Hot Water Recirculation and Control, a Solution to Reduce Energy Consumption

Similar documents
Indoor thermal comfort by controlling heat transfer through building envelope

HUMIDITY RELATIONSHIP DETERMINATED IN THE DRYING CEREAL SEED FLUIDIZED BED

Technical paper Selection of district heating house stations

Domestic Hot Water production

A Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration

A Review of Hydronic Balancing of Cooling Water Circuit

Analysis of ventilation system for a microwave assisted drying unit

Fuzzy Controller for Adjust the Indoor Temperature and Preservation the Buildings

AQUAMATIC HOT WATER IS YOUR NEW WELLNESS. Instant producer of sanitary hot water

Modeling and Simulation of Axial Fan Using CFD Hemant Kumawat

CASE STUDY REGARDING ENERGY EFFICIENCY OF A VENTILATION SYSTEM WITH RECUPERATIVE HEAT RECOVERY

Mechanical Redesign, Proposal Elizabeth C. Krauss Mechanical Option September 18, 2013

Arrangements of heating systems in compliance with official regulations

Dynamic Simulation of Double Pipe Heat Exchanger using MATLAB simulink

EXERGY ANALYSIS OF DOMESTIC REFRIGERATOR WITH DIFFERENT REFRIGERANTS

Performance Evaluation of Hybrid Solar Water Heating System Using Wire Screen Packed Solar Air Heater

Thermodynamic Study Regarding the Use of Dimethylether as Eco-Refrigerant

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS

Minimization of Mass Flow in District Heating Network Equipped with One Stage Domestic Hot Water Production Substations

HEAT RECOVERY APPARATUS FOR THE LOCAL AIR TREATMENT

- Application A Boiler Control 262 & One Stage Setpoint Control 150. Mechanical Remote Display Module (D1) 040 MODE 1

heat interface units A BOILER WITHOUT A FLAME

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

THERMAL ANALYSIS OF TANKLESS HEATING SYSTEM

Technical Report #3 Mechanical Systems Existing Conditions Evaluation

Dr. Riaan Rankin & Dr. Martin van Eldik M-Tech Industrial (Pty) Ltd / North-West University October 2010.

Experimental study of hybrid loop heat pipe using pump assistance for high heat flux system

Domestic Hot Water Application manual

Performance of an Improved Household Refrigerator/Freezer

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

Experimental Evaluation of a Gas Engine Driven Heat Pump Incorporated with Heat Recovery Subsystems for Water Heating Applications

Topic 2. ME 414/514 HVAC Systems Overview Topic 2. Equipment. Outline

- Essay Control Functions and Benefits

Analysis of Triangle Heating Technique using High Frequency Induction Heating in Forming Process of Steel Plate

HyBo - Hydraulic Interface Unit AMBIENT HEATING AND DOMESTIC HOT WATER PRODUCTION FOR CENTRAL HEATING SYSTEM UNIT CODE EHIU1

Technological Variations for Domestic Waste Water Heat Recovery

RESULTS OF WORLDWIDE RESEARCH REGARDING MACHINES FOR SPRAYING HERBICIDES ON FIELD CROPS

How about Savings in Time, Money, Energy and Longer Life?

Measurement and modelling of a multifunctional solar plus heatpump system from Nilan. Experiences from one year of test operation.

Contact person Date Reference Page Daniel Månsson P07886E-rev2 1 (14) Energy and bioeconomy

Contact person Date Reference Page Daniel Månsson P07886C-rev2 1 (14) Energy and bioeconomy

Mains Pressure Hot Water from an existing vented copper cylinder... Allows the cold water tank to be removed, freeing loft space.

hydronics WHAT S WRONG WITH THIS SCHEMATIC?

