TotalPac X Firecycle III Preaction Double interlock system

Similar documents
TotalPac X Single interlock SUREFIRE system

TotalPac 3 Firecyle III Deluge Remote controlled system

TotalPac 3 Single interlock Firecyle III Preaction Self-contained system

TotalPac 3 Wet pipe system c/w retard chamber

TotalPac 3 Double interlock Preaction, Electric/PneuLectric release Self-contained system

N2 BLAST Datasheet Preaction double interlock, Electric/Pneumatic c/w N 2 Blast Nitrogen generating system Self contained unit

Datasheet. Dry-pipe Vacuum Sprinkler System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description

N2 BLAST Datasheet SUREFIRE double interlock c/w N 2 Blast Nitrogen generating system Self contained unit

Datasheet. Vacuum Double-interlock Preaction System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description

N2 BLAST Datasheet Preaction double interlock, Electric/Pneulectric c/w N 2 Blast Nitrogen generating system Self contained unit

Advanced Integrated Fire Protection Systems TOTALPAC 2. Owner's Operation and Maintenance Manual FIRECYCLE III. September 2009 FM-086G-0-5E

TotalPac 3 Deluge, Electric release Self-contained system

TOTALPAC2 Integrated Fire Protection System

TotalPac 3 Non interlock Preaction, Electric release Self-Contained system

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC RELEASE

TotalPac 3 Single interlock Preaction, Electric release Self-contained system

Not to be distributed outside of FM Approvals and its affiliates except by Customer APPROVAL REPORT

FireFlex DUAL Double Interlock, Self-contained system

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEUMATIC RELEASE 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

TECHNICAL DATA. 319a. January 27, 2012

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEU-LECTRIC RELEASE

TECHNICAL DATA OBSOLETE

TECHNICAL DATA 1. SYSTEM DESCRIPTION 2. SYSTEM OPERATION 3. INSTALLATION. Page 1 of 5

Deluge System. Pneumatic Release. Deluge System. Pneumatic Release

Pre-Pack INTEGRATED PRE-ACTION SYSTEM

Technical Data. Approvals The 1-1/2 in. to 8 in. (DN40 to DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types:

Technical Data. Approvals The 1-1/2 thru 8 inch (DN40 thru DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types:

Deluge & Preac tion Systems

Worldwide Contacts.

BERMAD Fire Protection

TECHNICAL DATA. Factory Mutual Approval is pending for the system as a whole.

DV-5 Red-E Cabinet Integrated Deluge Fire Protection Package. General Description. Technical Data. Page 1 of 6 AUGUST 2018 TFP1300. Worldwide Contacts

Technical Data. Working Pressure Range 20 to 250 psi (1,4 to 17,2 bar)

DOUBLE INTERLOCK, PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC RELEASE

Instructions for. Care and Maintenance 10 psi (0,7 bar) Pneumatic Supervising Pressure. Single Interlock

SINGLE INTERLOCK, SUPERVISED PREACTION SYSTEM WITH ELECTRIC RELEASE

TECHNICAL DATA DELUGE SYSTEM CONTROLLED BY ELECTRIC RELEASE

Model DDX Deluge Valve

SINGLE INTERLOCK, SUPERVISED PREACTION SYSTEM WITH WET PILOT ACTUATION

TECHNICAL DATA. model c-2

Becoming an Expert on Dry-pipe, Preaction, and Deluge Sprinkler Systems

Instructions for Installation, Operation, Care and Maintenance

TECHNICAL DATA OBSOLETE

B. The sprinkler system shall be designed to meet the more stringent of the requirements of NFPA 13 and FM Global requirements.

