I/A Series 716C 1/16 DIN Temperature Controller

Similar documents
7EF/7HF/7EC/7ES Temperature Controllers

02/11/2015

02/11/2015

Temperature Controllers

UDC 700 Universal Digital Controllers and Indicator Specifications

Nov 08 PRODUCT SPECIFICATION SHEET

UDC1000 and UDC1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS

ABB Instrumentation. Specifications. COMMANDER 150 Universal Process Indicator. the 1 /8 DIN indicator to match all your display requirements

VERTEX VT10 SERIES PID OPERATION MANUAL MICROPROCESSOR BASED PID CONTROLLER

UDC100 Universal Digital Controller Specifications

F4 Process Controller Installation and Operation Guide

ABB MEASUREMENT & ANALYTICS DATA SHEET. C50 1/16 DIN controller / alarm unit

Universal controller for panel mounting Models CS6S, CS6H, CS6L

Model 96VTR ¼ DIN Process Controller

Specification , July 2015

Process & TeMPerATUre UniversAl input DigiTAl MeTers

PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS

SA200. General Description. Features. Temperature Controller SA200. Self-Tuning Algorithm. Close Vertical or Horizontal Mounting

Series Temperature Controller Instruction Sheet

/8 DIN Level Indicator

99 Washington Street Melrose, MA Phone Toll Free Visit us at

STT 3000 Series STT250 Smart Temperature Transmitters Specifications Models STT25T EN0l-6091 February 2009

SA100. General Description. Features. Temperature Controller SA100. Corresponding to Various Applications. Simple Mounting on DIN Rail

ALM 1 OUT 1 2 FUNCTION AUTO TUNE. Figure 1 - UDC2000 Mini-Pro Controller. Features, continued

AutomationDirect PM24. Microprocessor - Based Process/Temperature Limit Controller. Operator s Manual. Technical Support.

Micro-controller X C C1 C2 AL1 AL2 AL3. Model: PXR4/5/9. Operation Manual SEL PXR. ECNO:406e

Tempco Part Number PCT30006 Temperature Control Enclosure with Relay Output for Tote Tank Heating Applications

User Manual. Digi-Sense TC9600 Advanced Multiparameter Temperature Controller with Thermocouple, Thermistor, and RTD Inputs

OVEN INDUSTRIES, INC.

Digi-Sense TC9000 Advanced PID and On/Off Temperature Controller with Thermocouple Input

Table of Contents SECTION PAGE

INSTRUCTION MANUAL Micro-computer based digital indicating controller

Tempco PCT-3000 Series Temperature Control Console with Relay Output for Heating or Cooling Applications

AutomationDirect. PC35 Configuration Sheet

User Manual. Digi-Sense TC9500 Advanced Multiparameter Temperature Controller with Thermocouple, Thermistor, and RTD Inputs

Series 155. Mass Flow Computers TECHNICAL SPECIFICATIONS

MICRO CONTROLLER S Z SERIES

AH3000 SERIES 180MM CHART PEN TYPE HYBRID RECORDER

General Specifications

UDC1000 & UDC 1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS

INSTRUCTION MANUAL FOR MICROCOMPUTER BASED TEMPERATURE INDICATING CONTROLLER JCD-13A, JCR-13A

Serie Rugghölzli 2 CH Busslingen. Tel. +41 (0) Fax +41 (0)

CN4800 Series CONTROLLER

TEMPERATURE CONTROLLER

GCS-300 No.GCS31E

Communications None RS-232C RS-422* RS-485* BCD Transmission output*/** (4 to 20 ma) E5AX- E5AX- L(M)A02 L(M)A03

Communications* None RS-232C RS-422 RS-485 BCD Transmission output** (4 to 20 ma)

Instruction manual Temperature Controller KT7

Instruction manual Micro-computer based digital indicating controller

Multi-Gas-Controller MGC2

873A Series Electrochemical Analyzers ph, Contacting Conductivity, Electrodeless Conductivity, and Resistivity