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

RISK AND HAZARD PREVENTION USING REMOTE INTERVENTION

A REVIEW ON GREEN TECHNOLOGY IN HVAC

union swing check valve spring loaded check valve purging valve pressure relief valve relief valve metered balancing valve

Regenerator Design for Open Cycle Liquid Desiccant Systems Theoretical and Experimental Investigations

Maximum Obtainable Efficiency For Engines And Refrigerators Based On The Stirling Cycle

Design, Development & Testing of Double Pipe Heat Exchanger With Heat Transfer Enhancement Liners

Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad B.Tech (III II SEM) MECHANICAL ENGINEERING

Laird Engineered Thermal Systems Application Note. Liquid to Liquid Ambient Cooling Systems for Semiconductor Tools

D8) Saving water and energy on water systems. W.G. van der Schee (1) Abstract. Keywords. 1 Introduction. (1)

Influence of the method of implementing the forced air flow through the cooling system on the temperature of the coolant in heavy-duty engines

6th IASME/WSEAS International Conference on HEAT TRANSFER, THERMAL ENGINEERING and ENVIRONMENT (HTE'08) Rhodes, Greece, August 20-22, 2008

1 DOCUMENT REVISION CONTROL ELEMENTS... 9

Steven Winter Associates, Inc. J827

product overview ProControl

Hydraulic balance in a district cooling system

Hydronic Mechanical Panels

Balancing & Control. Frese OPTIMIZER 6-way. Pressure Independent Control Group

Efficiency of Application the Condensing Heat Utilizers in the Existing Boiler's Unit in Heat Power Station

Distribution systems in apartment buildings

More than twenty years Hungarian experience in one pipe heating system renovation

Development of Motor Fan Noise Prediction Method in Consideration of Operating Temperature during Engine Idling

3D-Evaluation Method for Descaling Capability of Hot Strip Mill

The product segments Heating, ventilation, air conditioning. Control Products & Systems OEM.

Design and Experimental Studies on Modified Solar Dryer

PERFORMANCE OF EARTH TUBE HEAT EXCHANGER COOLING OF AIR A REVIEW

Digital Hot Water Systems

Numerical Simulation of Fluid Flow and Heat Transfer in a Water Heater

Technical paper Hydraulic balance in a district cooling system

A. Detail drawing M1 Standard Chilled Water Schematic 1.03 DESCRIPTION OF THE PULLMAN CAMPUS CENTRAL CHILLED WATER LOOP SYSTEM:

ClimateWell package solution description

A Hot water revolution

INSTRUMENTATION AND EVALUATION OF COMMERCIAL AND HOMEMADE PASSIVE SOLAR PANELS

Fin-Fan Control System

COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd

AUTOMATION OF BOILERS USING LABVIEW

WRAS TEST & ACCEPTANCE CRITERIA Issue No: 1 Date of issue: October Sheet 1 of 7

THE INFLUENCE OF CONSTRUCTIVE AND ENVIRONMENTAL FACTORS ON THE PERFORMANCE OF REFRIGERATION INSTALLATIONS

Press. Solar heating from Viessmann: innovative collectors for DHW generation and auxiliary heating

HVAC SYSTEMS FOR HOSPITAL BUILDINGS

Technote. Frese AquaHeat HW - DH. Application. Design. Features and Benefit. Operation. Optional.

VERSO DOMEKT. Residential ventilation units m³/h. Non residential ventilation units m³/h

Portable Fire Detector

Instruction Sheet. Variable Speed - Solar (00-VT) 00 and Load Match Cartridge Circulators

DYNAMIC ANALYSIS OF A CRIMPING DEVICE WITH MULTIPLE CAMS USING MSC ADAMS

Divacondens D Plus Atmospheric condensation wall-mounted boilers, with instant domestic hot water production

Operating Guide. Termix Compact 28 VX-FI / HWP / HWS. 1.0 Table of Contents. 1.0 Table of Contents

Akva Vita Instantaneous water heater

H O B O K E N R E S I D E N T I A L

Metering systems 0548EN April 2014

Lesson 25 Analysis Of Complete Vapour Compression Refrigeration Systems

Application of the VRV Air-Conditioning System Heat Recovery Series in. Interior Zone and Analysis of its Energy Saving

Residential Water Conservation Research Brief On-Demand Hot Water Systems

Optimized Finned Heat Sinks for Natural Convection Cooling of Outdoor Electronics

A study of Transient Performance of A Cascade Heat Pump System

Performance Analysis of Domestic Refrigeration System with Thermoelectric Module

Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length

Transcription:

Adriana Tokar, Arina Negoițescu ANALELE UNIVERSITĂŢII EFTIMIE MURGU REŞIŢA ANUL XXII, NR. 1, 2015, ISSN 1453-7397 Hot Water Recirculation and Control, a Solution to Reduce Energy Consumption For the energy consumption reduction in the buildings sector, EU proposes guidelines regarding energy performance. EU Member States must take measures to ensure the conversion of buildings into nearly zero energy buildings, which should also include measures to optimize installations for domestic hot water (DHW). From this point of view the present paper deals with issues regarding hot water recirculation and control aiming to reduce fuel consumption necessary for DHW preparation. To this end the benefits of DHW preparation process optimization were analyzed, in order to ensure a theoretical constant temperature having values in a narrow domain and an efficient thermal fluid distribution in the network for better controlling hot water temperature. Keywords: domestic hot water, temperature, flow, energy, recirculating pump 1. Introduction The role of indoor domestic hot water supply installations is to provide water supply flow and pressure, required to all consumers under energetic efficiency conditions. Thus, it is necessary to implement the most efficient solutions regarding design, thermal rehabilitation and modernization of these installations for energy efficient utilization [1]. In order to reduce the energy consumption for domestic hot water (DHW) preparation, an efficient alternative is represented by using regenerable sources, such as: solar or geothermal energy. Although the hot water consumption during all the year is relative constant, the regenerable sources are variable. Therefore, in order to prepare hot water there are required supplementary energy sources. For the building global energetic balance, plumbing installations intervene directly through the thermal energy required for hot water preparation. On the other hand they indirectly intervene through the pumping energy given by the water consumption volume and simultaneousness and by pressure losses through fric- 415

tion. A secondary aspect of the energy consumption is quantified by uncontrolled water losses in the installations. Into the hot water supply installations with no recirculation (Fig.1a) frequently appear situations when after a certain time period (from 5 to 20 minutes) water reaches the required temperature at the consumers [2]. a) without recirculation b) with recirculation Figure 1. Plumbing installation for domestic hot water supply In centralized systems, this quantity of water is metered at the hot water price and directly discharged into the sewer systems. The loss is assessed both by large water quantities lost at every waiting period and by the costs for the unused water quantity circulation. Inside the most existing buildings with no rehabilitation, the major drawbacks of indoor plumbing installations are structural, namely with no recirculation pipes and if there are recirculation pipes these are not equipped as to ensure an optimal operation. From energy and water consumption reduction point of view, inside the indoor plumbing installation for DHW a solution is to equip it with DHW recirculation installations (Fig. 1b). Thus, the hot water recirculation installation can lead to a significant water loss reduction and to the increase of comfort degree. 2. The hot water recirculation installation balancing In order to increase the hot water recirculation installation efficiency, a necessary condition is represented by the achievement of the minimal temperature value 416

at the beginning of the normal consumption period in all the connection points at the supply network. This condition can be accomplished both by a proper hydraulic balance and by the correlation between the hot water consumption and the installation operation. Thus, unbalanced hydraulic recirculation installations have the disadvantage that water flows only through minimum resistance pipes circuits, while on the other circuits it will be at a standstill. This situation is similar with the operation of plumbing installation with no recirculation. The recirculation installation adjustment can be performed by selecting during the design phase the convenient diameters of the return pipe and equipping these pipes with regulators, control valves, diaphragms and control systems or through the control valves adjustment at the putting into service of the installation (slow and not recommended adjustment). The final goal is the energy economy achievement [1], [2], [3]. In Figure 2 it is presented the schematic diagram of a DHW plumbing installation with recirculation, heat exchanger (HE) and recirculation pump (PC). In this case it is obvious that the water circulation on some recirculation circuits will be advantaged compared to other circuits leading to a water temperature into the last columns lower than the required value. Figure 2. DHW plumbing installation with recirculation, heat exchanger and recirculation pump [2] This phenomenon can be prevented by mounting the balancing recirculation valves (VC) on each column and a Partner valve on the main pipe (Fig. 3). The Partner valve (VP) indicates the differential pressure exceedance. The pump rotation speed can be accordingly reduced and the Partner valve will reopen. The pressure drop in the Partner valve and the pumping height can be reduced which lead 417