DIVISION 21 FIRE SUPPRESSION SECTION FIRE PROTECTION SPECIALTIES

Operation & Maintenance Manual

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Deluge Fire Protection Package General Description

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Preaction Fire Protection Package General Description

Options for Diesel Fire Pump Controllers

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014

Model: 400E-5M. Bermad Hydraulically Controlled Anti-Columning Deluge Valve, with Easylock Manual Reset. Installation Operation Maintenance

VIZOR Electronic Dry Pipe Accelerator (EDPA) Quick-Opening Device for Dry Pipe Systems General Description

Specification/ Data Sheet

Technical Data. Minimum Inlet Supply Pressure All MCC Models...0 psi. Minimum Inlet Supply Capacity Match system design calculations

Technical Data. Minimum Inlet Supply Pressure All MCC Models...0 psi. Minimum Inlet Supply Capacity Match system design calculations

Gas Station & C Store SECTION CWM Job No

SECTION PREACTION SPRINKLER SYSTEMS

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

CONSTRUCTION REQUIREMENTS

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE

AQUAMIST Mist Control Center (MCC) Pump Skid Unit. General Description. Technical Data. Page 1 of 8 JANUARY 2016 TFP2270. Worldwide Contacts

DELUGE VALVE MODEL: SD-DVH2 TECHNICAL DATA TRIM DESCRIPTION DESCRIPTION VALVE OPERATION. 82 ASTM A 216 WBC.

FireFlex 1230 Self-contained system

FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel

LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS

Model QRS Electronic Accelerator (Quick Opening Device) For Dry Pipe or Preaction Systems General Description

30.45 Electric Release PDRP-2001

Commercial and Light Industrial Fire Alarm Control Panel

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL

Global Property. QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:

Annual Report of Inspection, Testing & Maintenance of Automatic Sprinkler System

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE

OPEN SPRINKLER SYSTEM

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE

Global Property. SEMIANNUAL FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:

SECTION SPRINKLER SYSTEMS

FIRE-PAC SERIES 745 FIRELOCK SYSTEMS

TECHNICAL DATA. 31a. September 18, (DN25 - DN50)

TECHNICAL DATA. 32a. September 18, /4-8 (DN32 - DN200)

ON THE BUTTON A reference guide to environmental ratings used for push button enclosures

Discontinued Product

TECHNICAL DATA OBSOLETE

TECHNICAL DATA. Notes: For use with Trim Charts on Pages 227b - d

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

VDC. Wireless AC Voltage Detection Sensor. The Leader in Low-Cost, Remote Monitoring Solutions. General Description. Monnit Sensor Core Specifications

SPECIFICATION: CARBON DIOXIDE ENGINEERED FIRE SUPPRESSION SYSTEM

SECTION DRY-PIPE SPRINKLER SYSTEMS

ECS Pre-Engineered Nitrogen Generator. ECS Pre-Engineered Wall Mount Nitrogen Generator PGEN-3/(PGEN-3E) PGEN-5/(PGEN-5E)

ECS Pre-Engineered Nitrogen Generator. ECS Pre-Engineered Wall Mount Nitrogen Generator PGEN-10/(PGEN-10E)

1.2 CODES AND REGULATIONS A. Sprinkler system design, equipment, materials, devices, and installation shall conform to the following:

TECHNICAL DATA EASYPAC COMMERCIAL RISER MANIFOLD ASSEMBLIES 1-1/4-8 (DN32 - DN200)

esfr dry pendent sprinkler Vk502 (k14.0)

West District Library Section Campeau Drive, Ottawa SPRINKLER SYSTEMS City of Ottawa Project No. CR Page 1 of 8

Box-in-Box Cold Storage Fire Protection Options

SECTION SPRINKLER SYSTEMS

ECS Protector Nitrogen Generator PGEN-40FK/PGEN-50FK/PGEN-60FK PGEN-40M/PGEN-50M/PGEN-60M

THE JAMES RUSHTON EARLY LEARNING AND FAMILY SUCCESS CENTER #2616 ISSUE FOR CONSTRUCTION

PHYSICAL FACILITIES. 1 General. 2 Related Requirements. 5 Quality Assurance. 3 Wiring. 4 Submittals

Model AV Alarm Valve With and Without Model RC-1 Retard Chamber European Conformity Valve Trim General Description

TN-25 Tunnel Fire Protection System. Safer. Smarter. Tyco.

