Fire-Cryer. Plus Application Guide APPLICATION GUIDE FIRE EXIT VIMPEX. Shaping Alarm Technology

Similar documents
Hydrosense. Vimpex Limited. Star Lane. Great Wakering. Essex SS3 0PJ. Tel: +44 (0) Fax +44 (0)

The EN54 Part 2 & 4 Fire System

Conventional Fire Alarm System 2014 V1.2

The system is expanded via the RCC network with each RCC capable of passing information to and from up to 31 detection or output devices.

Excel-EN Conventional Fire Control Panel

OPERATION AND INSTALLATION MANUAL

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER

Conventional Fire Detection

Control Panel Engineering and Commissioning Instructions

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

INSTRUCTION MANUAL A105NAPPX & AL105NAPPX APPELLO Alarm Tone and Voice Annunciation Sounder

NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL

SOUNDER CONTROL MODULE SCM-AS4

General Purpose IO Technical Manual

Revision November 2013 JVA Technologies. Ethernet General Purpose IO Technical Manual

The EN54 Part 2 and 4 Fire System

Application, Installation, Operation & Maintenance Manual

Intelligent Security & Fire Ltd

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

Intelligent Security & Fire Ltd

ZIOU/230 - MAINS IO INSTRUCTION MANUAL

Xenex Conventional Fire Detection & Alarm System

General Routing Interface

System 800 Addressable Fire Detection & Alarm System

Ethernet General Purpose

Control Panel User Guide

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual

EvacU Emergency Warning Control and Indicating Equipment (Occupant Warning Systems) Technical Manual MAN3072-9

An introduction to... Sigma

SYSTEM MANUAL FT1-SB. Single Zone Fire Alarm System

Fire Alarm Control Panel Installation, Commissioning & Operation MAN

Installation, Operating and Maintenance Manual

Discovery 1-4 Loop 32 Zone, 40 Character Analogue Addressable Control Panel. Application Guide

APPLICATION NOTE. Document Type. Application Note. Document Title. Date January Version DS0167/Iss 2. ESP Technical Summary

SECURIT 700L PLUS ENGINEERING MANUAL

XP95 Sounder VAD Base

Intellia Sounder Bases and Sounder Beacon Bases

Conventional & Twin-wire Fire System

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3

VIMPEX BS Evacuation. Fire Alarms EN Banshee. Beacons. FlashDome. Electronic Sounders. Audible Alarm

INSTRUCTION MANUAL A105NAPPX & AL105NAPPX APPELLO Alarm Tone and Voice Annunciation Sounder

The EN54 Part 2, 4 and 13 Fire System

EXTINGUISHING AGENT RELEASE MODULE

Interface Modules for SENTRI

Intelligent addressable fire alarm control panel

Solution F2. Fire Alarm Control Panels one step ahead.

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

INSTALLATION MANUAL SECURIT 802 CONTROL PANEL

Unity DAU Voice Alarm System

EvacU Emergency Warning Control and Indicating Equipment (Occupant Warning Systems) Technical Manual MAN3072-5

DCA4. Digitally controlled Audio Matrix. Current Thinking. Product Specification March Document Number DDC DCA ACS

The Kentec driver connects to the Kentec Syncro range of fire detection panels. Available for Commander and ObSys.

Gen4 Domestic Intruder Panels RELIABLE AND FLEXIBLE INTRUDER PANELS. Domestic applications

BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL

Reflective Optical Beam Smoke Detector User Guide

Surveyor Excel. Fire Alarm Control Equipment Network version. Programming Manual MASTER MANUAL. VERSION 14.0 and Above

FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL

INSTRUCTION MANUAL A121APPX, AL121APPX & MV121 APPELLO Alarm Tone and Voice Annunciation Sounder

Fire Signalling. Signalling Solutions

PRODUCT INSTRUCTIONS. Fire Door Control Panel (FDCP) Stock Code Description Doc No: PI-115. Ellard Fire Door Control Panel Ellard Slave Repeater Unit

Fire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63

CONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

The ID51 & ID52 can be upgraded to 2 loops without the need to change back box. FEATURES. Intelligent Features

Reliably Advanced Extinguishing Control

Door Release Power Supply

Control/Communicator Installation Manual

WD-CS. Water leak detection cable. Technical Overview. Features. Page 1. Data Sheet Ref: Issue: 5.1.

