A. Furnish and install luminaires, lamps, ballasts and in-line fuses as herein specified and shown on the Drawings.
|
|
- Hester Ami Lang
- 5 years ago
- Views:
Transcription
1 DIVISION 26 ELECTRICAL SECTION PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install luminaires, lamps, ballasts and in-line fuses as herein specified and shown on the Drawings. B. Luminaire Manufacturer and model numbers shall be as scheduled on the Drawings. Luminaires not bearing a letter symbol shall match adjacent luminaire in space. C. All lamps and ballasts for a given luminaire type shall be by the same Manufacturer QUALITY ASSURANCE A. All equipment shall be UL listed and labeled and in accordance with applicable NEMA and ANSI Standards. B. Ballasts shall be certified by ETL and CBM. Ballasts shall match lamps with appropriate ANSI code SUBMITTALS A. For Review: 1. Luminaires a. Product data sheets for each fixture. b. Lamp product data sheets for each fixture. c. Ballast, LED driver, or power supply product data sheets for each fixture. 2. Construction Drawings for custom luminaires B. To be included in Record and Information Manuals: 1. One (1) copy each of approved submittal 2. Spare lamp inventory list 3. Certificate of Material Receipt 1.04 MANUFACTURERS A. Luminaires 1. Refer to Luminaire Schedule on the Drawings. B. Lamps 1. Incandescent a. General Electric Company b. Osram/Sylvania Corporation c. Philips Lighting Company 13-HC
2 2. Fluorescent a. General Electric Company b. Osram/Sylvania Corporation c. Philips Lighting Company C. Ballasts 1. Electronic a. Advance Transformer Company b. Universal Lighting Technologies c. General Electric Company d. Osram/Sylvania Corporation e. Robertson Inc. 2. Emergency a. Bodine Company b. Iota Engineering Company c. Chloride Systems 3. Fluorescent Dimming a. Lutron b. Leviton c. Advance Transformer Company PART 2 PRODUCTS 2.01 LUMINAIRES A. Luminaires shall be as scheduled on the Drawings LAMPS A. Unless specifically indicated otherwise, all fluorescent lamps shall be energy saving, T8 Type with 3500 degree Kelvin color temperature and minimum of 80 CRI, low mercury green label. B Unless specifically indicated otherwise, all compact fluorescent lamps shall have a color temperature of 3000 degrees Kelvin, and a minimum of 82 CRI. Lamp base shall match luminaire socket FLUORESCENT BALLASTS A. Electronic ballasts for T8 lamps shall meet the following criteria: 1. Minimum power factor of 95%. 2. UL listed class "P." 3. Class "A" sound level. 4. Current crest factor < Input total harmonic distortion (THD) < 20%. 6. Parallel wire lamp connection with programmed start operation. 7. High frequency operation degree F or Zero degree F starting temperature. 9. Ballasts shall have end of lamp life fault mode shutdown protection HC1-033
3 B. Compact fluorescent electromagnetic ballasts shall be energy saving, high power factor, Class "A" sound rating, Class "P" ballast protection, CSA certified, 50 degree F or 0 degree F starting temperature. C. Compact fluorescent electronic ballasts shall be energy saving, high power factor (minimum 95), Class "A" sound rating, high frequency Class "P" ballast protection, CSA certified, 0 degree F starting temperature, current crest factor <1.5, input total harmonic distortion (THD) <10%, with integral end of lamp life fault mode shutdown protection. D. Fluorescent emergency ballasts shall be integral mounted, ninety (90) minute capacity, sealed maintenance free nickel cadmium battery, and have remote mountable charging indicator light and test switch. Ballasts shall feature a self-diagnostic circuit that automatically tests unit and reports failure with an audible and visual alarm. E. Fluorescent Dimming Ballasts 1. Fluorescent dimming ballasts shall be UL listed, with minimum light level of 1% unless noted otherwise on the Drawings. Ballasts shall preheat lamp cathodes before starting to maintain lamp life. Ballasts shall limit in rush current to prevent circuit breaker nuisance tripping. 2. Ballast specifies as follows: Power Factor - Minimum 0.95 Ballast Factor - Minimum 0.85 THD - Maximum 20% Crest Factor - Maximum Ballasts shall start lamps at any light level. Starting at maximum level shall not be necessary. 4. Ballasts shall not create any audible noise. 5. Ballasts shall start lamps down to 50 degrees F ambient LUMINAIRE ACCESSORIES A. Luminaires located in mechanical and electrical rooms shall have guards provided with each luminaire. B. Luminaires located in gypsum board (drywall) or plaster ceilings shall have appropriate plaster rings provided with each luminaire. C. Luminaires provided by the Manufacturer with cords attached shall be coordinated by the Division 26 Contractor so that cord lengths are of appropriate lengths for each luminaire installation. D. Luminaires shall be provided with all required mounting hardware for a complete installation. 13-HC