Transcription:

DESCRIPTION This TOTALPAC X integrated fire protection system by FireFlex Systems Inc. consists of a multicycling Firecycle III system trim totally pre-assembled, pre-wired and factory tested. All electrical and mechanical components of the system are contained in one single unit TOTALPAC X Firecycle preaction systems are built around the Viking trim using flow control valves model H-3 for 1½" (40 mm) diameter and model H-1 for 2" (50 mm) diameter and up. Firecycle double interlock preaction systems uses closed automatic sprinklers in the sprinkler piping. A detection network is used in parallel with the automatic sprinkler system and is designed to operate before a sprinkler head fuses. This network is electric and may be actuated by manual or rate compensated temperature. The detection system operates before the sprinkler fuses and gives an alarm. The operation of both a sprinkler and a detector is required before the valve will open, allowing water to enter the system piping. In addition to automatically detecting a fire and turning the system on, Firecycle III has the added ability to sense when the fire has been controlled, and automatically turn off the water flow once a preprogrammed "Soak Timer" has been satisfied. Should the fire rekindle, the control panel (supplied by others) will initiate the sequence again. This unique Firecycle III feature will repeat as long as power is available to the panel, helping to minimize water usage, water damage, and the danger of pollution to surrounding areas. The Firecycle III preaction system requires a VIKING VFR-400 control panel (supplied by others). All the valves are rated up to a maximum of 250 psi WWP (1724 kpa) max. and are available in the following diameters: 1½" (40 mm) 3" (80 mm) 6" (150 mm) 2" (50 mm) 4" (100 mm) Standard features NEMA 3 or NEMA 4 construction Factory assembled and tested under ISO-9001 standards Prewired to a terminal block Easy and compact installation Viking conventional trim rated at 250 psi (1724 kpa) Galvanized trim piping Serial number for easy reference Wide door for easy access Quarter turn door latches Lockable door to protect against tampering Lifting lugs provided for safe and easy handling Corrosion resistant paint finish Water supply and drain through the bottom center of the unit to avoid freeze-up potential Single drain connection 1 of 12 FM-076D-0-26C

Cabinet NEMA 3 Enclosures constructed for either indoor or outdoor use to provide a degree of protection of the equipment inside the enclosure against ingress of solid foreign objects (falling dirt and windblown dust); to provide a degree of protection with respect to harmful effects on the equipment due to the ingress of water (rain, sleet, snow); and that will be undamaged by the external formation of ice on the enclosure. NEMA 4 Enclosures constructed for either indoor or outdoor use to provide a degree of protection of the equipment inside the enclosure against ingress of solid foreign objects (falling dirt and windblown dust); to provide a degree of protection with respect to harmful effects on the equipment due to the ingress of water (rain, sleet, snow, splashing water, and hose directed water); and that will be undamaged by the external formation of ice on the enclosure. NEMA 3X Enclosures constructed for either indoor or outdoor use to provide a degree of protection of the equipment inside the enclosure against ingress of solid foreign objects (falling dirt and windblown dust); to provide a degree of protection with respect to harmful effects on the equipment due to the ingress of water (rain, sleet, snow); that provides an additional level of protection against corrosion and that will be undamaged by the external formation of ice on the enclosure. NEMA 4X Enclosures constructed for either indoor or outdoor use to provide a degree of protection of the equipment inside the enclosure against ingress of solid foreign objects (windblown dust); to provide a degree of protection with respect to harmful effects on the equipment due to the ingress of water (rain, sleet, snow, splashing water, and hose directed water); that provides an additional level of protection against corrosion; and that will be undamaged by the external formation of ice on the enclosure. COMPARISON OF SPECIFIC NON-HAZARDOUS APPLICATIONS Type of enclosure Provide a degree of protection against the following environmental conditions 3 a 3X a 4 4X Incidental contact with enclosed equipment Rain, snow and sleet Hose down and splashing water Corrosive agents Ingress of solid foreign object (circulating or setting airborne dust, lint, fibers, and flyings) b Ingress of solid foreign objects (winblown dust, lint, fibers, and flyings) b a : these cabinet may be ventilated. b : these fibers and flyings are non hazardous materials and are not considered class III type ignitable fibers or combustible flyings. FM-076D-0-26C 2 of 12

