Roof Top Packaged Unit (RTU-1) Specification

Similar documents
Roof Top Units - RTU-1/2/3/4

FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 3 of 13

Submittal. Date: March 20, Customer P.O. Number: Customer Project Number: Job Number: Job Name: General Dynamics

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

Product Data. 50LJS/TJS Single- Package. Features / Benefits. Rooftop Units - 50 Hz 6 to 12 Nominal Tons

Product Catalog. Packaged Rooftop Air Conditioners Foundation Electric/Electric Tons, 50 Hz RT-PRC073B-EN. May 2018

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

Product Catalog. Packaged Rooftop Air Conditioners Foundation Cooling and Gas/Electric 3 to 5 Tons, 60Hz RT-PRC078C-EN.

DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data

SUBMITTAL. Project. CLU Swenson Center. Date 01/07/2010. Mechanical Contractor. West Coast Air Conditioning. Mechanical Engineer

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical

LGH/LCH WARNING. CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges.

Commercial High-Efficiency Condensing Units

Product Catalog. Packaged Rooftop Air Conditioners Foundation Electric/Electric 3 to 5 Tons, 50Hz RT-PRC079B-EN. June 2017

PGF SERIES 7-1/2 Ton. Belt Drive CONVERTIBLE SINGLE PACKAGE GAS/ELECTRIC UNIT

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: INDOOR UNIT:

48PGD/E/F/L/M/N PG20-28

RGE 13 A T - 1 A

DSH Model Air Cooled Self Contained Indoor Packaged Units 2-5 Tons Preliminary Application Data

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

Product Data. Features/Benefits. 50TJ S Side Discharge Single-Package Rooftop Units 50/60 Hz 15 to 30 Nominal Tons

13 GEP A L P - 1 A

VertiCool Aurora Engineering Guide

PAJ3. Product Specifications

Advance Release September 2009

60 TON AIR-COOLED CHILLER. Call us today! (800) PA-ACCTR-60 GENERAL DIMENSIONS ELECTRICAL DATA 60 TON AIR-COOLED CHILLER FEATURES

Water-Cooled Self-Contained Units

Product Catalog. Packaged Rooftop Air Conditioners Foundation Cooling and Gas/Electric 15 to 25 Tons, 60 Hz RT-PRC060H-EN.

technical guide Water-Cooled Self-Contained Units

C13-Series Engineering Guide

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

MIN. CCT. QTY RLA LRA HP FLA AMPACITY /1/ /3/

Weathermaster Series 48HJ004, 005, 006, 007, 008, 009, 012 & 014 COMBINATION GAS HEATING/ ELECTRIC COOLING UNITS

Commercial High-Efficiency Condensing Units

PAR5. Product Specifications

48TF GAS HEATING/ ELECTRIC COOLING UNITS

48TM GAS HEATING/ELECTRIC COOLING UNITS

PACKAGE AIR CONDITIONER

Ruud Commercial Achiever Series Package Gas Electric Unit

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

Call us today! (800)

UP to 14.5 SEER, PACKAGE AIR CONDITIONER UNIT, 2 to 5 TONS 208/230 Volt, 1 phase, 60 Hz REFRIGERATION CIRCUIT

Submittal Summary Page

Packaged Heat Pumps. Precedent - R-410A Tons 60 Hz. Packaged Heat Pumps (WSC) PKGP-PRC013-EN. August 2009

Packaged Heat Pumps. Precedent - R Tons 60 Hz. Packaged Heat Pumps (WSC) PKGP-PRC003-EN. November 2008

EMBASSY SERIES SINGLE PACKAGE AIR CONDITIONERS (WATER-COOLED) C2ED060, 090, 120 & 180 5, 7-1/2, 10 & 15 Nominal Tons

Call us today! (800)

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

Call us today! (800)

CHS. Product Specifications COMMERCIAL SPLIT SYSTEMS HEAT PUMP UNITS R 410A, 6 10 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

Packaged Cooling with Electric Heat Rooftop Units

Submittal Data DESCRIPTION STANDARD FEATURES. Base Unit. Cabinet. Refrigerant System. Gas Heat

Packaged Rooftop Air Conditioners Precedent - Cooling, Gas/Electric, Heat Pump 3-5Ton Standard and High Efficiency 3 Phase Rooftop Units

SUBMITTAL DATA. Medbrooke ADD. Stuart Mc Munn Company 137 North Sixth Street Clarksburg, WV for. Prepared for