4 PART 3 EXECUTION 3.01 APPLICATION A. Ballasts 1. Fluorescent ballasts in luminaires located exterior to the building and in unheated spaces shall have a 0 degree F starting temperature. 2. Fluorescent ballasts located within the building shall have a 50 degree F starting temperature. 3. Electronic ballasts shall be used in all luminaires where available. B. Single and multiple lamp ballasts shall be provided in luminaires as required to permit lamp switching configurations as shown on the Drawings. C. Dimming ballasts shall be provided in luminaires as required to provide dimming as shown on the Drawings. D. New fluorescent lamps must be burned-in (seasoned) at full intensity for 100 hours (before dimming for extended periods). Without these operating hours, lamps may fail prematurely. E. Each ballast shall have a disconnecting means located within 24 inches of the ballast INSTALLATION A. Luminaires shall be securely mounted to elements of the building structure such that they will be square, plumb, and rigid, and will not fall or sag. Flush luminaires shall be furnished with installation provisions compatible with the suspended acoustical system furnished by the General Trades Contractor. This Contractor shall verify the actual suspension system to be used and make all adjustments in luminaire installation provisions. B. All open type fluorescent troffers shall be shipped from the Manufacturer with the louver enclosed in plastic wrap. The Contractor shall install the luminaires with the plastic wrap intact and only remove the wrap after the work environment is clean. Contractor shall patch any holes in the wrap to keep dirt out of the luminaire during construction. C. All luminaires mounted in suspended acoustical tile ceilings shall be securely attached to the ceiling grid system by removable grid clips or fasteners. Recessed "can" type luminaires shall have bar hangers attached to the ceiling grid system. D. All luminaires mounted on suspended acoustical tile ceilings shall be mounted to junction boxes with bar hangers attached to the ceiling grid system. In addition, luminaires heavier than ten (10) pounds shall have hangers attached to the ceiling grid system. E. All luminaires that are wall mounted or surface mounted to other than suspended acoustical tile ceilings shall be attached to outlet boxes that are securely supported to the building structure and UL listed for luminaire support HC1-033
5 F. All surface mounted and recessed fluorescent luminaires installed in suspended acoustical tile ceilings, shall have a supplemental support means attached to the building structure consisting of chain or cable, installed with 6 inches of slack. This support means shall be attached from the structure to the luminaire at each end and shall be capable of suspending the luminaire in the event the ceiling grid at the luminaire is removed. G. Clean both inside and outside surfaces of luminaires after installation. No luminaires shall be installed until the painting work of the General Trades Contractor is completed. Damaged, deformed or defective luminaires are to be replaced. H. Install lamps in all luminaires in accordance with the Luminaire Schedule. I. Only the number of lamps required to provide adequate lighting for work yet to be done, in each area, and acceptable temporary lighting elsewhere shall be installed by this Contractor at the time luminaires are installed and tested. Remaining lamps to be installed not more than ten (10) days prior to date of Contract Completion of the project. Replace lamps used for temporary lighting with new lamps not more than ten (10) days prior to date of Contract Completion of the project. J. All lamps are to be in working order at the time of Contract Completion. This Contractor shall replace all defective lamps with new lamps up until the time of Contract Completion. K. Prewired flush luminaire shall have minimum 90 Degree C wiring. Junction box capacity shall be sufficient for the circuit wiring requirements. L. Furnish all required installation accessories for the luminaires as required for specific location whether or not included in the Manufacturer's catalog number. Such accessories include plaster frames, rings, flanges, canopies, stem hangers, and suspension straps. REFER TO ARCHITECTURAL ROOM TREATMENT SCHEDULE. M. Designated night light, emergency egress, and exit signage luminaires shall be connected ahead of any switching. N. Install emergency ballasts integrally within the luminaire if possible, otherwise, remote mounted from the luminaire to building structure above ceiling. Install test switch/charging light plate in ceiling tile next to luminaire. O. Luminaires provided by the Manufacturer with cords attached shall be coordinated by the Division 26 Contractor to assure adequate cord length for each individual luminaire installation. P. Coordinate exact wiring requirements to luminaire ballasts with Manufacturer. Q. Flexible conduit or cord run down to suspended luminaires shall be installed along side of the suspension chain and neatly attached along its entire length. R. Fixture whips shall be of a minimum size as specified in Section , "Wire and Cable" and Section , "Conduit and Fittings". 13-HC
6 3.03 SPARE PARTS A. Lamps 1. Provide spare lamps of each wattage as follows: LAMP TYPE TOTAL NUMBER OF LAMPS INSTALLED IN PROJECT NUMBER OF SPARES FLUORESCENT UP 40 B. Division 26 Contractor shall include in his/her bid an allowance for furnishing and installing five (5) additional exit sign luminaires (with average length of conduit and wire) at completion of project as directed by the Architect. If not all used, remaining value shall be credited to Owner or turned over to Owner as additional spares per Owner's discretion WARRANTY A. Fluorescent electronic and emergency ballasts shall have a Manufacturer's full warranty for five (5) years. END OF SECTION HC1-033
WINDSOR FOREST HIGH SCHOOL HVAC REPLACEMENT ADDENDUM #2 SAVANNAH CHATHAM COUNTY PUBLIC SCHOOL SYSTEM FEBRUARY 18, 2016
SECTION 26 2030 - LIGHTING FIXTURES PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. Drawings and general provisions of the Contract, including General and Special Conditions and Division 1 Specification Sections,
More informationSECTION INTERIOR LIGHTING
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the
More informationB. It is recognized that these standards are updated irregularly and lighting technology is changing rapidly.
