Midas. Gas monitoring system for fast and reliable detection of flammable and toxic gases used in industrial manufacturing processes

Similar documents
MDA Scientific Midas. Gas monitoring system for fast and reliable detection of flammable and toxic gases used in industrial manufacturing processes

Life Safety Network. Intelligent solutions for advanced requirements

Satellite XT. Analogue or digital Point-of-Use gas detection transmitter to detect toxic, corrosive and combustible gases

Touchpoint 1. The Touchpoint 1 controller provides 24 hour protection from flammable, toxic or Oxygen gas hazards.

Touchpoint 4. The Touchpoint 4 controller provides protection of personnel and plant from flammable, toxic and Oxygen gas hazards

Signalpoint. The Signalpoint range of flammable, toxic and Oxygen gas detectors offer users a low cost solution to their indoor gas monitoring needs

Unipoint controller. The Unipoint, a simple DIN rail mounted controller

Unipoint Controller. The Unipoint, a simple DIN rail mounted controller

Sieger Apex. Flexibility that meets your requirements

Series 3000 XPIS. 2-wire loop powered toxic and Oxygen gas detector for use in potentially explosive atmospheres

Metro Gas Detector. The Metro addressable gas detector enables remote monitoring of flammable and toxic gas hazards

Sensepoint. Fit For Purpose Flammable, toxic and oxygen versions available High performance, low cost Suitable for new and retro fit applications

Sensepoint. Fit For Purpose Flammable, toxic and Oxygen versions available High performance, low cost Suitable for new and retro fit applications

Sensepoint. The Sensepoint range of flammable, toxic and oxygen gas detectors offer users a low cost solution to their gas monitoring needs.

Satellite XT. Analog or digital Point-of-Use gas detection transmitter to detect toxic, corrosive and combustible gases

FREEDOM SERIES 5000 AND 5600 GAS TRANSMITTERS

Operating Instructions and Maintenance Manual

Unipoint Controller. The Unipoint, a simple DIN rail mounted controller

Searchpoint Optima Plus

REMOTE TOXIC, COMBUSTIBLE, AND OXYGEN GAS SENSORS

Ordering Information. Ordering Information. Transmitter S3KUX S3KAX

Fixed-Point Industrial Gas Detection

Xgard. Fixed detectors For flammable, toxic or oxygen gases

Model D12. Digital Gas Transmitter

Equipment. Model R002. Description. SF6 leak detector

Sensepoint XCD. Flammable, toxic and oxygen. catalytic, electrochemical cell and infrared sensors.

Sieger Sensepoint. Easy to Use Factory set operation Simple to replace Minimal training required

Detection of explosive gases, toxic gases or oxygen. Infrared XP version. SIL 2 high reliability IP 66. Certifications. The Fixed Gas Detection People

Fixed-Point Industrial Gas Detection

3years. Detection of explosive gases, toxic gases and oxygen. Infrared XP IR version. SIL 2 high reliability IP 66.

Detection of explosive gases, toxic gases or oxygen. Infrared XP version. SIL 2 high reliability IP 66. Aluminium or Stainless Steel version

SIL 2. Ultima X Series Gas Monitors CERTIFIED

Operating Instructions

5New features & EXtreme design, now with HART Protocol and DuraSource Technology. Ultima X Series Gas Monitors

Toxic Gas Detection. Model F12. Toxic Gas Detection

Digital Gas Transmitters with Auxiliary Inputs & Control. PolyGard 2 DC6

XNX Universal Transmitter

Sensepoint XCL Fixed Gas Detector

Zareba Sensepoint Pro

Operating Instructions

Sensepoint XCL. Gas Detection. Fixed Gas Detector FEATURES & BENEFITS. Flexible Output Options. Visual Integration. Faster Installation

System 57. An advanced world of intelligent gas detection system management

OLC(T) 100 FIXED GAS DETECTOR

Sensepoint XCD. Flammable, toxic and oxygen deficiency gas detector using catalytic, electrochemical cell and infrared sensors.

