SECTION WET-PIPE SPRINKLER SYSTEMS

Similar documents
SECTION WET-PIPE FIRE-SUPPRESSION SPRINKLERS

ADDENDUM NO. 3 March 19, 2018

SECTION DRY-PIPE FIRE-SUPPRESSION SPRINKLERS

May 2017 Middleton Heritage 09T SC DIVISION 21: FIRE SUPPRESSION END OF TABLE OF CONTENTS

DIVISION 21: FIRE SUPPRESSION WATER BASED FIRE SUPRESSION SYSTEMS

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

DIVISION 21 FIRE SUPPRESSION SECTION FIRE PROTECTION SPECIALTIES

THE JAMES RUSHTON EARLY LEARNING AND FAMILY SUCCESS CENTER #2616 ISSUE FOR CONSTRUCTION

West District Library Section Campeau Drive, Ottawa SPRINKLER SYSTEMS City of Ottawa Project No. CR Page 1 of 8

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

SECTION FIRE PROTECTION. A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section

SECTION SPRINKLER SYSTEMS

North Hanover Township School District North Hanover Township, New Jersey

Gas Station & C Store SECTION CWM Job No

WET-PIPE SPRINKLER SYSTEMS

SECTION DRY-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS

A. Section includes wet-pipe sprinkler system, system design, installation, and certification.

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University.

SECTION DRY-PIPE SPRINKLER SYSTEMS

SECTION AUTOMATIC SPRINKLER PIPING

B. Related Sections: The following Sections contain requirements that relate to this Section.

SECTION WET-PIPE SPRINKLER SYSTEMS

A. Standard-Pressure Piping System Component: Listed for 175-psig minimum working pressure.

MLA Architects Pierz Public Schools ISD #484 Healy High School Multi-Purpose & Choir Additions Pioneer Elementary School Class Room Addition Pierz, MN

FIRE SUPPRESSION SPRINKLER SYSTEM

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements.

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

SPRINKLERS TABLE OF CONTENTS

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL

B. Standard-Pressure Standpipe Piping: Fire-suppression standpipe piping designed to operate at working pressure 175 psig (1200 kpa) maximum.

SECTION FIRE PROTECTION

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

SECTION PREACTION SPRINKLER SYSTEMS

Mercury Plastics New Building February TABLE OF CONTENTS

ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1. The Curators of the University of Missouri

1.2 CODES AND REGULATIONS A. Sprinkler system design, equipment, materials, devices, and installation shall conform to the following:

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE

SECTION FIRE-SUPPRESSION STANDPIPES

A. All Fire Suppression System design and installation shall comply with the most current and adopted version of NFPA 13.

DIVISION 21: FIRE SUPPRESSION

DARTMOUTH COLLEGE DESIGN November 15, 2007 & CONSTRUCTION GUIDELINES

A. This Section includes the following fire-suppression piping inside the building:

TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION WATER BASED FIRE PROTECTION SYSTEMS... 5

SECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM

Port of St Helens SIA Aircraft Hanger Scappoose, OR

SECTION FIRE-SUPPRESSION PIPING

PART 1 - GENERAL SECTION FIRE PROTECTION BASIC MATERIALS AND METHODS

A. This section includes design and performance information for fire protection and suppression systems.

2016 CDM Smith All Rights Reserved July 2016 SECTION FIRE PROTECTION - SPRINKLER AND STANDPIPE SYSTEMS

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE

B. The sprinkler system shall be designed to meet the more stringent of the requirements of NFPA 13 and FM Global requirements.

Environmental Health & Safety

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 21 FIRE SUPPRESSION

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE

Addendum No. 2 to the Contract Documents

TABLE OF CONTENTS

2. Welding Materials and Procedures shall conform to the ASME Code.

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

DIVISION 21: FIRE SUPPRESSION

B. Section Identification for Fire Suppression Piping and Equipment.

SECTION WET AUTOMATIC FIRE SPRINKLER SYSTEMS

B. Galvanized-Steel-Sheet Sleeves: inch minimum thickness; round tube closed with welded longitudinal joint.

DIVISION 21 - FIRE SUPPRESSION

SECTION FIRE-SUPPRESSION SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS

New Rigby Elementary School February TABLE OF CONTENTS

Essex County College - West Essex Campus Addition And Renovations dlb # / 11-14

DIVISION 21 - FIRE SUPPRESSION

DIVISION 21: FIRE SUPPRESSION

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 21 FIRE SUPPRESSION

SECTION FIRE SUPRESSION

SECTION SPRINKLER SYSTEMS

Facility Fire-Suppression Water-Service Piping

Kenworth Sales Co. - North Las Vegas, Nevada November TABLE OF CONTENTS

DIVISION 21 FIRE PROTECTION ISSUE DATE REVISION

Division 21: FIRE SUPRESSION WET-PIPE SPRINKLER PROTECTION SYSTEM. The Academy Sept Table of Contents 1 Division 21

SECTION SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING

Model F3-80 Dry K8.0 (115 metric) Standard-Response, Standard Spray Sprinklers

UC Santa Cruz Campus Design Guide. Includes the following sections: None DESIGN REQUIREMENTS

Design and Construction Standards SECTION FIRE SUPPRESSION

Copyright 2016 AIA MasterSpec Full Length 09/16 PRODUCT MASTERSPEC LICENSED BY AVITRU, LLC TO VICTAULIC COMPANY.

SECTION WET FIRE SPRINKLER SYSTEMS

Lucy s Pizza 100% CD Specification 06/22/2018

SECTION (13900) - FIRE SUPPRESSION SYSTEMS

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM

Copyright 2016 AIA MasterSpec Full Length 09/16 PRODUCT MASTERSPEC LICENSED BY AVITRU, LLC TO VICTAULIC COMPANY.

ACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO

UMC El Paso Far East Clinic and Neighborhood Healthcare Center West Issue for Construction Page Project No and April 13, 2015

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION GENERAL-SERVICE COMPRESSED-AIR SYSTEMS

SECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

DIVISION 21: FIRE SUPPRESSION SYSTEMS SECTION Fire Protection Systems Protecting Cold Storage and Unheated Warehouses

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Fire Pump Specification

KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

University of Missouri St. Louis September 9, 2013 Recreation and Wellness Center #S

Transcription:

SECTION 21 1313 WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Includes But Not Limited To: 1. Furnish and install complete wet-pipe fire sprinkler system as specified in Contract Documents. B. Products Installed But Not Supplied Under This Section: 1. Firestopping C. Related Sections: 1. Section 07 8400: Quality of Firestopping. 2. Section 28 3123: Fire Detection and Alarm Annunciation Panels including connection of tamper switches and flow detectors to alarm system and furnishing and installing of low temperature switch. 3. Section 33 1119: Fire Suppression Utility Water Distribution Piping. 1.2 REFERENCES A. American Society For Testing And Materials: 1. ASTM A 53-02, 'Standard Specification for Pipe, Steel and Hot-Dipped, Zinc-Coated, Welded and Seamless.' 2. ASTM A 234-05, 'Standard Specification for Piping Fittings of Wrought Carbon Steel and Alloy Steel for Moderate and Elevated Temperature Service.' 3. ASTM A 395-99 (2004), Standard Specification for Ferritic Ductile Iron Pressure-Retaining Casting for Use at Elevated Temperatures. 4. ASTM A 536-84 (2004), 'Standard Specification for Ductile Iron Castings.' 5. ASTM A 795-04, Standard Specification for Black and Hot-Dipped -Coated (Galvanized) Welded and Seamless Steel Pipe for Fire Protection Use. B. American Society of Mechanical Engineers / American National Standards Institute: 1. ASME / ANSI B 16.3-1998, 'Malleable-Iron Threaded Fittings.' 2. ASME / ANSI B 16.4-1998, 'Gray Iron Threaded Fittings.' 3. ASME / ANSI B 16.5-2003, ' Pipe Flanges and Flanged Fittings NPS 1/2 Through NPS 24.' C. American Water Works Association: 1. AWWA C-606-2004, Joints, Grooved and Shoulder Type. D. National Fire Protection Association / American National Standards Institute: 1. NFPA / ANSI 13-2002, 'Installation of Sprinkler Systems.' 1.3 SUBMITTALS A. Shop Drawings: 1. Size sprinkler system by one of following methods: a. Pipe schedule method in accordance with NFPA/ANSI 13. b. Hydraulic calculation design method based on water supply evaluation performed at building site. 542-6677-08010101 1 Section 21 1313

c. On submittals, refer to sprinkler heads by sprinkler identification or model number published in appropriate agency listing or approval. Trade names and other abbreviated designations are not acceptable 2. Submittal Procedure: a. After award of Contract and before purchase of equipment, submit seven sets of shop drawings with specifications and hydraulic calculations, if pipe schedule method is not used, to Architect and two sets to local jurisdiction having authority for fire prevention for review. b. After integrating Architect's and AHJ's comments into drawings, licensed certified fire protection engineer of record submitting fire sprinkler system design construction documents shall stamp, sign, and date each sheet of shop drawings and first page of specifications and calculations. c. Submit stamped documents to Owner and to AHJ for fire prevention for final approval. d. After final approval, submit four copies of approved stamped documents to Architect. e. Failure of system to meet requirements of authority having jurisdiction shall be corrected at no additional cost to Owner. B. Closeout: 1. Operation And Maintenance Manual Data: a. Modify and add to requirements of Section 01 7800 as follows: 1) Provide master index showing items included. 2) Provide name, address, and phone number of Architect, Architect's Fire Sprinkler Consultant, General Contractor, and Fire Protection subcontractor. 3) Provide operating instructions to include: a) General description of fire protection system. b) Step by step procedure to follow in putting system into operation. 4) Maintenance instructions shall include: a) List of system components used indicating name and model of each item. b) Manufacturer's maintenance instructions for each component installed in Project. Instructions shall include installation instructions, parts numbers and lists, operation instructions of equipment, and maintenance and lubrication instructions. 5) Include copies of approved shop drawings and copies of required warranties. b. If system has both wet and dry segments, provide single Operations And Maintenance Manual for total Fire Suppression System. 2. Inspection Checklist: a. Provide Owner with checklist and brief explanation of following inspections: 1) Weekly Inspection. 2) Monthly Inspection. 3) Quarterly Inspection. 4) Semi-Annual Inspection. 5) Annual Inspection. 1.4 QUALITY ASSURANCE A. Qualifications: 1. Designer: a. Licensed fire protection engineer or fire protection system designer certified by NICET to level three minimum and engaged in design of fire protection systems. Engineer / designer shall: 1) Design system so it can be completely drained. 2) Be responsible for overseeing preparation of shop drawings, hydraulic calculations where applicable, and system installation. 3) Make complete inspection of installation including capability of being completely drained. 4) Provide corrected record drawings to Owner with letter of acceptance. 5) Certify that installation is in accordance with Contract Documents. 2. Installer: Licensed by jurisdiction having authority over installed fire protection systems for location of Project. Furnish verified list of similar projects installed during past 5 years minimum. 542-6677-08010101 2 Section 21 1313

B. Requirements of Regulatory Agencies: 1. Unless noted otherwise, system shall conform to: a. NFPA / ANSI 13-2002 'Light & Ordinary Hazard Occupancies.' b. NFPA / ANSI 24-2002 'Service Mains and Their Appurtenances, Private.' c. NFPA / ANSI 101-2000 'Life Safety Code.' d. Requirements of local water department and local authority having jurisdiction for fire protection. e. Applicable rules, regulations, laws, and ordinances. f. Underwriter's Laboratories Publication, 'Fire Protection Equipment Directory', current edition at time of Pre-Bid Meeting. g. Comply with backflow prevention requirements and, if required, include device in hydraulic calculations. 1.5 OWNER'S INSTRUCTIONS A. Instruction Sessions: 1. Instruct Owner's personnel in operation and maintenance of system utilizing Operation And Maintenance Manual when so doing. Minimum instruction period shall be four hours. 2. Instruction sessions shall occur after Substantial Completion inspection when system is properly working and before final payment is made. B. Posted System Diagram: 1. Provide single, color-coded floor plan diagram showing total system. Color dry pipe system elements BLUE and wet pipe system elements RED. Indicate locations of dry pipe system drains and inspector test valve station. 2. Include following information on diagram sheet: a. Explanation of principles behind operation of dry pipe system alarm valve. b. Step by step shut down procedure. c. Step by step system drainage procedure. d. Step by step start-up procedure. e. Step by step procedure for protection of system from freezing. 3. Laminate diagram with plastic and mat or frame suitable for hanging near riser. 1.6 MAINTENANCE A. Extra Materials: Furnish twelve spare heads of each type and temperature rating used, properly boxed with sprinkler head wrench. PART 2 - PRODUCTS 2.1 COMPONENTS A. General: Use only domestically manufactured pipe, pipe fittings, valves, sprinkler heads, and other components. B. Pipe 1. Schedule 40 Welded Steel a. Exterior, Above Ground: Schedule 40 hot-dip galvanized welded steel meeting requirements of ASTM A 53 or ASTM A 795. b. Interior, Above Ground: Schedule 40 black welded steel meeting requirements of ASTM A 53 or ASTM A 795. 2. Schedule 40 Mechanical Grooved Pipe And Fittings: Mechanical grooved pipe, couplings, and fittings by Victaulic. 3. Grooved Coupling Gaskets: a. Class Two Quality Standard: 542-6677-08010101 3 Section 21 1313