PART 1 GENERAL 1.01 Lighting design: A. Reference UAF Facilities Services Guidelines for Average Illumination Levels. B. It is recognized that these standards are updated irregularly and lighting technology
More informationMASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 26 ELECTRICAL
SECTION 265100 - INTERIOR LIGHTING PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Interior lighting fixtures, lamps, and ballasts. 2. Emergency lighting units. 3. Exit signs. 4.
More informationA. Furnish and install wiring devices and plates as specified herein and as shown on the Drawings.
DIVISION 26 ELECTRICAL SECTION 26 27 26 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install wiring devices and plates as specified herein and as shown on the Drawings. B. Specialty switches and outlets
More informationSECTION LIGHTING
SECTION 26 50 00 LIGHTING PART 1 GENERAL 1.1 DESCRIPTION A. Scope: 1. CONTRACTOR shall provide all labor, materials, equipment, and incidentals as shown, specified, and required to furnish and install
More informationSECTION INTERIOR LIGHTING
SECTION 26 51 00 INTERIOR LIGHTING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More information2. Lighting fixtures mounted on exterior building surfaces.
PART 1 - GENERAL... 1 1.1 RELATED DOCUMENTS... 1 1.2 SUMMARY... 1 1.3 DEFINITIONS... 2 1.4 SUBMITTALS... 2 1.5 QUALITY ASSURANCE... 3 1.6 COORDINATION... 3 1.7 WARRANTY... 4 1.8 EXTRA MATERIALS... 4 PART
More informationE. Luminaire: Complete lighting fixture, including ballast housing if provided.
SECTION 16511 - INTERIOR LIGHTING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 16 Specification
More informationSECTION INTERIOR LIGHTING
PART 1 - GENERAL 1.1 DESCRIPTION: SECTION 26 51 00 SPEC WRITER NOTES: Use this section only for NCA projects. Delete between //----// if not applicable to project. Also, delete any other item or paragraph
More informationSECTION INTERIOR LIGHTING
SECTION 26 51 00 INTERIOR LIGHTING PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationSECTION INTERIOR AND EXTERIOR LIGHTING FIXTURES
SECTION 26 50 00 INTERIOR AND EXTERIOR LIGHTING FIXTURES PART 1: GENERAL 1.1 WORK INCLUDED: A. Interior lighting fixtures and accessories B. Exterior lighting fixtures and accessories C. Emergency battery
More information.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority.
Fitness Facility Addition Page 1 1.1 CODES AND STANDARDS.1 Do complete installation in accordance with the latest edition of the CSA C22.1 as amended by the latest editions of the National Building Code
More informationSECTION C. Section Cable Trays for Electrical Systems: Additional identification requirements for cable tray systems.
SECTION 26 0553 PART 1 GENERAL 1.1 SECTION INCLUDES A. Electrical identification requirements. B. Identification nameplates and labels. C. Wire and cable markers. D. Voltage markers. E. Underground warning
More informationM001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings
1 T Consultant: NOTES, SYMBOLS & ABBREVIATIONS - MECHANICAL Number Description M001 Vestibule 117 LAN/IT Coffee 115 116 Mail Room 118 114 113 112 Scanning 119 Open Office 101 FIRST FLOOR PLAN - MECHANICAL
More informationSPECIFICATIONS: FIREGUARD CROSS CORRIDOR CC
SPECIFICATIONS: FIREGUARD CROSS CORRIDOR CC SECTION 08 35 13.23 ACCORDION FOLDING FIRE DOORS PART 1 GENERAL 1.01 SUMMARY OF WORK A. Division 0 and 1, as indexed, apply to this section. B. Furnish and install
More information1. Building wires and cables rated 600 V and less. 2. Connectors, splices, and terminations rated 600 V and less.
