ENGINE GENERATORS AND ACCESSORIES

Similar documents
B. Section Transfer Switches: Automatic transfer switch.

TT /97. Features INSTALLATION INSTRUCTIONS. Horn. Lamps

SMALL WORKS PROJECT REQUEST FOR SEALED BIDS

SECTION EMERGENCY POWER SYSTEMS

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

This Addendum includes the following changes and clarifications to the Contract Documents:

STATEMENT OF WORK I. SCOPE OF WORK:

DGC-500 DIGITAL GENSET CONTROLLER

CHAPTER 20 SERVICE EQUIPMENT

16620 EMERGENCY POWER SYSTEMS

STA16 SELECTRONIC ALARM ANNUNCIATORS DESIGN, INSTALLATION AND OPERATING MANUAL STA16

SECTION AUTOMATIC TRANSFER SWITCHES

Replacement of Fire Pump and Generator Upgrade, H Building, Sexton Campus

EMERGENCY POWER SYSTEMS

Spectron LSN (Life Safety Network) Suggested Specifications

1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1 ANSI/NFPA 20, Centrifugal Fire Pumps.

Step by Step Detailed Procedure Expected Result Observations Verify power off at all loads on emergency power. Verify all loads have power.

PowerWizard. Level 1.0 & Level 2.0 Control Systems Training

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: HVAC Standards

Digital Control Systems & Remote Communications Options

Electrical Design Guidelines Table of Contents

PowerWizard Range. Digital Control Systems & Remote Communication Options. PowerWizard Providing Safe Control of Your.

Prefunctional Checklist

SECTION AUTOMATIC TRANSFER SWITCHES

DGC-1000 DIGITAL GENSET CONTROLLER

SECTION ISOLATED POWER SYSTEMS

B. Provide factory test, startup by a supplier authorized by the equipment manufacturer(s), and on-site testing of the system.

Liebert CSU3000 Chiller

Baldor Electric ProSPEC MASTERFORMAT SPECIFICATION 10/26/05

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES

Annunciation, Remote Monitoring, Control Industrial Control Panels

University of Houston Master Construction Specifications Insert Project Name SECTION FIRE PROTECTION PUMPS PART 1 - GENERAL

PowerWizard Range. Digital Control Systems & Remote Communication Options.

GARCIA GALUSKA DESOUSA Consulting Engineers

ELECTRICAL - V DESCRIPTION 16.1 GENERAL

CONTENTS AUTOMATIC TRANSFER SWITCHES

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA

SECTION GENERATOR PARALLELING CONTROLS

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

POWER GENySYS P ROJECT E XPERIENCE I NFORMATION - D ISTRIBUTED G ENERATION

SECTION PANELBOARDS Painting Wire and Cable Overcurrent Protective Devices.

SECTION POWER SUPPLIES AND DISTRIBUTION

Guide Specification Model CTG Automatic Transfer Switch

SETION EMERGENCY LIGHTING NATIONAL FIRE PROTECTION ASSOCIATION (NEPA) (2006) Life Safety Code, 2006 Edition

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

IMPORTANT NOTICE BUILDERS AND CONTRACTORS WORKING IN NORTH RICHLAND HILLS, TEXAS. June 17th, 2016

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

WATER-TUBE POOL HEATERS

elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems

WATER-TUBE POOL HEATERS

AS DIGITAL FIRE PUMP CONTROLLER

A. This Section includes transfer switches rated 600 V and less, including the following:

National Electrical Code

National Industrial Security Monitoring Station Evaluation

21-light Remote Annunciator. Owner s Manual

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

ILLUMINATOR EM. CENTRAL LIGHTING INVERTER 1000 VA/W through 2800 VA/W 98% Efficiency!

Laboratory Enclosed Scroll Air Compressor System with Premium NFPA Controls

Functional Performance Test

Fire Alarm System Inspection and Testing Report

INSTALLATION INSTRUCTIONS

CITY OF WHITEHORSE SERVICING STANDARDS MANUAL SECTION 2 - CONSTRUCTION DESIGN CRITERIA SUB-SECTION 2.A SCADA STANDARDS.

