TOSHIBA AIR CONDITIONING. TOSHIBA Super Heat Recovery Multi System Standard Specification

Similar documents
TOSHIBA AIR CONDITIONING

TOSHIBA Super Heat Recovery Multi Enhanced System Standard Specification

TOSHIBA AIR CONDITIONING

Product Launch SHRMi

MiNi-SMMS WHEN COMMERCIAL MEETS RESIDENTIAL

MiNi-SMMS Design Manual HFC R-410A. Indoor unit. Outdoor unit

Inventor of the Inverter

Super Modular Multi Design Manual HFC R-410A. Indoor unit. Outdoor unit

DESIGN MANUAL R410A. Outdoor Unit. FS unit FILE NO. A RBM-Y1122FE RBM-Y1802FE RBM-Y2802FE

DESIGN MANUAL R410A. Indoor Unit. Outdoor Unit FILE NO. A Cooling Only Model <Inverter Unit> Heat Pump Model <Inverter Unit>

Business. The business range. The most advanced solutions for larger buildings.

Single Fan MiNi VRF Apartment Ready

Simultaneous. Heating and Cooling Solution for Large Buildings. Air Conditioning for large buildings

Engineering Data Book

Engineering. Super Heat Recovery Multi System

excellence in seasonal efficiency BUSINESS SOLUTIONS

Blending Commercial and Residential. MiNi VRF

Index. Toshiba Solutions. Absolute comfort

Side blow VRF. Engineering Data Book. Outdoor units E Model name: MCY-MHP0404HT-E MCY-MHP0504HT-E MCY-MHP0604HT-E

TVR 5G GUIDE SPECS. TVR 5G GUIDE SPECS - JUL.2014 Page 1

All side discharge units are having high pressure switch (LP switch- Optional) and time delay relay. Compressors are scroll type, Copeland make.

Commercial Air Conditioning Equipment

DESIGN GUIDELINES SPLIT TYPE AIR TO AIR HEAT PUMPS PAGE 1 of 6

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

LSA LSA A + Air cooled water chillers with axial fans VERSIONS ACCESSORIES

3 rd Generation of VRV. The professional solution for your professional project

Air Conditioning For Large Buildings

Engineering Data Book

NFZP Variable Refrigerant Flow Guide Specification

CZT CZT. High efficiency air to water heat pumps with E.V.I. compressors E.V.I. HP OTHER VERSIONS ACCESSORIES

LZT High efficiency air to water heat pumps with E.V.I. compressors

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module

CZT CZT E.V.I. High efficiency air to water heat pumps with E.V.I. compressors OTHER VERSIONS ACCESSORIES

LZA High efficiency air to water heat pumps with HP compressor

HYDROCIAT LW R407C. Water cooled chillers USE RANGE

SPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw

JOB NAME: LOCATION: PURCHASER: ENGINEER: SUBMITTED TO: FOR: REFERENCE [ ] APPROVAL [ ] CONSTRUCTION [ ] SUBMITTED BY: DATE:

BRT C/H Series PACKAGED AIR TO AIR UNITS COOLING / HEATING APPLICATIONS OUTDOOR INSTALLATION. Ver. 1.01

CMA TECHNICAL MANUAL CONDENSING UNITS FOR OUTDOOR INSTALLATION O L S A F RA N

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual

Light commercial range. Passion at work

VRF Series. The most advanced commercial air conditioning system

LZT High efficiency air to water heat pumps with E.V.I. compressors

Condensing Units CUS 15-60

Technical Guide. Multizone: Multi-Split Type Heat Pump Systems

Blower-YEFB-020-3R-1maxVel

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points

CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL

AIR CONDITIONER (MULTI TYPE) Owner s Manual. Outdoor Unit. Owner s Manual 1 English. Owner s Manual xx Xxxxx. Model name: <Cooling Only Model>

All series is using Hitachi scroll compressor, low vibration and high efficiency. Internal thermostat embedded compressors, and it can react quickly.

Technical HandBook. Version

AIR-CONDITIONER SERVICE MANUAL

EPCE00-10B. Powerful. air cooled. Hydronic systems EUWA*40-200K(A)X

LDK LDK. Air to water chillers and heat pumps VERSIONS ACCESSORIES

SECTION VARIABLE REFRIGERANT VOLUME (VRV) HVAC SYSTEM

AIR CONDITIONER (MULTI TYPE) Owner s Manual. Outdoor Unit. Model name: Heat Pump Model MCY-MHP0406HT-E MCY-MHP0506HT-E. English. For commercial use

ELECTRICAL QUANTITY WEIGHT (LB)

NEXT EVO DXR410A NEXT EVO DX NEW SOFTWARE. rcgroupairconditioning

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

30RB Air-Cooled Liquid Chillers. Nominal cooling capacity 8-14 kw. Features. Quiet operation

LSK LSK. Air to water chillers and heat pumps VERSIONS ACCESSORIES

Compact 4-way Cassette ( ) Type

DC Inverter Smart VRF Products(R410A)

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

Technical Data OPA 101, 150, 180. Ducted Three Phase Packaged Air Conditioner kw 18.5 kw. Extra Long Life Epoxy Coated Outdoor Coil

EMI ENGINEERING SUBMITTAL

Advance Split

WZT High Efficiency Air to Water Split System Heat Pumps With E.V.I. Compressors

Hybrid VRF Next Generation 2-Pipe Heat Recovery Systems

LIGHT COMMERCIAL RANGE Inverter heat pumps suitable for both homes and commercial premises