Sequence of operation (see trim diagram) In a fire condition, operation of the detection system activates the first initiating circuit in the system control panel, causing an alarm to activate. When a sprinkler operates, air pressure escapes from the sprinkler piping. The air supervisory switch activates the second initiating circuit in system control panel. When BOTH initiating circuits have been activated, system control panel energizes normally closed Solenoid valve (F2) open and normally open solenoid valve (F1) closed. Pressure is released from the priming chamber of the flow control valve (A1) to the open drain manifold faster than it is supplied through the restricted orifice (B3). The flow control valve clapper opens to allow water to flow into the system piping and alarm devices, causing the alarm pressure switch (C1) and optional water motor alarm (C2) to activate. When a sprinkler head opens, water will flow from the system. When the flow control valve operates, the PORV (B9) is pressurized, causing it to latch open. Water discharges until all Firecycle detectors have reset (cooled below their set point). After all detectors have reset, the Firecycle III control panel activates the soak timer, allowing the system to flow water for a pre-determined period of time. When the soak timer has elapsed, the control panel de-energizes the normally closed solenoid valve (F2), allowing it to close, the normally open solenoid (F1) remains energized closed until the system is manually reset or all power (both AC and batteries) is lost). The flow control valve re-primes and closes, stopping the flow of water through the piping system. Should a Firecycle detector go into alarm, the control panel reenergizes the normally closed solenoid valve (F2) open, and the entire cycle repeats. Systems hydraulic limitations WARNING The information contained herewith is for estimation and evaluation purposes only. Its use remains the responsibility of the designer. Designers should refer to the appropriate NFPA Standards and any other applicable codes for their final design. Also refer to FireFlex Systems Inc. appropriate user manuals and to manufacturer's data sheets for additional details. Systems limitations indicated below are nominal flow limitations. Piping Equivalent Lengths w/o System size Usage Range shut off valve (in.) (gpm) (m.) (ft.) 1½ 0 200 8.6 28.2 2 0 330 12.9 42.3 3 125-700 19.8 64.8 4 250 1200 27 88.8 6 750-2800 31.2 102.4 3 of 12 FM-076D-0-26C

Standard equipment Flow control valve The Viking flow control valve is a quick opening, differential type flood valve with a spring loaded rolling diaphragm clapper. The flow control valve can be used to facilitate manual or automatic on/off control. As an on/off control valve it may be used on deluge systems. The Viking flow control valve is an integral part of the Viking Firecycle System. Pneumatic actuator Used in conjunction with the solenoid valve, the Viking Pneumatic Actuator is a spring loaded, rolling diaphragm and piston operated valve. It is used wherever a combination is required between the detection and system s loss of air. Preaction riser check valve Water supply control valve The water inlet control valve is a supervised, indicating butterfly valve. Purpose of this vale is to manually shutoff the preaction system. The Viking spring loaded In-Line check valve is a general purpose rubber-faced check valve approved for use in fireservice systems. The Spring Loaded In-Line check valve is manufactured with a brass body, brass seat, and a rubberfaced clapper assembly. The Viking Easy Riser Swing check valve is a general purpose rubber-faced check valve approved for use in fire service systems. The valve is for use in preaction system risers. Solenoid valve The high pressure solenoid valve is a two-way type with one inlet and one outlet. It is a packless, internal pilot operated valve, suitable for use in releasing water pressure from the priming chamber of Viking deluge valves. The solenoid valve has floating diaphragm construction, which requires a minimum pressure drop across the valve to operate properly. IN OUT FM-076D-0-26C 4 of 12

Standard equipment (continued) Alarm pressure switch The alarm pressure switch monitors the water flow within the sprinkler piping. Should the Deluge Valve clapper opens to allow water to flow into the sprinkler piping. The alarm pressure switch will activate, indicating a water flow signal. POTTER PS10-1A Low air supervisory switch The low pressure switches monitors the pressure within the sprinkler piping should a loss pressure of the air below 25PSI occurs, the pressure switch contacts transfer indicating low air supervisory signal. Should a loss pressure of the air below 23PSI occurs, the pressure switch contacts transfer indicating low air alarm signal. POTTER PS40-2A 5 of 12 FM-076D-0-26C

