Table of Contents. CAT CONDENSING UNITS 2

Similar documents
Catalog Air Cooled Split System Condensing Units for Rooftop Systems and Air Handlers

Commercial High-Efficiency Condensing Units

Air Cooled Split System Condensing Unit for Rooftop Systems and Air Handlers

Commercial High-Efficiency Condensing Units

Air-Cooled Split System Condensing Unit for Rooftop Systems and Air Handlers

Installation and Maintenance IM 962-3

PACKAGE AIR CONDITIONER

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

Air-Cooled Split System Condensing Units for Remote DX Coils and Air Handlers. Models RCS 015D to 140D R-410A Refrigerant.

MACH N-407 Heat Pump Air-Cooled Chiller

MAC N-407 Air-Cooled Chiller

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

TECHNICAL GUIDE MODELS: H5CE090, H3CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS EER DESCRIPTION

INSTALLATION AND OPERATING INSTRUCTIONS

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

Air-Cooled Split System Condensing Units

MAC-120HE-03 Air-Cooled Chiller

FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 3 of 13

JOB NAME: LOCATION: PURCHASER: ENGINEER: SUBMITTED TO: FOR: REFERENCE [ ] APPROVAL [ ] CONSTRUCTION [ ] SUBMITTED BY: DATE:

Submittal. Date: January 8, Customer P.O. Number: Customer Project Number: CARROLLTON, TX 75006

072, 090, 120, 180 & 240 MODELS C SERIES CONDENSING UNITS P SERIES HEAT PUMPS

CHS. Product Specifications COMMERCIAL SPLIT SYSTEMS HEAT PUMP UNITS R 410A, 6 10 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

WLCG/WLHG. Specifications and Performance WLCG/WLHG. (with EMI AmericaSeries condensers)

Rheem Commercial High-Efficiency Condensing Units

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

13 GEP A L P - 1 A

Concealed Ducted Split Series R-407C MBH

60 TON AIR-COOLED CHILLER. Call us today! (800) PA-ACCTR-60 GENERAL DIMENSIONS ELECTRICAL DATA 60 TON AIR-COOLED CHILLER FEATURES

MHH. 13 SEER High Efficiency R410a. SPECIFICATION sheet

TECHNICAL GUIDE LISTED. SPLIT-SYSTEM AIR CONDITIONERS 10 SEER R22 60Hz MODELS: H*BA-(T,W)036 THRU 076 (3 THRU 6.3 NOMINAL TONS, 3 PH) DESCRIPTION

RGE 13 A T - 1 A

TECHNICAL GUIDE LISTED. SPLIT-SYSTEM AIR CONDITIONERS 10 SEER R22 60Hz MODELS: AC036X10(3,4) THRU 060 (3 THRU 5 NOMINAL TONS, 3 PH) DESCRIPTION

2 shp 13 lc 1 36 t - 1 a

MERIT Series R-410A. SEER up to to 5 Tons Cooling Capacity - 17,500 to 59,000 Btuh AIR CONDITIONERS 13ACXN PRODUCT SPECIFICATIONS

Liebert CSU3000 Chiller

Product Data. Features/Benefits. 38AH Commercial Air-Cooled Condensing Units 50/60 Hz. 20 to 130 Nominal Tons (63 to 390 Nominal kw)

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

T-SERIES SPLIT SYSTEM UNITS R-410A - 60 HZ. EER up to to 20 Tons Cooling Capacity - 71,000 to 236,000 Btuh AIR CONDITIONERS TS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

CONDENSING UNITS. Equipped with the Award Winning Comfort Control System UARL- JEZ. Four Models

T P A 120 S 4 S N 1 Y

Call us today! (800)

Product Data. Split System Heat Pump B-EN. February A6H6024H1000A

Air-Cooled Condensers

Advance Product Data. Features/Benefits. 42WKN Hydronic Fan Coil Units

DRY CHARGE UNITS. 1.5 to 5 Tons AIR CONDITIONERS LCS13DC PRODUCT SPECIFICATIONS L C S 13 DC MODEL NUMBER IDENTIFICATION

Nominal Capacity 024 = 7 kw (2 tons) 036 = 10.5 kw (3 tons) 048 = 14 kw (4 tons) 060 = 17.5 kw (5 tons)

Product Data. Features/Benefits. 50TJ S Side Discharge Single-Package Rooftop Units 50/60 Hz 15 to 30 Nominal Tons

Split System Heat Pump Product Data

Air-Cooled Condensers

SPLIT SYSTEM HEAT PUMP 1½ 5 TON HERITAGE 13 MODELS 2A6H A American Standard Heating & Air Conditioning

Call us today! (800)

Product Data. 50HS Single-Package Heat Pumps to 5 Nominal Tons

Product Data. 50LJS/TJS Single- Package. Features / Benefits. Rooftop Units - 50 Hz 6 to 12 Nominal Tons

PAJ3. Product Specifications

50TM COMBINATION HEATING/COOLING UNITS

30GT FLOTRONIC AIR-COOLED CHILLERS

Rooftop Units 60HZ. PACKAGED HEAT PUMPS 13HPP / rhp13 PRODUCT SPECIFICATIONS 13 HPP 36 A P - 1 A RHP 13 A 36 T - 1 A MODEL NUMBER IDENTIFICATION

Product Data. Split System Heat Pump D-EN. February 2016

30GN FLOTRONIC II AIR-COOLED CHILLERS

50HS018, 024, 030, 036, 042, 048 & 060 STANDARD-EFFICIENCY COMBINATION HEAT PUMP UNITS W/OPTIONAL ELECTRIC HEAT

Split System Cooling Product & Performance Data

Call us today! (800)

3 to 5 Tons. AIR CONDITIONERS 2scu13. Dry Charge Split System - 60 HZ PRODUCT SPECIFICATIONS. 2 scu 13 lc 1 36 t - 1 a MODEL NUMBER IDENTIFICATION