Modular Air Cooled Scroll Chillers

CHAPTER 6 CONDENSING UNITS

DYNACIAT LGN. Description. Split system Water chillers. High energy efficiency Compact and quiet Scroll compressors Brazed-plate heat exchangers

Technical Data OPA 294, 340, 370. Ducted Three Phase Packaged Air Conditioners kw 34.0 kw 39.1 kw. Twin System Enables Staging

Light commercial range. Passion at work. Light commer

30RB Air-Cooled Liquid Chillers PRODUCT SELECTION DATA. Easy and fast installation. Compact, reliable and efficient

LZT LZT E.V.I. High efficiency air to water heat pumps with E.V.I. compressors OTHER VERSION ACCESSORIES

Super. Digital Inverter. Inverter Air Conditioning for Light Commercial Use

4,5 22,5 kw. technicalcatalogue. Air-conditioned server-racks for direct installation into the room T_CLSEVO_0113_GB

SECTION VARIABLE REFRIGERANT FLOW SYSTEM

EMI ENGINEERING SUBMITTAL

Fan Coil Range HYDRONIC TERMINALS

MACH N-407 Heat Pump Air-Cooled Chiller

Heat Pump Air Conditioning Systems


PRODUCT LINEUP VRF. For LIGHT COMMERCIAL & RESIDENTIAL, COMMERCIAL

PACKAGE AIR CONDITIONER

Technical Data OPA RKTBG-P. Ducted Three Phase Packaged Air Conditioners. 47 kw 96 kw

Specification Data. General:

Technical Data Ducted Three Phase Split System Air Conditioner

AIR COOLED CHILLERS FOR OUTDOOR INSTALLATION WITH INTEGRATED FREE COOLING MULTISCROLL SERIES

Toshiba solutions 3 At Toshiba, we believe that Evolu on is leading the path to a be er future. Through the decades, we have been constantly crea ng i

AIR CONDITIONER (MULTI TYPE) SERVICE MANUAL

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

High Ambient / High Efficiency Series. R - 410a. 50Hz. Ducted Split Air Conditioners (5.0 kw kw)

. Creating Maximum Comfort

Integrated VarIable refrigerant flow ahu/pau (r410a)

APPLICATION GUIDE FLATAIR FMC - H FIC - H FSC - H. Horizontal packaged air conditioners kw FLATAIR AGU-MSL E. lennoxemeia.

BRAN Residential chillers and heat pumps. Reversible unit, air source for outdoor installation 4,81-27,2 kw <<< BACK INDEX.

Transcription:

Introduction The following specification describes the Toshiba 3-Pipe Super Heat Recovery Multi air conditioning system(s) to be installed at the below site: (ADD SITE NAME) The system(s) shall consist of the following components. It shall be the responsibility of the nominated installer to supply and install these system components in accordance with Toshiba Installation Guidelines. 1) Toshiba Super Heat Recovery Multi external air cooled condensing unit(s) 2) Toshiba Super Heat Recovery Multi compatible type indoor units 3) Interconnecting U1 & U2 control wiring from Outdoor Unit(s) to Indoor Units 4) Interconnecting U5 & U6 control wiring between Outdoor Units (if required) 5) Toshiba TCC Link Integrated Controls 6) Interconnecting refrigerant pipe work from Outdoor Units to Indoor Units using Toshiba Y-Branch Kits/Header Kits/ Tee-Piece Kits. System Operating Range Mode of operation Cooling Heating Max. Outdoor Air Temperature Min. Outdoor Air Temperature Max. Indoor Air Temperature 0 C db 43 21 0 C db -5-15 0 C db - 29 0 C wb 28 - Min. Indoor Air Temperature 0 C db - 4 0 C wb 15 - Maximum indoor Humidity % RH 80 System Description The installation shall provide an energy efficient R410A Variable Refrigerant Flow (VRF) comfort air conditioning system(s) to the designated area(s)/zone(s) as per the (insert either equipment schedules, drawings, schematics etc) attached, utilising Toshiba 3-Pipe Super Heat Recovery Multi system(s) and shall be installed in accordance with relevant codes of practice and regulations.

The system(s) shall comprise of Toshiba 3-Pipe Heat Recovery Multi outdoor units connected to indoor fan coil units, via the most appropriate and cost efficient combination of Y-Branch Kits/Header Kits/ Tee-Piece Kits. The system(s) shall be controlled with Toshiba s TCC-Link controls system selected in accordance with the specific control requirements detailed below: (Insert controls requirements) The total refrigerant pipe work circuit can be a maximum linear distance of 125 m between the outdoor and the furthest heat pump indoor unit and incorporate a height difference of: - 50 m - indoor unit below outdoor unit 30 m - indoor unit above outdoor unit The maximum elevation between the highest and lowest indoor units shall not exceed 35 m, in accordance with Toshiba Installation Guidelines. It shall not be necessary to include oil traps, sight glasses, or external driers in any of the pipe work. All equipment supplied shall have a manufacturer s warranty of at least 3-years on all parts in accordance with Toshiba s warranty guidelines. Design Criteria The air conditioning system(s) shall be designed and equipment selected to conform to the following design criteria: Internal Conditions Summer 22 C db, 50% RH Winter 21 C db External Conditions Summer 29 C db, 21.5 C wb Winter -5 C db System Specification The system(s) shall be VRF 3-Pipe Super Heat Recovery Multi and multiple indoor units to provide simultaneous heating and cooling. The system will use non-ozone depleting HFC refrigerant R410A and be able to run with a minimum indoor cooling demand of 2.2 kw. The air conditioning system must automatically adapt to the number of fan coil units turned on by the room tenants. The system shall allow a user-driven operating environment to be established where users can directly request their own choice of temperature and on/off control etc. The equipment must be suitable for operating on a 220-240 volt, single-phase, 50 Hz supply for indoor units and a 380-415 volt, three-phase, 50 Hz supply for the outdoor units.