Optional equipment Shut-off valve & sight glass option The Shut-off Valve & Sight Glass Option is intended to be used for applications where testing of the system operation without filling the sprinkler piping network is desirable and where it is critical that all functions of the preaction system be tested under actual discharge conditions. Shut-off valve (D4) Heater option Heater option is recommended where ambient temperatures can drop below 40 F (4.5 C). The cabinet s electric heater temperature cut-out point is set at 50 F (10 C). The heater option is equipped with a low temperature sensor that will activate a supervisory signal when temperature drops below 40 ±5 F (4.5 ±3 C). Heater option can be ordered in two supply voltage settings: 120Vac-60Hz. 400Watts. 220Vac-50Hz. 400Watts. Sight glass Point flashlight here Warning: TOTALPAC X cabinet is rated to provide freeze protection down to a minimum temperature of 14 F (-10 C). Insulated enclosure (standard with heater option) Insulation is made on foam core 2 thick R13 and have a foilfaced sheathing board composed of a uniform closed cell polyisocyanurate foam core bonded on each side to a triminate foil facer. One side has a foil reflective facer and the other side has a non-reflective foil facer. Low temperature sensor (standard with heater option) The low temperature sensor will close the normally open contact when the temperature drops below 40 F (4,5 C. The sensor will automatically reset to its normal state when the temperature rises above 40 F (4,5 C). Light option Optional fluorescent enclosure light is available for all cabinet configurations. Remote door switch activates the light when the door is opened. Light option can be ordered in two supply voltage settings: 120Vac-60Hz. 220Vac-50Hz. FM-076D-0-26C 6 of 12

Air supply Direct air compressor (Style A ) Used only for the sprinkler piping network of the preaction system. Air supply style "A" includes the air compressor mounted inside the TOTALPAC X cabinet with its supervisory trim and options. Compressors are of the tankless, oiless piston type and are factory piped to the sprinkler system riser, all within the TOTALPAC X cabinet. Air Pressure Maintenance Device (Style B ) Used only for the sprinkler piping network of the preaction system, when an external air supply is provided by others (tank mounted compressor, plant air or dry nitrogen cylinders) and piped to the air inlet port of the unit. Air supply style "B" provides an Air Pressure Maintenance Device (APMD) trim, factory mounted in the TOTALPAC X cabinet. Note: Direct air compressor is available only with NEMA 3, 3X cabinet. Compressors are available in four (4) sizes; 1/6HP 1/3HP 1/2HP 1HP Direct air, external compressor (Style D ) Mainly used with Preaction systems protecting refrigerated spaces and freezers, where a special dry external air supply unit is piped directly to the system riser inside the freezer itself, as shown in NFPA-13. Air supply Style "D" provides only an air supervisory and shut-off trim. Note: The external air supply must be restricted to insure that it cannot replace air as fast as it escapes when a releasing device or sprinkler operates. Air compressor selection Table: H.P. CFM @ 40 psi 120Vac System capacity (gallon) to Pump to 40 psi in 30 Minutes 220Vac System capacity (gallon) to Pump to 40 psi in 30 Minutes 1/6 1.33 110 90 1/3 2.61 215 170 1/2 4.06 335 270 1 7.40 610 400 Warning: When air supplies style "B" or "D" is selected, the air supply should be provided and installed by the sprinkler contractor OUTSIDE of the TOTALPAC X cabinet. It is NOT provided with the unit. Compressor Amp rating Compressor Size Amp. Rating at (HP) 120Vac 60Hz Amp. Rating at 220Vac 50Hz 1/6 6.6 A 3.3 A 1/3 6.6 A 3.3 A 1/2 8 A 4 A 1 12.4 A 6.2 A 7 of 12 FM-076D-0-26C

Details & field wiring diagrams Cabinet with main components, shown without door FM-076Z-0-41A FM-076D-0-26C 8 of 12

Trim diagram Components: A2 Flow control valve B1 Priming valve B2 Strainer B3 1/16" Restricted orifice B4 Spring loaded check valve B5 Alarm test valve B6 Flow test valve B7 Drip check valve B8 Drain check valve B9 Pressure operated relief valve (PORV) B10 Emergency release valve B11 Prime pressure water gauge & valve B12 Water supply pressure gauge & valve B13 Clapper check valve C1 C2 D1 D2 D3 F1 F2 F3 Alarm pressure switch Connection to water motor gong (strainer supplied by contractor) Water supply control valve Riser check valve Main drain valve N.O Solenoid Valve 24Vdc N.C Solenoid Valve 24Vdc Pneumatic Actuator 9 of 12 FM-076D-0-26C