DRY CHARGE UNITS. 1.5 to 5 Tons. HEAT PUMP OUTDOOR UNITS lps13dc PRODUCT SPECIFICATIONS L P S 13 DC MODEL NUMBER IDENTIFICATION

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

50TM TFF COMBINATION HEATING/COOLING UNITS

High Ambient / High Efficiency Series. R - 410a. 50Hz. Ducted Split Air Conditioners (5.0 kw kw)

Packaged Heat Pump. 20 Ton Rooftop Units with ReliaTel TM Controls NOTICE

ELITE Series R-410A. SEER up to to 5 Tons Cooling Capacity - 17,800 to 60,000 Btuh AIR CONDITIONERS EL16XC1 PRODUCT SPECIFICATIONS

UP to 14.5 SEER, PACKAGE AIR CONDITIONER UNIT, 2 to 5 TONS 208/230 Volt, 1 phase, 60 Hz REFRIGERATION CIRCUIT

.2 Section Waste Management and Disposal.

SPLIT SYSTEM COOLING 1 1 / 2 5 TON MODELS 4A7A

48GS HIGH-EFFICIENCY SINGLE-PACKAGE GAS HEATING/ ELECTRIC COOLING UNITS

48GS(N) STANDARD EFFICIENCY 48GX(N) HIGH-EFFICIENCY SINGLE-PACKAGE GAS HEATING ELECTRIC COOLING UNITS

Product Data. GEMINI SELECT 09DPS ,09DPM Air-Cooled Condensers with PURON Refrigerant (R-410A) 50/60 Hz

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

Product Data. Split System Heat Pump A-EN. March 2016

WH1T SERIES Constant Torque Motor (ECM) Efficiencies up to 14 SEER. FORM NO. H REV. 1 Supersedes Form No. G Rev. 3

SPLIT-SYSTEM HEAT PUMPS 50 AND 60 HZ DESCRIPTION

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

Split System Cooling Product Data

HIGH EFFICIENCY AIR HANDLER

Product Data. Features/Benefits. 50HS Single-Package Heat Pump Units 50 Hz

48TM GAS HEATING/ELECTRIC COOLING UNITS

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: INDOOR UNIT:

Split System Cooling Product Data

Split System Heat Pump Product Data

SECTION ROTARY-SCREW WATER CHILLERS

Split System Heat Pump Product Data

SPLIT SYSTEM COOLING 1½ 5 TON ALLEGIANCE 14 MODELS 4A7A C/30-060B American Standard Heating & Air Conditioning

Product Data. Split System Cooling D-EN. August 2016

Product Data PH13(N,P)R FEATURES AND BENEFITS. SPLIT SYSTEM HEAT PUMP For Use With R Refrigerant 1---1/2 TO 5 TONS ( )

MHNCCW (4-Pipe) Chilled/Hot Water Ceiling Concealed 208/230V 4-Pipe Heating & Cooling Fan Coil 12,000 BTUH

Split System Cooling Product Data

Submittal. Split System Cooling 4A7A6024J-SUB-1B-EN. January A7A6024J1000B TAG:

Transcription:

Catalog 223-4 Air-Cooled Split System Condensing Units Model RCS 06G through 20F 6.5 through 20 Tons R-410A Refrigerant 6.5 7.5 Tons 10.0 12.0 Tons 15.0 20.0 Tons

Table of Contents Introduction...3 Why Use a High Efficiency, Air-Cooled Split System? 3 Agency Listed...3 Daikin s Unique Features...4 Components...5 Accessories................................ 6 Application Data...7 General Rooftop Applications...7 Physical Data...8 Unit Capacity and Physical Data................ 8 Table of Contents Performance Data...9 Gross Capacity and Power...9 Unit Capacities...10 Dimensional and Weight Data...14 Electrical Data...16 Power Wiring.............................. 16 Wiring Diagrams...17 Engineering Guide Specification...20 CAT 223-4 CONDENSING UNITS 2 www.daikinapplied.com

Introduction Introduction Why Use a High Efficiency, Air-Cooled Split System? The size ranges offered by Daikin allow you to mix or match components to meet actual job requirements, thus eliminating the need to use oversized or undersized equipment. Equipment sized to meet the actual building load will provide better operating economy, better humidity control, and longer equipment life. With an air-cooled system, you have no water or sewer connections to make, and no troublesome or costly water treatment. An air-cooled split system is inherently more efficient than a air-cooled chiller system. The air-cooled split system has no pump and runs at a higher, more efficient suction pressure. Remote mounting of the already quiet condensing unit keeps the compressor and condenser fan noise outside. Vertical discharge fans also contribute to quietness, carrying the noise up and away from the surrounding area. Because of the simple design of the Daikin condensing unit, installation is quick, simple, and very little maintenance is required. Agency Listed NOTE: For further information on a complete air-cooled split system, refer to Catalog 580 (Destiny Indoor Air Handlers). Nomenclature R C S 06 F 079 C Rooftop Condensing System Nominal capacity (tons) 06 = 6.5 07 = 7.5 10 = 10 12 = 12 15 = 15 20 = 20 Refrigerant F = R-410A G = R-410A Voltage C = 208/230-3 - 60 D = 460-3 - 60 Y = 575-3 - 60 Compressor 079 = 6.5 ton, single 091 = 7.5 ton, single 121 = 10 ton, single 150 = 12.5 ton, tandem 180 = 15 ton, tandem 240 = 20 ton, tandem NOTE: For larger size units (greater than 20 ton), refer to Catalog 222 www.daikinapplied.com 3 CAT 223-4 CONDENSING UNITS