TC515 and TC600 Installation Manual. a Winters company

CM 16. Temperature controllers with compact dimensions. Manual 42/61-72 EN Rev. 01

AL3000 SERIES 100MM CHART MULTI-POINT TYPE HYBRID RECORDER

CM 8. Temperature controllers with compact dimensions. Manual 42/61-71 EN Rev. 01

Series Digital Controller Instruction Sheet

TAIE. Features. FY600 (96mm X 48mm) Application:Control temperature,humidity, FY Series Digital PID Controller

Temperature Controller

SX65 and SX75. Electronic process controllers

4TEMPERATURE CONTROLLER

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

INSTRUCTION MANUAL FOR MICROCOMPUTER BASED TEMPERATURE INDICATING CONTROLLER FCS-23A

Oxygen (O2) Single-Point Gas Detection System

DIGITAL METERS Large Display Temperature Meters Instruction Manual

4/8/12/16 Channel Temperature Scanner with FREE Data Logging PC Software RS485

MODELS T16 & P16 - TEMPERATURE/PROCESS CONTROLLERS

Programmable Output Dual Relay Quad Relay. (Trip Points, High Alarm, Low Alarm, Failsafe, Non-Failsafe, Normally Open, Normally Closed)

Temperature + Humidity (%RH) Control & Recording System with 8 / 16 Channel Mapping. Touch Panel PPI

Analog Input Module IC670ALG630

Interchangeable thermistor (THE types) Output Contact E5CS-R1KJX-F E5CS-R1PX-F E5CS-R1GX-F Voltage E5CS-Q1KJX-F E5CS-Q1PX-F E5CS-Q1GX-F

Installation Manual Tracker 221

Advanced Test Equipment Rentals ATEC (2832)

Oakton TEMP 9500 Advanced Multiparameter Controller

Instruction manual for DIN rail mounting type indicating controller DCL-33A

The range of ATR243 controllers comes in three versions. Refer to the table below to easily select your preferred model.

TAIE. Features. FY900 (96mm X 96mm) Application:Control temperature,humidity, FY Series Digital PID Controller

NOVUS AUTOMATION 1/5. Range: -35 to 720 C (-31 to 1328 F) Range: -90 to 1300 C (-130 to 2372 F) Range: 0 to 1760 C (-32 to 3200 F)

Two-Channel Gas Controller

Non-contact voltage (for SSR drive): V DC DC current: 4 to 20mA DC Thermocouple: K, J, E Input. RTD: Pt100, JPt100

STT 3000 Series STT250 Smart Temperature Transmitters Specifications Models STT25H, STT25S, STT25M, STT25D EN0I-6031 March 2010 Rev.

Model 144H. Product Data Sheet , Rev DB February Content

Model 1062 Environment Monitor

VT4810 SINGLE / DUAL ZONE CONTROLLER INSTALLATION MANUAL

Dissolved Oxygen Measurement liquisys M COM 223 / 253

+ A B V B NO NC V COM PV PV

MEAS CAL ALARM WASH CONF APT4000 CC ENCLOSURE TYPE 2

MEAS CAL ALARM WASH CONF APT4000 PH ENCLOSURE TYPE 2. Description

MICRO CONTROLLER E Z SERIES

DS 96/48 P. Digital indicator. Short manual 41/33-89 EN Rev. 00 DIM

DIGITAL INDICATOR JIR-301-M

Series 945 User s Manual

INSTRUCTION MANUAL FOR MICROCOMPUTER BASED TEMPERATURE INDICATING CONTROLLER GCD-200, GCR-200

Danfoss gas detection units

Warning Caution INSTRUCTION MANUAL DIN RAIL MOUNTING TYPE INDICATING CONTROLLER

User s Guide. CN616 Series 1 4 DIN Economical 6-Zone PID Temperature Controllers. Shop online at omega.com SM

INSTRUCTIONS FOR THE 8500 SERIES MICROPROCESSOR BASED TEMPERATURE CONTROL

User s Guide CN616A. Universal 6 Channel ¼ DIN Process Controller. Shop online at omega.com

JIR-301-M No.JIR31E To prevent accidents arising from the misuse of this instrument, please ensure the operator receives this manual.