1) Victaulic E EPDM-Type A, Grade, temperature rated minus 30 deg F to 150 deg Fminus one deg C to 65 deg C. C. Fittings: 1. Usage: a. 2 inches 50 mm And Smaller: Welded, screwed, flanged, or roll grooved coupling system. At Contractor s option, piping 1-1/4 inches 32 mm and smaller, may be Victaulic FIT locking lug fittings with pressure responsive gasket. For use with schedule 40 carbon steel pipe. b. 2-1/2 inches 63 mm And Larger: Welded, flanged, or roll grooved coupling system. 2. Types And Quality: a. Screwed: 1) Cast iron meeting requirements of ANSI B 16.4 or ductile iron meeting requirements of ANSI B 16.3 and ASTM A 536, Grade 65-45-12. 2) Threaded fittings and pipe shall have threads cut to ANSI B1.20.1. a) Do not extend pipe into fittings to reduce waterway. b) Ream pipe after cutting to remove burrs and fins. b. Flanged: Steel meeting requirements of ANSI B16.5. c. Welded: 1) Carbon steel meeting requirements of ASTM A 234. 2) Weld pipe using methods complying with AWS D10.9, level AR-3. Welding procedures and performance of welders shall comply with ASW D10.9, level AR3. d. Roll Grooved Pipe Coupling System: 1) Ductile iron meeting requirements of ASTM A 395 and ASTM A 536, and UL listed and FM approved. 2) Couplings: a) UL listed and FM approved. b) Rigid: (1) Cast to provide rigidity for support and hanging in accordance with NFPA-13. (2) Category Four Approved Products. See Section 01 6200 for definition of Categories. (a) Gruvlok 7401. (b) Tyco (Grinnell) 772 (c) Victaulic Style 005. c) Flexible: (1) Use in locations where vibration attenuation and stress relief are required. (2) Category Four Approved Products. See Section 01 6200 for definition of Categories. (a) Gruvlok 7000. (b) Tyco (Grinnell) 705 (a) Victaulic Style 75. d) Flange Adapters: (1) Class 125 or 150. (2) Category Four Approved Products. See Section 01 6200 for definition of Categories. (a) Gruvlok 70R. (b) Tyco (Grinnell) 71 (a) Victaulic Style 744. 3) Grooved products used on Project shall be from same manufacturer. Grooving tools shall be as recommended by manufacturer of grooved products. D. Hangers, Rods, And Inserts 1. Galvanized, unless specified otherwise, and UL approved for service intended. 2. Class One Quality Standard: a. Hangers and accessories shall be Anvil numbers specified or equals by B-Line. b. Clevis Hangers: Equal to Anvil Fig 65. c. Roller Assembly: Equal to Anvil Fig 181. d. Riser Clamps: Equal to Anvil Fig. 40. 3. Concrete Inserts: 542-6677-08010101 4 Section 21 1313

a. Equal to Anvil Fig 282. Suitable for special nuts size 3/8 inch10 mm through 7/8 inch22 mm, with yoke to receive concrete reinforcing rods, and with malleable iron lugs for attaching to forms. b. Continuous Inserts: 1) Class Two Quality Standard. See Section 01 6200. (1) Unistrut P-3246 through P-3270. 4. Steel Deck Bracket: a. Class Two Quality Standard. See Section 01 6200. 1) Unistrut P1000 with clamp nut, minimum 6 inch150 mm length. E. Valves: 1. Butterfly Valves: a. UL / FM approved. b. Indicating type. c. Category Four Approved Products. See Section 01 6200 for definitions of Categories. 1) Milwaukee: a) Model BB-SC502 threaded ends with tamper switch One to 2 inches. b) Model BBVSC502 Grooved ends with tamper switch 2 to 2-1/2 inches. 2) Nibco: a) Model WD3510-8 Wafer type with valve tamper switch. b) Model GD4765-8N Grooved type with valve tamper switch, 2-1/2 to 8 inches. 3) Tyco (Grinnell): a) Model TFP1515 wafer. b) Model TFP1510 Grooved. 4) Victaulic: Series 705W Grooved end type with internal supv. switches. 2. Gate Valves: a. UL / FM approved. b. Outside Screw and Yoke Type (O.S.&Y). c. Class 150 psi. 1) Nibco: a) T-1040 with Threaded Ends 1/2 to 2 inches. b) F-637-31 Flanged Ends. 2) Mueller: R-2360-6 Flanged Ends. 3) Victaulic: Series 771 Grooved Ends 3. Ball Valves: a. UL / FM approved. b. Valve tamper switch. c. Category Four Approved Products. See Section 01 6200 for definitions of Categories. 1) Milwaukee: BB-SC502 with threaded ends. 2) Nibco: KT-505 with threaded ends. 3) Nibco: KG-505 with grooved ends. 4) Victaulic: Series 728 with grooved or threaded ends. 4. Swing Check Valves: a. 1/2 to 3 inch 13 to 75 mm horizontal check. 1) Regrinding type. 2) Renewable disk. 3) Bronze Class 125 with threaded ends. 4) Category Four Approved Products. See Section 01 6200 for definitions of Categories. a) Nibco: KT-403-W. b) Victaulic: Series 712. b. 2 to 4 inch 50 to 100 mm Horizontal check: 1) Grooved ends.. 2) Ductile iron body. 3) Rated 300 psi. 4) Category Four Approved Products. See Section 01 6200 for definitions of Categories. a) Tyco (Grinnell): CV-1F Grooved ends. b) Victaulic: Series 712. c) Viking: D-1 Grooved ends. c. 2-1/2 to 12 inch 63 to 300 mm Horizontal check: 542-6677-08010101 5 Section 21 1313

