Fire Safety. Installation Instructions Model SMB-2 Main Control Board OPERATION INSTALLATION

Similar documents
Fire Safety. Installation Instructions Model MMB-2 Main Control Board OPERATION. INSTALLATION Always remove power before installation.

AND ARCHITECT SPECIFICATIONS

Fire Safety. Installation Instructions. Model RCC-2/R and RSE-1 Remote Control Centers OPERATION INTRODUCTION INSTALLATION

Installation Instructions Model DLC

Fire Safety. Installation Instructions. Model ADBX-11. Audible Base INTRODUCTION. Model ADBX-11

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

Advanced Protection System

MXL-IQ CONTROL PANEL. Operation, Installation, and Maintenance Manual. Siemens Industry, Inc. Building Technologies Division Florham Park, NJ

Installation Instructions Model HZM

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual

Marine Fire Detection System Manual MXL Control Panel

Addressable NAC Output Module D327A

ANNUNCIATOR FIXED MODULE

Fire Safety. Installation Instructions Model NIM-1W Network Interface Module MXL NETWORK INTERFACE APPLICATIONS OPERATION NIM-1W

Installation Instructions Model SSD-C-REM

Cautions and Warnings. Introduction 4009 NAC POWER EXTENDER

AND ARCHITECT SPECIFICATIONS

PSN-1000 & PSN 1000(E) Installation Manual

Installation Instructions Model CDC-4

4100U City and Relay Cards Installation Instructions

FireSeeker Fire Alarm Control Panel Model FS-100 Installation, Operation, and Maintenance Manual

AND ARCHITECT SPECIFICATIONS

Operating Instructions MXL Multi-Line Keyboard/Display Panel

LDM Series Lamp Driver Modules For Graphic Annunciation and Control

Installation, Operating and Maintenance Manual

Fire Safety. Installation Instructions Model PSR-1 Remote Power Supply INTRODUCTION. Figure 1 PSR-1 Remote Power Supply

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

FireNET Plus Wiring Instructions

Remote NAC Power Supply D7038

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description

Supplement to The PDRP-1001/PDRP-1001A/PDRP-1001E Deluge Preaction Control Panel Manual

TECHNICAL DATA OBSOLETE

Booster Power Supply Manual

Harrington Signal HS-3100/3200 Fire Alarm Control Unit

Installation Instructions Model ABHW-4S

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

Conventional Releasing Control Panel

AND ARCHITECT SPECIFICATIONS

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

June 10, 2002 DF C S2424

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

TYPE C: RETURN AIR UNDER POSITIVE PRESSURE FROM SEPARATE BLOWER

30.45 Electric Release PDRP-2001

Public Safety DAS Annunciator Panel

LifeAlarm Fire Alarm Controls

Multiplex Eight Input Remote Modules

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

/5121/5122 TrueAlert Power Supply Installation Instructions

MR-2602 Two Zone Fire Alarm Control Panel

INSTALLATION GUIDE XR5FC AND XR5SL COMMERCIAL FIRE PANELS

FireSeeker Fire Alarm Control Panel Model FS-250 Installation, Operation and Maintenance Manual

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

Air Duct Housings. Description

NETWORK FIRE ALARM CONTROL PANEL. Features

General Routing Interface

DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

Addressable Fire Alarm Control Panel

These instructions detail procedures to follow in order to avoid damage to equipment.

GENERAL STANDARD FEATURES. ISO-9001 Engineering and Manufacturing Quality System Certified to International Standard ISO-9001 PATENT PENDING

LED Driver Module. These instructions contain procedures to follow in order to avoid personal injury and damage to equipment.

MPC-6000 / MPC-7000 / RND-2

Desigo TM Fire Safety System A comprehensive fire-protection system

ACCURATE ELECTRONICS INC PO BOX SW HALL BLVD BEAVERTON OR USA FAX

I NSTALLATION M ANUAL

I TS-12 1 Y K DO WHAT THEY DON T. Model. INSTALLATION lnstrljctlons. FIRE BURGLARY lnstrumentsrn INC.

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep.

IDP-Zone-6 Six Zone Interface Module

Cerberus TM PRO Fire Safety System A comprehensive fire-protection system

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

July 14, 1999 DF C-100.