TEMPERATURE CONTROL MODULE MODEL R3-TC2

TYPE CM-2201 NELSON SINGLE POINT CIRCUIT MANAGEMENT SYSTEM

Transcription:

Product Specifications I/A Series 716C 1/16 DIN Temperature Controller PSS 2C-1B5 A The Foxboro 716C is a powerful compact, 1/16 DIN, microprocessor-based temperature controller that offers a variety of standard features commonly found only as options with other models. The 716C offers advanced features, such as Modbus serial communication where data collection capabilities and remote operation are needed. Adaptive Auto-Tune keeps your temperature control process under control. The NEMA 4X faceplates allow these units to be used in applications where washdowns and dust conditions exist. Designed specifically for manufacturers who need communications to data acquisition equipment, this light and very compact (1/16 DIN size) instrument can perform the most demanding applications with easy configuration and reliable control. The 716C start-up is as simple as: wiring the instrument configuring set points and alarm thresholds initiating the autotune function Engineers, technicians, and operators, with or without skills in temperature process or knowledge of PID control parameters, can obtain perfect process control. FEATURES Dual 4-digit LED display Universal input (T/C, RTD, mv, V, ma) Adaptive Auto-Tune NEMA 4X UL, CSA rating PID control with 0 to 20 ma or 4 to 20 ma control signal Time proportional control Safety lock-out function prevents unauthorized configuration Two independent set points selectable from external input contact Up to two independent alarms configurable with automatic or manual reset Instrument configurable by keyboard or through serial link Output Turn Off function, turns off the output and allows the controller to operate as an indicator Opto-isolated RS-485 serial communication interface with Modbus (optional) 24 V ac/dc supply (optional) Conforms to the applicable European Union directives (symbolized by the CE Logo marking on the product) The 716C offers advanced features, usually found in higher priced models, enabling quick start-ups, safe operation, and precise measurement readings. Quick Start-Ups The 716C is equipped with a proprietary self-tuning algorithm, SMART (see Figure 1). During start-up and control, the SMART algorithm continuously monitors the process variable and automatically adjusts the PlD parameters according to the response of the process variable. The advantage of this continuous self-tuning algorithm is its ability to operate without injecting any artificial change into the system.

Page 2 Measured Value 60 50 40 30 20 10 0 Set Point Start-up SMART calculates PID values for optimal set point approach and decreased overshoot SMART adapts the PID setting in response to set point or load changes. Process Control 100% Measured Value 0% Set Point A Set Point B First Set Point Change RAMP and SOAK Second Set Point Change Set Point C Two Independent Programmable Ramp Rates During start-up, the SMART algorithm implements the self-tuning function, calculating the value of the PID parameters in order to optimize the set point approach and decrease overshoot. During control, the SMART algorithm dynamically adapts the PlD parameters for precise control when set point or load changes. Safe Start-Up and Operation with Soft Start Implementing Soft Start in heating and cooling control processes can avoid thermal shock and increase the heater life. The Soft Start function enables gradual preheating of the controlled process; simply program the output and time duration to be used during preheating phase. See Figure 2. The Soft Start function can limit the rate of output change for infinite duration, ensuring that the process will always operate in safe conditions. 100% Figure 1. Quick Start-Ups with SMART Adaptive Self-Tuning SOFT-START Figure 3. Two Independent Ramp Functions for Set Point Changes Ramp Function There are two independent ramps (ramp up and ramp down) for set point changes (see Figure 3). Some processes require a ramp to reach a new set point value. Often the temperature process may need a fast ramp rate for heating and a slow ramp rate for cooling. Independent ramps can be applied to both set points. Precise Measurement Readings with Offset In many applications offset is needed to adjust the measured variable for physical differences which affect the signal received by the controller. In some cases the sensor is not located in the ideal position, which may produce a measurement error. A constant offset can be configured to compensate for the error. Configuration Tool Configure the 716C with any personal computer running MS-DOS 5.0 or higher. The configuration tool easily organizes your applications, storing all configuration data for quick start-ups. Output 0% Output Level Limit Configure time duration of output level limit Configurable output; Maximum rate of change Figure 2. Assurance of Safe Start-Ups Computer Interface Provides two types of protocol, RS-485 with MODBUS or JBUS. Communicates to Small System using Foxboro I/A Series system for Windows NT Provides DDE Interface to Windows-based applications Provides an integration tool for applications running under Windows. DDE makes data available to your application. The data can then be processed for trending, SPC, data storage, or man/machine Interface. To order, see Model Code.