Copyright 2010 AlA MasterSpec Full Length 09/10 SECTION 260519- LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES PART I-GENERAL 1.1 SUMMARY A. Section Includes: 1. Building wires and cables rated 600
More informationSpringpoint Architects, pc SECTION Childcare Center Architect s Project No TABLE OF CONTENTS Monroe County Comm. Sch. Corp.
Volume 1 Bidding Requirements, Contract Forms, Conditions of the Contract, Division 1, Architectural and Site Specifications 000107 Certification Page 000110 Table of Contents DIV00 PROCUREMENT AND CONTRACTING
More informationMaxLite LED Round Pendant Highbay Series
General Safety Information To reduce the risk of death, personal injury or property damage from fire, electric shock, falling parts, cuts/abrasions, and other hazards read all warnings and instructions
More informationPage 1 of General
Page 1 of 8 16.1 General 1. This section covers items common to sections of CSI s Master Format - Division 16. 2. Dalhousie University is certified by IBEW for new construction and all electrical contractors
More informationInvestSmart Business Energy Upgrades Lighting Equipment Catalog 01/01/2018
2018 InvestSmart Business Energy Upgrades 01/01/2018 Table of Contents 1 Lighting Improvement Measures...1-1 1.1 Lighting... 1-1 1.2 Occupancy Sensors... 1-3 1 Lighting Improvement Measures This Equipment
More informationPowerWave 2 Busway System
PowerWave 2 Busway System Guide Specifications (Revision 004, 11/17/2017) 1 GENERAL 1.1 Summary This specification covers the electrical characteristics and general requirements for a continuous opening,
More informationElectrical Design Guidelines Table of Contents
C: Compliant Rev. 3 Dated June 13 11 NC: Non-Compliant NA: Not Applicable Page1 16.1 General 16.2 Single Line Diagrams 16.3 Electric Motor Equipment and Controls 16.4 Lighting 16.5 Emergency Lighting 16.6
More informationLED Lighting: Technology Selection and System Commissioning Course Number: CXENERGY1519
AABC Commissioning Group AIA Provider Number: 50111116 LED Lighting: Technology Selection and System Commissioning Course Number: CXENERGY1519 Michael Chow, P.E., CxA, LEED AP BD+C, Metro CD Engineering
More informationLED RETROFIT CONVERSION KITS
Engineered Products Company s LED RetroFit Conversion Kits convert older 4-foot and 8-foot T8 or T12 strip-type fixtures into energy efficient LED luminaires. High quality components and attractive design
More informationBdl60u Fluorescent Emergency Ballast
A Division Of Philips Electronics North America Corporation One- or two-lamp emergency; Universal input voltage: 120 through 277 V, 50 or 60 Hz; Replaces B60U Bdl60u Fluorescent Emergency Ballast Product
More informationB. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.
DIVISION 21 21 05 00 COMMON WORK RESULTS FOR FIRE SUPPRESSION PART 1 GENERAL 1.1 SECTION INCLUDES A. Pipe, fittings, sleeves, escutcheons, seals, and connections for sprinkler systems. 1.2 RELATED REQUIREMENTS
More informationSECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM
SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationLED Flat Panel Retrofit
LED Flat Panel Retrofit Installation Instructions For 2 x2, and 2 x4 LED Flat Panel Retrofits (RP Series) PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLATION INTRODUCTION The LED Flat Panel Retrofit fits
More informationHIGH BAY APPLICATIONS
STAIRWELLS The IIS Inverter can operate multiple fixtures in a building s stairwell and can be wired to bypass dimmers or occupancy sensors...keeping your egress corridors lit without sacrificing your
More informationFillmore Small Pendant Assembly and Installation Instructions
CAUTION: Fillmore Small Pendant Assembly and Installation Instructions BEFORE INSTALLING FIXTURE, MAKE SURE THE POWER TO THE CIRCUIT IS TURNED OFF AT THE MAIN FUSE BOX / CIRCUIT BREAKER UTILITY BOX. Important
More informationA. This Section includes the following lighting control devices:
Attachment G LIGHTING CONTROL SPECIFICATIONS (Download Document separately) LIGHTING CONTROL SPECIFICATIONS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including
More informationLUCE 1 TL. specifications: internal. specifications: external. ordering logic. builder. Job/Location:
LUCE 1 TL indoor / damp Job/Location: Contractor: Prepared By: Job Type: Date: The LUCE-1TL thinline emergency ballast is designed to provide emergency illumination to existing or new fluorescent luminaires.