1) Bolted bonnet. 2) Raised face flanges. 3) Bronze mounted with ductile iron body. 4) 125 lb Class A. 5) Category Four Approved Products. See Section 01 6200 for definitions of Categories. a) Nibco: F-938-31. b) Mueller: A-2120-6. c) Tyco (Grinnell) CV-2 grooved and flanged. d) Viking: G-1 grooved and flanged 5. Wafer Type Check Valves: a. 4 to 8 inch 100 to 300 mm cast iron body. b. 175 psi 1200 KPa minimum working pressure. c. Rubber Seat. 1) Nibco: KW-900-W. 2) Mueller: A-2102. 6. Grooved-End Check Valves: a. UL listed and FM approved to 250 psi 1725 kpa maximum operating pressure. b. 2-1/2 to 12 inch 63 to 300 mmductile iron body. c. Disc And Seat: 1) 2-1/2 And 3 Inch 63 to 75 mm: Aluminum bronze disc with mounted elastomer seal and PPS (polyphenylene sulfide) coated seat. 2) 4 Inch 100 mm And Larger: Elastomer encapsulated ductile iron disc with welded in nickel seat. 1) Nibco: KG-900-W grooved ends 2) Victaulic Series 717. 7. Alarm Check Valves: a. Category Four Approved Products. See Section 01 6200 for definitions of Categories. 1) Reliable: E with gauges and drain. 2) Tyco (Grinnell): Model AV-1-300. 3) Victaulic: Series 751 with gauges and drain. 4) Viking: J-1 with gauges and drain. 8. Backflow Preventer: Make and model shown on Drawings or as required by local codes. 9. Retard Chamber: a. Self-draining. b. Category Four Approved Products. See Section 01 6200 for definitions of Categories. 1) Reliable: E-1. 2) Victaulic: Series 752. 3) Viking: C-1. 10. Inspector's Test Valve: a. Bronze body with threaded or grooved ends. b. Combination sight glass / orifice. c. Category Four Approved Products. See Section 01 6200 for definitions of Categories. 1) Tyco (Grinnell): Model F350. 2) Victaulic: Testmaster Alarm Test Module Style 720. F. Sprinkler Heads: 1. Concealed Pendant: a. Adjustable cover. b. Coordinate concealed cover finish with Architect. c. Type One Acceptable Products: 1) Wet Pendant, Flat Profile: a) Reliable: F4FR. b) Victaulic: Model 3810. c) Viking: Model VK462. d) Tyco (Grinnell): Model RF11. e) Equal as approved by Architect before bidding. See Section 01 6200. 2) Dry Pendant: a) Flat Profile: 542-6677-08010101 6 Section 21 1313

(1) Tyco (Grinnell): DS-C. (2) Victaulic: V3618. b) Equal as approved by Architect before bidding. See Section 01 6200. 2. Horizontal Sidewall Sprinkler: b. Recess adjustable. c. Where guards are required, use chrome plated sprinkler guards that are listed, that are approved by Sprinkler Manufacturer for use with head, and that are supplied by Sprinkler Manufacturer. d. Type One Acceptable Products: 1) Wet System: a) Reliable: F1FR. b) Tyco (Grinnell): Model TY3331. c) Victualic: Model V2710. d) Viking: VK305. e) Equal as approved by Architect before bidding. See Section 01 6200. 2) Dry System: a) Reliable: F3. b) Tyco (Grinnell): TY3338. c) Victualic: Model V3610. d) Viking: VK162. e) Equal as approved by Architect before bidding. See Section 01 6200. 3. Attic Sprinklers, Upright: b. Approved for use in roof structures, combustible and non-combustible, with ceiling below. c. Category Four Approved Products. See Section 01 6200 for definitions of Categories. 1) Tyco: BB, SD, or HIP. 4. Pendant Sprinklers: b. Where guards or escutcheons are required, use chrome plated sprinkler guards and escutcheons that are listed, that are approved by Sprinkler Manufacturer for use with head, and that are supplied by Sprinkler Manufacturer. c. Type One Acceptable Products: 1) Reliable: F1FR. 2) Tyco: TY3231. 3) Victaulic: Model V2726. 4) Viking: VK302. 5) Equal as approved by Architect before bidding. See Section 01 6200. 5. Upright Sprinklers: b. Type One Acceptable Products: 1) Reliable: F1FR. 2) Tyco: TY3331. 3) Victaulic: Models V2704. 4) Viking: VK300. 5) Equal as approved by Architect before bidding. See Section 01 6200. G. Water Flow Alarm: 1. Mechanical Flow Alarm: Water Gong. b. Category Four Approved Products. See Section 01 6200 for definitions of Categories. 1) Reliable: C. 2) System Sensor: SSV 120 or SSM 24 Series. 3) Tyco: WMA-1. 4) Victaulic: Series 760. 5) Viking: F-2. H. Pressure Gauges: 1. Mechanical Water Pressure Gauges: 542-6677-08010101 7 Section 21 1313

b. 3-1/2 inch 88 mm diameter dial. c. 0 to 300 psi0 to 2 000 KPa in 5 psi50 Kpa increments. 1) Reliable: UA. 2) HO Trerice: 500. 3) Viking: 01124A. I. Waterflow Detectors: 1. Electrical Water Flow Switch: a. UL / FM approved. b. Switch activates with flow of 10 gpm or more. c. Two single pole double throw switches. d. Automatic reset. e. Category Four Approved Products. See Section 01 6200 for definitions of Categories. 1) Potter-Roemer: Model 6201-6208. 2) System Sensor: WFD. 3) Viking: VSR-F and VS-SP. J.Tamper Switch 1. Weather and Tamper Resistant Switch. a. UL listed and FM approved. b. Two Single Pole Double Throw Switches, contact rating 5 amps at 120 VAC. c. Removal of switch or cover shall activate trouble signal. d. Alarm shall activate between first and second revolution of valve wheel. e. Mount to monitor valve and not interfere with operation. f. Shall operate in horizontal and vertical position. g. Category Four Approved Products. See Section 01 6200 for definitions of Categories. 1) Control Valves, Butterfly Valves, Post Indicator Valves: a) Federal: Model PIV b) Potter-Roemer: Model 6223 c) Notifier: Model PIBV2 d) System Sensor: Model PIBV2. 2) O.S. & Y Valves: a) Federal: Model OSY b) Notifier: Model OSY2 c) Potter-Roemer: Model 6220 d) System Sensor: Model OSY2 K. Automatic Drain Device: 1. Straight Design, 3/4 inch19 mm. 2. Category Four Approved Products. See Section 01 6200 for definitions of Categories. a. Nibco: Ball-Drip. b. Potter-Roemer: Figure 5982. c. Viking: B-1 L. Fire Department Connection: 1. Two-way Inlet with single clapper. 2. Polished Brass. 3. Class One Quality Standards. See Section 01 6200. a. Round 'AUTO SPKR' identification plate, polished brass by Potter-Roemer Fig. 5962. 4. Category Four Approved Products. See Section 01 6200 for definitions of Categories. a. Croker: 6405-PB. b. Potter-Roemer: Fig. 5710. M. Post Indicating Valve: 1. Polished brass. 2. Supervisory switch. 3. Category Four Approved Products. See Section 01 6200 for definitions of Categories. a. As required by Authority Having Jurisdiction (AHJ). 542-6677-08010101 8 Section 21 1313