Page 3 Operator Interface UPPER DISPLAY Shows the actual measured value or (during configuration) the value of the selected parameter. LOWER DISPLAY Shows the operating set point; the output level; the heater current (in Amperes); and the abbreviated name of the selected parameter. Descriptions of the displays are shown below. O 1 U 2 T 3 3250. REM 3250 C F SP2 SMRT FUNC 716C Button Description Indicator Description FUNC + + FUNC Decreases the selected parameter. Increases the slected parameter. Displays in sequence all parameters and saves the new settings or displays the output level and heater current. Switches from auto to manual mode and vice versa. Starts the default parameters loading procedure. Enables/disables the output power OFF function. REM SP2 SMART C/ F OUT1 OUT2 Out3 Instrument is under control of the serial link. Flashing at a slow rate when SP2 is used. ON or flashing when Auto-tune is operating. Instrument operating in manual mode. When input sensor is a TC or RTD, shows the selected engineering units. Main output in ON. ON when: Output 2 is used as cooling output and is ON; or, Output 2 is configured as alarm and instrument detects an alarm or the alarm has not been reset. Alarm 2 is in alarm state. Flashes at slow rate when heater current is lower than programmed threshold (HBD). Flashes at higher rate when HBD alarm and alarm 2 are both in alarm state.

Page 4 STANDARD SPECIFICATIONS Housing ABS gray. Self-extinguishing degree V-O per UL-94. Agency Certification These controllers have been designed to meet the safety standards of UL, CSA, and CE. For detailed information, or status of testing laboratory approvals/certifications, contact Foxboro. Environmental Protection Designed and tested for IP65 and NEMA 4X for indoor locations (when panel gasket is installed) Installation Panel mounting by means of brackets Rear Terminal Block Up to 15 screw terminals with safety rear cover Dimensions See Dimensions Nominal section Mass 250 g maximum (1 lb) Power Supply (Switch Mode) 100 to 240 V (nominal value) or 24 V ac/v dc (±10% of the nominal value) Power Consumption 10 VA Insulation Resistance >100 M Ω per IEC 348 Isolation Voltage 1500 Vrms per IEC 348 Sampling Time For linear inputs - 250 ms For TC or RTD inputs - 500 ms D/A Conversion Dual slope integration Accuracy ±0.2% full scale value @ 25 C and nominal power supply voltage Noise Immunity EMISSION Generic emission standard EN 50081-2 Basic emission standard EN 55011 IMMUNITY Generic immunity standard EN 50082-2: a.electrical discharge requirements: Severity Level 3 (per IEC 801-2) b.electrical fast transient/burst requirements: Severity Level 3 (per IEC 801-4) c.radiated electromagnetic field immunity between 27 MHz - 1000 MHz, 10 V/m (per IEC 801-3) Common Mode Rejection 120 db @ 50/60 Hz Normal Mode Rejection 60 db @ 50/60 Hz Normal Operating Temperature Limits 0 and +50 C (32 and 122 F) Storage Temperature Limits -20 and +70 C (-4 and +158 F) Relative Humidity Limits 20% and 85% RH, noncondensing Protection a. Watchdog for automatic reset b. DIP Switches for configuration and calibration parameters Universal Analog Input ANALOG INPUT All inputs are factory calibrated and selectable by front keyboard. THERMOCOUPLES TYPE J, K, L, R, S, T and N are keyboard configurable. ENGINEERING UNITS C and F keyboard configurable CALIBRATION Per IEC 584-1 SENSOR BREAK Downscale or upscale programmable. On RTD input, a special test is provided to signal overrange when input resistance is less than 15 Ω. (Short circuit sensor detection.) INPUT IMPEDANCE >1M Ω REFERENCE JUNCTION Automatic compensation for an ambient temperature between 0 and 50 C