Introduction Daikin s Unique Features 2 1 Side/End View 3 4 6 5 Top View End View 1 Louvers Full- face coil louvers for aesthetics and hail protection 2 Durable construction Pre-painted exterior cabinet panels pass 1000-hour ASTM B 117 Salt Spray Test for durability 3 Condenser fans Vertical air discharge for quiet operation 4 Condenser coils Large face area High efficiency enhanced copper tubing All aluminum fin design 5 R410A refrigerant Environmentally friendly Excellent efficiency Insignificant glide making system easier to service 6 Scroll compressors Provide maximum dependability, efficiency and quiet operation CAT 223-4 CONDENSING UNITS 4 www.daikinapplied.com

Introduction Components Cabinet Galvanized steel with powder coat paint finish. The powder coat paint finish is high gloss, durable and capable of withstanding a 1000 hour salt spray test per ASTM B117. Unit is of the frame and panel type construction which allows all access panels to be opened or removed without affecting the structural strength of the unit. Fastening screws are also of the 1000 hour type. Stamped louver panels offer 100% protection for the condenser coil. Base Pan Galvanized steel with powder coat paint finish. Compressors High efficiency Copeland scroll compressors. Engineered for long life and durability. Unloading (50%) is available on 10 to 20 ton models. All compressors have inherent high temperature protection. Mounted on isolators which reduce vibration and noise. Condenser Coil Constructed with copper tubes and aluminum fins and mechanically bonded to the tubes for maximum heat transfer capabilities. Condenser coil assemblies are leak tested up to 450 psig internal pressure. Refrigerant Connections Field sweat joints are made external of the unit and are located close to the ground for a neat looking installation. Crankcase Heaters Standard on 6 20 ton models. Low Ambient Control Pressure sensitive fan cycling control allows operation down to 0 F [-17.8 C]. Service Valves Standard on liquid and suction lines for all models. Service Access Control box with separate line and control voltages, as well as compressor and other refrigerant controls are accessible through access panels. Electrical access cover may be opened or removed without affecting normal operation of the unit. Condenser fan motors have molded plugs for easy removal. Removable louver panels/end access panel for coil cleaning. Condensing Section Open design permits unrestricted condenser airflow, access to compressors, refrigeration components, piping, and access for roof maintenance. High efficiency Copeland scroll compressors. 12 20 ton units feature dual compressors for redundancy and efficient capacity control. Large face area condenser for high operating efficiencies. Vertical air discharge minimizes noise. High Pressure Control Manual reset control deactivates system (opens contactor circuit) if abnormally high pressure occurs. Low Pressure Control Automatic reset control deactivates system if abnormally low pressure or refrigerant loss occurs. Condenser Fan Motors Direct drive, single-phase, permanently lubricated motors with inherent thermal overload. Equipment Ground Lug for field connection of ground wire. Testing All units are run-tested at the factory prior to shipment. Units are shipped with a nitrogen holding charge. www.daikinapplied.com 5 CAT 223-4 CONDENSING UNITS

Introduction Accessories Accessories (Table 1) can be added to further enhance the unit. Table 1: Accessories Accessory Description Model Number Sizes Anti-short cycle timer kit 1 RXAT-A01 All Sight glass RXAG-A048 6.5 15 ton RXAG-A020 20 ton RXAV-CD078 6.5 & 7.5 Liquid Solenoid Valve RXAV-CD120 10, 11, & 12 RXAV-CD180 15 & 20 1. Not required when Daikin programable thermostat is purchased. Programmable Thermostat (P/N 113129801) The commercial setback digital thermostat uses microcomputer technology to provide precise time and temperature control. This thermostat offers the flexibility to design heating and cooling programs that fit building needs. This thermostat is adaptable to most residential 24 volt forced air multi-stage systems with electric or fossil fuel auxiliary and is the ultimate for comfort, convenience, and performance. Figure 1: Digital Thermostat Features The thermostat can enhance your HVAC system by offering you the following performance features. Automatic heat/cool system changeover Fossil fuel or electric heat compatible Large luminescent display and industry first lighted keypad Permanent program memory Configuration menu allows keypad selection of options, no additional sub-bases required Selectable energy management recovery Onboard system and thermostat diagnostics Single stage models accept remote indoor sensor Staging models accept up to three indoor sensors and offer temperature averaging or weighted average by sensor location and program time Typical Connection Use the terminal output information below to help you wire the thermostat properly for your multi-stage system. Colors shown are typical. Thermostat Terminals (Upper) L PH D SA SB SC OT Malfunction Light X-10 Module Input Not Used Remote Sense A Remote Sense B Remote Sense C Outdoor Sensor Thermostat Terminals (Lower) System E C R W3/A 1 W 2 E 2 /P W 1 Y 2 Y 1 B O G Multi- Stage No Function 24 Volt (Common) Br R Bk C R W1 24 Volt (Hot) Bl W2 Heat Mode 3rd Stage G Heat Mode 2nd Stage Y1 1 Use a wirenut to extend from the leads provided in the unit to the thermostat. 2 W1, W2, Y2 are optional depending upon size/options. No Function Y2 Heat Mode 1st Stage Cool Mode 2nd Stage Cool Mode 1st Stage Energized in Heat and Off Mode Energized in Cool Mode Blower/Fan Energized on call for Cool (and heat if configured to Electric Heat) O Y G CAT 223-4 CONDENSING UNITS 6 www.daikinapplied.com