ULTIMA XL/XT Series Gas Monitors. [ Ultimate Features Extreme Design ]

REMOTE TOXIC, COMBUSTIBLE, AND OXYGEN GAS SENSORS WITH LOCAL DIGITAL DISPLAY

Electrochemical DrägerSensor Sensors for Fixed Gas Detectors

Sensepoint XCD RTD. Remotely monitor toxic gases in Class 1, Div 2 areas while reducing the maintenance, training and overall cost of gas monitoring

EC FX NH3 SECONDARY HEADLINE. A new and improved approach to ammonia gas detection

Technical Summary. Searchpoint Optima Plus Specification. Output ma sink or source, (Default current source) 0-4 ma (Default 4 ma)

3M Oldham OLCT 100. Description. Fixed Gas Detector

GAS DETECTOR ST400EC PART.NO

System 57. An advanced World of intelligent gas detection system management

PHD6. Flexible, comprehensive monitoring backed up by high performance functionality

P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification

Honeywell Analytics is pleased to announce the release of Version firmware software for the SPM Flex TM product line.

Toxic Smarter Transmitter Instruction Manual

Gas Detection. MeshGuard RAE Systems by Honeywell Battery-Powered Wireless Gas Detector

Touchpoint Pro Flexible Gas Control System

EXAMPLES OF HOW TO ORDER

OLCT 100 DETECTION DE GAZ FIXE. Certifications. Better detection. Better protection. Detection of Combustible, Toxic or Oxygen gases

Sieger Sensepoint. Easy to Use Factory set operation Simple to replace Minimal training required

Zareba Metro Gas Detector

XNX Universal Transmitter. A universal transmitter compatible with all Honeywell Analytics gas sensor technologies DRAFT

Sensepoint XCD RTD. A gas transmitter for use with directly or remotely mounted toxic and Oxygen gas sensors

EXAMPLES OF HOW TO ORDER

Introducing gas detection so intelligent, it s as close to 100% prevention as you can get

Fixed Gas & Flame Detection International Product Range Overview

Quality. Water. Water Quality. Testing. Testing. Toxic Gas Detection. Toxic Gas. Detection. Air Quality. Monitoring. Monitoring. Monitoring.

Industrial Grade Gas Detection Detecting The Difference

Gas Detection For Life

GasSens. Self Checking Gas Sensors. Modular Gas Detector... Gas & Range Availability

Polytron 2. The smart gas detector

SPM Flex Chemcassette Tape-Based Gas Detector

Detectors-Transmitters for Flammable, Toxic Gases and Oxygen. Non-intrusive operation via intrinsically safe infrared remote control.

compact detector Detection of more than 200 flammable and toxic gases iso 9001:2008

Self-contained and intrinsically safe wireless stand-alone multi-point gas detector.

XNX Universal Transmitter

Application Note. Comparison of optical detection systems for Infrared (IR) Hydrocarbon gas detection

PROTECTION THAT MAKES SENSE Bluetooth Enabled Gas Detector

Micro III (Models G203, G203S, and G213) Operation Manual

Installation Guide and Operating Manual MAN0932_V1_ _Rev B_08-12

Honeywell Analytics. Order List BW Clip & IntelliDoX

G-TECTA TM. Portable Gas Detection Instruments

EAGLE 2. 6 Channel Capacity. Inlet fitting. Loud buzzer (95dB) IrDA communication port Low flow shutoff and alarm Alarm LED s with wide visibility

Monitores Personales. Personal Monitor

PolyGard Single Point Controller SPC-X3-11XX for Toxic Gases and Oxygen

Safety Manual. XNX TM Universal Transmitter. Table of Contents SIL 2 Certificates Overview Safety Parameters

Zareba Unipoint controller

Oxygen Deficiency Monitor

SP-220. Features. Combustible handheld gas leakage detector

Stand Alone DYNAGARD SP Operation Manual

Lumidor portable gas detection. Portable protection from hazardous gas

WARRANT Y AND LIMITS OF LIABILIT Y Vulcain Inc. warrants to the original purchaser that its product, and the component parts thereof, will be free fro

ALTAIR 5X Multigas Detector Product Specification

Neotronics Impact & Impact Pro

Two-Channel Gas Controller

Warranty Registration

5 Operating Modes GX Smallest 6 gas sample draw PID library of over 600 VOC s 2 Interchangable smart sensor slots

Danfoss gas detection unit Type GD Heavy Duty

Transcription:

Midas Gas monitoring system for fast and reliable detection of flammable and toxic gases used in industrial manufacturing processes