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL

user manual Document No , Revision 03 November 2015

EUROFIRE Fire Control Panel

Menvier Fire System MF9300

Fire Control Panel FS5100

DUAL MONITORED INPUT/OUTPUT UNIT BN-305-2

Addressable Loop Modules

QA16 Addressable System

IFD-E Flame Detector User Manual

Installation, Commissioning & Operating Manual

FEC403EN Installation Manual

Version 1.03 January-2002 USER S MANUAL

FEC400 Series. Installation Manual

USER MANUAL FOR OPERATING SYSTEM

SOLO Single Loop Addressable Fire Control Panel

DL100 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

Saffire User & Installation Manual. IMPORTANT This manual should be left with the panel after installation.

Gas Safety Products. Installation, operating and maintenance 11/18/2015. Merlin 1000S+ Gas Utility & Electrical Isolation Controller

FIREBETA EXTINGUISHING CONTROL PANEL (ECP)

Gas Safety Products. Installation, operating and maintenance. Merlin 1000S+i Gas & Electric Utility Controller. Rev: 03 Date:

THANK YOU FOR VOTING TEXECOM INSTALLATION MANUAL. Security Control Panel with Communicator Interface

TECHNICAL MANUAL EDITION 1.0 VANDAL RESISTANT AUDIO AND VIDEO DOOR ENTRY SYSTEMS

PREMIER EX8 INSTALLATION MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 & EN54 PARTS 2 & 4 INSTALLATION MANUAL

FR-4000 & FR-8000 Fire Alarm Monitor Installation Manual

Technical Data Sheet

ED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR

Model 17A00 Expansion Enclosure

SERIES 3000 INTELLIGENT FIRE ALARM CONTROL PANEL ENGINEERING PROGRAMING MANUAL TABLE OF CONTENTS.. 1 INTRODUCTION.. 3 SYSTEM POWER UP.

4 wire conventional alarm system

Fire detection and alarm system Operating instructions

Emergi-Lite Orbis detectors

Transcription:

Fire-Cryer Plus Application Guide APPLICATION GUIDE FIRE EXIT VIMPEX Shaping Alarm Technology

Fire-Cryer Plus The Fire-Cryer range of voice sounders was first introduced to the market by Vimpex in 1999. The continuing research and development of voice sounders by Vimpex Limited has kept us as the market leader in performance, technical capability and diversity of range and applications. The Fire-Cryer is, in its simplest form, an electronic sounder capable of delivering clear, intelligible and synchronised voice messages and tones. Requiring just 2 wires, a positive and negative, to deliver 24VDC to any one of the Fire- Cryer family of voice sounders it can be retrofitted to existing conventional sounder circuits. The cost savings of using existing wiring can be considerable. With the use of proprietary interfaces the Fire-Cryer can also be easily integrated onto addressable loops and is approved by Hochiki and Apollo. The latest range of Fire-Cryer voice sounders is now capable of holding and broadcasting up to 7 different messages and any number of tones. These messages and tones are programmed into each sounder head. This latest range of Fire-Cryer voice sounders is now known as Fire-Cryer Plus The Fire-Cryer Plus Range of Voice Sounders Mini Fire-Cryer Plus Standard Fire-Cryer Plus Midi Fire-Cryer Plus Maxi Fire-Cryer Plus Animate Fire-Cryer Plus A white base sounder for installation under ceiling mounted detectors. Part Ref. FC3/C A red wall mounted sounder supplied with or without a beacon. Available with a shallow or deep base. Part Ref. FC3/A A high output open area sounder in red. Can be supplied with back box. Part Ref. FC3/B An extra high output industrial sounder, IP67. Part Ref. FC3/D A sounder designed to meet the requirements of low frequency sounders for animals with specific auditory sensitivity levels. Part Ref. FC3/E DIL switches on all sounders can be used to vary the dba output and the beacon output on the FC3/A. Each one of these sounders can be used as a simple single message sounder and any one of the programmed messages can be pre-selected by the user using a DIL switch on the sounder.