N. Propylene Glycol: 1. Category Four Approved Product. See Section 01 6200 for definition of Categories. a. Dow Frost by Dow Chemical. 2.2 MANUFACTURERS A. Contact Information: 1. Anvil International, Portsmouth, NH www.anvilintl.com. 2. Croker Corp, Elmsford, NY www.croker.com. 3. Dow Chemical, Midland, MI www.dow.com. 4. Gruvlock by Anvil International, Portsmouth, NH www.anvilintl.com. 5. HO Trerice Company, Oak Park, MI www.hotco.com 6. Milwaukee Valve Co, Milwaukee, WI www.milwaukeevalve.com. 7. Mueller Company, Decatur, IL www.muellerflo.com. 8. Nibco Inc, Elkhart, IN www.nibco.com. 9. Potter-Roemer, Cerritos, CA www.potterroemer.com. 10. Reliable Automatic Sprinkler Co, Mount Vernon, NY www.reliablesprinkler.com. 11. System Sensor, St Charles, IL www.systemsensor.com. 12. TYCO Fire & Building Products, Oak Creek, WI www.tyco-fire.com. 13. Victualic Company of America, Easton, PA or Victualic Company of Canada, Rexdale, ON www.victaulic.com. 14. Viking Corp, Hastings, MI www.vikingcorp.com. PART 3 - EXECUTION 3.1 EXAMINATION A. Drawings: 1. Fire Protection Drawings show general arrangement of piping. Follow as closely as actual building construction and work of other trades will permit. Install system so it can be completely drained as designed. 2. Consider Architectural and Structural Drawings part of this work insofar as these drawings furnish information relating to design and construction of building. These Drawings take precedence over Fire Protection Drawings. 3. Because of small scale of Drawings, it is not possible to indicate all offsets, fittings, and accessories that may be required. Investigate structural and finish conditions affecting this work and arrange work accordingly, providing such fittings, valves, and accessories required to meet conditions and to enable system to be completely drained. 3.2 INSTALLATION A. Interface With Other Work: Provide inserts for attaching hangers in concrete floor construction at time floors are placed. B. Connect system to flange provided under Section 33 1119. C. Install sprinkler systems in accordance with requirements of latest editions of NFPA 13, FM Global, and as specified below: 1. Install to enable complete drainage of system. Drain trapped piping in accordance with NFPA 13, Paragraph 8.15.2.5 and 8.16.4.1. a. Install main drain from riser. b. Install auxiliary drains in low points of piping system and inspector's test valve drain to mechanical pad located outside building unless otherwise directed by Architect. 2. Install piping system so it will not be exposed to freezing temperatures. 3. Do not use dropped, damaged, or used sprinkler heads. 542-6677-08010101 9 Section 21 1313

4. Install sprinkler lines concealed. 5. Install tamper switches and flow detectors where located by Architect. 6. Install automatic ball drip device in lowest point of piping to fire department connection and drain to floor drain or to exterior of building. 7. Brace and support system to meet seismic zone requirements for building site. 8. Incorporate provisions for manual introduction of propylene glycol mixture into antifreeze loop system at highest point. Prepare and introduce into system mixture of water and propylene glycol at concentration appropriate for winter design conditions. a. Propylene Glycol Winter Design Percent by Weight Temp 10 percent 27 Deg F 15 percent 19 Deg F 20 percent 17 Deg F 25 percent 11 Deg F 30 percent 5 Deg F 35 percent minus 3 Deg F 40 percent minus 11 Deg F 45 percent minus 23 Deg F 50 percent minus 41 Deg F 55 percent minus 60 Deg F D. Flush system at full design flow rate for minimum five minutes. Route water to outside of building. Protect landscaping and other exterior elements from damage during flow tests. 3.3 FIELD QUALITY CONTROL A. Site Tests: 1. Test system according to 'Contractor's Material And Testing certificate for Above Ground Piping' NFPA-13, figure 16.1. 2. Tests shall be witnessed by Architect and representative of local jurisdiction over fire prevention. 3. Test blanks shall have red painted lugs protruding beyond flange to clearly indicate their presence and be numbered to assure their removal when testing is completed. END OF SECTION 542-6677-08010101 10 Section 21 1313

SECTION 21 1316 DRY-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Includes But Not Limited To: 1. Furnish and install complete fire sprinkler system as specified in Contract Documents. B. Products Installed But Not Supplied Under This Section: 1. Firestopping. C. Related Sections 1. Section 07 8400: Quality of Firestopping. 2. Section 28 3123: Fire Detection and Alarm Annunciation Panels including connection of tamper switches and pressure flow detectors to alarm system and furnishing and installing of low temperature switch. 3. Section 33 1119: Fire Suppression Utility Water Distribution Piping. 1.2 REFERENCES A. American Society For Testing And Materials: 1. ASTM A 53-02, 'Standard Specification for Pipe, Steel and Hot-Dipped, Zinc-Coated, Welded and Seamless.' 2. ASTM A 234-05, 'Standard Specification for Piping Fittings of Wrought Carbon Steel and Alloy Steel for Moderate and Elevated Temperature Service.' 3. ASTM A 395-99 (2004), Standard Specification for Ferritic Ductile Iron Pressure-Retaining Casting for Use at Elevated Temperatures. 4. ASTM A 536-84 (2004), 'Standard Specification for Ductile Iron Castings.' 5. ASTM A 795-04, Standard Specification for Black and Hot-Dipped -Coated (Galvanized) Welded and Seamless Steel Pipe for Fire Protection Use. B. American Society of Mechanical Engineers / American National Standards Institute: 1. ASME / ANSI B 16.1-1998, 'Cast Iron Pipe Flanges and Flanged Fittings, Class 25, 125, 250, and 800.' 2. ASME / ANSI B 16.3-1998, 'Malleable-Iron Threaded Fittings.' 3. ASME / ANSI B 16.4-1998, 'Gray Iron Threaded Fittings.' C. National Fire Protection Association / American National Standards Institute: 1. NFPA / ANSI 13-2002, 'Installation of Sprinkler Systems.' 1.3 SUBMITTALS A. Shop Drawings: 1. Size sprinkler system by one of following methods: a. Pipe schedule method in accordance with NFPA / ANSI 13. b. Hydraulic calculation design method based on water supply evaluation performed at building site. 542-6677-08010101 1 Section 21 1316 Hickory Flat, Canton Wards June 10, 2009 (Rev) Dry-Pipe Sprinkler Systems