Application Data General Rooftop Applications Units are intended for use in normal heating, ventilating, and air conditioning applications. Consult your local Daikin sales representative for applications involving operation at high ambient temperatures, high altitudes, non-cataloged voltages, and for job specific unit selections that fall outside of the range of the catalog tables. For proper operation, units should be rigged in accordance with instructions stated in IM 962 (6 to 20 ton units). Follow factory check, test and start procedures explicitly to achieve satisfactory start-up and operation (refer to IM 962). Unit Location A structural engineer must verify that the roof has adequate strength and ability to minimize deflection. Unit condenser coils should be located in an area that will avoid contact with any heated exhaust air. Allow sufficient space around the unit for maintenance/service clearance. Refer to Figure 2 for recommended clearances. Consult your Daikin sales representative if available clearances do not meet minimum recommendations. Where code considerations (such as the NEC) require extended clearances, those codes take precedence. Service Clearance Application Data Allow recommended service clearances for units as shown in Figure 2. Provide a roof walkway along the sides of the unit for service and access to controls and components. Contact your Daikin sales representative for service requirements less than those recommended. Unit Wiring All units require three phase, 60 Hz, 208/230, 230, 460, or 575 volt power supply. All units include branch circuits and short circuit protection and are available with a power block. All wiring must be installed in accordance with the National Electric Code (NEC) and local codes. Figure 2: RCS 06F 20F Service Clearances www.daikinapplied.com 7 CAT 223-4 CONDENSING UNITS

Physical Data Unit Capacity and Physical Data Physical Data Table 2: RCS 06G 20F Physical Data Model Capacity and Weight RCS 06G Single 07G Single 10G Single 12F Tandem 15F Tandem 20F Tandem Capacity (tons) [kw] 6.5 [22.9] 7.5 [26.4] 10 [35.2] 12 [42.2] 15 [52.8] 20 [70.3] Number of circuits 1 Operating weight (lbs) [Kg] Shipping weight (lbs) [Kg] Compressor 245 [111.1] 307 [139.2] 557 [253.0] 650 [294.8] 746 [338.4] 952 [431.8] 252 [114.3] 313 [141.9] 597 [271.0] 690 [313.0] 786 [356.5] 992 [450.0] Quantity 1 2 Type Scroll RPM 3500 Capacity Control, Stages Refrigerant charge R410A oz. [g] Condenser Fans 1 2 219 [6209] 400 [11340] 437 [12,389] 378 [10,716] 506 [14,345] 655 [18,569] Quantity 1 2 3 CFM [L/s] 5700 [2690] 5700 [2690] 8000 [3775] 8100 [3882] 12,000 [5663] 12,000 [5663] Diameter (in.) [mm 26 [660] 26 [660] 24 [610] 24 [610] 24 [610] 24 [610] Drive Motor horsepower each [W] Condenser Coil Cabinet Direct 1/2 [373] 1/2 [373] 1/3 [249] 1/3 [249] 1/3 [249] 1/3 [249] Type ECM PSC RPM 975 1075 Quantity 1 2 Rows 1 2 3 Fins per inch 22 22 18 22 22 22 Sq. ft. [m2] 28.38 [2.64] 28.38 [2.64] 32.88 [3.05] 33.9 [3.05] 40.38 [3.75] 40.38 [3.75] Fins/tubes Finish Sheet metal Aluminum/Copper Powder Coat Galvanized Gauge (nominal) top 20 Sides 20 Base rails 14 Refrigerant Connection Vapor sweat (in.) [mm] Liquid sweat (in.) [mm] 1-1/8 [29] 1-1/8 [29] 1-3/8 [35] 1-3/8 [35] 1-5/8 [41.3] 1-5/8 [41.3] 1/2 [13] 1/2 [13] 5/8 [16] 5/8 [16] 5/8 [16] 7/8 [22] CAT 223-4 CONDENSING UNITS 8 www.daikinapplied.com