Using Multi Message Mode and the Multi Message Switching PCB (MMSP) To use the Fire-Cryer Plus sounders in their multi message mode it is necessary to send commands to the Fire-Cryer Plus sounders to instruct the sounders which of the seven messages they should broadcast. This is achieved by introducing the Multi Message Switching PCB (MMSP). (See Figure 1) Figure 1 The Multi Message Switching PCB (MMSP) has developed into a versatile, expandable and user friendly interface to control up to seven different messages using just two cores. It is capable of handling One out all out scenarios as well as phased evacuation or staged fire alarms. It is as ideally suited to new compact conventional single zone builds, complex networked sites with many zones as well as retrofitting to existing systems. With the addition of interfaces such as the Hochiki CHQ-DSC and the Apollo SCC the Fire-Cryer Plus can be successfully installed on addressable loops. Each MMSP has two 2A sounder circuits which are monitored by the Fire Alarm Control Panel. The MMSP can be supplied separately or within an enclosure, with or without a keypad. The MMSP has six inputs available to trigger the auxiliary messages. These are identified as MA, MB, MC, MD, ME and MF. The primary message, which is known as the DEFAULT message, is usually FIRE or EVACUATE and preceded by an alerting tone chosen by the user. The remaining six messages are know as AUXILLARY messages as any of these will be overridden by the DEFAULT message. Two of the six auxiliary inputs (MA and MB) are monitored providing the opportunity to include panic alarms and terrorist or bomb alerts. These inputs can be triggered by a 470Ω resistor in series with a switch e.g a manual call point. The auxiliary messages MC, MD ME and MF can be activated by introducing a link between their respective inputs and COM. This can be achieved by a relay, key switch, IO unit, call point or similar switch. The MMSP has LED indicators on board for troubleshooting and testing.

The MMSP is either installed between the sounder circuit outputs of the Fire Alarm Control Panel (FACP) and the sounder circuits to the field. (See Figure 2) Diagram of FACP MMSP Sounder Circuits or between the loop interface (S/C) and the sounder circuits to the field. (See Figure 2) In each of these cases the last device on the sounder circuit should contain an to match the FACP being used. The MMSP in its quiescent state is invisible to the FACP and will monitor the devices on the sounder circuit in its normal manner. Zone Extension PCB (Part Ref. ZEP) A zone extension PCB is also available to seamlessly add an additional 3 zones. Each zone has two sounder circuits rated at 2A each. With the MMSP this provides up to 4 zones or 8 sounder circuits with a total load of 16A. Each ZEP has LED indicators for test and troubleshooting. When the ZEP is attached to the MMSP, all messages, whether fire or auxiliary, are synchronised. If a zone goes to Fire it will change its message immediately, or at the

end of the current auxiliary message. If an additional zone goes to Fire then it will broadcast an alarm tone until it synchronises with the zone already in Fire Zone Expansion Many MMSPs can be connected together via an Inter Synch connection to allow for synchronisation for the S1 / S2 message across any number of zones. Each MMSP can support one Zone Extension PCB and any number of MMSPs can be connected together. MMSP Options and Advanced Programming Pulsing Inputs The MMSP can be programmed at time of order to recognise a pulsed input of 1 second on, 1 second off, from the sounder circuit as a pre-alarm or alert signal. The MMSP will then instruct the Fire-Cryer Plus sounder to broadcast the predefined pre-alarm or alert message. Auto All Clear The MMSP can also be programmed at time of order to automatically broadcast an All Clear message if the Alert message is cancelled before progressing to the default message. This All Clear message can also be programmed to repeat a given number of times. Timeout The MMSP can be programmed at time of order to broadcast the Alert message for a specified period of time before broadcasting the default message to allow confirmation of the default signal. The length of this time is user definable, between 30 seconds and eight minutes, using DIL switches 1 to 4.

