Heat recovery units Description www.alnor.com.pl Dimensions Ø 125 600 660 702 Podręcznik użytkownika rekuperatorów is the smallest heat recovery unit in the range of MinistAIR products. With a total air supply output of 220 m 3 /h, the unit can be installed in small indoor areas which will benefit from a compact footprint and Elementy low weight składowe of the product. Centrale wentylacyjne są przeznaczone do odzyskiwania części energii z powietrza wylotowego w uk Key performance features: wentylacyjnym. Odzyskana energia jest przekazywana bezpośrednio do dostarczanego świeżego powietrza, co pozwala ogr Maximum heat recovery ratio 85.8%, tested as zyć per obciążenie EN 308 układu klimatyzacji. by TÜV SÜD Plastic counter-flow heat exchanger Design Automatic air flow bypass Freeze protection BMS connectivity (via Modbus) Preheater and secondary heater control connectivity 5 Programmable week control timer Filter clogging monitor 4 Class G4 filters in standard (class F7 filters available on request) Supported sensor typees: CO 3 2, RH, and pressure switch Wall-mounted or free-standing Metal duct connections with EPDM gaskets for air tightness class D EBM PAPST energy-efficient fans 380 400 Control When ordering, specify the control type. There are two versions of control available - wired and wireless: - with a wired controller W - with Wi-Fi control 1 6 2 1. Control 2. Air supply & exhaust filters 1 Sterowanie 3. Damper actuator 4. Counter-flow heat exchanger Filtry powietrza wylotowego 2 5. Housing i nawiewanego 6. Air exhaust & supply fans 3 Siłownik przepustnicy 4 Wymiennik przeciwprądowy 680 5 6 Obudowa Wyciągowy i nawiewny
Heat recovery units Technical specifications 350 300 Air flow rate (m 3 /h) * 220 Rated power supply (V/Hz/Ph) 230 / 50 / 1 Maximum power consumption (W) 112 Maximum sound pressure level (db (A)) ** 46 Weight (kg) 24 Filters * The static pressure is 100 Pa. ** Measured 1 m away from the unit. Performance curve Class G4 filter as per EN 779 (class F filter available on request) 250 Static pressure (Pa) 200 150 100 50 0 0 50 100 150 200 250 300 Air flow rate (m 3 /h) 681
Rekuperatory Technical specifications Sound level chart Octave sound pressure level (db: general A) Frequency 682
Heat recovery units Technical specifications The air tightness was tested per EN 308. The air leak rate was measured at an air flow rate of 221 m 3 /h and an air pressure of 100 Pa. The following table lists the internal and external air leak rates and percentage vs. the overall air flow rate: Test No. P stst (Pa) Air leak rate (m 3 /h) Inner air leak Percentage ratio (%) Air leak rate (m 3 /h) Outer air leak Percentage ratio (%) 1-400 2.4 1.1 2-300 1.9 0.8 2.8 1.3 3-250 1.6 0.7 4-200 1.3 0.6 2.1 0.9 5-100 0.7 0.3 1.3 0.6 6-50 0.4 0.2 0.7 0.3 7 0 0.0 0.0 0.0 0.0 8 50 0.3 0.2 0.7 0.3 9 100 0.6 0.3 1.2 0.5 10 200 1.2 0.5 2.0 0.9 11 250 1.4 0.6 12 300 1.7 0.7 2.7 1.2 13 400 2.1 0.9 The thermodynamic test was completed as per EN 308. The following temperature coefficients were measured for the heat recovery unit: 4 V 6V 8V 10 V Supply air q m2 [m 3 /h] 40 113 151 226 Exhaust air q m1 [m 3 /h] 40 114 153 230 Static pressure (supply) [Pa] 49 50 96 98 Static pressure (exhaust) [Pa] 48 47 95 96 Supply temp. recovery ratio eta t,sup [%] 87 85 83 80 Exhaust temp. recovery ratio eta t,eha [%] 71 76 75 74 Mean temp. recovery ratio eta t,epb [%] 79 80 79 77 683
Heat recovery units Energy class B 57 db 220 m 3 /h ENERGIA ЕНЕРГИЯ ΕΝΕΡΓΕΙΑ ENERGIJA ENERGY ENERGIE ENERGI 2016 1254/2014 684
Heat recovery unit controller manual controller HRU-MinistCONT-Man Function Description Availability Fan speed control Fan speed boost Filter clogging indicator Automatic air flow bypass Electric heater control Sensor (VOD) Sensor (Humidity) Freeze protection Preheater control BMS connectivity Modbus connectivity Programmable week control timer Air supply and air exhaust fans are provided with a 3-speed control system. This function increases the fan speed: Option 1: Press the BOOST button on the control panel Option 2: Activated with an external dry relay input or an external 230 V input (activated e.g. by a lamp switch in the kitchen, bathroom, etc.) on the controller s PCB. Two filter clogging indicator options: Option 1: The filter clogging indicator counts down the unit's operating time to a preset value. When the preset value is reached, a filter