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

ASHRAE 90.1 EFFICIENCY PACKAGE AIR CONDITIONER UNIT MBtuh

50TM COMBINATION HEATING/COOLING UNITS

Packaged Heat Pumps. Precedent Tons 60 Hz. Packaged Heat Pumps (WSC) PKGP-PRC003-EN. February 2007

Packaged Heat Pumps. Voyager 12½ to 20 Tons 60 Hz PKGP-PRC001-EN. September 2004

HEATING & COOLING SUBMITTAL The DuraPac Series Unit 559F/579F180, 216, 240, , 18, 20, and 25 NOMINAL TONS

MAC N-407 Air-Cooled Chiller

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING

MHCCW Chilled Water Ceiling Concealed With 5kW Electric Heat 2-Pipe Heat / Cool Fan Coil 30,000 BTUH

R7DA Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 6 and 7 ½ Ton DOAS Packaged Gas/Electric Units

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

DCG Series. Submittal Data Form. 7½- to 12½-Ton Three-Phase Packaged Air Conditioners

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw)

VariCool VAV Engineering Guide

DCC Series. Submittal Data Form 15- & 20-TON, THREE-PHASE PACKAGED AIR CONDITIONERS UP TO 11 EER

MHCCW Chilled Water Ceiling Concealed Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000 BTUH

50TM TFF COMBINATION HEATING/COOLING UNITS

MACH N-407 Heat Pump Air-Cooled Chiller

13 SEER PACKAGE GAS / ELECTRIC UNIT (575V -3 Ph -60Hz) 36 to 61 MBtuh

ADDENDUM 1. Southeast High School Auditorium & Gymnasium HVAC Improvements

Submittal. Date: January 8, Customer P.O. Number: Customer Project Number: CARROLLTON, TX 75006

4YCC3048A3096A /3/ /

STANDARD EFFICIENCY PACKAGE A/C UNIT to 216 MBtuh

SECTION AIR-SOURCE UNITARY HEAT PUMPS

2YCC3060A1120A /1/ / YCC3060A1096A /1/ /

P8SE Series. 14 SEER, Single Phase Packaged Air Conditioner TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 3, 4, 5 Ton Units

Split System Heat Pumps

Technical Guide SUNLINE 2000 DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWER K4EU NOMINAL TONS (WORLD 50 HZ)

Wall Mounted Air Conditioners with Gas Heat Models AVGA

MAC-120HE-03 Air-Cooled Chiller

Stanford University Facilities Design Guidelines SECTION DECENTRALIZED UNITARY HVAC EQUIPMENT

BARD MANUFACTURING COMPANY, INC. WG3S-WG5S 2-Stage Cooling with Gas Heat Engineering Specification Guide

TECHNICAL GUIDE MODELS: H5CE090, H3CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS EER DESCRIPTION

PRODUCT SPECIFICATIONS 2YCC3036A1096A /1/ /

PGB SERIES 3thru5Ton 10 SEER CONVERTIBLE SINGLE PACKAGE GAS/ELECTRIC UNIT

PRODUCT SPECIFICATIONS 2YCC3048A1120A /1/ /

SPECIFICATIONS 4YCC3060A-SPEC-1A SINGLE PACKAGED GAS HEATING ELECTRIC COOLING 4YCC3060A1096/120B TAG:

SPLIT-SYSTEM HEAT PUMPS 50 AND 60 HZ DESCRIPTION

WJH4 Product Specifications

50TJM Nominal Cooling Capacity Tons HFC R - 410A Refrigerant

Packaged Rooftops. Voyager, R-410A. 12½ - 25 Tons 60 Hz. Packaged Cooling (TC*) Packaged Gas/Electric (YC*) RT-PRC028-EN.

High Ambient / High Efficiency Series. R - 410a. 50Hz. Ducted Split Air Conditioners (5.0 kw kw)

Transcription:

Roof Top Packaged Unit (RTU-1) Specification Item Tag(s) Qty Description Model Number A2 10 Ton 1 10 Ton R410A PKGD Unitary Gas/Electric TRANE: YHC120F3RLA--07C1 Product Data - 10 Ton R410A PKGD Unitary Gas/Electric Rooftop All Units DX cooling, gas heat High efficiency Convertible configuration 208-230/60/3 Microprocessor controls 100% Power exhaust economizer with dry bulb control and VFD (Field Installed) Low gas heat Multi speed fan Hinged panels 2 MERV 8 pleated filters Condenser coil guard Human Interface for FDD (fault detection and diagnostics) Spring isolation roof curb, seismically calculated with restraints (Field Installed) 1