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

TECHNICAL DATA SHEET CONVENTIONAL FIRE ALARM SYSTEMS Conventional Fire Alarm Control Panel

LifeAlarm Fire Alarm Control Panels

AL600ULADA. NAC Power Extender. Installation Guide

ACC-25/50ZST. Zoned System Voice with Telephone Evacuation Control Panel

good things in small packages

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES

The TC-4F. Time Control Module C P/N 15972:C ECN For the Sensican 2000 Fire Alarm Control Panel

The ACM-8R Annunciator Control Module

D326A/D334A/D339A. Installation Instructions. Point Contact Modules

Notification Appliance Circuit Module

MANUAL RESET ALARM RELEASE

SC-6 Six Supervised Control Module

FA-1000 SERIES. Microprocessor-Based Fire Alarm Control Panel. Installation and Operation Manual

E-FSC. Conventional Fire Alarm Control Panels. Standard Features. Overview

INTELLIGENT FIRE ALARM AND AUDIO NETWORK SYSTEM. Features

POWERPATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262)

MMF Six Zone Interface Module

This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control

CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM

AL600ULX Series. Power Supply/Charger. Installation Guide

FCPS-24F FIRE ALARM FIELD CHARGER/POWER SUPPLY FOR FIRE PROTECTION/SIGNALING SERVICE FCPS-24F/FCPS-24FE. Field Charger/Power Supply

ACCURATE ELECTRONICS INC

FireShield Plus. GE Security. EST Life Safety & Communications Conventional Small Building Solutions. Conventional Fire Alarm Control Panels

1 INTRODUCTION NOTICE WARNINGS AND CAUTIONS NATIONAL APPROVALS EMC COMPATIBILITY UNPACKING...

21-light Remote Annunciator. Owner s Manual

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs

Transcription:

Fire Safety Installation Instructions Model SMB- Main Control Board OPERATION The SIEMENS Model SMB- board in each MXL-IQ System controls operations and monitors input device identity, network communication, and operator commands that are entered through the MKB- Annunciator/ Keyboard. The SMB- also provides two analog loop driver circuits. Each ALD loop can be used as Class B or Class A and can monitor and control up to 60 intelligent devices as well as programmable device relays. The SMB- module is field programmable. It is equipped with two programmable Class B (Style Y) or Class A (Style Z) notification appliance circuits. Each circuit can activate up to.5 amps of audible or visual notification appliances. The module also has auxiliary relays for the external monitoring of Common System Alarm and Common System Trouble. The SMB- includes a built-in battery charger and transfer circuit. The charger is microprocessor controlled and incorporates a brownout circuit that switches the System to standby batteries during the loss or reduction of the primary source AC. The System can display the real time battery voltage, the AC voltage, and the charger current on the MKB- alphanumeric display. It also has a amp, VDC output that powers CZM-/B6 modules. INSTALLATION Remove all system power before installation, first battery and then AC. (To power up, connect the AC first and then the battery.) Installing the SMB- Board Unpack the SMB-. Inspect the module, looking for such things as integrated circuits (ICs) not firmly seated in their sockets, bent IC pins, connectors not properly installed, dirt, packing material on the board, etc. The installation kit consists of the following items: Two #6 nuts Four #6 screws Six #6 washers Six #6 lockwashers Eight metal jumpers Three resistors Battery cable with wire To install the SMB-:. Place the SMB- over the two studs in the upper right-hand portion of the backbox, as shown in Figure.. Secure in place using the hardware provided. Be sure the screws and nuts are tight, as they provide the earth ground connection for the SMB-. Siemens Building Technologies, Inc. 8 Fernwood Road Florham Park, New Jersey 079 Siemens Building Technologies, Ltd. Kenview Boulevard Brampton, Ontario L6T 5E CN P/N 5-0959-7

SMB- Figure Installing the SMB- Figure SMB- Main Board

CONFIGURATION The SMB- has two jumpers jumper P5 for MNET and jumper P7 for Real Time clock which must be set for proper operation. Refer to Figure for the location of the jumpers. MNET Set jumper P5 on the SMB- to the S position. Real Time Clock The second jumper on the SMB- is P7 which must be set for the real time clock to operate properly. Move the jumper to the on position to provide backup battery power to the real time clock. Note: The real time clock requires MXL-IQ firmware Revision 5.0 or higher to operate. Internal Wiring To complete the SMB- internal wiring connections, follow the steps below, skipping those that do not apply to your particular MXL-IQ System.. Main Power Connections Primary power for the SMB- is provided by the MPS-6/-6W or MPS-/-W. Both of these mount in the lower right-hand corner of the MXL-IQ enclosure. Follow the instructions below for the appropriate power supply. MPS-6/-6W Install the MPS-6/-6W (See MPS-6/-6W Instructions, P/N 5-090/W). With the AC mains disconnected, connect the MPS-6/-6W power cable to P of the SMB-. Be sure that the jumper assembly is installed in P of the SMB-. If this jumper is not installed, the SMB- will detect a permanent AC fail or indicate auxiliary power voltage is low. MPS-/-W Install the MPS-/-W (See MPS-/-W Instructions, P/N 5-0900/W). Remove and discard the jumper assembly installed in P of the SMB-. Disconnect the AC mains. Connect the MPS-/-W power cable to P of SMB-.. Battery Power Connection The SMB- kit includes a battery cable (wiring harness). Use the harness to connect the V backup batteries to P of SMB-.. MOM-/ Optional Module Card Cage There are two connections between the SMB- and the MOM-/ board. a. If the SMB- is replacing an SMB-, then the cable to P (P is limited to amps) can be installed to the SMB-, or the SMB- can be wired as shown in Figure. The SMB- allows the use of either an MPS-6/-6W or an MPS-/-W. TB terminals and 5 supply V to the MOM- with a maximum of 6 amps (MPS-6/-6W) or amps (MPS-/-W) available. This output must be derated by the total current drawn from NAC (.5A max), NAC (.5A max) and the CZM-/B6, power (A max) on the SMB-. Connect TB, and 5 on the SMB- to TB6, and on the MOM-/. Refer to Figure for the wiring diagram. b. The second connection provides 5V power and the communication interface. Connect the 8-wire ribbon cable from P7 on the MOM-/ to P6 on the SMB-. Refer to Figure. MOM- P7 TB6 CABLE P/N 555-90967 SUPPLIED WITH MOM- 5 P6 AWG MIN 6A MAX (MPS-6) A MAX (MPS-) 8- VDC NOT POWER LIMITED TB SMB- Figure MOM- V Connection

