Ceiling-Mounted Motion Detector. 752/CD, 752/CP, 752/CU and 752/Cx180. Installation Instructions

Similar documents
180 Degree Ceiling Mounted Occupancy Sensors

Light Level Detector, Surface Mount 5754PE. Installation Instructions

F Type Shielded Masthead Amplifier 3105MH35U18V DIGITAL TERRESTRIAL TELEVISION READY. Installation Instructions

Infrascan Passive Infrared Motion Sensor Surface-Mount 753SSR Series. Installation Instructions

Push Button Electronic Timer. 31VETR3 Series. Installation Instructions

Push Button Electronic Timer. 31VETR Series. Installation Instructions

C-Bus PIR Occupancy Sensor. Installation Instructions 5751L

QUICKSMART Universal Exit Light EXITSM. Installation Instructions REGISTERED DESIGN REGISTERED PATENT

Passive Infrared Motion Detector 5420/90P. Installation Instructions

C-Bus Bus Coupler with Scenes 5102BCLEDL 5104BCL

WAFER Recessed Edgelite Exit LED EXITREC. Installation Instructions REGISTERED DESIGN REGISTERED PATENT

Mains Power Filter 970MF10 970MF20. Installation Instructions

Indoor Infrascan Passive Infrared Motion Sensor. Series. Installation Instructions. Please leave these instructions at the installation site.

C-Bus Black & White MK II Touch Screen. 5000CT2 Series. User s Guide

Clipsal is a registered trademark of Clipsal Australia Pty Ltd. Saturn is a trademark of Clipsal Australia Pty Ltd.

C-Bus Pascal Automation Controller 5500PACA. Installation Instructions

C-Bus Black & White MK II Desktop Touchscreen. 5000CTD2 Series. User s Guide REGISTERED DESIGN REGISTERED PATENT

Three Speed Capacitive Fan Controller. 4060CSFM Series. Installation Instructions 75VA

TrailingE dge Dimmer. 32E450T Series. Installation Instructions REGISTERED DESIGN REGISTERED PATENT

Universal Dimmer. 31E2RUD Series ROTARY CONTROL. Installation Instructions. Integrally Switched Rotary Controlled INTEGRALLY SWITCHED 240V

Line Isolation & Overload Monitor. E05 Series. Installation Instructions MU TE TE S T E. S.P. ALARM MUT E D OVE R LOAD WAR NING PHC WARNING

Trailing Edge Dimmer. 32E450T Series. Installation Instructions REGISTERED DESIGN REGISTERED PATENT

60W Security Spotlight. 754HB1/180/ Outdoor Motion Sensor. Installation Instructions. Please leave these instructions at the installation site.

INDOOR INFRASCAN. Passive Infrared Motion Sensors 751 SERIES INSTALLATION MANUAL. Please leave these instructions at the installation site

Passive Infrared (PIR) Wall Switch Occupancy Sensor Dual Circuit

Universal Dimmer. 31E2RUD Series ROTARY CONTROL. Installation Instructions. Integrally Switched Rotary Controlled INTEGRALLY SWITCHED 240V

Iconic Series ControlLink Pushbutton 41EPBM-VW PDL356PBSS-VW. Installation Instructions REGISTERED DESIGN

Universal Dimmer E450UD Series. Installation Instructions

Installation Instructions

Ultrasonic Wall Switch Occupancy Sensor Single Circuit

v3 360 Dual Technology Low Voltage Occupancy Sensor with Light Level, Isolated Relay and Manual On feature

Motion sensors for every application

Infrared Ceiling Mount Sensor

Sensors and Detectors

Dimmer / Fan Controller Installation Instructions

PSC-ID-x-CM Series Ceiling Mount Occupancy Sensor

Dual Technology Wall Mounted Occupancy Sensor. Manual & Specification

Infrared Ceiling Mount Sensor

754 Series. See Motion Sensors. in a new light. Sleek new styling and more features than ever before.

For assistance with the product please contact: HELPLINE. For a product brochure please contact:

Consumer Switchboards 4CS & 4FCS. Installation Instructions

Ceiling PIR HS presence detector. Product Guide. Overview. Features

Square D Clipsal Outdoor Light-Level Sensor

Installation Instructions

Installation Instructions

Ceiling PIR HS presence detector 1-10V, low temperature. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. IR Receiver

360º FLUSH MOUNT CEILING PIR LIGHT CONTROLLER INSTALLATION & OPERATING. Cat No. SLFM360 INSTRUCTIONS

EBDSPIR-PRM-VFC & EBDSPIR-PRM-VFC-NC

MLHG6-AU. Iso-Gard Line Isolation Monitor (LIM) Setup Guide ! WARNING. Components

A. This Section includes the following lighting control devices:

Universal Clamp Meter

Infrared Wall Mount Occupancy Sensor

DON T WAIT UNTIL IT S TOO LATE! Discover the seven steps to a safe and secure home.