Midas Features: Over 40 gases available with extended 2 year warranty* Smart sensor cartridge with on board e-calibration certificate 3 built in relays (Form C) for Alarm 1, 2 and Fault Power over Ethernet (PoE) communication and power platform Keypad Interface and remote Web Browser Interface Pyrolyzer and LonWorks interface optional modules that connect to any transmitter Password protected menu levels to preserve system integrity Bright LEDs and intuitive Icon Driven, large backlit LCD display Factory-calibrated sensors to reduce need for frequent gas testing Isolated 0-22mA Analog Output with fault and event reporting Modbus/TCP Ethernet for easy connectivity to all control and alarm systems ports for control connectivity and service interaction Robust extractive pump system (2 year lifetime) sampling up to 30m Interactive Training Simulator tool CE marked for total immunity to Radio Frequency Interference Reflex sensor health check for improved safety TempraSure TM temperature compensation technology as appropriate Event logging to review sensor history Patented reporting technology confirms likely gas release to avoid nuisance alarms (*standard 1 year warranty) Midas is a gas monitoring system for fast and reliable response to the presence of virtually all of the gases used or generated in the Semiconductor and other industrial manufacturing applications. Midas offers lower cost of ownership benefits for gas detection through a combination of extended sensor calibration periods, flexible communications architecture and patented diagnostics that monitor sensor performance and flow control. Midas is a universal transmitter platform that detects the majority of toxic, ambient and flammable gases that must be monitored in a typical industrial process environment. The pre-calibrated plug-and-play smart sensor cartridge makes sensor replacement quick and easy to manage with no tools required, and prevents any operator error associated with using incorrect or depleted sensors. Bright LED lights and an intuitive, icon driven interactive menu guarantee instant alert to the gas reading or alarm level coupled with password protected menus for configuration, test and calibration. Midas is very compact in size and easy access metal chassis design makes it simple to install in crowded, increasingly complex process environments or retro fit applications where space is at a premium. Midas has flexible power and communications built in as standard including 3 on-board relays, 0-22mA analog output, Modbus/ TCP Ethernet digital outputs, as well as the innovative Power over Ethernet (PoE) protocol - a single Ethernet connection for all power, control and communication requirements. Cost effective integration with PLC and FieldBus systems is greatly simplified with the Midas architecture. Midas will monitor points up to 30m (100ft) away from the transmitter and flow rates are regulated automatically using patented control technology to ensure error free gas sensing operation. Honeywell Analytics designs and manufactures its own sensors using advanced robotics to ensure unbeatable quality and reliability. Midas is complimented by the innovative Chemcassette range of ultra sensitive low ppb toxic gas detection analysers and our worldwide network of service engineers who operate on a 24 / 7 basis.

Installation Details Mechanical Removing cover Refitting chassis aligning connector and tubing chassis loosen connector PCB cover mounting bracket 1 screws pipes 4 chassis How cartridge is fitted chassis Removing chassis cartridge mounting bracket 2 5 Attaching bracket to screws on a wall How cover is fitted mounting bracket tighten screws 3 slots 6 cartridge fitted tabs