Page 5 STANDARD SPECIFICATIONS (Continued). Standard Ranges Table TC Type Range L 0/400.0 C L 0/900 C J 0/400 C J 0/1000 C K 0/400 C K 0/1200 C N 0/1400 C R 0/1760 C S 0/1760 C T 0/4000 C L 0/1650 F J 0/1830 F K 0/2190 F N 0/2550 F R 0/3200 F S 0/3200 F T 0/750 F NOTE For TC inputs, it is possible to set the minimum span to 300 C or 600 F. In this way, it is possible to increase the sensitivity of the control parameters. RTD INPUT Standard Ranges Table C F -199.9/400-199.9/750-200/800-330/1470 NOTE For RTD inputs, it is possible to set the minimum span to 100 C or 200 F. In this way, it is possible to increase the sensitivity of the control parameters. REFERENCE JUNCTION DRIFT 0.1 C/ C ma dc AND V dc LINEAR INPUTS ma dc Input (Standard) 0-20 ma dc and 4-20 ma dc, keyboard configurable Input Impedance <5 Ω V dc Input 0-5 V dc and 1-5 V dc configurable; input impedance: > 200 k Ω 0-10 V dc and 2-10 V dc configurable; input impedance: > 400 k Ω 0-60 mv dc and 12-60 mv configurable; input impedance: > 1 M Ω Read-out Keyboard configurable from -1999 to 4000 Decimal Point Configurable in any position Logic Input The 716C is equipped with a logic contact input to be used to select between the main set point and the auxiliary set point (SP or SP2). Set Points Two set points are available: - Main Set Point (SP) - Auxiliary Set Point (SP2) SET POINT TRANSFER Transfer from SP to SP2 and vice versa may be driven by logic input (contact closure). NOTE The transfer may be done by a step transfer or by a ramp with two different configurable rates of rise (ramp up and ramp down). SET POINT LIMITERS Set Point low limit and set point high limit are configurable. Control Action ALGORITHM PID + Smart AutoTune/Adaptive, and Time Proportional Control PROPORTIONAL BAND Configurable from 1.0% to 200.0% of the input span. Setting a PB equal to 0 sets the control action to On/Off.