More informationMaxLite 4, 6, 8 & 9 LED Architectural & Commercial Downlights
General Safety Information To reduce the risk of death, personal injury or property damage from fire, electric shock, falling parts, cuts/abrasions, and other hazards read all warnings and instructions
More informationUNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:
SECTION 233423 - HVAC POWER VENTILATORS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Provisions of the Contract and of the Contract Documents apply to this Section. 1.2 PERFORMANCE REQUIREMENTS A. Operating
More informationMLA Architects Pierz Public Schools ISD #484 Healy High School Multi-Purpose & Choir Additions Pioneer Elementary School Class Room Addition Pierz, MN
DIVISION 21 - FIRE SUPPRESSION (REFER TO SECTION 23 05 00 FOR BASIC FIRE SUPPRESSION REQUIREMENTS) 21 05 00 Common Work Results for Fire Suppression 21 13 13 Wet-Pipe Sprinkler Systems END OF SECTION FIRE
More informationSECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM
SECTION 213100 WET PIPE FIRE PROTECTION SPRINKLER SYSTEM PART 1 - GENERAL 1.01 GENERAL REQUIREMENTS A. The requirements of the General Conditions and Supplementary Conditions apply to all work herein.
More informationSECTION EXTERIOR LIGHTING
SECTION 26 56 00 PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation, and connection of exterior luminaries, controls, poles and supports. 1.2 RELATED WORK A. Section 26
More informationCL001 >400 Watt lamp basecase, up to 600 Watt replacement fixture $95.00 Fixture
Lighting Specifications Business Please read the details below to ensure you are installing a qualifying product(s). An MID inspection of the pre-existing lighting scheme is required prior to the installation
More informationDESIGN & CONSTRUCTION GUIDELINES
ADMINISTRATIVE SERVICES 4202 E. FOWLER AVENUE, FPC110 PHONE: (813) 974-2625 FACILITIES PLANNING & CONSTRUCTION TAMPA, FLORIDA 33620-7550 WEBSITE: USF.EDU/FPC DESIGN & CONSTRUCTION GUIDELINES DIVISION 21
More informationSECTION AUTOMATIC TRANSFER SWITCHES
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 This section specifies the furnishing, complete installation, and connection of automatic transfer switches. 1.2 RELATED WORK A. Section 14 21 00, ELECTRIC
More informationPARISIAN ARCHITECTURAL BRASSERIE PENDANT 9
PARISIAN ARCHITECTURAL BRASSERIE PENDANT 9 PARTS ENCLOSED (A) Mounting Strap (1) (B) Threaded Nipple (1) (C) Mounting Screws (2) (D) Mounting Loop (1) (E) Canopy (1) (F) Canopy Ring (1) (G) Chain (1) (H)
More informationLED RETROFIT CONVERSION KITS
Our LED RetroFit Conversion Kits come with a complete Gear Tray Assembly to convert older 4-foot and 8-foot T8 or T12 strip-type fixtures into energy efficient LED luminaires. High quality components and
More informationTABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION WATER BASED FIRE PROTECTION SYSTEMS... 5
DOC Cremer Heating and Hot Water Plant Project Number: M 1411-04 TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION 21 30 00- WATER BASED FIRE PROTECTION SYSTEMS... 5 SECTION 22 40 00 -PLUMBING
More informationUNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-23 83 00.00 20 (April 2006) -------------------------------- Preparing Activity: NAVFAC Replacing without change UFGS-15768N (September 1999) UNIFIED FACILITIES GUIDE
More information2018 Instant Lighting Rebates Product Catalog
MIDSTREAM LIGHTING PRODUCTS Product Code 463993 Interior 4 LED T8 Lamp Product Description Rebate/Unit Page # $5.00/Lamp 8 464791 Commercial LED Candelabra: 1 to
More informationEmergency Lighting. Product Guide LED. The right source for the. right light
Emergency Lighting Product Guide LED The right source for the right light Contents Emergency Lighting Is Code-Required...... 2 Life Safety Code...4 Emergency Backup Options...6 LED Terminology..........................
