panel Functions & Indicators - Key to Icons General & Zone Fire LEDs ACCEPT SOUNDERS START/ STOP RESET BUZZER MUTE KEYSWITCH DELAY ON/OFF ITEM SELECT

OPERATION & INSTALLATION MANUAL FOR ALARM PANEL M2AP01

BiWire Flexi. BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI Installation Manual

4 wire conventional alarm system

Door Release Power Supply

RP1r-Supra / VSN-RP1r+ / ESS-RP1r-Supra Extinguishing Control Panel User Manual. HLSI-MN-103I v.06 September 2017

VSN-RP1r Extinguishing Control Panel. User Manual (Software version 3.x) by Honeywell. doc. MIE-MN-570I rev.008

installation & maintenance manual LPCB APPROVED CFP 2/4/8 ZONE FIRE ALARM CONTROL PANEL approved document no. DFU rev 5

FIREBETA EXTINGUISHING CONTROL PANEL (ECP)

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0

HA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE

Fire Alarm Control Panel. System Maintenance and Log Book

SFC-200 SERIES LED FIRE ALARM PANEL

Fire Alarm Control Panel. Installation, Commissioning & Operating Manual

JUNO-NET. Fire Alarm Control Panel OPERATION & MAINTENANCE MANUAL

Technical Data Sheet

System 800 Addressable Fire Detection & Alarm System

Intruder - Fire - Water Combined Alarm

Firetrax Professional Conventional Fire Control Panel

MR-2602 Two Zone Fire Alarm Control Panel

Scimitar user manual & log book. Petersfield Business Park, Bedford Rd, Petersfield, Hampshire GU32 3QA Tel: Fax:

CONTENTS. 1 INTRODUCTION 2 Planning the installation 2 Nexus 8 installation example 3

Operating instruction

PROFYRE C8 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK FIRE ALARM CONTROL PANEL USER MANUAL, MAINTENANCE GUIDE & LOG BOOK

Fire Alarm Control Panel Installation, Commissioning & Operation MAN

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual

Control Panel Engineering and Commissioning Manual (TO BE RETAINED BY THE COMMISSIONING ENGINEER)

INFINITY 8 INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL

Transcription:

Saffire+ 8-12 User & Installation Manual IMPORTANT This manual should be left with the panel after installation. We reserve the right to change product specifications without prior notice. Copyright VRC Terofire Products 2003

2 VRC Terofire Products Introduction The information provided in this manual covers the Saffire+ 8-12 fire alarm control panel. The Saffire range is designed to meet the requirements of EN54 Parts 2 & 4. This product should be installed, commissioned and maintained by suitably qualified service personnel with reference to IEE regulations and any statutory requirements. General Description The Saffire+ 8-12 range of fire alarm control panels are microprocessor controlled and are available with either 8 or 12 sense zones (detector zones) dependent on the model. Both panels have 2 alarm zones (bell zones), zone disable facility, one man test, a class change input, nonlatching facility, a permanent 28V fused supply, a 28V supply energised on fire, one set of volt free changeover contacts which operate on fault, and two sets of volt free changeover contacts which operate on fire. Installation Procedure Before proceeding with the installation, please read the section Panel Operation. Installation of the panel should be carried out by qualified personnel. Using the metal box as a template, mark the position of the fixing holes on the wall. Drill and plug the wall, then screw the panel to the wall. Ensure the panel is free from knockout discs, swarf and other debris. Do not remove any end of line resistors from the panel until after the following test is performed. With all end of line resistors fitted inside the panel, connect the panel mains supply to an exclusive 240V AC fused supply. Switch the mains supply on. The internal buzzer will sound. Connect two sealed lead acid batteries to the panel - they should be connected in series providing a 24V DC supply. With both the mains and battery supplies connected, the panel should be silent and in its normal operating mode (power lamp on, alarms & buzzer silent). If a fault is indicated, refer to the fault finding section before proceeding. Disconnect the batteries and switch off the mains supply. Remove the 3k3 end of line resistor from sense zone 1. Terminate sense