change request indicator is activated on the control panel. Option 2: Filter clogging can be monitored with a pressure switch. When the filter reaches the clogging limit, the pressure switch activates a filter change request indicator on the control panel. The filtered fresh air is supplied indoors, bypassing the heat exchanger. The interfaced electric heater can have the output automatically switched between a maximum of 2 levels the selection of which depends on the desired temperature setting and the actual indoor temperature. The fans are operated continuously by the control output of a CO2 sensor or an air quality sensor. The fans are operated continuously by the control output of an indoor air humidity sensor. If the outdoor temperature is low, the freeze protection function is activated to protect the heat exchanger from freezing. If the outdoor temperature is low, the fresh air supply is treated by a preheater upstream of the unit. This function protects the heat exchanger from freezing. IN: The unit can be turned on and off using an external control panel. OUT 1: Unit status output OUT 2: Unit fault alarm output This feature allows operating all controls of the unit via a PC or a central automation system. The unit can be programmed to operate at specific hours in a weekly cycle. 3 speeds (all fans) (High / Medium / Low) Optional Optional Optional Data logging This function allows logging all available operating options of the unit. Fire mode This function activates a special operating status in the case of a fire alarm. Alarms - Filter change required - Fan failure - Preheater failure - Heater failure (Error code display) Child lock Locks the control keypad to prevent inadvertent operation. 690
Heat recovery unit controller HRU-MinistCONT-WiFi controller Kontroler HRU-MinistCONT-WiFi umożliwia zdalne starowanie centralami rekuperacyjnymi z serii HRU-MinistAIR - oznacza to, że z dowolnego miejsca na świecie możesz wybrać rodzaj trybu pracy centrali rekuperacyjnej odpowiadający Twoim aktualnym potrzebom w zakresie jej funkcjonowania. Wraz z zakupem centali, dokupując HRU-MinistCONT-WiFi otrzymujesz zainstalowaną puszkę sterującą wraz z adresem internetowym oraz danymi do zalogowania się i obsługiwania zdalnie Twojej centrali. Function Description Availability Fan speed control Fan speed boost Filter clogging indicator Automatic air flow bypass Electric heater control Sensor (VOD) Sensor (Humidity) Freeze protection Preheater control BMS connectivity Modbus connectivity Programmable week control timer Air supply and air exhaust fans are provided with a 3-speed control system. This function increases the fan speed: Option 1: Press the BOOST button on the control panel Option 2: Activated with an external dry relay input or an external 230 V input (activated e.g. by a lamp switch in the kitchen, bathroom, etc.) on the controller s PCB. Two filter clogging indicator options: Option 1: The filter clogging indicator counts down the unit's operating time to a preset value. When the preset value is reached, a filter change request indicator is activated on the control panel. Option 2: Filter clogging can be monitored with a pressure switch. When the filter reaches the clogging limit, the pressure switch activates a filter change request indicator on the control panel. The filtered fresh air is supplied indoors, bypassing the heat exchanger. The interfaced electric heater can have the output automatically switched between a maximum of 2 levels the selection of which depends on the desired temperature setting and the actual indoor temperature. The fans are operated continuously by the control output of a CO2 sensor or an air quality sensor. The fans are operated continuously by the control output of an indoor air humidity sensor. If the outdoor temperature is low, the freeze protection function is activated to protect the heat exchanger from freezing. If the outdoor temperature is low, the fresh air supply is treated by a preheater upstream of the unit. This function protects the heat exchanger from freezing. IN: The unit can be turned on and off using an external control panel. OUT 1: Unit status output OUT 2: Unit fault alarm output This feature allows operating all controls of the unit via a PC or a central automation system. The unit can be programmed to operate at specific hours in a weekly cycle. 3 speeds (all fans) (High / Medium / Low) Optional Optional Optional Data logging This function allows logging all available operating options of the unit. Fire mode This function activates a special operating status in the case of a fire alarm. Alarms - Filter change required - Fan failure - Preheater failure - Heater failure (Error code display) Child lock Locks the control keypad to prevent inadvertent operation. 691