LIGHTING CONTROL DEVICES

EBDSPIR-PRM-LV Product Guide

Dual Technology Wall Switch Occupancy Sensor. Manual & Specification

PSC-BL-I-FM-DC0(-BLE) Bi-level Dimming PIR Sensor

Installation Manual. Features SMART SWITCH OCCUPANCY SENSOR. Maximum Versatility. Maximum Energy Savings

Ceiling PIR presence detector DALI / DSI dimming. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. PIR Sensor.

EBMPIR-MB. Batten mount PIR detectors. Product Guide. Overview. Features

LUX Hardwired - Installation Notes

EBDSPIR-PRM-2CH, EBDSPIR-PRM-2CH-NC

Installation Manual. Models 99168, 99169, 99170

SWITCHLITE MRE SLD MAN SWITCHLITE MRE SLD IP55

Sensors Explained AUTOMATION

Stick Mixer Set brushed stainless steel housing

52 BERKSHIRE CEILING FAN

Intercom Systems Video Intercoms

Airflow. Add a little Sunshine to your bathroom

Technical Application Guide

Technology. Occupancy & Vacancy Sensors & Timers. Technology. Occupancy & Vacancy Sensors & Timers L-2

PPAD-C-230V. Ceiling PIR presence/absence detector. Product Guide. Overview. Features

PIR/INT & PIR/INT-D. Batten mount PIR detectors. Product Guide. Overview. Features

52 BAYTOWNE CEILING FAN

Ceiling Mounted Ducted Exhaust Fan Kit

VITMR-EBDSPIR-PRM. PIR Presence/Absence Detector IR with Ceiling Rose. Product Guide. Overview. Features

SMART HOME LIGHTING CONTROL C LIPSAL

Ceiling Mount Air Purification System

High bay PIR presence detector DALI / DSI dimming. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. IR Receiver

Model: EF34. Owner's Guide & Installation Manual

For assistance with the product please contact: HELPLINE. For a product brochure please contact:

360º Surface Mount Ceiling PIR Light Controller

52 SAN LUCAS CEILING FAN

Dual Relay Multi-Technology Wall Switch Occupancy Sensors

DS9370-BEL. Installation Instructions TriTech Ceiling Mount PIR/Microwave Intrusion Detector

A. This Section includes the following lighting control devices:

Specifications Occupancy/Vacancy Sensors CSI ASHRAE AIA Division 16 Section 16950

High bay PIR presence detector 1-10V dimming. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. IR Receiver

52 STRATHMERE CEILING FAN

Product Specifications Dialog Room Controller* (*patent pending)

EBDHS-DD-LT30. Ceiling PIR HS presence detector DALI / DSI, low temperature. Product Guide. Overview. Features

52 BARSTOW CEILING FAN

48 TAYLOR CEILING FAN

PMCSF6 OCCUPANCY SENSOR

Ceiling Microwave presence/absence detector 12-24V AC/DC

5800-OD Wireless Outdoor Motion Sensor Installation Instructions

Wall Fan. 3 Speed, 40cm MWF40

ADDENDUM NO. 2 COOK LIBRARY BATHROOM RENOVATIONS PROJECT NUMBER TU-1874-SBR

IN2 Lighting Control Devices

Transcription:

Ceiling-Mounted Motion Detector 752/CD, 752/CP, 752/CU and 752/Cx180 Installation Instructions