Fire-Cryer Plus Voice Message Controllers (Part Ref. VMC) The MMSP can be supplied with or without an enclosure and with options to include a ZEP, Key Pad and power supply units (PSU) See below (Other bespoke configurations available)

Extinguishant PCB (Part Ref EP) This smaller board was developed to satisfy several modes of operation, but small enough to fit into fire and extinguishant panels. It can be mounted on spacers, or in a DIN rail housing. In extinguishing mode the PCB recognises the outputs from the extinguishant panel and enables 1 st Stage, 2 nd Stage, Extinguishant Released and Hold messages to be broadcast without any other interfaces. Used with the FC3/A with integral strobe the installation costs can be substantially reduced. It can be also used as a simple 4 message switching PCB where no monitoring is required on the MA and MB inputs. Intelligent PIC Modules The PIC module is designed to detect the same signals as the Fire-Cryer Plus Plus range of sounders. It has two outputs, one is used to power a device when the Alert signal is detected and the second to power another device when the Alarm signal is detected. This is often used to activate a red or white strobe when in Alarm and an amber strobe when in Alert. When any other signal is detected from any of the other auxiliary inputs none of the devices will activate. A version with two relays that will switch up to 1A strobes or any other device is also available.

The Fire-Cryer Plus Multi Message Switching PCB Part Ref: MMSP Features: 2 Sounder Circuits rated @ 2A per circuit 7 messages Fully monitored sounder circuits with two additional fully monitored inputs for panic or incident alarm All messages synchronised within a 4 zone (8 Sounder Circuits) system (when used with the Vimpex Zone Extension PCB Part Ref. ZEP) Fully expandable with limitless zones with added MMSP and ZEP Diagnostic LEDs Optional integrated keypad and enable key switch for message selection Optional Metal enclosure designed around the Kentec range of panels. Can be delivered prewired with or without a PSU LED Indicators (Refer to Figure 3) Power healthy and MMSP powered illuminates the GREEN LED under Reset. Processor healthy will be indicated by a blinking GREEN LED marked PROC Transmission of a message illuminates the RED LEDs on both sounder circuits (S1A and S1B) Activation of auxiliary messages (MA through to MF) will illuminate the corresponding RED LEDs,,,, If the input to S1A or S1B is energised and LED or is not illuminated, then the fuses should be checked. If LED or is illuminated and the incorrect message is being broadcast this may indicate excessive volt drop (<20VDC) Terminals (Refer to Figure 3) AUX - - + + 24VDC Input S1A / S1B AUX. The sounder circuits S1A and S1B are provided with auxiliary terminals. Fit the panel manufacturer s recommended Resistor here. This suppresses fault signals when an auxiliary message is broadcast. MA, MB, MC, MD, ME and MF These are 6 additional inputs. MA and MB are fully monitored inputs requiring a 3K3Ω termination resistor which is supplied. To activate MA or MB, a 470Ω resistor is needed in series with the switch. The remaining four inputs when linked to COM will trigger the remaining auxiliary messages. INTERBOARD SYNC This terminal is used to link multiple MMSPs and ensures synchronisation for S1A and S1B across all MMSPs Factory Set Options. The following options can be requested when placing the order Pulsing Input If the sounder inputs are pulsed 1 second on, 1 second off, this will automatically broadcast a pre selected message, usually an ALERT or pre-alarm message. FACTORY DEFAULT IS OFF Auto All Clear Mode If the ALERT or pre-alarm message is cancelled a pre selected ALL CLEAR message will be automatically broadcast. The number of repeats of the ALL CLEAR is also set at this time. FACTORY DEFAULT IS OFF Timeout This allows a message to be broadcast for a time set by DIL switches 1-4 (see Table 1) to allow for investigation prior to evacuation. FACTORY DEFAULT IS OFF Latch Inputs Any or all inputs MA, MB, MC, MD, ME and MF can be latched. FACTORY DEFAULT IS OFF Message Termination - Messages can be set to terminate immediately or at end of message. FACTORY DEFAULT IS END OF MESSAGE User Options 8-way DIL switch SW7 and SW8 are used to disable MA and/or MB indicators respectively on the keypad. SW1-4 are used to set the time in timeout mode as a field adjustable function. (See Table 1) SW5 and SW6 have no function at present.