Item: A2 Qty: 1 Tag(s): 10 Ton 10 Ton Dual compressor Performance Data -10 Ton R410A PKGD Unitary Gas/Electric Rooftop Tags 10 Ton Design Airflow (cfm) 4000 Airflow Application Horizontal Cooling Entering DB (F) 80.00 Cooling Entering WB (F) 67.00 Ent Air Relative Humidity (%) 51.08 Ambient Temp (F) 95.00 Evap Coil Leaving Air Temp (DB) (F) 58.23 Evap Coil Leaving Air Temp (WB) (F) 57.62 Cooling Leaving Unit DB (F) 60.15 Cooling Leaving Unit WB (F) 58.35 Gross Total Capacity (MBh) 113.97 Gross Sensible Capacity (MBh) 94.06 Gross Latent Capacity (MBh) 19.91 Net Total Capacity (MBh) 107.10 Net Sensible Capacity (MBh) 87.20 Net Sensible Heat Ratio (Number) 0.81 Heating EAT (F) 70.00 Heating LAT (F) 98.10 Heating Delta T (F) 28.10 Input Heating Capacity (MBh) 150.00 Output Heating Capacity (MBh) 120.00 Output Heating Cap. w/fan (MBh) 126.86 Design ESP (in H2O) 1.000 Component SP (in H2O) 0.150 Field supplied drive kit required None Indoor mtr operating power (bhp) 2.45 Indoor RPM (rpm) 1519 Indoor Motor Power (kw) 1.83 Outdoor Motor Power (kw) 0.53 Compressor Power (kw) 7.80 System Power (kw) 10.16 IPLV @ AHRI (IPLV) 15.2 MCA (A) 46.10 MOP (A) 60.00 Compressor 1 RLA (A) 19.60 Compressor 2 RLA (A) 10.40 Evaporator fan FLA (A) 8.50 Condenser fan FLA (A) 2.70 Evaporator face area (sq ft) 16.65 Evaporator rows (Each) 4.00 Evaporator fin spacing (Per Foot) 192 Evaporator face velocity (ft/min) 240 Min. unit operating weight (lb) 1259.0 Max. unit operating weight (lb) 1608.0 Fan motor heat (MBh) 6.86 Dew Point (F) 57.23 Ducted Discharge Heating - 63 Hz (db) 82 Ducted Discharge Heating - 125 Hz (db) 90 Ducted Discharge Heating - 250 Hz (db) 87 Ducted Discharge Heating - 500 Hz (db) 83 2

Ducted Discharge Heating - 1 khz (db) 79 Ducted Discharge Heating - 2 khz (db) 75 Ducted Discharge Heating - 4 khz (db) 75 Ducted Discharge Heating - 8 khz (db) 67 Ducted Inlet Heating - 63 Hz (db) 81 Ducted Inlet Heating - 125 Hz (db) 81 Ducted Inlet Heating - 250 Hz (db) 82 Ducted Inlet Heating - 500 Hz (db) 71 Ducted Inlet Heating - 1 khz (db) 62 Ducted Inlet Heating - 2 khz (db) 61 Ducted Inlet Heating - 4 khz (db) 64 Ducted Inlet Heating - 8 khz (db) 54 Outdoor Noise Heating - 63 Hz (db) 89 Outdoor Noise Heating - 125 Hz (db) 87 Outdoor Noise Heating - 250 Hz (db) 91 Outdoor Noise Heating - 500 Hz (db) 85 Outdoor Noise Heating - 1 khz (db) 80 Outdoor Noise Heating - 2 khz (db) 77 Outdoor Noise Heating - 4 khz (db) 73 Outdoor Noise Heating - 8 khz (db) 66 Rated capacity (AHRI) (MBh) 113.00 Exhaust fan power (kw) 0.65 Refrig charge (HFC-410A) - ckt 1 (lb) 7.1 Refrig charge (HFC-410A) - ckt 2 (lb) 5.0 ASHRAE 90.1 Yes Saturated Suction Temp Circuit 1 (F) 52.30 Saturated Discharge Temp Circuit 1 (F) 119.00 Saturated Suction Temp Circuit 2 (F) 56.40 Saturated Discharge Temp Circuit 2 (F) 122.40 IEER ( ) 15.20 EER @ AHRI Conditions (EER) 12.4 Total Static Pressure (in H2O) 1.150 3