Contents 1.0 Description...3 1.1 Contents of the Box...3 2.0 Safety...4 3.0 Coverage Patterns...4 3.1 PIR 360 degree...4 3.2 Ultrasonic 360 degree...5 3.3 Dual Technology 360 degree...5 3.4 Ultrasonic 180 degree...6 3.5 Dual Technology 180 degree...6 4.0 Installation...7 4.1 Coverage Direction for the 180-degree Detector...7 4.2 Mounting with the Supplied Mounting Post...7 4.3 Flush Mounting...8 5.0 Wiring Diagram...9 6.0 Operation...9 7.0 Detector Adjustment... 10 7.1 PIR and Ultrasonic...10 7.2 Dual Technology...10 7.3 Mode Switch...11 7.4 Sensitivity Dial...11 7.5 Photocell Dial...12 7.6 Time Delay DIP Switch...12 7.7 Detector Masking...13 8.0 Specifications... 14 9.0 Two-Year Warranty...15 10.0 Warranty Statement...15 2 of 16 2014 Schneider Electric. All Rights Reserved.

1.0 Description The 752 Series Motion Detectors are Class 2 devices ideal for use in business and office settings to accurately detect occupancy and automatically control lighting. The ceiling-mount design of these low-profile detectors allows the greatest possible motion sensitivity. After installation, an adjustment panel, conveniently located on the front of the detector, provides ready access to set the controls. There are five models of ceiling mounted detectors: 752/CP Passive Infrared (PIR), 360 detection pattern 752/CU Ultrasonic, 360 detection pattern 752/CD Dual Technology, PIR and Ultrasonic combined, 360 detection 752/CU180 Ultrasonic, 180 detection pattern 752/CD180 Dual Technology, 180 detection pattern. 1.1 Contents of the Box Item Description Quantity Motion detector 1 Mounting adapter plate 1 Threaded mounting post 1 Washer 1 Lock nut 1 Mounting screws 2 Masking strips sheet, see Note 1 Note: Supplied with PIR and Dual detectors only. 2014 Schneider Electric. All Rights Reserved. 3 of 16

2.0 Safety Follow all safety information on the motion detector and follow the safety warnings below. DANGER Hazard of Electric Shock, Explosion or Arc Flash This equipment must be installed and serviced by qualified electrical personnel. Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. Turn off all electrical power supplying this equipment before working on or inside the equipment. Always use a properly rated voltage sensing device to confirm power is off. Replace all devices, doors and covers before turning on power to this equipment. Failure to follow these instructions could result in death or serious injury. Control power must be provided by a 752PP or 5752PP Series Occupancy Controller, or an approved equivalent. Changes or modifications to this device that are not expressly approved by Clipsal or Schneider Electric might void the warranty and void the user s authority to operate this equipment. When wiring the unit, follow all applicable national and local codes. 3.0 Coverage Patterns The figures that follow show the coverage patterns for the five types of motion detectors for 2.7m (9 ft) ceiling. 3.1 PIR 360 Degree Area of Detection 4 of 16 2014 Schneider Electric. All Rights Reserved.

3.2 Ultrasonic 360 Degree Area of Detection 3.3 Dual Technology 360 Degree Area of Detection 2014 Schneider Electric. All Rights Reserved. 5 of 16

3.4 Ultrasonic 180 Degree Area of Detection 3.5 Dual Technology 180 Degree Area of Detection 6.7 m 6 of 16 2014 Schneider Electric. All Rights Reserved.

4.0 Installation Installation and configuration is simple. The detector mounts directly to the ceiling or a ceiling junction box. The detector can be mounted to a variety of ceiling surfaces, such as acoustical tile, drywall, plywood, etc. Two possible mounting methods are described in this booklet. Note: Install the detector at least 1.5m (5 feet) away from sources of airflow, such as HVAC vents, ceiling fans, etc. 4.1 Coverage Direction for the 180-Degree Detector The 180 degree motion detector has a small directional arrow to indicate the coverage direction. Determine the direction to mount the detector and point the arrow in the desired direction. Directional arrow 4.2 Mounting with the Supplied Mounting Post Ensure that the circuit breaker supplying power to the occupancy controller is turned off. Refer to the figure and the following instructions. 1. Drill a 23mm (7/8 in.) hole in the mounting location. Note: For acoustical tile, you can use the cutter on the end of the threaded mounting post to cut a hole. Press the cutter end of the mounting post firmly against the tile and twist to cut the tile. 2014 Schneider Electric. All Rights Reserved. 7 of 16

2. Feed the detector wire through the mounting post and then twist and lock the mounting post to the back of the detector. 3. Insert the mounting post into the hole drilled in Step 1. Secure the detector from the top of the ceiling tile using the supplied washer and lock nut. 4. Wire the detector according to the wiring diagram in this booklet. Follow all applicable national and local electrical codes. 4.3 Flush Mounting Ensure that the circuit breaker supplying power to the occupancy controller is turned off. Refer to the figure and the following instructions. 1. Drill a hole large enough to accommodate wiring at the mounting location. 2. Attach the mounting adapter plate to the ceiling using a secure method, such as with screws and wall anchors (not provided). 8 of 16 2014 Schneider Electric. All Rights Reserved.