More informationFPLHB - Fidelux Premier Linear Highbay
FPLHB - Fidelux Premier Linear Highbay Product Description Fidelux LED Linear High Bays meet the challenging maintenance, safety, and performance requirements of industrial environments through an unbeatable
More informationelite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems
5/25/16 rev 6 elite Model ELN General Specification 550 W to 1.5 KW elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems 1.0 General General Specification This specification
More informationApplications. Standard Materials
Mercmaster III Low Profile Compact Fluorescent Luminaires Compact Fluorescent listed for simultaneous exposure to combustible dusts and flammable gases or vapors. Applications Enclosed and gasketed fixtures
More informationCOBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM
SECTION 21 10 00 PART 1 - GENERAL 1.1 CODES A. Work shall conform to NFPA 13 Sprinkler Systems, 2002 Edition and NFPA 24 Outside Protection, 2002 Edition. NFPA 14 Standpipe Systems, 2000 Edition and International
More informationROAM DCM Control Specification Guideline Division 16520
ROAM DCM Control Specification Guideline Division 16520 PART 1. GENERAL 1.1 INTRODUCTION A. The intent of this specification is to provide for furnishing, installing, testing and placing into operation,
More informationSECTION AUTOMATIC TRANSFER SWITCHES
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph
More informationSECTION ENCLOSED CONTROLLERS
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes ac,
More informationPSO Business Rebates Retrofit Lighting Technical Requirements
PSO Business Rebates Retrofit Lighting General LED Requirements LED replacement and LED luminaires must be listed on the Design Lights Consortium (DLC) or ENERGY STAR Qualified Products List (QPL). DLC
More informationWest District Library Section Campeau Drive, Ottawa SPRINKLER SYSTEMS City of Ottawa Project No. CR Page 1 of 8
City of Ottawa Project No. CR006230 Page 1 of 8 PART 1 - GENERAL 1.1 Reference Standards.1 Conform to the following:.1 Provincial and municipal building and fire regulations as approved by Provincial Fire
More informationEarthTronics products. About us. Where efficiency meets innovation. T5 & T8 Linear. Founded in 2007, EarthTronics, Inc. is a Michigan based
LED Product Guide About us EarthTronics products We are dedicated to developing innovative energy efficient lighting products that provide a positive economic and environmental impact for our customers.
More informationSECTION (16140) - WIRING DEVICES
SECTION 26 27 26 (16140) - WIRING DEVICES PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Receptacles, Connectors, Switches, and Finish Plates. B. Related Sections: 1. Section 00 31 13.43 (00370) -
More information1 x4 Dimmable LED RetroFits
1 x4 Dimmable LED RetroFits Installation Instructions Ordering Code: RF16UQT1XXCDL RF16UHT1XXDL RF32UQT1XXCDL RF32UHT1XXDL PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLATION OF THE FOLLOWING: 4 STRIP FIXTURES
More informationHi-lume 3D Overview. Fluorescent Dimming Ballasts Hi-lume 3D Architectural Dimming
Fluorescent Dimming s Hi-lume 3D Architectural Dimming Hi-lume 3D Overview 369-280f 1 03.08.12 Hi-lume 3D architectural electronic dimming ballasts are designed to meet the most demanding lighting requirements.
More information1. Division 26 Section Electrical General Requirements. 2. Division 26 Section "Wiring Devices" for wall-box dimmers and manual light switches.
PART 1 - GENERAL... 1 1.1 RELATED DOCUMENTS... 1 1.2 SUMMARY... 1 1.3 REFERENCES... 2 1.4 DEFINITIONS... 2 1.5 SUBMITTALS... 2 1.6 QUALITY ASSURANCE... 3 1.7 COORDINATION... 3 1.8 DELIVERY, STORAGE, AND
More informationEligible Prescriptive Measures List:
Eligible Prescriptive Measures List: Business, Non-Profit, Institutional Energy Savings Program Products must meet the Canadian Certification Standards as outlined by the Standards Council Canada for product
More informationBAS SFP22 Edge-lit LED Panel
Project Name Fixture Type Catalog # BAS SFP22 The ultra-thin, edge-lit LED panel (BAS SFP22) series is designed to deliver general ambient lighting in a variety of indoor settings, including schools, offices,
More informationUBC Technical Guidelines Section Edition Interior Building Lighting Page 1 of 5
Page 1 of 5 1.0 GENERAL 1.1 Related UBC Guidelines.1 Section 27 05 05 Communication Rooms Design Guidelines 2.13 1.2 Coordination Requirements.1 UBC Energy & Water Services.2 UBC Building Operations Electrical
More informationUltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW
12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes
More informationSECTION ELECTRICAL SYSTEMS COMMISSIONING
SECTION 16990 PART 1 - GENERAL 1.01 SECTION INCLUDES A. Section Includes: 1. General requirements for Commissioning (Cx) of lighting systems components, lighting controls and HVAC systems line voltage
More informationUniversity of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL
SECTION 21 13 16 DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
More informationEcoSystem H-Series Ballasts
Fluorescent Dimming s Eco H-Series Architectural Dimming Eco H-Series s 369266o 1 11.29.17 Eco H-Series digitally addressable ballasts provide a low-cost, flexible solution for any space in any application.