Saffire+ 8-12 Instruction Manual 3 zone 1 circuit wiring in the panel observing correct polarity and fit the end of line resistor at the very end of the circuit. Check that all the detectors and call points are correctly wired. With sense zone 1 connected and all other end of line resistors fitted inside the panel, connect the mains and battery supplies. If the panel indicates a fault, refer to the fault finding section before proceeding. Do not megger cables connected to either the panel or any field devices. If no faults are indicated then power down the panel and follow the same procedure with the additional sense zones and then the alarm zones. Adding the zones one at a time makes fault finding and commissioning much simpler. Make sure that no bare wires come into contact with the panel circuit boards during installation. Detector Head Removal The Saffire+ 8-12 range supports head removal. The basic principle of head removal is to ensure that all call points will function even if a detector head has been removed. Head removal requires either zener clamp bases or schottky diode bases with the appropriate end of line device to be fitted. When a detector head is removed, the panel will show a fault, but the sense zone circuit will remain intact. Consult the table on page 9 for further information.

4 VRC Terofire Products Panel Operation Enabling the front panel buttons. To enable the front panel buttons, the key switch in the top left of the panel must be turned to the On position. Performing a lamp test. If the panel is in its normal condition, pressing the Reset button will cause the panel to perform a lamp test. Resetting the panel after a fire is detected. To reset the panel after a fire event, press the Silence button followed by the Reset button. Resetting the panel. If any of the panel functions have been activated, pressing the Reset button will return the panel to its normal condition. Silencing/resounding the alarms. If a fire is detected, the panel will automatically activate the alarm circuits. To silence the alarms, press the Silence button once. To resound the alarms, press the Silence button again. Silencing the internal buzzer. If a fault is detected by the panel, the internal buzzer will sound. To silence the buzzer press the Silence button. Using the one man test function. To enter test mode, press the Test button. The test LED will be lit and zone 1 fault LED will be flashing. To place zone 1 into test mode, press the Silence button. Press the Test button again and now zone 2 fault LED will be flashing with zone 1 fault LED on steady if it is in test mode. To select further zones, press the Test button to cycle through the zones and use the Silence button to toggle the status of the selected zone. Placing too many zones into test mode at the same time may leave the building with inadequate protection. When a zone in test mode detects a fire event, the alarms will ring for a few seconds before resetting. If the panel is left in test mode and no events occur for approximately 10 minutes, the panel will automatically exit test mode and resume normal operation.

Saffire+ 8-12 Instruction Manual 5 If a fire is detected on a zone not in test, then the panel will enter the fire condition and exit test mode. To exit test mode and return the panel to normal operation, press the Reset button. Using the disable function. The panel allows the user to selectively disable the sense zones and the alarm zones. The selection process is very similar to that used in the test function. To enter disable mode, press the Disable button. The disable LED will be lit and zone 1 disable LED will be flashing. Pressing the Silence button will toggle the status of the selected zone and pressing the Disable button will cycle through the available zones. Once the required zones have been selected, press the Reset button. If any zones were disabled, the disable LED and the relevant zone disable LED(s) will remain lit. All incoming signals from disabled sense zones will be ignored. If the alarm zones are disabled, then the alarms will not be activated even if the panel detects a fire event on an active sense zone. Selecting a zone as non-latching. In some situations, such as interlinking fire alarm panels, it is necessary to set a sense zone as non-latching. When a fire event is detected on a nonlatching zone, the panel will go into fire as usual but will automatically reset as soon as the device signalling fire is reset. To enter the non-latching selection mode, press and hold down the Test button. While still holding the Test button, momentarily press the CPU RESET button inside the panel, followed by the WATCHDOG RESET button. Keep the Test button held down until the disable and general fault LEDs light, then release the Test button. Zone 1 fault and disable LEDs will be flashing. Pressing the Silence button will toggle the status of the selected zone and pressing the Test button will cycle through the available zones. After the relevant zones have been selected, press the Reset button.