Field Wiring (Refer to Figure ) The screw terminals for the field wiring circuits are located on the left and right sides of the SMB-. They are labeled TB through TB5. The field wiring circuits available are: CZM-/B6 power Analog device loop Analog device loop Notification appliance circuit (Styles Y and Z) Notification appliance circuit (Styles Y and Z) Common alarm relay Common trouble relay Style RS-85 Network (MNET) The following sections describe each circuit type and give the related instructions. Refer also to the wiring diagrams. Auxiliary Class B V Power Auxiliary power is available on TB5, terminals 9 and. The circuit is power limited per NEC Article 760 and is rated at amp, 8- VDC. This power supply is for use with the CZM-/B6 Remote Conventional Zone module. Figure shows Class B wiring. Class B wiring can be used to obtain the maximum of 0 CZM-/B6s. Each Class B wire run can support a maximum of 0 CZM-/B6s, ohms max. Multiple Class B power connections can be used provided you do not exceed the rating above (0 CZM-/B6s max and ohms per run max). For example, you could have four Figure CZM-/B6 Supervised Auxiliary Power Class B Wiring individual Class B power runs, for a total of 0 devices (6,,, and 7 CZM-/B6s), each of the four runs not exceeding ohms resistance. Refer to Wiring Specification for MXL, MXL-IQ and MXLV Systems, P/N 5-0977 revision 6 or higher, for additional wiring information. Analog Device Loops and (TB and TB) These two loops each support up to 60 analog type devices. To install a device for Class B, refer to Figure 5 and the electrical specifications. To install a device for Class A, refer to Figure 5 and the electrical specifications. Electrical Specifications for the Analog Device Loops. Electrical ratings: SUPERVISORY: 0 VDC peak, 66mA max ALARM: 0 VDC peak, 66mA max (60 devices in alarm). All wiring must be in accordance with Article 760 of NEC or the local building codes. Refer to Figure 5.. Only the list of devices in Table may be used. A maximum of 60 devices may be connected to a single loop.. No end of line device is required. 5. Both circuits are power limited per NFPA 70, NEC. Each detector, or group of detectors, requires a two-wire circuit of 8 AWG minimum thermoplastic fixture wire, enclosed in a conduit, or 8 AWG limited-energy shielded cable without conduit, if permitted by local building codes. 6. Total circuit resistance must not exceed 00 ohms. Maximum capacitance: 0.µF Line to Line. 0.8µF Line to Ground. 7. T-tapping is NOT allowed on Class A loops. 8. Refer to Wiring Specification for MXL, MXL-IQ and MXLV Systems, P/N 5-0977 revision 6 or higher, for additional wiring information.