Mechanical Specifications - 10 Ton R410A PKGD Unitary Gas/Electric Rooftop Item: A2 Qty: 1 Tag(s): 10 Ton General The units shall be convertible airflow. The operating range shall be between 115 F and 0 F in cooling as standard from the factory for units with microprocessor controls. Operating range for units with electromechanical controls shall be between 115 F and 40 F. Cooling performance shall be rated in accordance with ARI testing procedures. All units shall be factory assembled, internally wired, fully charged with R-410A, and 100 percent run tested to check cooling operation, fan and blower rotation, and control sequence before leaving the factory. Wiring internal to the unit shall be colored and numbered for simplified identification. Units shall be culus listed and labeled, classified in accordance for Central Cooling Air Conditioners. Casing Unit casing shall be constructed of zinc coated, heavy gauge, galvanized steel. Exterior surfaces shall be cleaned, phosphatized, and finished with a weather-resistant baked enamel finish. Unit's surface shall be tested 672 hours in a salt spray test in compliance with ASTM B117. Cabinet construction shall allow for all maintenance on one side of the unit. Service panels shall have lifting handles and be removed and reinstalled by removing two fasteners while providing a water and air tight seal. All exposed vertical panels and top covers in the indoor air section shall be insulated with a cleanable foil-faced, fire-retardant permanent, odorless glass fiber material. The base of the unit shall be insulated with 1/8 inch, foil-faced, closed-cell insulation. All insulation edges shall be either captured or sealed. The unit's base pan shall have no penetrations within the perimeter of the curb other than the raised 1 1/8 inch high downflow supply/return openings to provide an added water integrity precaution, if the condensate drain backs up. The base of the unit shall have provisions for forklift and crane lifting, with forklift capabilities on three sides of the unit. Unit Top The top cover shall be one piece construction or, where seams exist, it shall be double-hemmed and gasket-sealed. The ribbed top adds extra strength and enhances water removal from unit top. Two-Inch Pleated Filters 2" pleated media filters shall be available on all models. Compressors All units shall have direct-drive, hermetic, scroll type compressors with centrifugal type oil pumps. Motor shall be suction gas-cooled and shall have a voltage utilization range of plus or minus 10 percent of unit nameplate voltage. Internal overloads shall be provided with the scroll compressors. Dual compressors are outstanding for humidity control, light load cooling conditions and system back-up applications. Dual compressors are available on 7½-10 ton models and allow for efficient cooling utilizing 3-stages of compressor operation for all high efficiency models. Notes: Crankcase heaters are optional on YSC (036, 048, 060, 072, 090, 102, 120); standard on YHC (036, 048, 060, 072, 092, 102, 120). Indoor Fan The following units shall be equipped with a direct drive plenum fan design (T/YSC120F,T/YHC074F, T/YHC092F,T/YHC102F, 120F). Plenum fan design shall include a backward-curved fan wheel along with an external rotor direct drive variable speed indoor motor. All plenum fan designs will have a variable speed adjustment potentiometer located in the control box. 3 to 5 ton units (high efficiency 3-phase with optional motor) are belt driven, FC centrifugal fans with adjustable motor sheaves. 3 to 5 ton units (standard and high efficiency 3-phase) have multispeed, direct drive motors. All 6 to 8½ ton units (standard efficiency) shall have belt drive motors with an adjustable idler-arm assembly for quick-adjustment to fan belts and motor sheaves. All motors shall be thermally protected. All 10 tons, 6 ton (074), 7½ to 8½ (high efficiency) units have variable speed direct drive motors. All indoor fan motors meet the U.S. Energy Policy Act of 1992 (EPACT). Outdoor Fans The outdoor fan shall be direct-drive, statically and dynamically balanced, draw-through in the vertical discharge position. The fan motor shall be permanently lubricated and shall have built-in thermal overload protection. Multi-Speed Indoor Fan System Multi-speed indoor fan system is designed for use in applications for meeting the minimum requirement of CA Title 24. This system incorporates a multi-speed fan control to change the speed of the fan to 67% of full airflow based off of compressor stages 4