Outdoor Unit(s) MMY-MAP0802FT8, MMY-MAP1002FT8, MMY-MAP1202FT8. Each outdoor unit shall be factory assembled, pre-wired, works tested, supplied with a refrigerant pre-charge and complete with fully sealed pipe work connections. The noise level for each unit shall not be more than 59 db(a) (for a single condenser) and 63 db(a) (for the maximum combination of three condensers) when measured 1m horizontally and 1m above the base of the unit(s). The access panel shall be easily removable for servicing. The condensing unit shall be fitted with its own electrical compartment with all necessary electrical and control components. An oil management system is to be fitted, to allow oil transfer between connected outdoor units, thereby ensuring that adequate lubrication is provided to every compressor. Provision must be made to facilitate piping connections to the front or bottom of the unit. The unit must consist of an individual compressor/condenser section and condenser fan housed in a sturdy weatherproof casing manufactured from Galvatite steel plate with a Silky shade (Munsell 1Y8.5/0.5) electrostatic spray finish protected to IP X4 and shall contain the following components: Dual Inverter Driven Twin Rotary Compressors These are to be contained in a single housing with high-pressure discharge gas, medium pressure liquid, low-pressure gas, oil transport connections and crankcase heater. Each compressor shall be of the twin rotary type, contained in a single housing and driven by a High-Speed Calculation Vector Control Inverter, creating seamless capacity control from 0.8 hp upwards to match the connected indoor cooling or heating demand. Fixed speed compressors of any type are not to be used. The compressor shall be mounted on springs and shock-absorbing rubber to minimise vibration. Heat Exchangers Each outdoor unit shall be fitted with a main and a sub heat exchanger. The sub heat exchanger is to increase efficiency by providing further sub-cooling to the refrigerant, when appropriate. The two heat exchangers shall be factory constructed of rifled copper tubing, mechanically bonded to aluminium fins. The aluminium fin material shall be coated with a hydrophilic coating to prevent corrosion and to assist condensate dispersal. Each coil shall have a large surface area to minimize noise and maximise heat transfer. Fan and Motor The fan shall be a three-blade, flash-wing, low noise type and shall be both dynamically and statically balanced to produce minimum noise and vibration. The fan shall be directly coupled and driven by a drip proof, permanently lubricated variable speed high-efficiency inverter controlled motor. The outdoor fan speed shall be matched automatically to the energy demands of the heat exchanger. The fan shall have a factory set external static resistance capability of 15 Pa. However, the fan must be able to be boosted by a simple adjustment to the PCB to overcome a resistance of 35 Pa with no loss of performance. A maximum external static resistance of 45 Pa must be achievable with no more than 3% reduction in performance. Suction Line Accumulator The cylindrical accumulator shall be fabricated from press formed mild steel plates. The accumulator shall have sufficient capacity to prevent any liquid refrigerant from flowing back into the compressor section. The accumulator must be fitted with a heater.

Additional Features & Safety Devices 4-way reversing valve; solenoid valves; pulse motor valves; liquid receiver; strainer; dryer; service valves with gauge ports; high and low pressure transducers; high pressure switch, fuses, over current relay; thermal protectors for compressor and fan motor; recycling guard timer; over-current sensor; compressor suction and discharge temperature sensor and a 3- phase and neutral isolator protected to IP65 containing mains power input, terminals, internal wiring and controls. Flow Selector Units RBM-Y1122FE RBM-Y1802FE RBM-Y2802FE The simultaneous heating and cooling function is to be achieved with the use of flow selector units. Generally, each indoor unit should be supplied by its own dedicated flow selector unit. However, a flow selector must be able to supply multiple indoor units operating as a group if the application allows, but future flexibility with minimal system adjustment must be considered. If a connected indoor unit is only required for cooling, then the relevant flow selector unit can be omitted. The flow selector unit is to be no more than 200mm in height. Each flow selector unit is to be powered from the indoor unit via a 5 m power and communication lead. A 10 m extension kit is to be available to allow a 15 m separation between the indoor unit and the flow selector unit. Indoor Units Each indoor unit shall be from Toshiba s R410A VRF range of units and must operate on 220-240 volt, single-phase, 50 Hz supply. It must be fully compatible with all TCC-Link network systems, including a self-diagnostic TCC-Link remote controller or TCC-Link central controller with liquid crystal display to set mode, room temperature, timer, louver (as applicable), fan speed and on/off functions. In the event of a fault, an alphanumeric malfunction code will be displayed. Each indoor unit address is to be automatically set by the system and retained in memory in the event of a power failure. An option to manually set the address must also be available. Electrical isolation of any indoor unit must not affect the operation of the remaining components in the system. An auxiliary 12V DC output is to be available using the CN32 connection. This can be used to operate a ventilation fan via a relay (RBC-SMFI) when the indoor unit is operated. The heat exchanger shall be factory constructed of rifled copper tubing, mechanically bonded to aluminium fins. The aluminium fin material shall be coated with a hydrophilic coating to prevent corrosion and to assist condensate dispersal. The coil shall have a large surface area to minimize noise and maximise heat transfer. An electronic expansion valve shall be factory brazed to the inlet of the coil. It shall modulate the refrigerant volume continuously in response to load variations in the room to maintain a precise constant temperature to within +/-0.5 C (the dead band is configurable and may be set as high as 10 K). A fully insulated condensate drip tray must be fitted, which spans the full width of the coil connections and complete with a drain connection point.