Heat recovery unit controller HRU-MinistCONT-Wifi Controller Login panel: All users receive their personal user names and passwords for remote access to the device they purchase. Alnor ventilation controller configuration pane: The wizard's steps guide the user through the commissioning and local network configuration of the device. Heat recovery unit start and stop: ON / OFF 692
Heat recovery unit controller HRU-MinistCONT-Wifi Controller Heat recovery unit work mode selection: adjust the continuous operation of the unit to your needs, or use the predefined options as follows: STANDARD MODE: continuous air change. Enables work mode selection for the AIR SUPPLY fan and the AIR EXHAUST fan. AIR EXHAUST MODE: controls the air exhaust fan only. Fan work modes: speed 1, 2, 3 or OFF. Start the function to extract stale air from the area and return to the air change mode by selecting STANDARD. 693
Heat recovery unit controller HRU-MinistCONT-Wifi Controller AIR SUPPLY MODE: controls the air supply fan only. Fan work modes: speed 1, 2, 3 or OFF. Start the function to supply fresh air indoors and return to the air change mode by selecting STANDARD. VOD MODE: in the Ventilation On Demand mode, the air supply and air exhaust rates depend on the humidity readout from the optional indoor air humidity sensor connected to the heat recovery unit. The sensor is sold separately. Remote temperature setting: choose the indoor temperature for the room. Indoor air temperature: shows the actual temperature of the air exhausted from the area, which is changed by the controller via the heat recovery system to match the remote temperature setting. The outdoor air intake temperature. The temperature of the air supplied by the heat recovery unit to the area. 694 Alarm code: displays the error code of the heat recovery unit. (See the error code definitions in the User Manual.) BY-PASS FUNCTION: the heat recovery unit supplies fresh and filtered outdoor air bypassing the heat exchanger. When this indicator is checked, the By-Pass Mode is running. ONLINE: shows the status of the data connection between the controller and the heat recovery unit. When this indicator is lit, the data connection is correct.
Heat recovery unit accessories F7 filter EU4 filter EU7 (F7) filter elements are fine filters with the rated separation efficiency at 80 90% for 0,4 µm particulates. Product code Filter class Dimensions (mm) HRF-Mair-250-F7 F7 150x360x30 HRF-Mair-400-F7 F7 215x605x45 Product code Filter class Dimensions (mm) HRF-Mair-250-EU4 EU4 150x360 HRF-Mair-400-EU4 EU4 215x605 Humidity sensors An air humidity sensor can operate a heat recovery unit by regulating the air fan speed via its output signals. The air fan is switched between three 3 speeds which correspond to air humidity presets. H7015B1060 duct air humidity sensor Maintenance-free and automatic humidity and temperature measurement Power supply Humidity measurement range Output signal Temperature measurement range Protection rating Wiring length 24 V 0 to 100% RH 1 to 10 V 0 to +50 C IP65 200 m 695
Heat recovery unit accessories T7560C1006 room air humidity sensor CO 2 sensors Automatic humidity and temperature measurement Power supply Humidity measurement range Output signal Temperature measurement range Protection rating Sensor typee CO 2 (carbon dioxide) sensors allow regulating -W-450 heat recovery units according to the indoor or duct CO 2 concentration levels (depending on where the sensor is installed). 24 V 10 to 95% RH 1 to 10 V +6 to +40 C IP30 20 kω NTC AQS71-KAM-T duct CO 2 sensor Maintenance and calibration free Power supply Test Measurement accuracy Temperature measurement range Output signal 24 V 0 to 2000 ppm +/- 50 ppm 0 to +50 C 1 to 10 V C7110D1009A room CO 2 sensor Automatic humidity and temperature measurement Self-calibration algorithm Power supply Test Measurement accuracy Temperature measurement range Output signal Sensor typee 24 V 0 to 3000 ppm +/- 50 ppm 0 to +50 C 1 to 10 V 20 kω NTC 696