Evaporator and Condenser Coils Internally finned, 5/16" copper tubes mechanically bonded to a configured aluminum plate fin shall be standard. Evaporator coils are standard for all 3 to 10 ton standard efficiency models. Microchannel condenser coils are standard for all 3 to 10 ton standard efficiency models and 4,5,6, 7.5, 8.5 ton high efficiency models. The microchannel type condenser coil is not offered on the 4 and 5 ton dehumidification model. Due to flat streamlined tubes with small ports, and metallurgical tube-to-fin bond, microchannel coil has better heat transfer performance. Microchannel condenser coil can reduce system refrigerant charge by up to 50% because of smaller internal volume, which leads to better compressor reliability. Compact all-aluminum microchannel coils also help to reduce the unit weight. These all aluminum coils are recyclable. Galvanic corrosion is also minimized due to all aluminum construction. Strong aluminum brazed structure provides better fin protection. In addition, flat streamlined tubes also make microchannel coils more dust resistant and easier to clean. Coils shall be leak tested at the factory to ensure the pressure integrity. The evaporator coil and condenser coil shall be leak tested to 600 psig. The assembled unit shall be leak tested to 465 psig. The condenser coil shall have a patent pending 1+1+1 hybrid coil designed with slight gaps for ease of cleaning. A plastic, dual-sloped, removable and reversible condensate drain pan with through-the-base condensate drain is standard. Tool-less Hail Guards Tool-less, hail protection quality coil guards are available for condenser coil protection. Controls Unit shall be completely factory-wired with necessary controls and contactor pressure lugs or terminal block for power wiring. Unit shall provide an external location for mounting a fused disconnect device. A choice of microprocessor or electromechanical controls shall be available. Microprocessor controls provide for all 24V control functions. The resident control algorithms shall make all heating, cooling, and/or ventilating decisions in response to electronic signals from sensors measuring indoor and outdoor temperatures. The control algorithm maintains accurate temperature control, minimizes drift from set point, and provides better building comfort. A centralized microprocessor shall provide anti-short cycle timing and time delay between compressors to provide a higher level of machine protection. 24-volt electromechanical control circuit shall include control transformer and contactor High Pressure Control All units include High Pressure Cutout as standard. Phase monitor Phase monitor shall provide 100% protection for motors and compressors against problems caused by phase loss, phase imbalance, and phase reversal. Phase monitor is equipped with an LED that provides an ON or FAULT indicator. There are no field adjustments. The module will automatically reset from a fault condition. Refrigerant Circuits Each refrigerant circuit offer thermal expansion valve as standard. Service pressure ports, and refrigerant line filter driers are factory-installed as standard. An area shall be provided for replacement suction line driers. Gas Heating Section The heating section shall have a progressive tubular heat exchanger design using stainless steel burners and corrosion resistant steel throughout. An induced draft combustion blower shall be used to pull the combustion products through the firing tubes. The heater shall use a direct spark ignition (DSI) system. On initial call for heat, the combustion blower shall purge the heat exchanger for 20 seconds before ignition After three unsuccessful ignition attempts, the entire heating system shall be locked out until manually reset at the thermostat/zone sensor. Units shall be suitable for use with natural gas or propane (fieldinstalled kit) and also comply with the California requirement for low NOx emissions (Gas/Electric Only). Hinged Access Doors Sheet metal hinges are available on the Filter/Evaporator, Supply Fan/Heat, and the Compressor/Control Access Doors. Plenum Fan The following unit shall be equipped with a direct drive plenum fan design (all 10 tons and 7.5-8.5 ton high efficiency units). Plenum fan design shall include a backward-curved fan wheel along with an external rotor direct drive variable speed indoor motor. All plenum fan designs will have a variable speed adjustment potentiometer located in the control box. Human Interface 5