All indoor units are provided with a return air temperature sensor. The heat exchanger will be protected against excessive temperatures both low and high. Cold draughts will be avoided when heating by automatically stopping the indoor fan motor when the heat exchanger is too cold. Excess heat is to be dissipated by operating the indoor fan motor for a further 30 seconds after unit shutdown. The evaporator fan shall be of the multi-blade type, performance matched to the coil. The fan shall be statically and dynamically balanced to ensure low noise and vibration free operation and be driven by a permanently lubricated motor fitted with maintenance free sealed-for-life sleeve bearings. 4-Way Cassette MMU-AP0091H, MMU-AP0121H, MMU-AP0151H, MMU-AP0181H, MMU-AP0241H, MMU-AP0271H, MMU-AP0301H, MMU-AP0361H, MMU-AP0481H, MMU-AP0561H expanded polyurethane foam. Knockouts are to be incorporated into the main chassis of the unit: One to provide a fresh-air intake facility to allow up to 10% fresh air (un-tempered) to be introduced into the conditioned space; Three further discharge ports (2 on one side and 1 on the opposite side) are to enable a maximum of 2 spur ducts to be fitted to supply improved air distribution characteristics in irregular shaped rooms or to provide nominal cooling to adjacent areas. An integral condensate lift pump is to be provided with a 640mm lift capability from the drain outlet. The cassette facia panel is to be manufactured from ABS plastic, finished in Moon White (Munsell 2.5GY 9.0/0.5) and complete with four synchronised, motor driven, fully adjustable discharge louvers. Each corner of the panel shall be removable to provide access to the drop rods to enable precise height adjustment. The airflow from the unit is to be configurable from the remote controller to compensate for high ceilings. The central return air grille must be fitted with a washable, long life air filter. An optional kit shall be made available (ref: TCB- BC1601UE) incorporating blockers to allow up to two air discharge ports to be closed to create a 2, or 3-way discharge pattern as required. An optional infrared remote control kit (ref: TCB-AX21U(W)-E) is to be available. Compact (600 x 600) 4-Way Cassette MMU-AP0071MH, MMU-AP0091MH, MMU-AP0121MH, MMU-AP0151MH, MMU-AP0181MH. expanded polyurethane foam. Knockouts are to be incorporated into the main chassis of the unit: One to provide a fresh-air intake facility to allow up to 10% fresh air (un-tempered) to be introduced into the conditioned space; Two further discharge ports (1 on each side) are to enable a maximum of 2 spur ducts to be fitted to supply improved air distribution characteristics in irregular shaped rooms or to provide nominal cooling to adjacent areas. An

integral condensate lift pump is to be provided with a 627mm lift capability from the drain outlet. The cassette facia panel is to be manufactured from ABS plastic, finished in Moon White (Munsell 2.5GY 9.0/0.5) and complete with four synchronised, motor driven, fully adjustable discharge louvers. Each corner of the panel shall be removable to provide access to the drop rods to enable precise height adjustment. The airflow from the unit is to be configurable from the remote controller to compensate for high ceilings. The central return air grille must be fitted with a washable, long life air filter. 2-Way Cassette MMU-AP0071WH, MMU-AP0091WH, MMU-AP0121WH, MMU-AP0151WH, MMU-AP0181WH, MMU-AP0241WH, MMU-AP0271WH, MMU-AP0301WH. expanded polyurethane foam. Knockouts are to be incorporated into the main chassis of the unit: One to provide a fresh-air intake facility to allow up to 10% fresh air (un-tempered) to be introduced into the conditioned space; two further discharge ports (1 on each side) are to enable a maximum of 2 spur ducts to be fitted to supply improved air distribution characteristics in irregular shaped rooms or to provide nominal cooling to adjacent areas. An integral condensate lift pump is to be provided with a 160mm lift capability from the drain outlet. The cassette facia panel is to be manufactured from ABS plastic, finished in Light Ivory (Munsell 10Y 9/0.5) and complete with two synchronised, motor driven, fully adjustable discharge louvers. The central return air grille must be fitted with a washable, long life air filter. 1-Way Cassette (Y Series) MMU-AP0071YH, MMU-AP0091YH, MMU-AP0121YH, expanded polyurethane foam. An integral condensate lift pump is to be fitted. The cassette facia panel is to be manufactured from ABS plastic, finished in Silky Shade (Munsell 1Y8.5/0.5) and complete with a single, motor driven, fully adjustable discharge louvre. The return air grille must be fitted with a washable, long life air filter. 1-Way Cassette (S Series) MMU-AP0151SH, MMU-AP0181SH, MMU-AP0241SH. expanded polyurethane foam. Knockouts are to be incorporated into the main chassis of the unit: One at the rear to provide a fresh-air intake facility to allow up to 10% fresh air (un-