c. On submittals, refer to sprinkler heads by sprinkler identification or model number published in appropriate agency listing or approval. Trade names and other abbreviated designations are not acceptable. 2. Submittal Procedure: a. After award of Contract and before purchase of equipment, submit seven sets of shop drawings with specifications and hydraulic calculations, if pipe schedule method is not used, to Architect and two sets to local jurisdiction having authority for fire prevention for review. b. After integrating Architect's and local jurisdiction's comments into drawings, licensed certified fire protection engineer of record submitting fire sprinkler system design construction documents shall stamp, sign, and date each sheet of shop drawings and first page of specifications and calculations. c. Submit stamped documents to area office and local jurisdiction having authority for fire prevention for final approval. d. After final approval, submit four copies of approved stamped documents to Architect. e. Failure of system to meet requirements of authority having jurisdiction shall be corrected at no additional cost to Owner. B. Closeout: 1. Operation And Maintenance Manual Data: a. Modify and add to requirements of Section 01 7800 as follows: 1) Provide master index showing items included. 2) Provide name, address, and phone number of Architect, Architect's Fire Sprinkler Consultant, General Contractor, and Fire Protection subcontractor. 3) Provide operating instructions to include: a) General description of fire protection system. b) Step by step procedure to follow in putting system into operation. 4) Maintenance instructions shall include: a) List of system components used indicating name and model of each item. b) Manufacturer's maintenance instructions for each component installed in Project. Instructions shall include installation instructions, parts numbers and lists, operation instructions of equipment, and maintenance and lubrication instructions. 5) Include copies of approved shop drawings and copies of required warranties. b. If system has both wet and dry segments, provide single Operations And Maintenance Manual for total Fire Suppression System. 2. Inspection Checklist: a. Provide Owner with checklist and brief explanation of following inspections: 1) Weekly Inspection. 2) Monthly Inspection. 3) Quarterly Inspection. 4) Semi-Annual Inspection. 5) Annual Inspection. 1.4 QUALITY CONTROL A. Qualifications: a. Licensed fire protection engineer or fire protection system designer certified by NICET to level three minimum and engaged in design of fire protection systems. Engineer / designer shall: 1) Be responsible for overseeing preparation of shop drawings, hydraulic calculations where applicable, and system installation. 2) Make complete inspection of installation. 3) Provide corrected record drawings to Owner with letter of acceptance. 4) Certify that installation is in accordance with Contract Documents. 2. Installer: Licensed by jurisdiction over installed fire protection systems for area of Project. Furnish verified list of similar projects installed during past five years minimum. B. Requirements of Regulatory Agencies: 1. Unless noted otherwise, system shall conform to: 542-6677-08010101 2 Section 21 1316 Hickory Flat, Canton Wards June 10, 2009 (Rev) Dry-Pipe Sprinkler Systems

a. NFPA / ANSI 13-2002 'Light & Ordinary Hazard Occupancies.' b. NFPA / ANSI 24-2002 'Service Mains and Their Appurtenances, Private.' c. NFPA / ANSI 101-2000 'Life Safety Code.' d. Requirements of local water department and local authority having jurisdiction for fire protection. e. Underwriter's Laboratories Publication, 'Fire Protection Equipment Directory', current edition at time of Pre-Bid Meeting. f. Comply with backflow prevention requirements and, if required, include device in hydraulic calculations. g. Applicable rules, regulations, laws, and ordinances. 1.5 OWNER'S INSTRUCTIONS A. Instruction Sessions: 1. Instruct Owner's personnel in operation and maintenance of system utilizing Operation And Maintenance Manual when so doing. Minimum instruction period shall be four hours. 2. Instruction sessions shall occur after Substantial Completion inspection when system is properly working and before final payment is made. B. Posted System Diagram: 1. Provide single, color-coded floor plan diagram showing total system. Color dry pipe system elements BLUE and wet pipe system elements RED. Indicate locations of dry pipe system drains and inspector test valve station. 2. Include following information on diagram sheet: a. Explanation of principles behind operation of dry pipe system alarm valve. b. Step by step shut down procedure. c. Step by step system drainage procedure. d. Step by step start-up procedure. e. Step by step procedure for protection of system from freezing. 3. Laminate diagram with plastic and mat or frame suitable for hanging near riser. 1.6 MAINTENANCE A. Extra Materials: Furnish six spare heads of each type and temperature rating used, stored in cabinet properly sized by Sprinkler Manufacturer, and sprinkler head wrench. PART 2 - PRODUCTS 2.1 COMPONENTS A. General: Use only domestically manufactured pipe, pipe fittings, valves, sprinkler heads, and other components. B. Pipe: 1. Above Ground: Schedule 40 hot-dip galvanized welded steel meeting requirements of ASTM A 53. a. 2 Inches 50 mm And Smaller: Screwed, flanged, or roll grooved coupling system. b. 2-1/2 Inches 62 mm And Larger: Flanged or roll grooved coupling system. C. Fittings 1. Screwed: Cast iron meeting requirements of ANSI B 16.4 or ductile iron meeting requirements of ANSI B 16.3 and ASTM A 536, Grade 65-45-12. 2. Flanged: Cast iron meeting requirements of ANSI B 16.1. 3. Roll Grooved Pipe Coupling System: 542-6677-08010101 3 Section 21 1316 Hickory Flat, Canton Wards June 10, 2009 (Rev) Dry-Pipe Sprinkler Systems