Please refer to the drawing and notes for each particular plan view. Site Plan S1-1 Site Drawing. Electrical E1-1 Main Electrical Drawing

GPS 140 NEC Requirements for Generators. Professional Development Seminar Series NEC Requirements for Generators

earth safe Fuel Systems for Critical Power

R E C T I F I E R I N V E R T E R C O N V E R T E R SB7

A. This Section includes packaged engine-generator sets for [emergency] [standby] power supply with the following features:

NEC Requirements for Standby Power Systems. New England Building Officials Education Association Annual Conference October 5, 2015

Related Sections: TBD. Effective Date: January 1, 2016

EG Controls. SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF E G

Fire Pump Supervision - Part 2 by Dean K. Wilson, P.E.

Building Division 201 SE 3 rd STREET (Second Floor) OCALA, FL Phone: (352) BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS

SECTION Fire Pumps

ILLUMINATOR E & IE CENTRAL INVERTER FOR EMERGENCY LIGHTING

LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS

PowerWave 2 Busway System

The following information shall become and form part of the contract documents.

Security CCTV System Construction Checklist

WORKING DRAFT OF COMMITTEE MEETING OUTPUT

SECTION HEATING BOILER FEEDWATER EQUIPMENT

PANELBOARDS & BUILDING DISTRIBUTION

SECTION AUTOMATIC TRANSFER SWITCHES

Utility Battery Chargers DC Power Systems Custom Design

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

SECTION INTRUSION DETECTION

A. Furnish and install luminaires, lamps, ballasts and in-line fuses as herein specified and shown on the Drawings.

XTHERM, TYPE WH - MODELS 1005A- 2005A DIVISION COMMERCIAL, WATER-TUBE, CONDENSING GAS DOMESTIC WATER HEATERS

Powerohm Resistors Digital HRG System


Tempco s process controllers provide integrated solutions to manage your thermal loop system.

2.07 Permit Application Checklist for Diesel Generators, Diesel Fire Pumps, and Fuel Tanks Serving Generators and Fire Pumps (2016)

Photovoltaic (Solar) Array Installation Guide

Liebert PPC Second Generation Power Distribution Cabinet

AL800ULADA. NAC Power Extender. Installation Guide

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

Guide Specifications

S AGE E NGINEERING A SSOCIATES, LLP

C. ASSE 1013: Performance Requirements for Reduced Pressure Principle Backflow Preventers.

Page 1 of General

ITC 2000 HEATING CONTROL CABINET. Installation & Operation Manual

Transcription:

ENGINE GENERATORS AND ACCESSORIES GENERAL INFORMATION 1.1 This section applies to engine generators and accessories. DESIGN REQUIREMENTS 2.1 The Engineer of Record will consult with the University s Engineering Department to coordinate design activities with the emergency power master plan which dictates that a central paralleled system be installed in the Mudd Building basement at the location of the former chiller plant. New generators, similar to the unit installed for the Northwest Corner Building, will be designed to be relocated to the central system. 2.2 All new generators will be 4160 Volts per our emergency generator master plan. 2.3 Provide a complete generator electric supply system, fully coordinated and compatible, which will automatically furnish power complete with all equipment, controls, wiring, conduit, outlets, fixtures and devices 2.4 The engine and starting equipment shall be designed to ensure the engine-generator is up to speed, on line, and capable of accepting the full generator load within a period of ten (10) seconds after the initiation of the starting signal, by automatic devices hereinafter specified, upon loss of normal AC supply to the system. 2.5 All ATS s are bypass-isolation type, 4-pole or switched neutral to suit application. 2.6 Provide battery-powered emergency lighting in the generator area connected to circuits serving the normal area lighting. All normal lighting circuits serving areas with equipment generator power system shall be secured from panels connected to the load side of the transfer switch. 2.7 Generators shall be installed with a minimum 4-foot working clearance on all sides. 2.8 Provide a minimum of two (2) receptacles located near the generator fed with generator power and labeled to indicate so. 2.9 Fuel oil systems shall be in accordance with NYC Code requirements. 2.10 Fuel oil piping shall be double wall and in rated enclosures where required by Code.