tempered) to be introduced into the conditioned space; One at the front to facilitate a ducted discharge capability. An integral condensate lift pump is to be provided. The cassette facia panel is to be manufactured from ABS plastic, finished in Silky Shade (Munsell 1Y8.5/0.5) and complete with a single, motor driven, fully adjustable discharge louver. The return air grille must be fitted with a washable, long life air filter. Standard Ducted MMD-AP0071BH, MMD-AP0091BH, MMD-AP0121BH, MMD-AP0151BH, MMD-AP0181BH, MMD-AP0241BH, MMD-AP0271BH, MMD-AP0301BH, MMD-AP0361BH, MMD-AP0481BH, MMD-AP0561BH. expanded polyurethane foam. The DC fan motor will be configurable, allowing a maximum external static resistance of 100 Pa to be overcome. The airflow from the unit is to be configurable from the remote controller to compensate for high ceilings. Air is to return to the unit at the rear via a washable, long life air filter. A knockout is to be provided to allow up to 10% fresh air (un-tempered) to be introduced into the conditioned space. An integral condensate lift pump is to be provided with a 271mm lift capability from the drain outlet. An optional infrared remote control kit with inclusive temperature sensor (ref: TCB-AX21E) is to be available. Slim Ducted MMD-AP0071SPH, MMD-AP0091SPH, MMD-AP0121SPH, MMD-AP0151SPH, MMD-AP0181SPH. The unit must be no more that 210 mm high and manufactured from galvanised steel sheet, insulated with closed cell expanded polyurethane foam. The DC fan motor will be configurable, allowing a maximum external static resistance of 50 Pa to be overcome. The airflow from the unit is to be configurable from the remote controller to compensate for high ceilings. Air is to return to the unit at the rear via a washable, long life air filter. A knockout is to be provided to allow up to 10% fresh air (un-tempered) to be introduced into the conditioned space. An integral condensate lift pump is to be provided with a 687 mm lift capability from the drain outlet. An optional infrared remote control kit (ref: TCB-AX21E) is to be available. High Static Ducted MMD-AP0181H, MMD-AP0241H, MMD-AP0271H, MMD-AP0361H, MMD-AP0481H, MMD-AP0721H, MMD-AP0961H.

expanded polyurethane foam. Each unit is to allow a maximum external static resistance of 200 Pa to be overcome. Air is to return to the unit at the rear. Ceiling Suspended MMC-AP0151H, MMC-AP0181H, MMC-AP0241H, MMC-AP0271H, MMC-AP0361H, MMC-AP0481H. expanded polyurethane foam and encased in an ABS plastic shell, finished in White (Munsell 10Y 9.3/0.4). A front mounted, motor driven, fully adjustable louver is to be fitted to allow air to be discharged horizontally for maximum cooling, or vertically downward for maximum heating. Primary, manually set louvers are to be incorporated to assist the air spread given by the motorised louver. Return air is to flow through washable, long life air filters mounted within the intake grilles on the underside of the unit. A rear knockout is to be incorporated into the main chassis of the unit to allow up to 10% fresh air (un-tempered) to be introduced into the conditioned space. Optional infrared remote control kit (ref: RBC-AX22CE) and drain pump (ref: TCB- DP22CE) are to be available. High-Wall MMK-AP0072H, MMK-AP0092H, MMK-AP0122H, MMK-AP0151H, MMK-AP0181H, MMK-AP0241H. expanded polyurethane foam and encased in an ABS plastic shell, finished in Silky Mist (Munsell IY8.9/0.5). A lower front mounted, motor driven, fully adjustable louver is to be fitted. Primary, manually set louvers are to be incorporated to assist the air spread given by the motorised louver. Return air is to flow through washable, long life air filters mounted within the intake grilles on the upper front of the unit. Chassis MML-AP0071BH, MML-AP0091BH, MML-AP0121BH, MML-AP0151BH, MML-AP0181BH, MML-AP0241BH. expanded polyurethane foam and be suitable for concealing behind a facia. It must be complete with a removable flange plate to allow the option of either top, or front discharge. Return air is to flow through washable, long life air filters mounted on the underside of the unit. Floor Standing

MML-AP0071H, MML-AP0091H, MML-AP0121H, MML-AP0151H, MML-AP0181H, MML-AP0241H. The unit will be manufactured from galvanised steel sheet and finished in Silky Shade (Munsell IY8.5/0.5). A removable discharge grille is to be fitted to allow the option of either top, or front discharge. Return air is to flow through washable, long life air filters mounted within the intake grilles on the lower front of the unit. Cabinet MMF-AP0151H, MMF-AP0181H, MMF-AP0241H, MMF-AP0271H, MMF-AP0361H, MMF-AP0481H, MMF-AP0561H The unit will be manufactured from galvanised steel sheet and finished in Silky Shade (Munsell IY8.5/0.5). Supply air is to be discharged forward at the top of the unit through motorised louvers. Return air is to flow through washable, long life air filters mounted within the intake grilles on the lower front of the unit. Refrigerant Pipe-Work All pipe-work shall be manufactured using de-oxidised, refrigerant quality copper to BS EN 1057:1996, and must be heat-treated as follows: 6.4mm (1/4 ) OD to 15.9mm (5/8 ) OD - 19.1mm (3/4 ) OD to 41.3mm (1 5/8 ) OD - Soft, Half Hard or Hard Tempered Half Hard or Hard Tempered When 1 5 / 8 tube is used, it must be 16 gauge. The length/height difference parameters and outside diameter of all piping is to be in accordance with the appropriate Toshiba manuals. All pipe work will be purged with oxygen-free nitrogen when brazing and capped at all other times. The system will be leak tested with oxygen-free nitrogen at a pressure of between 490 and 540 psig for a period of at least 8 hours. The oil balance pipe (if used) will be pressurised separately. The system will be de-hydrated by creating a vacuum deeper than 4 Torr before the vacuum pump is isolated for a period of no less than 30 minutes. If the vacuum falls during this time, oxygen free nitrogen will be added and the dehydration process repeated until the vacuum is maintained for 30 minutes. Virgin refrigerant (R410A) will be added in liquid form in accordance with Toshiba s requirements. All interconnecting refrigerant pipe work from Outdoor Units to Indoor Units is to utilise Toshiba joint kits to create the most practical refrigerant piping network. The range consists of: Tee-Piece Kit