to a considerable decrease in pumping costs. The optimal balancing is obtained when the balance valves will support the minimal load loss, allowing an accurate flow measurement. The exceeded pressure is overtaken by the Partner valve [1]. Figure 3. DHW plumbing installation with recirculation, heat exchanger, recirculation pump, balancing valves on columns and Partner valve [2] The balancing can be performed by using balancing taps with flow and differential pressure measurement inlet by TA (Tour&Andersson) method, using balancing computers and dedicated software. In this situation the calculation of the recirculculation flows which must be adjusted on each column is difficult to accomplish because these depend on a series of factors such as: air and water temperature inside the pipes, pipes diameter thickness and material, insulation type and thickness, etc. [2], [4]. In conclusion this system does not take under consideration the water temperature inside the recirculation columns which implies the use of water temperature control and automation equipment in order to ensure the recirculation only when it is requested. The solution can become expensive and complex. Therefore by using the recirculation installation during the consumption period will lead to an useless electric energy consumption. During the period when the energy source provides no heat for DHW preparation, using the recirculation instal- 418

lation will determine significant energy losses inside it. For this reason the recirculation installation automation is very important. In order to obtain hot water at the utilization temperature on the distribution pipe up to the connection point at the recirculation installation it is necessary that the recirculation pump to be programmed as to enter into the operation after the starting of the DHW supply installation and before the beginning of the hot water consumption [3]. A solution for solving these inconveniences regarding the water temperature control and the flow calculation on each recirculation pipe (Fig. 3) is the use of valves with pressure inlet (VPP) combined with thermostatic taps (VT), solution presented in Figure 4 [2], [3]. Figure 4. DHW plumbing installation with recirculation, heat exchanger, recirculation pump, valves with pressure inlet and thermostatic taps [2] This system presumes only the total flow calculation on the Partner valve because the required temperature is prescribed on each thermostatic tap. This tap will open only when the water temperature in the recirculation column decrease under the prescribed value and thus the balance both from the hydraulic and thermal point of view is achieved [2], [5]. 419

3. The optimization of DHW plumbing installations equipped with recirculation system Regardless, the adopted domestic hot water recirculation system, the design will be based on norms so that domestic hot water to be available at the tap after 10 seconds at operating temperature (45 C) and prevent stagnation of water in recirculation pipes [6], [7], [8], [9], [10]. Hot water supply installations may have sections without recirculating systems if it fulfills the user's comfort. Circulating DHW pumps have an important role in ensuring these conditions. Regarding the recirculation pump in DHW installations, it is necessary to ensure the consumers comfort (hot water is always available and at the same time to all the consumers) [5]. The pumps must meet standards requirements, applicable rules and regulations, high demands on hygiene and corrosion resistance performance under conditions of operation. Pumps that have adaptive system to the installation performance requirements (modern pumps high efficiency), consume a small amount of electricity, since it works all the time at full load. The savings potential that results from the use of high efficiency pumps is experimentally demonstrated and shows a reduction in electricity costs by 58% [5]. Thus, for a properly designed installation, recirculation pumps are a guarantee of comfort and quality. Because of the energy costs, a pump reduced power consumption is another priority criterion to take under consideration when a pump is chosen [5], [11]. A few efficient recirculating pumps solutions are presented in Figure 5 and Figure 6. One of the main factors that reduces energy consumption and increases reliability of supply hot water installations is the circulators pump operating time reduction. In housing and office buildings are recommended only circulators pumps with daytime operation. Currently, there is a limited range of hot water circulation pumps that use temperature as a control factor's operation time reduction, temperature sensors being mounted on the pipe near the end of the circulation loop. A more effective solution is to limit the operation time of circulator pumps by mounting them at the last consumer [13], [14]. 420

Figure 5. Recirculation pump without recirculation pipe [12] Figure 6. Recirculation pump which requires recirculation pipe [12] Systems using cold water pipes as return pipes recorded a series of problems caused by considering only the flow control factor. To prevent the flow from the cold water line to the hot water one, these systems are mounted on control valves, valves and thermostatic elements (Fig. 7) [15], [16]. The thermostatic valve remains open as long as the water temperature is below 50 C. 421

Figure 7. Fittings and sensors for flow control, mounted on pipes [15] Due to siphon phenomenon (Fig. 8), the water flows from the hot water pipe when the valve is opened. When a cold water tap is opened (CW), there is an instantaneous drop in pressure in the cold water pipes so that due to the highpressure hot water (HW) it passes through the control valve and opens the thermostatic valve. Following this process, the mixing of the hot water with cold or at room temperature water is achieved. Figure 8. Cold water siphon phenomenon [15] Regarding the use of thermostatic comfort valves for hot water circulation (COMFORT thermostatic VALVES - TCV), these are used in systems where pumps are installed in heat exchangers connected to the hot water supply pipe. Connecting cold and hot water pipes under the sink is achieved through TCV valves. Opening and closing the TCV is achieved as a result of material contraction respective expansion of the valve due to water temperature limit values (35 C), water which is in contact with the valve. 422