Performance Data Gross Capacity and Power Performance Data Table 3: RCS 06G 20F Gross Capacity and Power RCS 06G RCS 07G RCS 10G RCS 12F RCS 15F RCS 20F Saturated Evaporator Temperature F [ C] 40 [4] 45 [7] 50 [10] 40 [4] 45 [7] 50 [10] 40 [4] 45 [7] 50 [10] 40 [4] 45 [7] 50 [10] 40 [4] 45 [7] 50 [10] 40 [4] 45 [7] 50 [10] Outdoor Ambient Temp. F [ C] 75 [24] 80 [27] 85 [29] 90 [32] 95 [35] 100 [38] 105 [41] 110 [43] 115 [46] 86.1 [25.20] 84.0 [24.50] 81.2 [23.80] 78.7 [23.10] 76.2 [22.30] 73.6 [21.60] 70.7 [20.70] 68.0 [19.90] kw* 4.9 5.1 5.4 5.6 5.9 6.2 6.5 6.8 9.6 93.9 [27.50] 91.0 [26.70] 88.6 [26.00] 85.9 [25.20] 83.2 [24.40] 80.5 [23.60] 77.7 [22.8] 74.5 [21.80] kw* 5.0 5.2 5.4 5.7 6.0 6.2 6.5 6.9 9.5 104.6 [30.70] 102.0 [30.00] 96.4 [28.30] 93.6 [27.40] 90.7 [26.60] 87.7 [25.70] 84.4 [24.70] 81.4 [23.80] kw* 4.3 4.5 5.5 5.8 6.0 6.3 6.6 7.0 9.3 103.4 [30.3] 101.0 [29.50] 97.9 [28.7] 95.0 [27.90] 92.1 [27.00] 89.2 [26.10] 86.0 [25.20] 82.8 [24.30] kw* 6.0 6.3 6.6 6.9 7.2 7.6 7.9 8.3 8.6 112.1 [32.8] 109.0 [32.00] 106.2 [31.10] 103.2 [30.30] 100.2 [29.40] 96.9 [28.40] 93.2 [27.30] 89.8 [26.30] kw* 6.1 6.4 6.7 7.0 7.3 7.7 8.1 8.5 8.8 121.3 [35.60] 118.0 [34.70] 115.1 [33.70] 111.9 [32.80] 108.5 [31.80] 104.9 [30.70] 101.3 [29.70] 97.6 [28.60] kw* 6.3 6.6 6.9 7.2 7.6 7.9 8.3 8.7 9.0 112.3 [32.90] 110.0 [32.30] 107.9 [31.60] 104.5 [30.60] 101.3 [29.70] 97.4 [28.60] 93.5 [27.40] 89.3 [26.20] kw* 6.8 7.1 7.5 7.9 8.3 8.7 9.2 9.6 10.1 122.3 [35.90] 120.0 [35.30] 117.6 [34.5] 114.6 [33.60] 110.7 [32.40] 106.8 [31.30] 102.7 [30.10] 98.4 [28.8] kw* 6.9 7.3 7.6 8.0 8.4 8.8 9.2 9.7 10.2 133.0 [39.00] 131.0 [38.40] 128.0 [37.50] 124.6 [36.50] 120.8 [35.40] 116.8 [34.20] 111.9 [32.8] 107.7 [31.60] kw* 6.3 6.6 6.9 7.2 7.6 7.9 8.3 8.7 9.0 151.6 [44.42] 147.0 [43.06] 142.3 [41.70] 137.7 [40.33] 133.0 [38.97] 128.3 [37.61] 123.7 [36.24] 119.0 [34.88] kw* 9.5 10.0 10.6 11.1 11.6 12.1 12.7 13.2 13.7 164.3 [48.13] 159.4 [46.69] 154.5 [45.26] 149.5 [43.82] 144.6 [42.38] 139.7 [40.94] 134.8 [39.50] 129.9 [38.07] kw* 9.6 10.1 10.7 11.2 11.7 12.3 12.8 13.3 13.8 177.2 [51.90] 172.0 [50.39] 166.8 [48.88] 161.7 [47.36] 156.5 [45.85] 151.3 [44.34] 146.2 [42.82] 141.0 [41.31] kw* 9.7 10.3 10.8 11.3 11.9 12.4 12.9 13.4 14.0 200.8 [58.84] 194.3 [56.94] 187.8 [55.03] 181.3 [53.12] 174.8 [51.22] 168.3 [49.31] 161.8 [47.40] 155.3 [45.50] kw* 11.4 12.2 13.0 13.8 14.5 15.3 16.1 16.9 17.6 216.3 [63.38] 209.8 [61.47] 203.3 [59.56] 196.7 [57.64] 190.2 [55.73] 183.7 [53.82] 177.1 [51.90] 170.6 [49.99] kw* 11.8 12.6 13.3 14.1 14.8 15.6 16.3 17.1 17.8 222.7 [65.24] 217.8 [63.82] 213.0 [62.40] 208.1 [60.98] 203.3 [59.56] 198.4 [58.14] 193.6 [56.72] 188.7 [55.30] kw* 12.2 12.9 13.7 14.5 15.2 16.0 16.7 17.5 18.2 272.7 [79.90] 264.1 [77.39] 255.6 [74.88] 247.0 [72.37] 238.5 [69.87] 229.9 [67.36] 221.3 [64.85] 212.8 [62.35] kw* 17.6 18.5 19.4 20.4 21.3 22.2 23.1 24.0 24.9 294.3 [86.23] 285.6 [83.67] 276.9 [81.12] 268.1 [78.56] 259.4 [73.45] 250.7 [73.45] 242.0 [70.89] 233.2 [68.34] kw* 18.0 18.9 19.9 20.8 21.7 22.6 23.5 24.4 25.3 316.7 [92.79] 307.7 [90.14] NOTE: * kw = total kilowatts. MBh = gross capacity 1000 Btuh. All values at approximately 20 F [11.1 C] subcooling. Data includes 25 feet [7.62 m] of recommended vapor and liquid lines. 298.6 [87.50] 289.6 [84.86] 280.6 [82.22] 271.6 [79.58] 262.6 [76.94] 253.6 [74.29] kw* 18.5 19.4 20.3 21.3 22.2 23.1 24.1 25.0 25.9 61.4 [18.00] 69.5 [20.40] 76.8 [22.50] 79.9 [23.40] 88.4 [25.90] 95.5 [28.00] 87.0 [25.50] 94.3 [27.60] 101.3 [29.70] 114.4 [33.51] 125.0 [36.63] 135.8 [39.80] 148.8 [43.59] 164.1 [48.08] 183.9 [53.88] 204.2 [59.84] 224.5 [65.78] 244.5 [71.65] www.daikinapplied.com 9 CAT 223-4 CONDENSING UNITS

Performance Data Unit Capacities Figure 3: RCS 06G R410A Unit Capacities 110 Capacity at Evaporator 100 90 80 70 60 80 85 95 105 115 50 35 40 45 50 Saturated Suction Temperature Figure 4: RCS 07G R410A Unit Capacities 130 Capacity at Evaporator 120 110 100 90 80 70 80 85 95 105 115 60 35 40 45 50 Saturated Suction Temperature CAT 223-4 CONDENSING UNITS 10 www.daikinapplied.com

Performance Data Figure 5: RCS 10G R410A Unit Capacities 140 130 80 85 Capacity at Evaporator 120 110 100 90 80 95 105 115 70 35 40 45 50 Saturated Suction Temperature Figure 6: RCS 11F R410A Unit Capacities Capacity at Evaporator 140 130 120 110 100 90 80 80 85 95 105 115 70 35 40 45 50 Saturated Suction Temperature www.daikinapplied.com 11 CAT 223-4 CONDENSING UNITS

Performance Data Figure 7: RCS 12F R410A Unit Capacities Capacity at Evaporator 170 150 130 110 80 85 95 105 115 90 35 40 45 50 Saturated Suction Temperature Figure 8: RCS 15F R410A Unit Capacities Capacity at Evaporator 220 200 180 160 140 80 85 95 105 115 120 35 40 45 50 Saturated Suction Temperature CAT 223-4 CONDENSING UNITS 12 www.daikinapplied.com

Performance Data Figure 9: RCS 20F R410A Unit Capacities Capacity at Evaporator 290 265 240 215 80 85 95 105 115 190 35 40 45 50 Saturated Suction Temperature www.daikinapplied.com 13 CAT 223-4 CONDENSING UNITS