RBM-BT13FE This kit is to be used when two, or more condensers are to be connected together. It shall consist of components to create tee-pieces for the suction, discharge, liquid and oil balance pipes for all possible pipe sizes required for Super Heat Recovery Multi outdoor units. Y-Branch Kits RBM-BY53FE RBM-BY103FE RBM-BY203FE RBM-BY303FE These kits are to consist of a suction pipe branch, discharge pipe branch, liquid pipe branch and related pre-formed thermal insulation pieces. The branch pieces are to come complete with sockets of varying dimensions to accommodate all potential sizes of refrigerant pipe. Header Branching Kits RBM-HY1043FE RBM-HY1083FE RBM-HY2043FE RBM-HY2083FE These kits are to consist of a suction pipe branch header (with four, or eight inlets/outlets), discharge pipe branch header (with four, or eight outlets/inlets), liquid pipe branch header (with four, or eight outlets/inlets) and related pre-formed thermal insulation pieces. The header pieces are to come complete with sockets of varying dimensions to accommodate all potential sizes of refrigerant pipe. Interconnecting Controls Wiring The nominated installer shall be responsible for the following interconnecting controls wiring: 2-core, non-polar = Indoor units to Remote Controller (A, B) 2-core, twisted, screened, non-polar = Local Area Network (U1, U2) 2-core, twisted, screened, non-polar = External Controls Network (U3, U4 and/or X, Y) All electrical wiring, bonding and earthing shall be in accordance with the current edition of BS 7671: 2001 (IEE Wiring Regulations 16 th Edition). The single and three phase voltages stated are EC harmonised voltages, but the equipment shall be suitable for 200-240 volts single phase and 380-415 volts three phase as appropriate. Controls The 3-Pipe VRF Super Heat Recovery Multi system(s) shall be complete with the following TCC-Link controls.

Simplified TCC-Link Remote Controller RBC-AS21E The remote controller(s) shall be surface mounted and hard wired to the indoor unit(s) via the AB connections, to provide the user with either local individual control of the air-conditioned space. The controller shall be manufactured in ABS plastic with a liquid crystal display (LCD). A temperature sensor is to be incorporated within the casing to allow the user to set the sensing point at the controller, or at the indoor unit. The controller shall display an alphanumeric fault code in the event of system malfunction. The controller shall provide control of the following primary functions: Start/stop. Operating mode (auto, cool, heat, dry, fan only). Temperature set point (18 C to 29 C). Fan speed (high, medium, low & auto). Louver position (where applicable). Filter check. Test run (heating & cooling). Standard TCC-Link Remote Controller RBC-AMT31E The remote controller(s) shall be surface mounted and hard wired to the indoor unit(s) via the AB connections, to provide the user with either local individual control of the air-conditioned space, or group control of up to 8 indoor units. The controller shall be manufactured in ABS plastic with a liquid crystal display (LCD). A temperature sensor is to be incorporated within the casing to allow the user to set the sensing point at the controller, or at the indoor unit. The controller shall enable the user to interrogate the system and display an alphanumeric fault code in the event of system malfunction. The controller shall be able to provide control or indicate status of the following functions: Start/stop. Operating mode (auto, cool, heat, dry, fan only). Temperature set point (18 C to 29 C). Fan speed (high, medium, low & auto). Louver position (where applicable). Filter check. Test run (heating & cooling). Minimum and maximum temperature settings in each mode Dead band between heating and cooling. Stratification control. Central control address. Auto-restart. Temperature sensor in use. High ceiling compensation. Elapsed timer lock. Sensor data available from all associated indoor and outdoor units

