DIRTMAG dirt separator with magnet, adjustable for vertical or horizontal pipe

Similar documents
Installation, commissioning and servicing instructions

DIRTCAL - DIRTMAG dirt separator

5231 Series. Low Lead High Flow Thermostatic Mixing Valves. Installation, commissioning and service instructions ASSE 1017 NA10341

5231 Series. Low Lead High Flow Thermostatic Mixing Valves. Installation, commissioning and service instructions ASSE 1017 NA10341.

Thermostatic mixing valves with interchangeable cartridges

281 Series. ThermoBloc boiler protection recirculation and distribution unit. Installation, commissioning and servicing instructions

521 Series. MixCal adjustable three-way thermostatic mixing valve. Installation, commissioning and service instructions

Installation, commissioning and servicing instructions. Technical Characteristics. -Lead Plumbing Law Certifi ed by IAPMO R&T

2018 PLUMBING AND HYDRONICS CATALOG

CALEFFI. dirt separator series 01137/16 NA. Replaces 01137/15 NA. Product range. Technical specifications

CALEFFI. Thermostatic mixing valves with replaceable cartridge for centralized systems. 5230, 5231 series 01080/13 NA ASSE Replaces 01080/11 NA

Thermostatic mixing valves with replaceable cartridge for centralized systems

Davies Carries Parts for MF & SF Series Glycol Feeders

2019 PLUMBING AND HYDRONICS CATALOG

CALEFFI. SEP4 combination hydraulic, air, dirt and magnetic separator series 01249/13.1 NA. Replaces 01249/13 NA. Function.

caleffi hydronic valves page 1 of 12

CALEFFI. Thermostatic mixing valves, low-lead, high-flow series 01256/18 NA. Replaces 01256/15 NA

Adjustable three-way thermostatic mixing valve... connections ½", ¾", 1" NPT male union and sweat union and ¾" press

CALEFFI. water heater tank mixing valve. TankMixer. 520 series 01267/17 NA

R146C. Adjustable magnetic dirt separator. Versions and product codes. Datasheet 0840EN 10/2018

Installed together 5 year warranty

Function. Pressure Vessel Inspector; CRN registered Sizes 2 4

FOR INSTALLING AND USING

function Adjustable thee-way thermostatic mixing valve... connections 1/2", 3/4", 1" NPT male union and sweat union

INSTRUCTIONS REHAU PRO-BALANCE MIXING MODULE

union swing check valve spring loaded check valve purging valve pressure relief valve relief valve metered balancing valve

OPERATING AND MAINTENANCE MANUAL

FULL RANGE of products for the protection of boilers and water heating loops SLUDGE FILTERS FDM-1P / FDM-2 / FDM-3

AIRTERM DIRT AND AIRTERM MAG COMBINED SELF-CLEANING DIRT SEPARATORS / DEAERATORS

Product range Code HE1 Connection and energy management compact unit without anti-condensation valve

CALEFFI. Anti-condensation recirculation and distribution unit. 281 series 01224/14 GB. Replaces dp 01224/12 GB. Function

Hydronic Specialties and Circulator Pumps

Eliminator TotalGuard Installation Manual

CALEFFI. Set point thermostatic regulating unit. 182 series 01190/18 GB. replaces dp 01190/15 GB

Composite under-boiler dirt separator with magnet DIRTMAG

Radiator valve inserts

General System Layout Sketch

B OILER MAG XT. 2 flanged - COD flanged - COD flanged - COD flanged - COD flanged - COD.

Installation and Commissioning Instructions FMU3 Floor Mixing Unit with Grundfos UPM3 Pump

General System Layout Sketch

IMPORTANT SAFETY INFORMATION READ ALL...

PRODUCT GUIDE. High performance heating system filter Improves energy efficiency Captures magnetic and nonmagnetic.

Instruction Sheet AquaMotionHot One AMH1K-1 Point of Use Hot Water Recirculation System

Mercury Mixing Kit (Code: ME1053)

CALEFFI. Thermostatic regulating unit for heating systems. 166 series 01238/17 GB. replaces dp 01238/15 GB. Function

569, 570, 571, 572 Series

569, 570, 571, 572 Series

Installation Instruction. Puritan Bennett. Wall Air Water Trap For 800 Series Ventilator Basic Cart. Pla

DEFENDER DEFENDER. Models: MD22A OPERATION MANUAL. Full Flow Magnetic Filter

Installation & Operating Instructions

Zeparo Cyclone. Automatic air vents and separators Dirt and magnetite separator with Cyclonic technology

CALEFFI. Anti-condensation circulation unit. 282 series 01225/14 GB. replaces dp 01225/11. Code completion Setting 45 C 55 C 60 C 70 C.