More informationEcoSystem H-Series 347 V~ Ballast Overview
Fluorescent Dimming s EcoSystemR H-Series 347 V ~ Architectural Dimming EcoSystem H-Series 347 V~ Overview 369-352e 1 06.04.12 EcoSystem H-Series digitally addressable ballasts provide a low-cost, flexible
More informationSECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the
More informationIN2 Lighting Control Devices
Illinois Math and Science Academy DigitalCommons@IMSA Project Manuals IN2 2015 IN2 Lighting Control Devices Illinois Mathematics and Science Academy Follow this and additional works at: http://digitalcommons.imsa.edu/facility_in2_manuals
More informationRECESSED Spec Guide. up to 111 lm/w performance
RECESSED up to 111 lm/w performance Performance based on 4 luminaire at 4000K @ 25 o C Calculated L80 at 80,000 hours Lumens per foot are delivered lumens Page 2 of 10 260.599.3590 orders@luxilluminaire.com
More informationTROFFER RETROFIT KIT (TRK)
Not all products are qualified on the DLC QPL. To view our DLC qualified products, please consult the DLC Qualified Products List at www.designlights.org/qpl. TROFFER RETROFIT KIT (TRK) www.trulygreensolutions.com
More informationInde-Pendants Family. 32L Cylinder Plaster Trim, Grid and Drywall Ceiling Types. Document No
Inde-Pendants Family 32L Plaster Trim, Grid and Drywall Ceiling Types Installation instructions for 32L-C-P-ID 32L-C-P-D Document No. Supplied by Litecontrol 32L Inde-Pendants: (Plaster Trim, Grid and
More informationA. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:
SECTION 21 13 13 WET-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
More informationOCH-SS series Direct Wired Units Indoor * and Outdoor Comfort Heaters
1200 North Main Street Fostoria, OH 44830 Phone: 800-495-4525 Fax: 419-435-0842 A DIVISION OF www.fostoriaindustries.com OCH-SS series Direct Wired Units Indoor * and Outdoor Comfort Heaters *EXCLUDING
More informationInstallation Instructions
Installation Instructions Ordering Code: RF32UQT1XX PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLATION OF THE FOLLOWING: 4 STRIP FIXTURES 8 STRIP FIXTURES HARDWIRE 4 STRIP FIXTURES WRAP FIXTURES TROFFER
More informationB. Section Identification for Fire Suppression Piping and Equipment.
SECTION 211300 - FIRE SUPPRESSION SPRINKLERS PART 1 GENERAL 1.1 SECTION INCLUDES A. Dry-pipe sprinkler system. B. System design, installation, and certification. C. Fire department connections. 1.2 RELATED
More informationCommercial Lighting Catalog
Commercial Lighting Catalog DUAL HEAD FLOODLIGHT DUSK TO DAWN FLUORESCENT SECURITY LIGHT FLOODLIGHT QUARTZ 300 WATTS 671002 617126 671000 FLOODLIGHT WITH METAL HOUSING 1 LAMP FLOODLIGHT WITH METAL HOUSING
More informationBusiness Customer Information. Account Number (9 digits) Account Holder Name Phone (As shown on your utility bill) Service Street Address
Commercial Lighting Rebate Application Please complete the application including existing and installed information. Application will be returned without valid purchase receipt/invoice or if equipment
More informationLighting Existing Conditions and Design Criteria Report EXECUTIVE SUMMARY
Lighting Existing Conditions and Design Criteria Report EXECUTIVE SUMMARY The Lighting Existing Conditions and Design Criteria Report will examine the existing lighting conditions in the (in general and
More informationSECTION PANELBOARDS Painting Wire and Cable Overcurrent Protective Devices.
SECTION 16470 PANELBOARDS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 09900 - Painting. 2. 16120 - Wire and Cable. 3. 16475 - Overcurrent Protective Devices. 1.02 SYSTEM DESCRIPTION A. Performance
More informationLight Fixtures: A Lamp in a Box. Light fixtures are MORE than a decorative object.