Integral elapsed timer TCC-Link Central Controller TCB-SC642TLE A central controller shall be surface mounted and hard wired to the outdoor unit(s) via the U3, U4 network, to provide the user with individual control of up to 64 master indoor units. The controller shall be manufactured in ABS plastic with a liquid crystal display. It shall be supplied from a 220-240 V ac 50 Hz power source. A maximum of 10 central control devices must be able to be fitted to a single control network (U3, U4). It must be possible to switch the controller on and off from a remote source via a volt-free contact connected across the A series terminals. The B series terminals must provide operation and general fault outputs. The controller shall enable the user to interrogate the system and display a hexadecimal fault code for each master indoor unit in the event of system malfunction. The central controller shall display status and provide control of the following primary functions for each master indoor unit: Start/stop. Operating mode (auto, cool, heat, dry, fan only). Temperature set point (18 C to 29 C). Fan speed (high, medium, low & auto). Louver position (where applicable). Filter check. Automatic or manual central control addressing with the further option to provide this from the controller. In addition the central controller shall facilitate the use of remote controllers (RBC-AMT21E or RBC-AS21E) to provide the user with localised control of the air-conditioned space. When standard remote controllers are used, each master unit must have the capability to control up to 7 slave units if required (all will operate to the same conditions as the master unit). The central controller can restrict the operation of local controllers, preventing changes being made to: On /off settings. On/off, mode and temperature settings. Mode and temperature settings. Mode settings. When used in conjunction with a weekly timer (RBC-EXW21E) the following configurable relationships must be available: Indoor units are turned on/off with the weekly timer and remain open to local override for one time period. Indoor units are turned off with the weekly timer and rely on local override to operate for one time period. Indoor units have on/off control disabled with the weekly timer and rely on local override to operate for one ON time period. Indoor units are stopped and have on/off control disabled with the weekly timer and rely on local override to operate for one ON time period. Indoor units have all functions disabled with the weekly timer and rely on local override to operate for one ON time period.

Indoor units are stopped and have all functions disabled with the weekly timer and rely on local override to operate for one ON time period. Network Adaptor TCB-PCNT30TLE To facilitate the connection of Digital Inverter or Super Digital Inverter split systems to a U3/U4 network, a network adaptor must be fitted to each master indoor unit. TCC-Link Weekly Timer RBC-EXW21E A weekly timer shall be connected either to the central controller and/or each standard remote controller. It should be connected via a dedicated 4-core lead supplied with the timer. The weekly timer shall be wall mounted and manufactured in ABS plastic with an LCD display. The controller shall provide 3 on/off periods per day in a 7-day cycle with a day omit capability. In addition the controller shall be able to auto-restart the whole system after a power failure and have 100 hours backup memory. Fault Monitoring & Control Interface RBC-FDP2-F-PE Fault detection and control is to be provided via the AB network with, or without a remote controller. Each FDP2 is detect any fault generated by the system and provide an output for appropriate action to be taken by the user. Red and green LEDs are to be fitted to the unit to indicate the fault/no fault condition. The detection of a fault code must illuminate the red LED and close the internal volt-free contacts. A locking function can be initiated to provide pre-set conditions of: Cooling 19ºC; Auto 21ºC; Heat 23ºC. These pre-sets are to be selectable by switches on the FDP2 unit. It must be possible to control 8 indoor units with a single FDP2 and connect 16 FDP2 units together on a D-Bus network to allow a single remote controller to group control up to 128 indoor units. Run and standby control of two groups of indoor units is to be provided. In the event of a fault on the running group, both groups will be activated. The FDP2 must also be able to be configured for load sharing and customised control options are to be available from Toshiba. Fault Monitoring & BMS Control Interface RBC-FDP2-BMS-PE Fault detection and BMS control is to be provided via the AB network with, or without a remote controller. Each FDP2 is detect any fault generated by the system and provide an output for appropriate action to be taken by the user. Red and green LEDs are to be fitted to the unit to indicate the fault/no fault condition. The detection of a fault code must illuminate

the red LED and close the internal volt-free contacts. BMS control for temperature, fan speed, mode, louver, on/off and remote controller lock is to be provided by variable voltage, or resistance inputs. It must be possible to control 8 indoor units with a single FDP2 and connect 16 FDP2 units together on a D-Bus network to allow a single remote controller to group control up to 128 indoor units. Run and standby control of two groups of indoor units is to be provided. In the event of a fault on the running group, both groups will be activated. The FDP2 must also be able to be configured for load sharing. Further customisation is to be available from Toshiba to fulfil specific end user requirements. Start/Stop and Fault Interface TCB-IFCB-4E Each indoor unit (master unit if grouped) is to be fitted with an interface to allow each indoor unit to be externally switched on and off by means of any volt-free external terminals. The interface shall be linked to the indoor unit using CN61 on the PCB. This device must also have the capability of providing a positive indication of the operation of the indoor unit and signal any errors (system and indoor unit stopping faults) via externally fitted volt-free contacts. The interface shall be fitted in position near the relevant indoor unit. External switching components can include: Time switch BMS Passive infra-red occupation sensor Auto restart Frost thermostat Fire alarm Outdoor Unit Control Board TCB-PCM02E An additional PCB is to be fitted to each master outdoor unit to provide one of the following functions: a) Mode selection allows an external switch to determine the choice of operating mode. b) Snowfall Fan Control When activated the outdoor unit fan will run independently of the compressor to prevent snow from settling on the unit when not in normal operation. c) On/Off External master start, or stop signals can enable, or disable each system. d) Set-Back When activated, the compressor and fan will be restricted in speed to provide a reduction in sound level for a single unit from 59 db(a) to 43 db(a). Lon Works Interface