Radiator Connection System, Thermostatic Valve and Return Valve with Shutoff Function

Allcan TM Installation Manual

DEVIATING VALVES ART K063

Mikrotherm. Manual Radiator Valves With presetting

FIREPLACE INSTALLATION

Item # /2" NPT, 2 STAGE AIR FILTER/DRYER SYSTEM INSTRUCTIONS

Installation and Servicing Instructions

Parasitic Cysts - Cryptosporidium and Giardia, Chemicals, Heavy Metals, Dissolved Salts, Offensive Tastes and Odours, Sediment, Dirt,

THERMOSTATIC SINGLE-PIPE AND DOUBLE-PIPE VALVES

Beautifully Traditional

Boiler protection kit guide

Greenstar System Filter

SPEAKMAN SPEAKMAN SPECIFICATIONS

ACCREDITED. Product range Code A2L Pre-assembled set point temperature regulating unit with manifolds and box, with UPM3 Auto L pump

Regulux. Return Lockshield Radiator lockshield with consistent presetting and drain-off facility

Crown Boiler Company

QVE1901U Flow Switch. Technical Instructions Document No September 20, Description. Features. Application.

VENTS. Main Steam Vents. How to Select Steam Vents. For Steam Vent selection information, please refer to Selection Guidelines on page 133.

ASTRO EXPRESS 2 HOT WATER DELIVERY SYSTEM

DHC-E TANKLESS ELECTRIC WATER HEATERS INSTALLATION INSTRUCTIONS FOR THE LICENSED PLUMBER AND ELECTRICIAN

INSTALLATION INSTRUCTIONS

The Ultimate in Distribution Efficiency. Air Eliminator Dirt Separator Low Loss Header Hydraulic Separator

Commercial Electric Water Heater USE & CARE MANUAL

! WARNING. Before using product, read and understand instructions.

HOMEADVANTAGE II IMPORTANT SAFETY INFORMATION

Patterson/AMT Inline Circulator Pump Refer to pump manual for General Operating and Safety Instructions.

Flow Factor ~

RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, Dual-Purpose Water Supply, Domestic and Fire Sprinkler System General Description

SPIROVENT JUNIOR. Microbubble Separators Dirt Separators Combination Air/Dirt Separators. The Ultimate in Distribution Efficiency

Series 20 Dual Check Backflow Preventers

Operating Instructions. Boilermag XL Filter. High Intensity Magnetic Separator

Radiator Valve Program

CalMag Filter Installation Instructions

SuperKlean Washdown Products

Installation S

Patterson/AMT Inline Circulator Pump Refer to pump manual for General Operating and Safety Instructions.

TREVI BLEND SINGLE LEVER SHOWER VALVES. INSTALLER After installation pass to user for future reference

Installation S

Installation S

PRO SERIES IMPORTANT SAFETY INFORMATION

A AD Oil burners fuel unit. deltapumps.com. DE A-AD_en_0709.pdf Page 1/1

DISCALDIRT deaerator-dirt separator

Threaded. Flanged. Model PSH. Primary Secondary Header A-451

Caleffi Hydronic Solutions Contact: Rex Gillespie, Director of Marketing Phone: (414)

J120 STEAM BOOSTER INSTALLATION, OPERATION, AND SERVICE MANUAL J120 STEAM BOOSTER. J120 Steam Booster Manual D

HKF 8180 Operating instructions

Beautifully Traditional

Main Steam Vents. Hoffman Specialty Regulators. How to Select Steam Vents

Transcription:

DIRTMAG dirt separator with magnet, adjustable for vertical or horizontal pipe Copyright 206 Caleffi NA0322.02 www.caleffi.com NA5453 Series Installation, commissioning and servicing instructions Function In heating and chilled water systems, the circulation of water containing impurities may result in rapid wear and damage to components such as pumps and control valves. It also causes blockages in heat exchangers, heating elements and pipes, resulting in lower thermal efficiency within the system. The dirt separator separates off these dirt particles, circulating within the closed circuit system. These particles are collected in a large chamber, requiring infrequent cleaning, which requires simply removing the magnet ring and opening the large drain valve while the system is running. This device is capable of efficiently removing particles to a very small size, with very low pressure head loss. The DIRTMAG magnetic dirt separator removes both ferrous and non-ferrous impurities continuously, featuring a powerful removable external magnet around the body that removes up to 00% of the ferrous impurities, including magnetite, that can form in a hydronic system. The DIRTMAG has 2½ times the removal performance of a standard dirt separator. The body of the NA5453 series separator is made of glass reinforced nylon specifically designed for use in heating and cooling systems. It also is especially versatile as it can be installed on either horizontal or vertical piping with the rotating brass base mount. The NA5453 series is available with conventional union NPT and union sweat union connections and the Presscon press copper tail-piece with union nut that makes installation and maintenance fast, easy and efficient. Special slots in the EPDM O-ring allows fluid to leak during system testing if unpressed and provide a perfect leak proof seal when completely pressed. Also, models are available with isolation inlet and outlet shutoff valves, which can be used as a dosing point to inject chemical additives into the hydronic circuit. Product range NA54530 series NA54535 series NA54539 series NA54536 series DIRTMAG dirt separator with magnet for horizontal and vertical pipes, connections NPT threaded male union, sizes ¾ and. DIRTMAG dirt separator with magnet for horizontal and vertical pipes with isolation shut off valves, connections NPT threaded female, sizes ¾ and. DIRTMAG dirt separator with magnet for horizontal and vertical pipes, connections sweat union, sizes ¾ and. DIRTMAG dirt separator with magnet for horizontal and vertical pipes, connections press union, sizes ¾ and.