Dimensional and Weight Data Figure 10: RCS 06G and 07G Dimensions and Weights Table 4: RCS 06G and 07G Operating Weights Dimensional and Weight Data RCS model Total weight lbs. [kg] Corner weight lbs. [kg] A B C D 06G 291 [132] 50 [22.7] 73 [33.1] 69 [31.3] 99 [44.9] 07G 318 [144] 53 [24.0] 84 [38.1] 71 [32.2] 110 [49.9] Table 5: RCS 06G and 07G Unit Dimensions RCS06G RCS07G Height H Inches [mm] 45[1143] 51 [1295] Length L Inches [mm] 35.75 [908] 35.75 [908] Width W Inches [mm] 35.75 [908] 35.75 [908] Figure 11: RCS 10G and 12F Dimensions and Weights B 60.625 38.375 High Voltage 1-3/4" Dia. Hole Low Voltage 7/8" Dia. Hole 44.75 Liquid Line 5/8" Dia. Hole CONTROL PANEL ACCESS Suction Line 1-3/8" Dia. Hole D A 7.5 7.875 8.75 39.94 C 62.125 31.25 28.25 16.25 11.25 Table 6: RCS 10G and 12F Operating Weights RCS model Total weight lbs. [kg] Corner weight lbs. [kg A B C D 10G 557 [253] 137 [62.0] 148 [67.0] 131 [59.0] 142 [64.0] 12F 650 [293] 160 [72.0] 171 [78.0] 154 [70.0] 165 [75.0] CAT 223-4 CONDENSING UNITS 14 www.daikinapplied.com

Dimensional and Weight Data RCS 15F 20F Dimensions and Weights B 38.375 87.375 High Voltage 1-3/4" Dia. Hole Low Voltage 7/8" Dia. Hole 44.75 Liquid Line Line 5/8" 5/8" Dia. Dia. I.D. Hole 15 Ton 7/8" Dia. I.D. 20 Ton CONTROL PANEL ACCESS D Suction Line 1-3/8" 1-5/8" Dia. Hole A 88.88 7.5 7.875 8.75 39.94 16.25 11.25 C 31.25 28.25 Table 7: RCS 15F and 20F Operating Weights RCS model Total weight lbs. [kg] Corner weight lbs. [kg] A B C D 15F 746 [338.0] 183 [83.0] 196 [89.0] 177 [80.0] 189 [86.0] 20F 952 [432.0] 234 [106.0] 251 [114.0] 226 [103.0] 241 [110.0] www.daikinapplied.com 15 CAT 223-4 CONDENSING UNITS

Electrical Data Power Wiring Electrical Data Table 8: RCS 06G 20F Electrical Data Model Compressor Motor RCS 06G 07G 10G 12F 15F 20F Voltage 208/230 460-208/230 460 208/230 460 208/230 460 575 208/230 460 575 208/230 460 575 Phase and hertz 3 60 Number of compressors Operating Current 1 2 Rated load amps (each) 1 25 11.8 27.9 13.6 32.6 14.8 22.4 10.6 7.7 25.0 12.2 9.0 33.3 17.9 12.8 Locked rotor amps (each)1 Condenser Fan Motors 149 83 164 100 225 240 130 75 54 164 100 78 239 125 80 Voltage 208/230 460 208/230 460 208/230 460 208/230 460 575 208/230 460 575 208/230 460 575 Phase Full load amps (each) System Characteristics Single 5.3 2.2 5.3 2.2 3.5 1.6 2.4 1.4 1.0 2.4 1.4 1.0 2.4 1.1 0.8 Unit full load amps 2 27.7 15.9 30.3 17.5 34.9 19.5 49.6 24.0 17.4 57.2 28.6 21.0 73.8 39.1 28.0 Minimum circuit ampacity 34.0 19.0 37.0 21.0 48.0 22.0 56.0 27.0 20.0 64.0 32.0 24.0 83.0 44.0 32.0 Maximum fuse size (amps) or HACR circuit breaker 50 25 60 30 80 40 70 35 25 80 40 30 110 60 40 ampacity 3 Disconnect size 60 30 60 30 100 60 60 30 30 100 60 60 200 60 60 NOTE: 1. Each compressor 2. Conditions at 45 suction and 95 ambient 3. Local codes take precedent over recommended fuse size CAT 223-4 CONDENSING UNITS 16 www.daikinapplied.com