a. Ductile iron meeting requirements of ASTM A 395 and ASTM A 536, and UL listed and FM approved. b. Couplings: 1) Rigid: a) Cast to provide rigidity for support and hanging in accordance with NFPA-13. b) Category Four Approved Products. See Section 01 6200 for definition of categories. (1) Gruvlok: 7401. (2) Tyco (Grinnell): 772 (3) Victaulic: Style 005. 2) Flexible: a) Use in locations where vibration attenuation and stress relief are required. b) Category Four Approved Products. See Section 01 6200 for definition of categories. (1) Gruvlok: 7000. (2) Tyco (Grinnell): 705 (3) Victaulic: Style 75. 3) Flange Adapters: a) Class 125 or 150. b) Category Four Approved Products. See Section 01 6200 for definition of categories. (1) Gruvlok: 7012. (2) Tyco (Grinnell): 71 (3) Victaulic: Style 744. c. Grooved products used on Project shall be from same manufacturer. Grooving tools shall be as recommended by manufacturer of grooved products. D. Valves: 1. Butterfly Valves: a. UL / FM / CASA approved. b. Indicating type. c. Category Four Approved Products. See Section 01 6200 for definitions of Categories. 1) Milwaukee: a) Model BB-SC502 threaded ends with tamper switch One to 2 inches. b) Model BBV SC502 Grooved ends with tamper switch 2 to 2-1/2 inches. 2) Mueller: a) Model B-3250-00 wafer type with tamper switch. b) Model 3250-52 grooved end type with tamper switch. 3) Nibco: a) WD3510-4 Wafer type with valve tamper switch. b) GD4765-8N Grooved type with valve tamper switch, 2-1/2 to 8 inches. 4) Tyco (Grinnell): a) Model TFP1515 wafer. b) Model TFP1510 Grooved. 5) Victaulic: Series 705-W Grooved end type with internal supervisory switches. 2. Gate Valves: a. UL / FM / CASA approved. b. Outside Screw and Yoke Type (O.S.&Y). c. Class 150 psi. 1) Nibco: a) T-1040 with Threaded Ends 1/2 to 2 inches. b) F-637-31 Flanged Ends. 2) Mueller: R-2360-6 Flanged Ends. 3) Victaulic: Series 771 Grooved Ends 3. Ball Valves: a. UL / FM / CASA approved. b. Valve tamper switch. c. Category Four Approved Products. See Section 01 6200 for definitions of Categories. 1) Milwaukee: BB-SC502 with threaded ends. 542-6677-08010101 4 Section 21 1316 Hickory Flat, Canton Wards June 10, 2009 (Rev) Dry-Pipe Sprinkler Systems

2) Nibco: a) KT-505 with threaded ends. b) KG-505 with grooved ends. 3) Victaulic: Series 728 with grooved or threaded ends. 4. Swing Check Valves: a. 2 to 4 inch 25 to 100 m, groved ends, ductile iron, 300 psi. 1) Regrinding type. 2) Renewable disk. 3) Bronze Class 125 with threaded ends. 4) Category Four Approved Products. See Section 01 6200 for definitions of Categories. a) Nibco: KT-403-W. b) Tyco (Grinnell): CV-1F grooved ends. c) Victaulic: 712 d) Viking: D-1 grooved ends. b. 2-1/2 to 12 inch 63 to 300 mm Horizontal check: 1) Bolted bonnet. 2) Raised face flanges. 3) Bronze mounted with ductile iron body. 4) 125 lb Class A. 5) Category Four Approved Products. See Section 01 6200 for definitions of Categories. a) Nibco: F-938-31. b) Mueller: A-2120-6. c) Tyco (Grinnell): CV-2 grooved and flanged. d) Viking: G-1 grooved and flanged. 5. Wafer Type Check Valves: a. 4 to 8 inch 100 to 300 mm cast iron body. b. 175 psi minimum working pressure. c. Rubber Seat. 1) Nibco: KW-900-W. 2) Mueller: A-2102. 6. Grooved-End Check Valves: a. 2-1/2 to 12 inch 63 to 300 mmductile iron body. b. 250 psi maximum working pressure. c. Disc And Seat: 1) 2-1/2 And 3 Inch 63 to 75 mm: Aluminum bronze disc with mounted elastomer seal and PPS (polyphenylene sulfide) coated seat. 2) 4 Inch 100 mm And Larger: Elastomer encapsulated ductile iron disc with welded in nickel seat. 1) Victaulic Series 717. 7. Dry Pipe Alarm Valves: a. Category Four Approved Products: 1) Reliable: D with gauges, drain, and trim. 2) Tyco: DPV-1. 3) Victaulic: Series 756. 4) Viking: F-1 with gauges, drain, and trim. 8. Air Maintenance Device: a. Maximum inlet air pressure 125 psi, minimum outlet air pressure 65 psi. b. Category Four Approved Products. See Section 01 6200 for definitions of Categories. 1) Reliable: B-1. 2) Tyco: AHD-1. 3) Victaulic: 757P. 4) Viking: D-2. 9. Accelerator: a. Install with pressure gauge. b. Category Four Approved Products. See Section 01 6200 for definitions of Categories. 1) Reliable: B-1. 2) Tyco: AMD-1. 3) Victaulic: 757P. 542-6677-08010101 5 Section 21 1316 Hickory Flat, Canton Wards June 10, 2009 (Rev) Dry-Pipe Sprinkler Systems

4) Viking: E-1. 10. Inspector's Test Valve: a. Combination sight glass/orifice. b. Bronze top works. c. Category Four Approved Products. See Section 01 6200 for definitions of Categories. 1) Tyco (Grinnell): Model F350. 2) Victaulic: Testmaster II Alarm Test Module Style 720. E. Sprinkler Heads: 1. Dry Concealed Pendant: b. Coordinate concealed cover finish with Architect. c. Flush Ceiling profile. d. Adjustable cover. e. Type One Acceptable Products: 1) Flat Profile: a) Tyco (Grinnell) DS-2 b) Victaulic: Model V3618. c) Equal as approved by Architect before Bidding. See Section 01 6200. 2. Upright Sprinklers: b. Include flush chrome escutcheon equal to Reliable C. c. Where guards are required, include chrome plated sprinkler guards that are listed, that are approved by Sprinkler Manufacturer for use with head, and that are supplied by Sprinkler Manufacturer. 1) Reliable: F1FR. 2) Tyco: TY3131. 3) Victaulic: Models V2704. 4) Viking: VK300. 3. Attic Sprinklers, Upright: b. Approved for use in roof structures, combustible and non-combustible, with ceiling below. c. Category Four Approved Products. See Section 01 6200 for definitions of Categories. 1) Tyco: BB, SD, or HIP. 4. Horizontal Sidewall Sprinkler: b. Recessed escutcheon. c. Where guards are required, include chrome-plated guard equal to Viking A-1. 1) Reliable: F3. 2) Tyco (Grinnell): TY3338. 3) Victaulic: V3610 4) Viking: VK162. F. Water Flow Alarm: 1. Mechanical Flow Alarm: b. Category Four Approved Products. See Section 01 6200 for definitions of Categories. 1) Reliable: C. 2) System Sensor: WFD. 3) Tyco: WMA-1. 4) Victaulic: Series 760. 5) Viking: F-2. G. Pressure Gauges: 1. Mechanical Water Pressure Gauges: b. 3-1/2 inch 88 mm diameter dial. 542-6677-08010101 6 Section 21 1316 Hickory Flat, Canton Wards June 10, 2009 (Rev) Dry-Pipe Sprinkler Systems