The Human Interface shall have a 5 inch color touchscreen display that conforms to FCC Part 15 Class B with an Ingress Protection Rating of IP24.The display text shall be readable by a person with 20/20 vision at a distance of 3 feet and 60 angle at lighting levels ranging from 100 lux - 25,000 lux. Also, the display shall operate at temperatures of -40 C to 70 C. Firmware and unit configurations shall be able to be restored via a USB storage device. Electrical/General Data - 10 Ton R410A PKGD Unitary Gas/Electric Rooftop Item: A2 Qty: 1 Tag(s): 10 Ton ELECTRICAL / GENERAL DATA GENERAL (2)(4)(6) HEATING PERFORMANCE Model: YHC120F Oversized Motor HEATING - GENERAL DATA Unit Operating Voltage: 187-253 MCA: Unit Primary Voltage: 208 Heating Model: MFS: Unit Secondary Voltage 230 Heating Input (BTU): MCB: Unit Hertz: 60 Heating Output (BTU): Unit Phase: 3 No. Burners: No. Stages EER Standard Motor Field Installed Oversized Motor Gas Inlet Pressure MCA: 46.1 MFS: 60.0 MCB: 60.0 MCA: MFS: MCB: Natural Gas (Min/Max): LP (Min/Max) Gas Pipe Connection Size: Low 150,000/105,000 120,000/84,000 3 2 4.5/14 10.0/14.0 3/4" INDOOR MOTOR Standard Motor Oversized Motor Number: 1 Number: Horsepower: 3.8 Horsepower: Motor Speed (RPM): -- Motor Speed (RPM): Phase 3 Phase Full Load Amps: 8.5-8.5 Full Load Amps: Locked Rotor Amps: -- Locked Rotor Amps: Field Installed Oversized Motor Number: Horsepower: Motor Speed (RPM): Phase Full Load Amps: Locked Rotor Amps: COMPRESSOR Circuit 1/2 OUTDOOR MOTOR Number: 2 Horsepower: 5.1/3.0 Phase: 3 Rated Load Amps: 19.6/10.4 Locked Rotor Amps: 136.0/73.0 Number: 1 Horsepower: 0.75 Motor Speed (RPM): 1100 Phase: 3 Full Load Amps: 2.7 Locked Rotor Amps: 9.8 POWER EXHAUST ACCESSORY (3) (Field Installed Power Exhaust) Phase: Horsepower: Motor Speed (RPM): Full Load Amps: Locked Rotor Amps: FILTERS Type: Furnished: Number Recommended Throwaway Yes 3 / 2 20"x25"x2" 20"x30"x2" (2) REFRIGERANT Type R-410 Factory Charge Circuit #1 7.1 lb Circuit #2 5.0 lb NOTES: 1. Maximum (HACR) Circuit Breaker sizing is for installations in the United States only. 2. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions. 3. Value does not include Power Exhaust Accessory. 4. Value includes oversized motor. 5. Value does not include Power Exhaust Accessory. 6. EER is rated at AHRI conditions and in accordance with DOE test procedures. 6

C B A AA A B Unit Dimensions -10 Ton R410A PKGD Unitary Gas/Electric Rooftop Item: A2 Qty: 1 Tag(s): 10 Ton CONTROL BOX SECTION ACCESS PANEL INDOOR TOP PANEL GAS CONNECTION (SEE NOTE 2) OUTDOOR TOP PANEL CONDENSER FAN EVAPORATOR SECTION ACCESS PANEL CONDENSATE (SEE NOTE 1) CONDENSER COIL 27 5/8" HORIZONTAL AIR FLOW 47 7/8" 53 3/4" COMPRESSOR ACCESS PANEL CONDENSER COIL SIDE POWER WIRE (SEE NOTE 3) PACKAGED GAS / ELECTRICAL ISOMETRIC VIEW THROUGH THE BASE CONDENSATE 27 9/16" 4 3/16" 33" SUPPLY 32 1/8" RETURN NOTES: 1. ALTERNATE CONDENSATE DRAIN CONNECTION 3/4" - 14 NPT DIA. HOLE 2. 1/2" NPT GAS CONNECTION (80 mbh, 120 mbh) ; 3/4" NPT GAS CONNECTION (150mbh, 200mbh, 250mbh) 3. UNIT POWER WIRE 1 3/8" DIA. HOLE. 4. THRU -THE -BASE ELECTRICAL AND GAS IS NOT STANDARD ON ALL UNITS. 5. VERIFY WEIGHT, CONNECTION, AND ALL DIMENSION WITH INSTALLER DOCUMENTS BEFORE INSTALLATION 17 1/2" 17 1/2" PLAN VIEW UNIT 62 1/4" DIMENSION DRAWING 9 3/8" COIL 52 5/16" 50 7/8" 32 1/4" 19 1/4" SUPPLY 16 11/16" RETURN 32 1/4" SERVICE SIDE HORIZONTAL AIR FLOW 4 1/4" 27 9/16" 4 3/4" CONDENSATE DRAIN 99 11/16" PACKAGED GAS / ELECTRICAL DIMENSION DRAWING 63 3/16" 162" 7

Accessory - 10 Ton R410A PKGD Unitary Gas/Electric Rooftop Item: A2 Qty: 1 Tag(s): 10 Ton 8