Wiring Diagrams Figure 12: RCS 06G and 07G Wiring Diagram Wiring Diagrams G/Y GND BK OFM LAC (OPT) CCH OPT. COMP (OPT) HPC LPC (OPT) HGS (OPT) Y Y Y Y Y G/Y GND BL (1T1) (1T2) (1T3) TDC R2 R1 Y1 Y2 (OPT) BR Y WIRING DIAGRAM WIRING SCHEMATIC BK BK AUX BK BK BK BR OPT AUX. (T2) (T1) (BK) (T3) T1 L1 CC (BK) T2 L2 (BK) T3 L3 GRD. LUG GND Y O BK BR BK/R R CT SEE NOTE 6 CT BL Y BR R Y BR R GND COMPONENT CODES NOTES AUX AUXILIARY CONTACT 1. CONNECTORS SUITABLE FOR USE WITH COPPER CONDUCTORS ONLY. CC COMPRESSOR CONTACTOR CCH CRANKCASE HEATER 2. COMPRESSOR MOTOR THERMALLY PROTECTED AND ALL 3 PHASE ARE CT CONTROL TRANSFORMER PROTECTED UNDER PRIMARY SINGLE PHASE CONDITIONS. COMP COMPRESSOR GND GROUND CHASSIS 3. CONNECT FIELD WIRING IN GROUNDED RAINTIGHT CONDUIT TO HGS HOT GAS SENSOR FUSED DISCONNECT VOLTAGE, HERTX, AND PHASE PER RATING PLATE. HPC HIGH PRESSURE CONTROL LAC LOW AMBIENT COOLING CONTROL 4. LOW VOLTAGE CIRCUIT TO BE N.E.C. CLASS 2 WITH A CLASS 2 LPC LOW PRESSURE CONTROL TRANSFORMER 24 VOLT, 50 OR 60 HERTZ. OFM OUTDOOR FAN MOTOR OPT OPTIONAL COMPONENT 5. TO THERMOSTAT SUB-BASE, REFER TO SYSTEM SCHEMATICS OR RES RESISTOR SCHEMATICS ON INDOOR SECTION FOR LOW VOLTAGE CONTROL WIRING. SC START CAPACITOR SR START RELAY 6. MAIN UNIT TRANSFORMER PRIMARY LEADS: TDC TIME DELAY CONTROL 208/230-460V 60HZ: BLACK-COM, RED - 208V, ORANGE - 230V, BLACK/RED - 460V 220/240V 50HZ: BLACK-COM, RED - 220V, ORANGE - 230V 380V 60HZ: ORANGE-COM, BLUE - 380V WIRING INFORMATION LINE VOLTAGE -FACTORY STANDARD -FACTORY OPTION -FIELD INSTALLED LOW VOLTAGE -FACTORY STANDARD -FIELD INSTALLED REPLACEMENT WIRE -MUST BE THE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (105C. MIN.) WARNING -CABINET MUST BE PERMANENTLY GROUNDED AND CONFORM TO I.E.C., N.E.C., C.E.C., NATIONAL WIRING REGULATIONS, AND LOCAL CODES AS APPLICABLE. BK...BLACK BR...BROWN BL...BLUE WIRE COLOR CODE G...GREEN GY...GRAY O...ORANGE PR...PURPLE R...RED W...WHITE Y...YELLOW ELECTRICAL WIRING DIAGRAM CONDENSING UNITS 208/230, 380, 460V, 3 PH, 60 Hz, 220/220, 380/415V, 3 PH, 50 Hz MODELED BY: DATE: PART NO.: REV.: TEW 06-09-17 90-101229-47 05 NOTE: THE DOTTED BOX NEAR THE DRAWING NUMBER REPRESENTS A.25 X.25 2D DATA MATRIX. SEE ADS-104669-01 FOR DATA MATRIX SPECS. APPROVED: MODELED BY: PART NO.: CHECKED: DATE: TEW 06-09-17 90-101229-47 ORIGINAL RELEASE NO.: A-1093S000 REV: 05 Y Y www.daikinapplied.com 17 CAT 223-4 CONDENSING UNITS

GND Wiring Diagrams Figure 13: Typical Wiring Schematic - RCS 10G BK BL BR A B C D Y TB 1 Y BR BR A B C D BL BK TB 2 TS 1 Y1 Y2 BL BL LINE VOLTAGE -FACTORY STANDARD -FACTORY OPTION -FIELD INSTALLED LOW VOLTAGE -FACTORY STANDARD -FIELD INSTALLED REPLACEMENT WIRE -MUST BE THE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (105C. MIN.) WARNING -CABINET MUST BE PERMANENTLY GROUNDED AND CONFORM TO I.E.C., N.E.C., C.E.C., NATIONAL WIRING REGULATIONS, AND LOCAL CODES AS APPLICABLE. G/Y G/Y TS TERMINAL STRIP COMP ODF2 ODF1 BK...BLACK BR...BROWN BL...BLUE WIRE COLOR CODE G...GREEN GY...GRAY O...ORANGE PR...PURPLE R...RED W...WHITE Y...YELLOW ELECTRICAL WIRING DIAGRAM APPROVED: CHECKED: MODELED DATE: BY: JHB 11/14/2017 PART NO.: 90-42663-13 ORIGINAL RELEASE NO.: A-1073S009 REV: 00 : GND BL WIRING INFORMATION NOTES COMPONENT CODES CAT 223-4 CONDENSING UNITS 18 www.daikinapplied.com

Wiring Diagrams Figure 14: RCS 12F 20F Wiring Diagram COMPONENT CODE AH SUPPLY FAN CC COMPRESSOR CONTACTOR CCH CR ANKCAS E HEAT ER COMP COMPRESSOR CT CONTROL TRANSFORMER DISC DISCONNECT SW ITCH FC FAN MOTOR CONTACTOR FCC FAN CYCLE CONTROL GND GROUND HR HEATER RELAY AS NEEDED HPC HIGH PR ESSURE CONTROL LPC LOW PR ESSURE CONTROL MS METAL ST RIP OFM OUTDOOR FAN MOTOR RC R UN CA PACITOR R RELAY TB TERMINAL BLOCK TH TH ER MOSTAT HEAT ING TDC TIME DE LAY CONTROL THM MOTOR SAFETY TH ER MOSTAT TOR THERMAL OV ER LOAD RE LAY WIRE NUT NOTES: 1. RE PL AC EMENT WIRE & FUSES MUST BE SAME TY PE & SIZ E AS OR IGINAL. 2. UNIT MUST BE PE RMANENTLY GROUNDED AND CONFOR M TO N. E. C. AND LO CAL CODES. 3. MAXIMUM IN RUSH VA NOT TO EXCEED 92 VA. 4. MINIMUM WIRE SIZE BASED ON 75 DE GREES C INSULATION COPPER WIRE. WIRING IN FORMATION 1. LINE VOLTAG E FACTORY STANDARD FACTORY OP TION FIELD INSTALLED 2. LOW VOLTAG E FACTORY STANDARD FACTORY OP TION FIELD INSTALLED 3. RE PL AC EMENT WIRE MUST BE TH E SAME SIZE AND TY PE OF INSULATION AS OR IGINAL (105 C MIN.) WARNING CABIN ET MUST BE PE RMANENTLY GROUNDED AND CONFORM TO I. E. C., N. E. C. (C.E.C.-CANADA) AND LO CAL. CODES AS APPLIC ABLE. WIRE COLOR CODE BK BLACK O ORANGE BR BROWN PR PURPLE BL BLUE R RED G GREEN W WHITE GY GRAY Y YELLOW WIRING SCHEMAT IC CONDENSING UNIT 208-230, 460, 575, 3 PH, 50 & 60 Hz 380, 3 PH, 60 Hz 90-42663-08-03 www.daikinapplied.com 19 CAT 223-4 CONDENSING UNITS