c. 0 to 300 psi in 5 psi increments. 1) Reliable: UA. 2) H O Trerice: 500. 3) Viking: 01124A H. Pressure Detectors: 1. Electrical Water Pressure Switch: b. Switch activates on pressure rise between 4 and 8 psi. c. Two single pole double throw switches. d. Automatic reset. e. Category Four Approved Products. See Section 01 6200 for definitions of Categories. 1) Potter Electric Signal Co: PS10. 2) System Sensor: EPS10. I. Low Pressure Supervisory Switch: 1. UL listed and approved. 2. Adjustable pressure range 1 to 100 psi. 3. Automatic reset. 4. Factory adjusted to separate on pressure decrease of 30 psi. 5. Category Four Approved Products. See Section 01 6200 for definitions of Categories. a. Potter Electric Signal Co: PS40-1. b. System Sensor: EPS10. J. Tamper Switch: 1. Weather and tamper resistant switch. 2. UL listed and approved. 3. Two single pole double throw switches. 4. Category Four Approved Products. See Section 01 6200 for definitions of Categories. a. Potter Electric Signal Co: PCVS. b. System Sensor: P1BV2. K. Fire Department Connection: 1. Two-way Inlet with single clapper. 2. Polished Brass. 3. 3/4 inch 19 mm Straight Design Automatic Drain Device by Potter-Roemer Fig. 5982. 4. Round 'AUTO. SPKR.' Identification Plate, Polished Brass by Potter-Roemer Fig. 5962. 5. Category Four Approved Products. See Section 01 6200 for definitions of Categories. a. Croker: 6405PB. b. Potter-Roemer: Fig 5710. L. Air Compressor: 1. Tank-mounted, 20 gallon 70 liter tank. ASME coded industrial receiver and safety valve. 2. Set tank-mounted air compressor on neoprene isolation pads located at each corner and sized 4 inches by 4 inches by 3/4 inches 100 mm by 100 mm by 19 mm high. 3. Wire air compressor to circuit breaker. 4. Furnish with air intake filter and silencer. 5. Overload protected 1750 RPM motor. One hp, single phase, 115V. 6. Industrial grade with OSHA compliant enclosed belt guard. 7. Auto control group mounted and pre-wired. Auto group includes pressure switch, check valve, manifold, safety valve, and mounting. 8. Type One Acceptable Products: a. Model LT900150 by General Air Products. b. Equal as approved by Architect before bidding. See Section 01 6200. 542-6677-08010101 7 Section 21 1316 Hickory Flat, Canton Wards June 10, 2009 (Rev) Dry-Pipe Sprinkler Systems

2.2 MANUFACTURERS A. Contact Information: 1. Anvil International, Portsmouth, NH www.anvilintl.com. 2. Croker Corp, Elmsford, NY www.croker.com. 3. Gruvlock by Anvil International, Portsmouth, NH www.anvilintl.com. 4. General Air Products, Exton, PA www.generalairproducts.com. 5. H O Trerice Company, Oak Park, MI www.hotco.com. 6. Merit Manufacturing Corp, Pottstown, PA www.meritmfg.com. 7. Milwaukee Valve Co, Milwaukee, WI www.milwaukeevalve.com. 8. Mueller Company, Decatur, IL www.muellerflo.com. 9. Nibco Inc, Elkhart, IN www.nibco.com. 10. Potter Electric Signal Co, St Louis, MO www.pottersignal.com. 11. Potter-Roemer, Cerritos, CA www.potterroemer.com. 12. Reliable Automatic Sprinkler Co, Mount Vernon, NY www.reliablesprinkler.com. 13. System Sensor, St Charles, IL www.systemsensor.com. 14. TYCO Fire & Building Products, Oak Creek, WI www.tyco-fire.com. 15. Victualic Company of America, Easton, PA or Victualic Company of Canada, Rexdale, ON www.victaulic.com. 16. Viking Corp, Hastings, MI www.vikingcorp.com. PART 3 - EXECUTION 3.1 EXAMINATION A. Drawings: 1. Fire Protection Drawings show general arrangement of piping. Follow as closely as actual building construction and work of other trades will permit. 2. Consider Architectural and Structural Drawings part of this work insofar as these drawings furnish information relating to design and construction of building. These drawings take precedence over Fire Protection Drawings. 3. Because of small scale of Drawings, it is not possible to indicate all offsets, fittings, and accessories that may be required. Investigate structural and finish conditions affecting this work and arrange work accordingly, providing such fittings, valves, and accessories required to meet conditions. 3.2 INSTALLATION A. Install system in accordance with NFPA / ANSI 13, Ordinary 1 Hazard B. Connect system to flange provided under Section 33 1119. C. Install system to drain. Drain trapped piping in accordance with NFPA / ANSI 13, Paragraphs 8.15.2.5 and 8.16.4.1. 1. Install main drain from riser. 2. Install auxiliary drains in low points of piping system and inspector's test valve drain to mechanical pad located outside building, unless directed otherwise by Architect. D. Install piping system so it will not fail due to freezing temperatures. E. Do not use dropped, damaged, or used sprinkler heads. F. Pendants: 1. Do not use regular pendants. 2. Install dry pendants with tees and not elbows. Do not adjust length with pipe nipples and couplings. 542-6677-08010101 8 Section 21 1316 Hickory Flat, Canton Wards June 10, 2009 (Rev) Dry-Pipe Sprinkler Systems

3. Individually measure and order each dry pendant based on measured distance from ceiling to face of branch line tee. G. Minimum slope of branch lines is 1/2 inch per 10 feet 12 mm in 3 meters. Minimum slope of main lines is 1/4 inch per 10 feet 6 mm in 3 meters. H. Install sprinkler lines concealed. I. Install tamper switches and pressure flow detectors where located by Architect. J.Install automatic ball drip device in lowest point of piping to the fire department connection and drain to exterior of building. K. Brace and support system to meet seismic zone requirements for building site. 3.3 FIELD QUALITY CONTROL A. Site Tests: 1. Test system according to 'Contractor's Material & Testing Certificate for Above Ground Piping' NFPA-13, figure 16.1. 2. Tests shall be witnessed by Architect and by representative of local jurisdiction having authority for fire prevention. 3. Test blanks shall have red painted lugs protruding beyond flange to clearly indicate their presence and be numbered to assure their removal when testing is completed. END OF SECTION 542-6677-08010101 9 Section 21 1316 Hickory Flat, Canton Wards June 10, 2009 (Rev) Dry-Pipe Sprinkler Systems