1 Light Fixtures: A Lamp in a Box Light fixtures are MORE than a decorative object. 2 What defines a Light Fixture? Keyless Porcelain Socket Keyed (pull chain) Porcelain Socket Specifications: Method of
More information2017 Lighting Incentive
Commercial & Industrial Retrofit 2017 Lighting Section A: CUSTOMER INFORMATION Customer Name Electric Account Number Rate Application Number Facility Address City State Zip Service Location Identification
More informationSpectron LSN (Life Safety Network) Suggested Specifications
1. General 1.1 Scope A Dual-Lite Spectron LSN (Life Safety Network) Series Inverter System shall be furnished to provide a reliable source of power, and shall operate during a utility line deficiency without
More informationHi-lume 3D Overview. Fluorescent Dimming Ballasts
Fluorescent Dimming s Overview 1 architectural electronic dimming ballasts are designed to meet the most demanding lighting requirements. By providing industry leading performance with a full-range of
More informationCatalog Number. Notes
Catalog Number FEATURES & SPECIFICATIONS INTENDED USE Built on the compact, low-profile Z strip channel, this LED strip offers long maintenance-free life, several color s, lumen outputs and lengths. Ideal
More informationEvolution EXWW RECESSED LINEAR WALL WASH LUMINAIRE
Evolution EXWW Project Name Date Type RECESSED LINEAR WALL WASH LUMINAIRE 3-13/16 (96.8mm) 5-1/8 (130.2mm) Extruded aluminum trim with formed cold rolled 20 gauge steel back box housing Highly reflective,
More informationSECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL
SECTION 16400 AUTOMATIC TRANSFER SWITCHES 1.01 RELATED DOCUMENTS PART 1 - GENERAL A. Drawings and general provisions of Contract, including General Conditions and Division 1 Specification sections, apply
More informationInstalling Industrial Lighting Systems
A M E R I C A N N A T I O N A L S T A N D A R D NECA/IESNA 502-2006 Standard for Installing Industrial Lighting Systems Published by National Electrical Contractors Association Jointly developed with Illuminating
More information2018 Midstream Lighting Product Catalog
MIDSTREAM LIGHTING PRODUCTS Product Code Product Description Rebate/Unit Page # 463993 Interior 4 LED T8 Lamp $5.00/Lamp Commercial LED Candelabra 2 Watts 462649 4 $7.00/Lamp Commercial LED Candelabra
More informationwww.greenelectricalsupply.com FLATMAX LED FLAT PANEL: PERFORMANCE SERIES USER MANUAL INSTALLATION GUIDE FOR: 1X4: MLFP14DP4535 MLFP14DP4541 MLFP14DP4550 2X2: MLFP22DP4535 MLFP22DP4541 MLFP22DP4550 2X4:
More informationDEMOLITION GENERAL NOTES As-built conditions have been determined from Record Drawings (if they exist), field investigations (accessible areas and
DEMOLITION GENERAL NOTES As-built conditions have been determined from Record Drawings (if they exist), field investigations (accessible areas and equipment), and discussions with maintenance personnel
More informationMaxim3 TM Series IP66. LED Vapor Tight - Waterproof Key Features
Maxim3 TM Series PROJECT NAME: CATALOG: NOTES: LED Vapor Tight - Waterproof Key Features Up to 146 IP66 87 UL 4, 5 & 8 K & K 110-277V NSF Stainless Steel Clips Operating Temp - o F to 105 o F 7 Year Warranty
More informationLUMINAIRE ID SIZE CENTER OPTICS SIDE OPTICS LIGHT SOURCE CRI LUMEN PACKAGES COLOR TEMP. VOLTAGE. LED - high performance LED 80-80CRI 90-90CRI
PROJECT: APPROVED BY: SIGNATURE: Grid - shown with a Nova flat lens Grid - shown with a Nova Slope lens TYPE QTY DESCRIPTION Nova is an efficient architectural LED troffer with a distinctive luminous shielding
More informationInstructions for completing the NE&C LIGHTING Rebate Worksheet
Instructions for completing the NE&C LIGHTING Rebate Worksheet General Note: 1. This application is for new high efficiency lighting fixtures, systems and controls. 2. All non code 10 fixture equipment
More informationNYC Approved Product Series
NYC Approved Product Series ON THE PROJECT, ON THE SHELF, ON THE JOB NYC APPROVED Table of Contents NYC Approved LED Exit & Combo Series P. 2 NYC Approved LED Battery Series P. 3 NYC Approved Total Edge
More informationC. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.
SECTION 218800 - FIRE PROTECTION 1. GENERAL A. Provisions of Division 1, GENERAL REQUIREMENTS, and Section 230000, MECHANICAL GENERAL CONDITIONS, and Section 230050, SEISMIC PROTECTION are a part of this
More informationEmery County Senior Center Green River 06/07
SECTION 260923 - LIGHTING CONTROL DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationInstallation Instructions. Tersen. Ratio Canopy 1.5
Installation Instructions Tersen TM Ratio Canopy 1.5 Ratio Canopy 1.5 tlroc15 Installation Instructions NOTE: This lighting fixture is designed for outdoor lighting services, and should not be used in
More information