6 VRC Terofire Products Fault Finding Front panel buttons not working. To activate the front panel buttons, turn the keyswitch in the top left of the panel to the ON position. Power LED blinks intermittently This is perfectly normal and indicates that the processor is running an internal memory check. Fault LED and sense zone fault LED flashing, buzzer sounding. Faults monitored are: Open circuit on the sense zone wiring. Short circuit on the sense zone wiring. Detector head removal. Check all detectors and call points on the sense zone indicated. Check wiring is as in example diagrams and ensure the end of line monitor is a 3k3 resistor or an active end of line device. Fault LED and alarm zone fault LED flashing, buzzer sounding. Faults monitored are: Open circuit on the alarm zone wiring. Short circuit on the alarm zone wiring. Blown alarm fuse(s) - Note that drawing excessive current from the 28V Aux supply will blow the fuse in Alarm Zone 2. Check alarm zone wiring is as in example diagrams and ensure that the 10k end of line resistor is fitted. Check alarm zone fuses and fuse clips. Fault LED flashing and PSU fault LED on, buzzer sounding. Faults monitored are: Battery supply not present. Batteries damaged or not fully charged. Blown battery fuse. Mains supply not present. Blown mains fuse. Check relevant fuses and fuse clips. Ensure batteries are connected correctly and battery leads are secure. Fault LED flashing and 28V fault LED on, buzzer sounding. The panel has detected a problem with the permanent 28V supply. Check the PERM 28V FUSE and fuse clips.

Saffire+ 8-12 Instruction Manual 7 Fault LED flashing and earth fault LED on, buzzer sounding. The panel has detected an earth fault. The only earth connection to the panel terminals should be to the mains input terminal block. Check that no other earth connections are present. Fault LED and CPU fault LED lit. Processor fault detected. If no other problems are found then reset the processor. Inside the panel are two push buttons marked CPU RESET and WATCHDOG RESET. Press CPU RESET followed by WATCHDOG RESET. Panel does not indicate fire when a call point or detector is tested. Either a faulty call point/detector or wiring not as shown in diagrams. Check the firing resistance of the device is 510 ± 200 ohms and ensure that the correct end of line device is fitted. Head removal not working. Check compatible base is being used and is wired correctly. Either a zener clamp base with a 3k3 end of line resistor, or a schottky diode base with an active end of line device must be used. Fuse ratings. Mains fuse... 1A A/S Alarm fuses (F10 & F11)... 300mA A/S Battery fuse (F2)... 2A A/S Permanent 28V fuse (F6)... 125mA A/S Other faults. For any other faults, perform a CPU reset. Inside the panel are two push buttons marked CPU RESET and WATCHDOG RESET. Press CPU RESET followed by WATCHDOG RESET. This will restart the processor, but all configuration information (disable, non-latching) will have to be reentered. Fault Output The fault output, marked FAULT on the PCB, is a set of volt free changeover contacts. When the panel is in fault, common (C) is shorted to normally open (NO). In normal operation with no faults, common (C) is shorted to normally closed (NC).

8 Panel Specifications VRC Terofire Products Saffire+ 8 Saffire+ 12 Mains Voltage (V AC) 240 240 System Voltage (V DC) 28. 4 28. 4 Quiescent Current, Unsilenced Fault (ma) 115 135 Minimum Battery Size 2 x 12V Required (Ah) 7 7 Detector Voltage (V DC) 20 20 Number of Sense Zones 8 12 Maximum Number of Detectors per Zone 30 30 Firing Resistance (Ohms) 510 ± 200 510 ± 200 Sense Zone End of Line (Ohms) 3k3 3k3 Alarm Voltage (V DC) 28. 4 28. 4 Number of Alarm Zones 2 2 Maximum Alarm Current per Zone (ma) 300 300 Maximum Number of Sounders per Zone 16 16 Alarm Zone End of Line (Ohms) 10k 10k Max. Auxiliary Supply Current in Fire (ma) 50 0 P anel Weight [Including Batteries] (kg) 4.25 [10] 4.25 [10] 5 Panel Dimensions (mm) 335 x 265 x 87 335 x 265 x 87 The 28V Aux supply is derived from Alarm Zone 2. This must be taken into account when calculating the alarm current.