TCB-IFLN640TLE A Lon Works Interface shall be hard wired to the U3 & U4 network, to enable the user to control up to 64 indoor units. Multiple interfaces may be connected to a Lon Works network to enable the user to monitor and adjust indoor units alongside any other integrated building services from a single PC. The interface shall enable the PC to display status, diagnostics by unit number and provide control of the following primary functions for each master indoor unit: - Mode of Operation (Auto, Cool, Heat, Fan Only) Temperature Set Point (18 C to 29 C) Fan Speed (High, Medium, Low & Auto) Louver Position (Where applicable) On/Off The interface shall permit the user to access the control of the system remotely via the use of a modem connection. In addition the interface shall facilitate the use of Remote Controllers (RBC-AMT31E or RBC-AS21E) to provide the user with local control of the air-conditioned space. When standard remote controllers are used, each master unit must have the capability to control up to 7 slave units if required (all will operate to the same conditions as the master unit). Trend BMS Interface RBC-LG1/LTX-21 TCB-PCNT20E A combination of a Lon Works interface and RealTime Controls LTX-21 shall allow the Toshiba air conditioning systems to communicate with a Trend BMS. An RBC-LG1/LTX-21 combination shall be hard wired to each indoor unit via the XY terminals on each protocol converter (TCB-PCNT20E), to enable the user to individually control up to 16 master indoor units when connected to a single system. Each master indoor unit is to be fitted with a protocol converter. Multiple interfaces may be connected to a Trend network to enable the user to monitor and adjust indoor units alongside any other integrated building services from a single PC. The LTX-21 connects directly to the supervisor port on a 2 series Trend outstation to permit all functions and settings to be modified. All of the system fault codes can be passed back through to the BMS that will allow the faults to be managed by the BMS alarm supervisor. The interface shall permit the user to access the control of the system remotely via the use of a modem connection. In addition the interface shall facilitate the use of Remote Controllers (RBC-AMT21E or RBC-AS21E) to provide the user with local control of the air-conditioned space. When standard remote controllers are used, each master unit must have the capability to control up to 7 slave units if required (all will operate to the same conditions as the master unit). Cylon (or other Modbus compatible) BMS Interface

RBC-LG1/LTX-51 TCB-PCNT20E This combination of a Lon Works interface and RealTime Controls LTX-51 shall allow the Toshiba air conditioning systems to communicate with a Cylon BMS. An RBC-LG1/LTX-51 combination shall be hard wired to each indoor unit via the XY terminals on each protocol converter (TCB-PCNT20E), to enable the user to individually control up to 16 master indoor units when connected to a single system. Each master indoor unit is to be fitted with a protocol converter. Multiple interfaces may be connected to a Cylon network to enable the user to monitor and adjust indoor units alongside any other integrated building services from a single PC. The LTX-51 connects directly to the modbus port on a UCC4 to permit all functions and settings to be modified. All of the system fault codes can be passed back through to the BMS that will allow the faults to be managed by the BMS alarm supervisor. The interface shall permit the user to access the control of the system remotely via the use of a modem connection. In addition the interface shall facilitate the use of Remote Controllers (RBC-AMT21E or RBC-AS21E) to provide the user with local control of the air-conditioned space. When standard remote controllers are used, each master unit must have the capability to control up to 7 slave units if required (all will operate to the same conditions as the master unit). Windows Package & Lonworks Interface RBC-WP1-PE TCB-IFLN640TLE A Windows Package (RBC-WP1-PE) shall be used in conjunction with a Lonworks Interface (TCB-IFLN640TLE). Each Lonworks Interface shall have the capability of individually controlling up to 64 indoor units and must be hard wired to the master outdoor unit via the U3 & U4 network. An unlimited number of Lonworks Interfaces can be connected to each Windows package. Each Lonworks Interface shall be powered by a 230V ac single-phase local supply. Each Lonworks Interface is then linked to the PC via the AB terminals. The Windows Package shall enable the user to control up to 1024 individual indoor units, and via the Lonworks Interface be capable of adjusting, managing and displaying all the following control functions: Mode of Operation (Auto, Cool, Heat, Fan Only) Temperature Set Point (18 C to 29 C) Fan Speed (High, Medium, Low & Auto) Louver Position (Where applicable) On/Off Fault Code Diagnostics Sensor Data Indoor Unit Locked Off On/Off Control Only Multiple Time Scheduling

In addition local control may be provided to any or all zones by the use of Remote Controllers (RBC-AMT21E or RBC-AS21E). When standard remote controllers are used, each master unit must have the capability to control up to 7 slave units if required (all will operate to the same conditions as the master unit). The controls software shall also enable the user to display unit locations via site specific floor plans and transmit system alarms via the following media types: - Fax, SMS, Modems, E-mail and Pager. To enable the Windows Package to be installed the following minimum system requirements shall be provided either by the end-user or the installer: - PIV or Greater Processor 512MB RAM Hard Drive with 50MB Free Space 16bit High Colour 800 x 600 SVGA or Greater Display (Not shared graphics card) Win NT, Version 4.0 or Later (Service Pack 3.0 or Greater) Win 2K Win XP Microsoft Word for Windows Internet Kit RBC-IK1-PE An Internet kit shall be used in conjunction with the Windows Package and Windows Gateway(s) to provide the following capabilities: Remote computer access to the server where the Windows Package is installed to allow up to 5 users at any one time to view, or change data using Microsoft Internet Explorer. Two levels of control: o Monitoring o Full Control Immediate access to operating conditions and historical performance, facilitating rapid response to customer/user enquiries. Energy Monitoring Kit RBC-EM1-PE Energy Monitoring kit(s) shall be fitted and used in conjunction with the Windows Package and Lonworks Interface(s) to provide a means of calculating total power consumption of the air-conditioning system, broken down by indoor unit. Using this data the Windows Package can generate bill reports to specific requirements and export data to billing software or an external site. Each kit consists of a power meter and a set of current transformers that are to be placed on the supply cables of up to six outdoor units.