General Specifications Electrical All wiring permutations shown for example purposes 63mm Analog Output 0-22mA Edge connector to Pyrolyzer or Analog Input Module 120mm 3 Relays Terminals for Alarm1, Alarm 2, Fault relays 24VDC if required Power On/ Off Switch Ethernet port (RJ45) Gland Fitting for DC power, analog, relays RJ45 CAT Ethernet Connector for Power and /or Modbus TCP Ethernet if required Sample Inlet Sample Outlet Cable Gland - PG16 Detectable Gases Gas Name Chemical Formula Range Sensor Part Number Ammonia NH 3 0-100ppm MIDAS-S-NH3 Arsine AsH 3 0-0.2ppm MIDAS-S-ASH Boron Trichloride BCl 3 0-8.0ppm MIDAS-S-HCL Boron Trifluoride BF 3 0-8.0ppm MIDAS-S-HFX Boron Trifluoride (Low Level) BF 3 0-2.0ppm MIDAS-S-HFL Bromine Br 2 0-0.4ppm MIDAS-S-BR2 Carbon Dioxide CO 2 0-2.0% vol MIDAS-S-CO2 Carbon Monoxide CO 0-100ppm MIDAS-S-COX Chlorine Cl 2 0-2.0ppm MIDAS-S-HAL Chlorine Dioxide ClO 2 0-0.4ppm MIDAS-S-BR2 Chlorine Trifluoride ClF 3 0-0.4ppm MIDAS-S-SF4 Diborane B 2 H 6 0-0.4ppm MIDAS-S-HYD Dichlorosilane H 2 SiCl 2 0-8.0ppm MIDAS-S-HCL Difluoromethane CH 2 F 2 0-120ppm MIDAS-S-CFX Disilane Si 2 H 6 0-20ppm MIDAS-S-SHX Fluorine F 2 0-4.0ppm MIDAS-S-HAL Germane GeH 4 0-0.8ppm MIDAS-S-HYD Hexafluorobutadiene C 4 F 6 0-40ppm MIDAS-S-CFX Hydrogen (% LEL)* H 2 0-100% LEL MIDAS-S-LEL Hydrogen (ppm) H 2 0-1000ppm MIDAS-S-H2X Hydrogen Bromide HBr 0-8.0ppm MIDAS-S-HCL Hydrogen Chloride HCl 0-8.0ppm MIDAS-S-HCL Hydrogen Cyanide HCN 0-20ppm MIDAS-S-HCN Hydrogen Fluoride HF 0-12ppm MIDAS-S-HFX Hydrogen Fluoride (Low Level) HF 0-2.0ppm MIDAS-S-HFL Hydrogen Sulphide H 2 S 0-40ppm MIDAS-S-H2S Hydrogen Sulphide (High Level) H 2 S 0-100ppm MIDAS-S-HSH Methane (% LEL)* CH 4 0-100% LEL MIDAS-S-LEL Methyl Fluoride CH 3 F 0-60ppm MIDAS-S-CFX Nitrogen Dioxide NO 2 0-12ppm MIDAS-S-NO2 Nitrogen Oxide NO 0-100ppm MIDAS-S-NOX Nitrogen Trifluoride NF 3 0-40ppm MIDAS-S-HFX Octofluorocyclopentene C 5 F 8 0-40ppm MIDAS-S-CFX Oxygen Proficiency & Deficiency O 2 0-25% vol MIDAS-S-O2X Ozone O 3 0-0.4ppm MIDAS-S-O3X Phosphine PH 3 0-1.2ppm MIDAS-S-PH3 Phosphorous Oxychloride POCl 3 0-0.4ppm MIDAS-S-POC Silane SiH 4 0-20ppm MIDAS-S-SHX Silane (low level) SiH 4 0-2.0ppm MIDAS-S-SHL Sulphur Dioxide SO 2 0-8.0ppm MIDAS-S-SO2 Sulphur Hexafluoride SF 6 0-8000ppm MIDAS-S-CFX Sulphur Tetrafluoride SF 4 0-0.4ppm MIDAS-S-SF4 Tetra Ethyl Ortho Silicate TEOS 0-40ppm MIDAS-S-TEO Tungsten Hexafluoride WF 6 0-12ppm MIDAS-S-HFX Tungsten Hexafluoride (Low Level) WF 6 0-2.0ppm MIDAS-S-HFL For standard 1 year sensor warranty use the order part number format MIDAS-S-XXX; for extended 2 year warranty use the format MIDAS-E-XXX * Midas detectors are not ETL approved for monitoring in or sampling from classified areas above 25% LEL Oxygen detection products must only be used to detect Oxygen depletion in air