When only cold water is used, the high pressure from the hot water pipe causes water siphoning in the cold water pipe through the opened TCV. If the water temperature from the heat exchanger do not reach 35 C, the valve remains closed and hence the waiting time of cold water at the consumer increases. This problem is solved by using a silent solenoid, which when it is closed prevents siphoning of hot water in the cold water pipe (Fig. 9). a) b) Figure 9. The solenoid utilization for optimizing the installation [15] a) unbalanced, b) balanced As it is shown in Figure 9, the advantage of using this solenoid is the installation hydraulic balancing [15]. 4. Conclusions In conclusion, by taking into account the necessity of energy consumption reduction for hot water preparation in buildings, DHW recirculation installations is required to be optimized. The continuous technological development has led to the equipment and valves upgradation for adjust and control water recirculated temperature. In this regard, by using modern control and adjusting devices, water circulation pumps operating time is reduced and prevents water non-siphon phenomenon in pipelines concomitantly with system hydraulic balancing. Not least the adjustment and control of water flow and temperature in the pipes increase the installation energy efficiency and improve the consumer s safety and comfort References [1] ***** Enciclopedia tehnică de instalații - Manualul de instalații sanitare, Ediția a II-a, Editura Artecno, București, 2010. [2] Popescu I.P., Echilibrarea instalației de recirculare a apei calde menajere. Tehnica Instalațiilor, nr. 5, pp.102-103, IMI Internațional România SRL, 2004, http://www.tehnicainstalatiilor.ro 423

[3] Georgescu M., Soluții de eficiență energetică pentru diferite tipuri de clădiri (Aspecte tehnice și economice, studii de caz). UAUIM, Craiova, 2012. [4] ***** IMI International Co. Sisteme de reglaj. Tehnica Instalațiilor. Anul VI., nr. 3 Vol. 34, 2006. [5] ***** Wilo, Siguranță și confort cu un consum energetic redus. Tehnica instalațiilor, Anul X. 02(76), nr.76, 2010. [6] ***** EN 806-1, Specifications for installations inside buildings conveying water for human consumption Part 1: General, BSI, 2000. [7] ***** EN 806-2, Specifications for installations inside buildings conveying water for human consumption Part 2: Design, BSI, 2005 [8] ***** EN 806-3, Specifications for installations inside buildings conveying water for human consumption - Part 3: Pipe sizing-simplified method, BSI, 2006. [9] ***** EN 806-4, Specifications for installations inside buildings conveying water for human consumption - Part 4: Installation, BSI, 2010 [10] ***** EN 806-2, Specifications for installations inside buildings conveying water for human consumption - Part 5: Operation and maintenance, BSI, 2012 [11] ***** Willo, Schimbarile climatice: soluții pentru alimentarea cu apă. Tehnica Instalațiilor, Anul IX, nr. 1, vol. 64, 2009. [12] Flo-Rite Plumbing Pty Ltd, Hot Water Circulation Pump Brisbane - Gold Coast, www.floriteplumbing.com.au, 2015 [13] ***** RedyTemp Intelli-Circ Optimizing Controller, Efficient Hot Water Circulation, http://www.redytemp.com. [14] ***** Water Recirculation Pumps, http://www.diyplumbingadvice.com. [15] ***** Hot water circulator problems solved. http://www.redytemp.com. [16] ***** Oventrop, Recircularea si controlul temperaturii apei calde menajere. Tehnica instalațiilor, nr. 17, vol. 104, 2015, www.tehnicainstalatiilor.ro. Addresses: Lect. Dr. Eng. Adriana Tokar, Faculty of Civil Engineering, Politehnica University Timișoara, 2 Traian Lalescu Street, 300223, Timișoara, adriana.tokar@upt.ro Conf. Dr. Eng. Arina Negoițescu, Faculty of Mechanics, Politehnica University Timișoara, 1 Mihai Viteazu BLV., 300222, Timișoara, arina.negoitescu@upt.ro 424