Engineering Guide Specification Engineering Guide Specification Part 1: General 1.01 Summary: A. Section includes design, performance criteria, refrigerants, and installation requirements for aircooled split condensing units 1.02 References A. ARI-365 Commercial and Industrial Unitary Aircooled Condensing Units B. ANSI / ASHRAE 15 Safety Standard for Refrigerated Systems 1.03 Submittals A. Submit Shop drawings and product data in accordance with the specifications. B. Submittals shall include the following: 1. Dimensioned drawings with required clearances and location of all field connections. 2. Summary of all auxiliary utility requirements, such as electricity, water, compressed air, etc. Summary shall indicate quality and quantity of each required utility. 1.04 Qualifications A. Qualifications: Equipment manufacturer must specialize in the manufacture of the type of products specified and have five years experience with similar equipment and refrigerant offered. B. Regulatory Requirements: Comply with the codes and standards specified. C. Manufacturer s plant must be ISO Registered. 1.05 Delivery and Handling A. Condensing units shall be delivered to the job site assembled and charged with a holding charge of dry nitrogen. B. Comply with the manufacturer s instructions for rigging and handling equipment. 1.06 Warranty A. The refrigeration equipment manufacturer s initial warranty shall be within 12 months from start-up or 18 months from shipment, whichever occurs first. The warranty shall provide for repair or replacement due to material and workmanship that proves defective within the above period, excluding refrigerant. 1.07 Maintenance A. Include instructions for installation, maintenance and service. B. Maintenance of the units shall be the responsibility of the owner and performed in accordance with the manufacturer s instructions. Part 2: Products 2.01 Acceptable Manufacturers A. Basis of design: Daikin B. (Approved Equal) 2.02 Unit Description A. Provide and install as shown on the plans factoryassembled, air-cooled scroll compressor, R410A condensing units in the size and quantity specified. Each unit shall consist of hermetic scroll compressor air-cooled condenser section. B. The complete unit shall be UL listed. 2.03 Design Requirements A. General: Provide a complete condensing unit as specified herein and as shown on the drawings. The unit shall be in accordance with the standards referenced in section 1.02 and any local codes in effect. B. Performance: Refer to the schedule of performance on the drawings. CAT 223-4 CONDENSING UNITS 20 www.daikinapplied.com

Engineering Guide Specification 2.04 Condensing Section (Scroll) A. Air-cooled Condenser 1. Exterior panels shall be constructed of prepainted steel with a 1000-hour ASTM B117 salt spray test. 2. The condensing section shall be open on the sides and bottom to provide access and to allow airflow through the coils. Condenser coils shall be constructed with 3/8 copper tubing mechanically bonded to aluminum fins for maximum heat transfer. Each condenser coil shall be factory leak tested with high-pressure air under water. 3. Condenser fans shall be direct drive, propeller type designed for low tip speed, vertical air discharge, and include service guards. Fan blades shall be constructed of steel and riveted to a steel center hub. Condenser fan motor shall be direct drive, single phase permanently lubricated PSC motors with inherent thermal overload. 4. Unit shall have standard pressure controls that cycle the condenser fan motors to maintain condensing pressures for operation down to 0 F ambient. 5. Unit shall be equipped with full-face louvers for hail protection. B. Scroll Compressors 1. Unit shall have heavy-duty Copeland scroll compressors. 2. Compressor shall be equipped with thermal overload protection. 3. Compressors shall be isolated with resilient rubber isolators to decrease noise transmission. 4. Compressor circuit shall be complete with low pressure control, liquid line shut off valve, and manual reset high pressure safety switch. C. Refrigerant Circuit: Capped connections shall be external to the unit providing for field connection of refrigerant piping. D. Unit shall have a liquid line and suction line service valve. 2.05 Controls A. Unit shall be equipped with a 24 V terminal strip for field supplied and installed controls. 2.06 Electrical A. All wiring shall comply with UL requirements. The unit shall be provided with a factory wired weatherproof control panel. Unit shall have a single point power terminal block for main power connection. A terminal board shall be provided for low voltage control wiring. B. Unit shall be equipped with low voltage transformers and motor starters. Part 3: Execution 3.01 Installation A. Install in strict accordance with manufacturer s requirements, shop drawings, and contract documents. B. Adjust and level unit in alignment on supports. C. Coordinate electrical installation with electrical contractor. D. Coordinate controls with control contractor. 3.02 Start-Up A. Install proper charge of refrigerant and oil. B. Provide testing and starting of machine, and instruct the owner in its proper operation and maintenance. www.daikinapplied.com 21 CAT 223-4 CONDENSING UNITS

Daikin Applied Training and Development Now that you have made an investment in modern, efficient Daikin equipment, its care should be a high priority. For training information on all Daikin HVAC products, please visit us at www.daikinapplied.com and click on Training, or call 540-248-9646 and ask for the Training Department. Warranty All Daikin equipment is sold pursuant to its standard terms and conditions of sale, including Limited Product Warranty. Consult your local Daikin Applied Representative for warranty details. To find your local Daikin Applied Representative, go to www.daikinapplied.com. Aftermarket Services To find your local parts office, visit www.daikinapplied.com or call 800-37PARTS (800-377-2787). To find your local service office, visit www.daikinapplied.com or call 800-432-1342. This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.daikinapplied.com. Products manufactured in an ISO Certified Facility. CAT 223-4 (06/18) 2018 Daikin Applied (800) 432 1342 www.daikinapplied.com