TB TB INSTALL METAL JUMPER (IF INCLUDED IN KIT) CLASS B WIRING* SUPERVISED, POWER LIMITED PER NEC 760 CLASS A WIRING** SUPERVISED, POWER LIMITED PER NEC 760 INSTALL METAL JUMPER (IF INCLUDED IN KIT) T-TAPPING ALLOWED INITIATING DEVICE TB TB NO T-TAPPING ALLOWED *OPERATES IN FULL CONFORMITY WITH STYLE **OPERATES IN FULL CONFORMITY WITH STYLE 6 Figure 5 Wiring the Analog Loops Compatible Devices TABLE COMPATIBLE DEVICES Base Installation Instructions C ZM- P/N 5-09075-8 C ZM-B6 P/N 5-09555-5 FP-* FP-*(d) FPT-* ID-60I/IH/IA/IAH ID-60IB/IBH ILI-/H ILI-A/AH ILP-/ILPT- ILP-(d) ILP-* ILP-*(d) ILT- DB-, DB-XRS DB-S DB-ADPT DB-ADPT ADBI-60 AD-ADPT AD-P/XP R P/N 5-095659- DB-, DB-XRS DB-S DB-ADPT DB-ADPT ADBI-60 AD-ADPT P/N 5-09087- AD-I AD-XRI P/N 5-09-6 P/N 5-095-5 P/N 5-09587- P/N 5-09587- P/N 5-0959-7 AD-ILP AD-XRILP P/N 5-09-6 P/N 5-095-5 P/N 5-09508-5 AD-ILP AD-XRILP P/N 5-09-6 P/N 5-095-5 P/N 5-096- M SI-0/0 P/N 5-09090- M SI-0B/0B P/N 5-099-5 M SI-MB6 P/N 5-096- T RI-B6/B6D/B6R P/N 5-095- T RI-B6M P/N 5-0957- T RI-S/D/R P/N 5-096- * The FP- is only compatible with MXL-IQ Rev. 6.0 or greater firmware. **The ILP- is only compatible with MXL-IQ Rev..0 or greater firmware. When the CSG-M is configured, the DUCT application must be selected when the device is used in an air duct housing or in a spot duct application. 5 Notification Appliance Circuits (TB5, - and TB5, 5-8) (Refer to Figure 6). These circuits are for notification appliances only, NFPA 7 Local. For NFPA 7 Municipal Tie or NFPA 7 Leased Line, use the Model CSM-.. All wiring must be in accordance with Article 760 of NEC or local building codes.. Both notification appliance circuits are power limited to NFPA 70 and NEC.. Electrical ratings: Supervisory: 8 to VDC, ma max Alarm: 8 to VDC,.5A max 5. End of line device: P/N 0-8080 6. Line Resistance: Must not exceed ohms max 7. Compatible Notification Appliances: For a list of Compatible Notification Appliances, refer to P/N 5-0966. 8. Refer to Wiring Specification for MXL, MXL-IQ and MXLV Systems, P/N 5-0977 revision 6 or higher, for additional wiring information.

CLASS B WIRING (STYLE Y) SUPERVISED POWER LIMITED 8, 7, 6, TB5 INSTALL METAL JUMPER (IF INCLUDED IN KIT) NOTIFICATION APPLIANCES EOL*.K /W 5, INSTALL METAL JUMPER (IF INCLUDED IN KIT) * EOL DEVICE P/N 0-8080 CLASS A WIRING (STYLE Z) SUPERVISED POWER LIMITED 8, 7, 6, 5, TB5 EOL*.K /W * EOL DEVICE P/N 0-8080 NOTIFICATION APPLIANCES Figure 6 Wiring Notification Appliance Circuits (Polarity Shown In Supervisory) Common Alarm Relay The common alarm relay changes state whenever a fire alarm is detected. The relay is rated A, 0 VDC/0 VAC resistive. See Figure 7 for the wiring connections. Use only with power limited/class circuits. Common Trouble Relay The trouble relay changes state whenever a System trouble is detected. The relay is rated for A, 0 VDC/0 VAC resistive. Refer to Figure 7 for the wiring connections. Use only with power limited/class circuits. FUSE REPLACEMENT IN THE MXL-IQ SYSTEM F F F F MPS-6 Input Battery Reversal FUSE RATINGS CZM-/B6 Power V Output (TB, terminals and 5) 8A, AG, Normal Blow 0A, AG, Normal Blow A, AG, Normal Blow 5A, AG, Normal Blow NOTE: The fuses are located on the upper left and right corners of the SMB- board. Style Network (MNET) The SMB- provides a Style MNET network for connection to remote annunciators (MOI-/7, RCC-/F). See Figure 8 for wiring instructions. 6

RATINGS A, 0 VDC/0 VAC RESISTIVE COILS ARE SUPERVISED WHEN DE-ENERGIZED CONTACTS ARE SHOWN IN NORMAL STATE REFER TO WIRING SPECIFICATION FOR MXL, MXL-IQ AND MXLV SYSTEMS, P/N 5-0977 REVISION 6 OR HIGHER, FOR ADDITIONAL WIRING INFORMATION. Figure 7 SMB- Relay Connections. Place EOLRs at the extreme ends of the network.. Use two EOL resistors only.. The SMB- does not have to be at the end of the network.. No T-Tapping. 5. Refer to Wiring Specification for MXL, MXL-IQ and MXLV Systems, P/N 5-0977 revision 6 or higher, for additional wiring information. Figure 8 Style Network (MNET) 7

Siemens Building Technologies, Inc. 8 Fernwood Road Florham Park, New Jersey 079 Siemens Building Technologies, Ltd. Kenview Boulevard Brampton, Ontario L6T 5E CN P/N 5-0959-7