Figure 3 470R MCP R1 MD ME MF R2 3K3 R1 NO NC Fire Panel Relay MC MCP R1 3K3 R2 470R AUX 24V DC Supply (Note: Join AUX 24VDC -(ve) to -(ve) of Fire Panel) R2 3K3 R1 NO NC Fire Panel Relay LED 8 LED 5 LED 1 LED 9 R1: 470Ω Resistor R2: 3K3Ω Resistor (Supplied) LED 7 LED 6 LED 4 LED 3 8-Way DIL Switch SW7 & SW8are used to disable MAand/or MB indicators respectively on the keypad. SW1-4 are used to set the time in 'timeout mode' as a field adjustable function Timeout Mode is a factory set option. See Table 1. SW5 & SW6 are not used LED 10 LED 2 To / From additional MMSP To / From additional MMSP 470R Fire Panel Sounder Outputs B A 3K3 R2 470R

Table 1

The Fire-Cryer Plus Zone Extension PCB Part Ref: ZEP Features: 6 Sounder Circuits rated and independently fused @ 2A per circuit Adds 3 zones or 6 Sounder circuits to an MMSP All messages synchronised within a 4 zone (8 Sounder Circuits) system (when used with the Vimpex Multi- Message Switching PCB Part Ref. MMSP) Fully expandable with limitless zones with added MMSP and ZEP Diagnostic LEDs Optional Metal enclosure designed around the Kentec range of panels. Can be delivered prewired with or without a PSU LED Indicators (Please refer to Figure 4) Power healthy and ZEP powered illuminates the GREEN LED POWER Transmission of a message illuminates the RED LEDs,,,,, on all sounder circuits. Terminals (Please refer to Figure 4) Ribbon Cable Link to MMSP S2A, S2B, S3A, S3B, S4A and S4B Sounder inputs from Control Panel S2A, S2B, S3A, S3B, S4A and S4B AUX. The sounder circuits S2A, S2B, S3A, S3B, S4A and S4B are provided with auxiliary terminals. Fit the panel manufacturer s recommended Resistor here. This suppresses fault signals when an auxiliary message is broadcast. S2A, S2B, S3A, S3B, S4A and S4B Sounder Outputs from ZEP AUX ++ -- 24VDC - Input (Max load of 12A requires Min. 1.5mm CSA up to 2 metres in length). Negative (ve) of AUX PSU MUST be connected to Negative (ve) of Control Panel and Negative (ve) of AUX PSU if used with MMSP.

Figure 4 Fire Panel Sounder Outputs A B AUX 24V DC Supply (Note: Join Aux -(ve) of PSU to Fire Panel -(ve) Fire Panel Sounder Outputs A B Fire Panel Sounder Outputs A B Ribbon cable link to MMSP LED 2 LED 3 LED 6 LED 7 Repeat for circuits S4B, S2A, S2B, S3A and S3B LED 5 LED 4 LED 1 Vimpex Ltd Star Lane Great Wakering Essex SS3 0PJ England Tel: +44 (0) 1702 216999 Fax: +44 (0) 1702 216699 E-mail: sales@vimpex.co.uk www.vimpex.co.uk Quality System Certificate No. 456 Assessed to ISO 9001:2000 Part No: DS/FCGUIDE/Iss 1 We reserve the right to change or amend any design or specification in line with our policy of continuing development and improvement.