5.0 Wiring Diagram The wiring diagram shows the maximum configuration of motion detectors on an occupancy controller. V DC V DC Follow the instructions in the Occupancy Controller Installation Instructions for wiring and operation of detectors, auxiliary switches and lighting loads. 6.0 Operation The following steps describe the basic operation of the motion detector. Refer to the occupancy controller instructions for information about the interaction between the detectors and the controller. 1. Turn on the circuit breaker and any wall switches that may be supplying power to the occupancy controller. 2. Set the occupancy controller to turn on the associated lighting load when the motion detection signal is active. The factory settings in the occupancy controller will do this. 3. Whenever motion is detected, the LED(s) on the detector housing flash on for approximately 0.5 seconds, and a signal is sent to the controller to turn on the lights or keep them on. Note: When powered on, the detector may have to warm up for a few minutes before it is fully operational. 2014 Schneider Electric. All Rights Reserved. 9 of 16

4. Set the timer duration to the Test setting of 15 seconds (refer to Detector Adjustment in this booklet). 5. Vacate the detection area until the lights turn off. 6. Re-enter the detection area. Lights should turn on immediately. If the lights do not turn on immediately, verify that the detector wiring is correct and that the detector s signal is not being overriden by another control function. Note: Lighting loads connected to ballasts will ramp to full power over a period of four seconds. 7. When the motion detector is operational, adjust the settings as described in Detector Adjustment. 7.0 Detector Adjustment The adjustment panel is located on the front of the detector housing. To access the adjustment controls, gently pry the cover off with a small flat blade screwdriver. To replace the cover, snap it back in place. Refer to the following figure and tables for adjustment details. 7.1 PIR and Ultrasonic 7.2 Dual Technology 10 of 16 2014 Schneider Electric. All Rights Reserved.

7.3 Mode Switch The Mode switch determines when the lights are turned on or remain on. Refer to the table that follows. Detector Mode Description PIR and Ultrasonic A M Automatic mode. Normal, default setting. Lights turn on and stay on only when the detector senses motion. Manual override on mode. Lights are always on. Dual Technology 1 Instant on setting. Either PIR or ultrasonic detection will turn the lights on or cause lights to remain on. 2 Normal default setting. Only PIR detection will turn the lights on. Either PIR or ultrasonic detection will cause the lights to remain on. 3 Override setting on. Lights are always on. 7.4 Sensitivity Dial The Sensitivity Dial determines the amount of movement required to trigger the detector and the distance from which movement can be detected. The sensitivity can be adjusted to the following percentages of the maximum coverage area: 360 PIR detector from 60% to 100%, default is 100% 360 ultrasonic and dual from 10% to 100%, default is 50% 180 ultrasonic and dual from 10% to 100%, default is 50%. Turn the dial to the desired setting. The minimum setting is fully counter clockwise and the maximum setting is fully clockwise. Note: Consider the characteristics of the room when adjusting the sensitivity of the Ultrasonic and Dual Technology detectors. Hard surfaces (concrete, glass and tile) are reflective and create a higher sensitivity for ultrasonic detection. Soft surfaces (carpet, drapes, cubicle walls and acoustical tile) absorb some of the ultrasonic energy and reduce the unit s sensitivity. 2014 Schneider Electric. All Rights Reserved. 11 of 16