Page 6 STANDARD SPECIFICATIONS (Continued) INTEGRAL TIME Configurable from 1 second to 20 minutes (or off). Setting the PB equal to 0 changes the control action to ON/OFF. HYSTERESIS (FOR ON/OFF CONTROL ACTION) Configurable from 0.1% to 10.0% of the input span DERIVATIVE TIME Configurable from 1 second to 10 minutes, or excluded (off) INTEGRAL PRELOAD Configurable for 1 control output, from 0 to 100% of the output range AUTO/UAL MODE Selectable by front pushbutton or logic input AUTO/UAL TRANSFER Bumpless OVERLAP/DEADBAND Keyboard configurable from -20% (deadband) to +50% (overlap) of the proportional band DIRECT/REVERSE ACTION Keyboard configurable Outputs Three output types provide one analog signal and two relay outputs. OUTPUT 1 TYPE Opto-isolated 0-20 ma or 4-20 ma configurable Function Programmable as: -control output (heating or cooling) -retransmission of the measured value -retransmission of the operating set point Scaling Configurable from -1999 to 9999 Maximum Load 500 Ω Resolution - 0.1% when used as control output - 0.05% when used as analog retransmission Digital Filter A digital filter for the retransmission output is available (with the same time constant as the readout). Output Level Indication (as control output only) From 00.0 to 100.0% Output Status Indication The OUT 1 indicator flashes with a duty cycle proportional to the output level. OUTPUT 2 TYPE SPST relay contact (NO or NC selectable by jumper) with rated current 2 A at 250 V ac on resistive load Function Configurable as: - Control output (heating or cooling) - Alarm 1 output OUTPUT 3 TYPE Relay with SPST contact with rated current 2 A at 250 V ac on resistive load Function Configurable as: - Control output (heating or cooling) - Alarm 2 output The two relays can be used together for heating and cooling. Relative Cooling Gain Keyboard programmable from.20 to 1.0 Cooling Cycle Time From 1 second to 200 seconds RELAY OUTPUTS The relay outputs are protected with a varistor. The contact rating for the main output is 3 A/250 V ac on resistive load. The contact rating for OUT 2 and OUT 3 is 1 A/250 V ac on resistive load. OUTPUT ACTION Direct or reverse function configurable Output Turn Off Function This function disables the control output allowing the instrument to operate as an indicator. When control is resumed, turn off is disabled and the instrument will operate as follows: The integral component of the output signal will be set to zero; The soft start function will be enabled; The alarm masking function will be enabled. Alarms Two alarms for Activation of two relays ALARM FUNCTIONS Each alarm can be configured as process alarm, band alarm, or deviation alarm. ALARM RESET Automatic or manual reset programmable on each alarm ALARM MASKING Each alarm can be configured as masked alarm or standard alarm. Alarm masking allows suppression of alarm indicators at start-up and after a set point change.

Page 7 STANDARD SPECIFICATIONS (Continued) ALARM INDICATIONS Two indicators show when respective alarm is on. ALARM OUTPUTS Two SPST relays; contact rated at 2 A 250 V ac resistive load PROCESS ALARM Operational Mode Configurable high or low Alarm Set Point Configurable in engineering units within the entire range Hysteresis Configurable from 0.1% to 10.0% of the input span BAND ALARM Operating Mode Inside or outside band configurable Alarm Set Point Configurable from 0 to 500 units Hysteresis Configurable from 0.1% to 10.0% of the input span DEVIATION ALARM Operating Mode High or low configurable Alarm Set Point Configurable from -500 to +500 units Hysteresis Configurable from 0.1% to 10.0% of the input span Serial Interface (Optional) TYPE RS-485 PROTOCOL TYPE Modbus, Jbus BAUD RATE Keyboard configurable from 600 to 19200 baud ADDRESS From 1 to 255 MODEL CODE 716C= Dual 4-Digit Display Temperature Controller Control Action 0 = PID or SMART Adaptive Control Output Analog Type 7 = ma linear Control Output Output Relay Type 1 = Two Relay Outputs Example: 716C-07113 Alarms And Communication 1 = Alarm 2 3 = Alarm 2 + Opto-isolated RS-485 Power Supply 3 = 100-240 V ac 5 = 24 V ac or dc DDE Interface to Windows Applications: use with Windows 3.10 or higher. Order Part No. 20AATZA. Configuration Software: use with MS-DOS 5.0 or higher. Order Part No. 20AATZG.

Page 8 48 1.9 DIMENSIONS - NOMINAL mm in 56 2.2 1 O U 2 REM C F 48 1.9 T 3 SMRT SP2 FUNC 716C 122 4.8 10 0.4 PANEL CUTOUT DIMENSIONS TERMINAL CONNECTIONS 75 3.0 45 (-0,+0.6) 1.77(-0,+0.02) 60 2.4 45 (-0,+0.6) 1.77(-0,+0.02) The Foxboro Company 33 Commercial Street Foxboro Massachusetts 02035-2099 Telephone (508) 543-8750 Facsimile (508) 549-6750 Foxboro and I/A Series are registered trademarks of The Foxboro Company. Siebe is a registered trademark of Siebe, plc. MS-DOS and Windows NT are trademarks of Microsoft Corporation. Copyright 1996 by The Foxboro Company All rights reserved A Siebe Group Company MB 010 Printed in U.S.A. 1196