SAFETY INSTRUCTION This safety alert symbol will be used in this manual to draw attention to safety related instructions. When used, the safety alert symbol means. ATTENTION! BECOME ALERT! YOUR SAFETY IS INVOLVED! FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN A SAFETY HAZARD. CAUTION: All work must be performed by qualified personnel trained in the proper application, installation, and maintenance of systems in accordance with all applicable codes and ordinances. CAUTION: If the DIRTMAG separator is not installed, commissioned and maintained properly, according to the instructions contained in this manual, it may not operate correctly and may endanger the user. CAUTION: Make sure that all the connecting pipework is water tight. CAUTION: When making the water connections, make sure that the pipework connecting the DIRTMAG is not mechanically over-stressed. Over time this could cause breakages, with consequent water losses which, in turn, could cause harm to property and/or people. CAUTION: Water temperatures higher than 00 F (38 C) can be dangerous. During the installation, commissioning and maintenance of the DIRTMAG separator, take the necessary precautions to ensure that such temperatures do not endanger people. Leave this manual for the user Technical specifications Materials Body: Dirt separator cover: Top dosing point port plug: Drain screw: Tee pipe fitting: Locking nut for tee pipe fitting: Internal element: Hydraulic seals: Drain valve: glass reinforced nylon PA66G30 glass reinforced nylon PA66G30 brass EN 264 CW64N brass EN 264 CW64N brass EN 982 CB 753S brass EN 2420 CW67N HDPE EPDM brass EN 265 CW67N 2

Performance Suitable Fluids: water, glycol solutions Max. percentage of glycol: 30% Max. working pressure: 45 psi (3 bar) Working temperature range: 32 95 F (0-90 C) Magnets: neodymium rare earth Paricle separation capacity: to 5µm ( 0.2 mil) Ferrous impurities separation efficiency: up to 00% removal Dosing capacity: 2 fluid oz Connections Main connections: ¾ and NPT male union ¾ and NPT female ¾ and sweat union ¾ and press union Lay length (press connection): size ¾": 4 ½" size ": 4 7/8 Drain valve: hose connection Hydraulic characteristics P kpa 6.9 5.5 6 5 4.5 4 3.5 2.8 3 2.6 2.4 2.2 2.8.6.4.2.9.8 psid.9.8.7.6.5.4.3.2 3/4 NA545355 NA545356 3/4 NA545305 NA545395 NA545365 NA545306 NA545396 NA545366 P ft. of hd 2.3.69..23 2 3 4 5 6 7 8 9 0 20 30 40 50 gpm flow rate.06.08..2.4.6.8.2.3.4.5.6.7.8.9 2.5 2 2.5 3 l/s 2.8.6.4.2.9.8.7.6.5.4.3 FLOW RATE (4 f/s) Size ¾" ¾ * * GPM 6 4 0 4 Cv 2 8.7 2.2 8.7 *unit with isolation shutoff valves 3

Installation The magnetic dirt separator should be installed in accordance with the flow direction indicated by the arrow on the tee fitting and the return circuit upstream of the boiler. The magnetic dirt separator should always be installed upstream of the pump and always with its body in vertical position. 4

Air vent Eliminate air collected in the top of the body by loosening the top plug screw. Draining off dirt and ferrous impurities Remove the magnetic ring () and drain the collected dirt and ferrous impurities. This can be done while the system is running, using the key provided (2). Maintenance To perform maintenance after isolating the separator, simply unscrew the top cover using the provided key and remove the attached internal element inside the collection chamber. WARNING: The symbol shown on the removable ring indicates the presence of magnets that generate a strong magnetic field. This could cause damages to electronic devices kept in its proximity.. Remove the magnetic ring containing the two magnets, that during operation attracted the magnetites. 2. Flush out the ferrous and nonferrous debris by turning the handle to open the drain valve. 2 Dosing This multifunction device can also be used as a dosing point to inject chemical additives into the circuit. Codes NA545355 and NA545356 offer integral isolation check valves making for a more convenient dosing vessal, providing an easy access point for routine system water treatment in hydronic systems. 3. When finished, replace the magnetic ring and close the drain valve. 5

Safety The magnetic dirt separator must be installed by a licensed plumber in accordance with national regulations and/or relevant local requirements. Make sure that all connecting joints are water tight. When making pipe connections take care not to damage the thread in the body of the valve by over tightening. Take care not to apply too much force to the body of the valve when making pipe connections. Water temperatures greater than 20 F may cause serious burns. When installing, using and maintaining dirt separators take appropriate measure to ensure that these temperatures do not cause harm. Leave this manual at the service of users for their use CALEFFI Caleffi North America, Inc. 3883 W. Milwaukee Road Milwaukee, WI 53208 T: 44.238.2360 F: 44.238.2366 04-20-6 6