7.5 Photocell Dial This dial sets the level above which ambient light will not trigger the detector. The ambient light level can be set from 5 2700 lux. Turn the dial to the desired setting from 5 lux (fully counter clockwise) to 2700 lux (fully clockwise). The default setting is 2700 lux. The default setting disables the photocell, such that ambient light does not inhibit detector operation. 7.6 Time Delay DIP Switch The four-position DIP switch determines how long the lights stay on after motion is no longer detected. Settings range from 15 seconds to 30 minutes. The default setting is 18 minutes. Refer to the following table. Time Delay DIP Switch position 1 2 3 4 15 seconds (test setting) On On On On 2 minutes On On On Off 4 minutes On On Off On 6 minutes On On Off Off 8 minutes On Off On On 10 minutes On Off On Off 12 minutes On Off Off On 14 minutes On Off Off Off 16 minutes Off On On On 18 minutes (factory setting) Off On On Off 20 minutes Off On Off On 22 minutes Off On Off Off 24 minutes Off Off On On 26 minutes Off Off On Off 28 minutes Off Off Off On 30 minutes Off Off Off Off The detectors include a patented feature that senses occupancy patterns and adjusts the time delay to an optimal setting. 12 of 16 2014 Schneider Electric. All Rights Reserved.

7.7 Detector Masking To help prevent unwanted detection, such as people moving in adjacent areas, you can partially mask the lens of the PIR and Dual Technology detectors. Use the supplied white masking strips as shown in the example below. 360 Detector 180 Detector 2014 Schneider Electric. All Rights Reserved. 13 of 16

8.0 Specifications Parameter Operating voltage Power requirement Coverage (360 degree units) Coverage (180 degree units) Isolated relay Adjustable time delay Ambient light level sensing Sensitivity range (percentage of maximum coverage) Motion indicator LEDs PIR Ultrasonic Dual technology Operating temperature Operating humidity Description 24V DC 360 PIR 21mA 360 Ultrasonic 34mA 360 Dual Technology 37mA 180 Ultrasonic 30mA 180 Dual Technology 33mA PIR 93m² (1000 ft²) Ultrasonic 186m² (2000 ft²) Dual Technology 186m² (2000 ft²) Ultrasonic 93m² (1000 ft²) Dual Technology 93m² (1000 ft²) Class 2, rating 1 A @ 24V DC 15 seconds to 30 minutes 5 lux to 2700 lux 360 PIR Detector 60% to 100% 360 Ultrasonic/Dual 10% to 100% 180 Detector 10% to 100% Red Red Red/Green 0 to 50 C (32 to 122 F) 90% maximum (non-condensing) 14 of 16 2014 Schneider Electric. All Rights Reserved.

9.0 Two-Year Warranty The 752/Cx series motion detectors carry a two-year warranty against manufacturing defects. 10.0 Warranty Statement The benefits conferred herein are in addition to, and in no way shall be deemed to derogate, either expressly or by implication, any or all other rights and remedies in respect to the Schneider Electric product, which the consumer has in the location where the product is sold. The warrantor is Schneider Electric with offices worldwide. This Schneider Electric product is guaranteed against faulty workmanship and materials for a period of two (2) years from the date of installation. Schneider Electric reserves the right, at its discretion, to either repair free of parts and labour charges, replace or offer refund in respect to any article found to be faulty due to materials, parts or workmanship. This warranty is expressly subject to the Schneider Electric product being installed, wired, tested, operated and used in accordance with the manufacturer s instructions. Any alterations or modifications made to the product without permission of Schneider Electric might void the warranty. Schneider Electric shall meet all costs of a claim. However, should the product that is the subject of the claim be found to be in good working order, all such costs shall be met by the claimant. When making a claim, the consumer shall forward the Schneider Electric product to the nearest Schneider Electric office. Provide adequate particulars of the defect within 28 days of the fault occurring. The product should be returned securely packed, complete with details of the date and place of purchase, description of load, and circumstances of malfunction. For all warranty enquiries, contact your local Clipsal sales representative. The address and contact number of your nearest sales office can be found at http:// www.clipsal.com/locations or by telephoning Clipsal CIS Technical Support 1300 722 247 (CIS Technical Support Hotline). 2014 Schneider Electric. All Rights Reserved. 15 of 16

Schneider Electric (Australia) Pty Ltd Contact us: clipsal.com/feedback National Customer Care Enquiries: Tel 1300 2025 25 Fax 1300 2025 56 Schneider Electric (Australia) Pty Ltd reserves the right to change specifications, modify designs and discontinue items without incurring obligation and whilst every effort is made to ensure that descriptions, specifications and other information in this catalogue are correct, no warranty is given in respect thereof and the company shall not be liable for any error therein. 2014 Schneider Electric. All Rights Reserved. Trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. F2294/02 SEAU115461 July 2014