2.11 Fuel oil system shall be provided with leak detection system. 2.12 The fuel oil system will utilize a day tank or main tank and day tank and will be sized to have a minimum of two (2) days of full load capacity taking into consideration the working volume of the tank not the labeled capacity. 2.13 There will be a fully alarmed fuel system including hi/low levels, overflow, leak detection, pressure alarms and any other system dependent requirement. 2.14 The day tanks or headers will be automatically fed with fill pumps and floats or pressure sensors. The Engineer will provide key bypasses for the floats so the pumps can be worked manually from the central control location. 2.15 The fuel system will be filtered with water separators integral to the engine. 2.16 Provide a circuit breaker and bus connection detail to facilitate the connection of a portable load bank. 2.17 Generator and each ATS shall be connected to power monitoring system. CONSTRUCTION REQUIREMENTS 3.1 Required factory unit tests include: a. Maximum power (kw). b. Maximum starting (kva). c. Time lag from signal to start, to operation at rated voltage and frequency for a cold engine having only the jacket coolant heater in operation. d. A minimum six (6) Hour Load Test: 1 hour at 50 percent load; 2 hours at 75 percent load; 1 hour at 100 percent load, and a 2 hour test running the generator continuously at 100 percent rated load at 0.8 power factor and a short run at 110 percent capacity. A full set of operating data will be recorded in real time and submitted to the contractor, the Engineer of Record and University for their approval. e. A complete functional test of all pre alarms and shutdowns. f. Full and partial rated load step applications and rejections shall be conducted and the frequency and voltage deviations and recovery times shall be within the performance requirements specified herein.

3.2 Provide alarm indication for the following conditions, utilizing either a solid state panel with LED or LCD readout or a panel with indicator lights and integral lamp test capability: a. Engine high-temperature pre-alarm [yellow]. b. Engine high-temperature shutdown [red]. c. Low lube oil pressure pre-alarm [yellow]. d. Low lube oil pressure shutdown [red]. e. Low coolant temperature alarm [red]. f. Low coolant level shutdown [red]. g. Battery charger malfunction [red]. h. Low battery voltage alarm [red]. i. High battery voltage alarm [red]. j. Over-speed shutdown [red]. k. Over-voltage shutdown [red]. l. Over-crank shutdown [red]. m. Fuel tank low level [red]. n. Fuel tank leak alarm [red]. o. Day tank low level [red]. p. Day tank leak alarm [red]. q. Control switch not in Auto position [flashing red]. r. Remote emergency stop [red]. s. Air damper closed [red]. t. Ground fault indication [red]. u. Generator supplying load [green]. v. Alarm horn with silencer switch.

3.3 Coolant Heaters: The engine shall be provided with thermostatically controlled tank type coolant heaters to maintain engine block coolant temperatures in the range of 100-120 degrees 3.4 Remote Annunciator: Provide a remote audible alarm panel to signal the occurrence of any of the events listed below at a remote panel, located as directed by Columbia. Utilize either a solid-state panel with LED or LCD readout or a panel with indicator lights and integral lamp test capability. Provide visual and audible indications and horn silence switch for the following functions: a. Engine high-temperature pre-alarm [yellow]. b. Engine high-temperature shutdown [red]. c. Low lube oil pressure pre-alarm [yellow]. d. Low lube oil low-pressure shutdown [red]. e. Low coolant temperature alarm [red]. f. Low coolant level shutdown [red]. g. Control switch not in Auto position [flashing red]. h. Battery charger malfunction [red]. i. Battery low/high voltage alarm [red]. j. Over-speed shutdown [red]. k. Over-crank shut down [red]. l. Main tank fuel oil low level [red]. m. Day tank fuel oil low level [red]. n. Main circuit breaker tripped [red]. o. Generator running [green]. p. Fault shutdown circuits. 3.5 Remote emergency-stop switch: Provide wall mounted emergency stop switch at each entry to generator room/enclosure arranged to shut down generator with protective cover to prevent accidental operation.

3.6 Where radiators cannot be unit mounted, provide closed loop, liquid cooled system with remote mounted radiator and with integral engine-driven coolant pump. 3.7 All fill and vent lines shall be brought to the exterior. 3.8 After successful test, the tank shall be marked with a UL approved label that states as a minimum: Special Purpose Flammable Liquid Tank, Secondary Containment Generator Base Tank with UL serial number, and the UL Mark. In addition, provide labels that contain the following: a. Fuel oil sub-base tank shall be double wall construction, a minimum of 30 percent larger than that required for 24 hours of fuel at continuous 100 percent load operation. A minimum of 4 feet shall be maintained on all sides of the sub-base fuel tank REFERENCE 4.1 The applicable CSI Specification Section is 263213.