Saffire+ 8-12 Instruction Manual 9 Detector Base and Call Point Wiring Information Part Number Terofire STB-4SDR Hochiki YBK-R/5ZD Hochiki YBN-R/4 Apollo Diode S60 Base Apollo S60 Common Base KAC Call Point Fulleon Call Point Resettable Call Point Positive In 4 L1 2 L1 I N L1 I N 1 470 Ohm s + I N Positive Out 4 L2 1 L1 OU T L1 OU T 1 470 Ohm s + OU T Negative In 1 C5 5 L2 L2 2 COMMO N - I N Negative Out 6 C6 6 L2 L2 2 COMMO N - OU T Remote Positive Indicator 4 L1 N/ A L1 I N 1 I N L A N/ N/ A N/ A Remote Negative Indicator 5 S3 N/ A -R -R N/ A N/ A N/ A End of Line Device Active End Line of 3k3 Resistor 3k3 Resisto r Active End Line of 3k3 Resistor To Suit Detector Base To Suit Detector Base To Suit Detector Base Head Removal Supported Yes Ye s No Ye s N o

10 VRC Terofire Products Sense Zone Wiring Diagrams Find the detector bases you will be using in the table on page 9 and check to see which end of line device is required - either a 3k3 resistor or an active end of line unit. The 3k3 resistor should be used if a zone is comprised entirely of call points. Sense zone with a 3k3 end of line resistor. Sense Zone + + in + out + in + out 3k3 EOL Sense Zone - - in - out - in - out orange orange red gold The colour bars on a 3k3 resistor are Sense zone with an active end of line. Sense Zone + Sense Zone - + in + out + in + out - in - out - in - out red Active EOL black The panel is supplied with 3k3 end of line resistors as standard. Active end of line units are available separately. Remote indicator connection details are shown in the table on page 9.

Saffire+ 8-12 Instruction Manual 11 Alarm Zone Wiring Diagram The alarm zones are wired as in the diagram below. A 10k end of line resistor must be fitted at the end of the circuit. Motorised fire bells may be used, but solenoid bells MUST NOT be connected to the panel. Alarm Zone + + in/out + in/out 10k EOL Alarm Zone - - in/out - in/out brown black orange gold The colour bars on a 10k resistor are Attaching a relay to an alarm zone. Alarm Zone + Alarm Zone - NO1 NC1 NO2 NC2 A relay may be connected anywhere on the alarm zone wiring provided that two diodes (1N4001 or equivalent) are fitted as shown in the diagram. The end of line resistor is not shown, but must be connected at the end of the alarm zone wiring. The relay must have a 24V DC coil. C1 C2 Alternatively, a relay can be connected to the Aux 28V terminals, however a diode must still be connected across the coil.

12 VRC Terofire Products Additional Wiring Information Ringing the alarms remotely. The class change (CC) facility allows a remote source to sound the alarms. When the CC terminal is connected to the Perm 28V - terminal, the alarms will sound. Class Change (CC) Remote C/NO Contacts Perm 28V - Signalling fire to another panel. By connecting two panels as shown below, when panel B closes its auxiliary contacts, panel A will go into fire. If the zone on panel A is set to non-latching it will automatically reset when panel B opens its auxiliary contacts. If both panels need to signal fire to each other, simply duplicate the circuit substituting panel A for panel B and vice versa. Sense Zone + 510R Resistor Panel A 3k3 EOL C/NO Contacts in Panel B Sense Zone -

Saffire+ 8-12 Instruction Manual 13 Connecting magnetic door holders. Low voltage magnetic door holders can be switched using a set of auxiliary contacts in the panel. When the panel goes into fire, power to the door holders is removed allowing the doors to close. Care must be taken to ensure that the auxiliary contacts rating of 24V / 1A is not exceeded. Mains voltages MUST NOT be switched directly from the auxiliary contacts - instead, fit a heavy duty relay operated from the auxiliary contacts. 24V Door Holder Power Supply + Panel Auxiliary Contacts C NC Door Holder Door Holder Door Holder -

14 VRC Terofire Products Saffire+ 8-12 System Log All events should be properly recorded in this log book. An event should include fire alarms (whether real or false), faults, tests, temporary disconnections and the dates of installing or servicing engineer s visits with a brief note of work carried out and outstanding. Name and address... of installation............ Person responsible... Date... for log book... Date...... Date...... Date... System installed by... and is maintained under contract by... Tel.... Notes:

Saffire+ 8-12 Instruction Manual 15 Date Time Zone Event Action Required Date Completed Initials

16 VRC Terofire Products Date Time Zone Event Action Required Date Completed Initials