Wiring diagram Waterflow Alarm switch TBA 1 2 3 4 TBB heater(optional) Light (optional) Very low air Alarm switch 5 6 7 8 M Low air Sup'v switch 9 10 11 12 Factory wired Main valve Sup'v switch 13 14 N.C. solenoid valve (See table below for details) 15 16 17 18 19 20 21 NOTES: - ALL DEVICES ARE SHOWN IN THEIR NORMAL SUPERVISORY STATE. - DRY CONTACTS RATINGS: PRESS. SWITCHES: 2.0A. 30VDC / 10A. 125/250 VAC SUPV. SWITCHES: 0.5A. 125 VDC /.025A. 250 VAC / 10A 125/250VAC USE ONLY WITH POWER LIMITED CIRCUITS - USE END-OF-LINE DEVICES COMPATIBLE WITH THE RELEASE CONTROL PANEL USED (NOT INCLUDED). N.O. solenoid valve (See table below for details) Low temperature Sup'v switch (optional) 22 23 24 25 26 Viking P/N Description Voltage Watts DC Amps 11591 SOLENOID VALVE ELECTRICAL RATINGS N.C. 24 Vdc 10 DC 416mA 11596 N.O. 24 Vcc 10 DC 416mA Pressure Rating 300 psi (2068 kpa) 300 psi (2068 kpa) Shut-off valve Sup'v switch (optional) 27 28 29 30 Notes: 1. Solenoid Valve is UL Listed as Fire Protection Special System Water Control Release Service (UL 429A Product category VLTR). 2. Voltage Drop: For proper operation, make sure that voltage at the solenoid valve is at least 85% of nameplate rating. 31 Factory wired 32 FM-076Z-0-33A FM-076D-0-26C 10 of 12

Dimensions B FACE VIEW S R A = Water inlet diameter B = Sprinkler riser diameter C = Drain diameter Q G SIDE VIEW K DRAIN - SCH.40 GROOVED OUTLET C WATER INLET SCH.40 GROOVED A M E O F D FM-076Z-0-54B L H N X J BOTTOM VIEW M O TOP VIEW V W NN Dimensions are nominal and may vary ±¼". Size A B C D E F G H J K L M N NN O Q R S T U V W X Y 1.5" 2" 1.5" 2" 50" 24.5" 14.5" 74" 11.5" 11" 68" 25" 5.5" 25" 25" 11" 60" 4.75" 6" 9.5" 10.5" 4" 5" 9.5" 7.75" 2" 2" 2" 2" 50" 23" 12" 74" 12" 11" 68" 25" 5" 25" 25" 11" 60" 4.75" 6" 9.5" 10.5" 4" 5" 9.5" 8" 3" 4" 3" 2" 50" 23" 12.5" 74" 8.5" 11" 68" 25" 5.5" 28.5" 22" 11" 60" 4.75" 6" 9.5" 10.5" 4" 5" 9.5" 8.5" 4" 4" 4" 2" 50" 22.5" 12.5" 74" 8" 12" 68" 25" 5.5" 25.5" 25.5" 12" 60" 4.75" 6" 9.5" 10.5" 4" 5" 9.5" 9" 6" 6" 6" 2" 50" 21" 12" 74" 8" 12" 68" 25" 5" 25" 25" 12" 60" 4.75" 6" 9.5" 10.5" 4" 5" 9.5" 9" 4.5" 4.5" 9/16" DIAM. (4 HOLES) 4.5" 4.5" FLOOR ANCHORING TEMPLATE 11 of 12 FM-076D-0-26C

1935, Lionel-Bertrand Blvd. Boisbriand QC Canada J7H 1N8 Tel.: 450-437-3473 Fax: 450-437-1930 Toll Free: 866-347-3353 Email: info@fireflex.com Web: www.fireflex.com FM-076D-0-26C 12 of 12