Technical Summary Transmitter Dimension Size (unit with Sensor) 120 x 63 x 150mm (H x W x D) Weight (unit with Sensor) 0.8kg Pyrolyzer Dimensions (Regular and High Temperature versions) Size (MIDAS-T-00P) 70 x 63 x 83mm (H x W x D) Weight (MIDAS-T-00P) 0.41kg Size (MIDAS-T-HTP) 113 x 10 x 140mm (H x W x D) Weight (MIDAS-T-HTP) 1.25kg Power Requirements Operating Voltage 24VDC Nominal + / - 10% Sampling Distance Tubing Length Ambient Point Monitoring Exhaust Length Tubing Requirement Sample Exhaust Operating Temperature Up to 30m (100ft) with FEP tubing dependent on gas In line air filter recommended Up to 30m (100ft) 6.35mm OD ( 1 /4") x 3.18mm ( 1 /8"), FEP, 30m (100ft) maximum dependent on gas type 6.35mm ( 1 /4") OD x 4.76mm ( 3 /16"), FEP, 30m (100ft) Operating Voltage with 36-57VDC via PoE, 48VDC Nominal Power over Ethernet (PoE) Power Consumption Transmitter Unit ~ 5.0W With Pyrolyzer (Option) < 12.95W Outputs Visual Alarm, Power and Fault lights as well as back lit LCD display with all gas readings and events Unit with Sensor Wiring Requirement 4-20mA/DC Power/Relays Digital Gas Concentration Display & Interface Instrument 0 C (32 F) to 40 C (104 F) 14 AWG Maximum Shielded CAT 5 cable or equivalent, RJ45 connector 4-digit alphanumeric display with separate measurement units, flow rate bar graph and other icon driven indicators. 4 button membrane keypad Relays 3 relays for Alarm1, Alarm 2 and Fault rated 1.0A @ 30VDC or 0.5A @ 125VAC; configurable NO or NC, latched or unlatched Analog Digital Communications Service Port Certification & Specification European Environmental 2-wire isolated, 0-22mA, Sink or Source Standard: Modbus / TCP Ethernet / Power over Ethernet (PoE). Option: LonWorks RS232C / PPP protocol CE marked; meets EN 50270:1999 (Type2) and EN 55011:2000 ETL approved UL 61010B and CSA-C22.2 No. 1010.1-92 Performance Designed to meet with UL 2075 (pending 2004) Remote Interface Warranty Transmitter Unit Sensor Cartridge Expected Lifetime of Pump Installation Details Mounting Material PC/ PDA Internet Browser access via Ethernet or other Bus system 1 year 1 year standard; 2 year with extended warranty program > 2 years Wall mounted using 2 pre-drilled holes on rear chassis Steel case with paint finish Electrical IEEE 802.3af-2003 Ordering Information Response Times Unit Part Number Flow Rate Transport Time Performance 500ml/min 2-30 seconds maximum LDL < LAL LAL = ½ TLV (typically 12% FSD) Transmitter Pyrolyzer (NF 3 ) Pyrolyzer (High Temperature) LonWorks Interface MIDAS-T-001 MIDAS-T-00P MIDAS-T-HTP MIDAS-T-LON FSD = 4 x TLV

Our Product Range Fixed Gas Monitoring Honeywell Analytics offers a wide range of fixed gas detection solutions for a diverse array of industries and applications including: Commercial properties, industrial applications, semiconductor manufacturers, energy plants and petrochemical sites. Detection of flammable, oxygen and toxic gases (including exotics) Innovative use of 4 core sensing technologies paper tape, electrochemical cell, catalytic bead and infrared Capability to detect down to Parts Per Billion (ppb) or Percent by Volume (%v/v) Cost effective regulatory compliance solutions Portable Gas Monitoring When it comes to personal protection from gas hazards, Honeywell Analytics has a wide range of reliable solutions ideally suited for use in confined or enclosed spaces. These include: Detection of flammable, oxygen and toxic gases Single gas personal monitors worn by the individual Multi-gas portable gas monitors used for confined space entry and regulatory compliance Multi-gas transportable monitors used for temporary protection of area during site construction and maintenance activities Technical Services At Honeywell Analytics, we believe in the value of great service and customer care. Our key commitment is providing complete and total customer satisfaction. Here are just a few of the services we can offer: Full technical support Expert team on hand to answer questions and queries Fully equipped workshops to ensure quick turnaround on repairs Comprehensive service engineer network Training on product use and maintenance Mobile calibration service Customised programmes of preventative/corrective maintenance Extended warranties on products Find out more www.honeywellanalytics.com Contact Honeywell Analytics: Europe, Middle East, Africa Life Safety Distribution AG Wilstrasse 11-U31 CH-8610 Uster Switzerland Tel: +41 (0)44 943 4300 Fax: +41 (0)44 943 4398 gasdetection@honeywell.com Americas Honeywell Analytics Distribution, Inc. 405 Barclay Blvd. Lincolnshire, IL 60069 USA Tel: +1 847 955 8200 Toll free: +1 800 538 0363 Fax: +1 847 955 8208 detectgas@honeywell.com Asia Pacific Honeywell Analytics Asia Pacific #508, Kolon Science Valley (1) 187-10 Guro-Dong, Guro-Gu Seoul, 152-050, Korea Tel: +82 (0)2 2025 0307 Fax: +82 (0)2 2025 0329 analytics.ap@honeywell.com Technical Services ha.emea.service@honeywell.com www.honeywell.com Please Note: While every effort has been made to ensure accuracy in this publication, no responsibility can be accepted for errors or omissions. Data may change, as well as legislation, and you are strongly advised to obtain copies of the most recently issued regulations, standards, and guidelines. This publication is not intended to form the basis of a contract. 12016 H_Midas_DS_V3_EMEA 10/07 2007 Honeywell Analytics