TECHNICAL MANUAL EXPLOSION PROOF STATUS LIGHT / LAMP BSL 125 / BSL 150. Scope: EXcite USER MANUAL BSL 125 / BSL 150. Date:

Similar documents
Approved by: Document no.: EGT

TECHNICAL MANUAL EXPLOSION PROOF SOUNDER/ HORN & BEACON BHB 125/ BHB 150. Scope: EXcite USER MANUAL BHB 125 / BHB 150 Date: Page: Checked by: Rev.

TECHNICAL MANUAL EXPLOSION PROOF MANUAL CALL POINT BCP 135. Scope: EXcite USER MANUAL BCP 135. Date: Page: Page 1 of 6.

EX-TECH SIGNALLING SAS SD100-1 WEATHERPROOF SOUNDER/HORN TECHNICAL MANUAL

INSTRUCTION MANUAL (ATEX / IECEx)

INSTRUCTION MANUAL (ATEX/IECEx/SIL2) BExBG05D-SIL Flameproof Xenon SIL 2 Beacons For use in Flammable Gas and Dust Atmospheres

INSTRUCTION MANUAL (ATEX / IECEx)

INSTRUCTION MANUAL (ATEX / IECEx)

INSTRUCTION MANUAL IS-mB1 Minialite Intrinsically Safe Round LED Beacon

INSTRUCTION & SERVICE MANUAL

INSTRUCTION MANUAL (ATEX/IECEx/SIL2)

INSTRUCTION MANUAL. E2xB05 & E2xB10 Xenon Beacons For use in Hazardous Locations

4) Intrinsic Safety Certification

Technical Manual for the Alarm Pull Station PH1

standards: standards:

INSTRUCTION MANUAL. D2xB1XH1 & D2xB1XH2 Xenon Beacons For use in Hazardous Locations

Technical Manual for the Horn DB1P UL DB1HP UL

EJBX. Ex d. AISI 316L stainless steel. - Zone 1, 2, 21, 22 - Group IIB+H2 - Stainless steel junction boxes - Choice of 13 sizes - IP 66 / 67

INSTRUCTION MANUAL. D1xB2XH2 Xenon Beacon For use in Hazardous Locations. 2) Rating & Marking Information

INSTRUCTION MANUAL. D1xB2XH1 Xenon Beacon For use in Hazardous Locations. 2) Rating & Marking Information

INSTRUCTION MANUAL (ATEX / IECEx)

Electrical Installations Design, Selection, Erection and Inspection

REGULATIONS EUROPEAN ATEX DIRECTIVE. INTERNATIONAL SCHEME: IECEx AREAS CLASSIFICATION DEFINED BY DIRECTIVE 1999/92/EC

Phoenix Explosion-proof. Pan & Tilt heads and Camera Housings for potentially exposed environments. Answers for infrastructure.

Technical Manual for the Strobe - SM87 HXB

Technical Manual for the Fire Alarm Call Point - SM87 PBL

Hazardous Areas - EXPLOSIONPROOF SOLENOIDS

Flameproof Manual Call Points

manual addendum DELPHI Ex

INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS FAW, FAW-C & FAW-C-T TYPE AIR WARMERS FCR & FCR-A TYPE CONVECTORS

E2S Datasheet v10a. The IS-mA1 is suitable for all intrinsically safe signalling applications including fire, security and process control.

GRP Flameproof Combination Signal db(a) / 5 Joule Series YL6S

Multiple Status Indicators Series MEXE, MS25, MS35, MS45, MS55

Beamex Calibration White Paper. Calibration in hazardous areas

Explosion-proof Immersion Heater Type D-8660

OPTIWAVE X500 Supplementary Instructions

Global Series. Installation and Maintenance Instructions. Model G-STR Strobe Beacon. For Use in Hazardous Locations

Earth-Rite II PLUS Static Earthing System

Beamex. Calibration White Paper. Calibration in hazardous areas

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-d.

Phoenix Flameproof. Pan & Tilt heads and Camera Housings for potentially explosive environments.

LIGHTING TEF 9980 STATUS LIGHT, MAIN LIGHT & REPEATER LIGHT ZONE 1, ZONE 2 & SAFE AREA USER MANUAL

Officine Meccaniche M.A.M. series for command, control, signaling and/or automation. DOCUMENT IS-EJB-A-14 rev. 0

CCAC. Ex d. - Zone 1, 2, 21, 22 - Group IIC - Aluminium junction boxes - Choice of 5 sizes - IP66. Stainless steel bolts.

INSTRUCTION MANUAL (ATEX)

Flammable gases Detectors. Model DAX 03F DAX 03F- C DAX 03F- H. Note for installation, use and maintenance. Version 1.2

E2S Datasheet v10a

Duct heaters for ATEX/IECEx hazardous areas or in non-atex version

Guide for hazardous areas

Explosion Proof Combination Signal db (A) / 5 Joule

Immersion heaters for ATEX/IECEx hazardous areas or in non-atex version

INSTRUCTION & SERVICE MANUAL

Dual certification! Air handling units for potentially explosive atmospheres

PRODUCT OVERVIEW. Light fittings, boxes & custom built control panels for explosive atmospheres

BC9700 series High Power LED Explosion Proof Light

Flameproof Manual Call Points Series MCP

official distributor of Newson Gale Ltd.

USER MANUAL FOR EXPLOSION PROTECTED FLUORESCENT LIGHT FITTING type PSF 218

Explosion Proof Combination Signal db (A) / 5 Joule Series YL60

INSTRUCTION & SERVICE MANUAL D1xS1 & D1xS2 ALARM HORNS For Use In Hazardous Locations - Gas

Matters Needing Attention of Electrical Equipment Installation Engineering in Hazardous Areas. Wang Qiaoli

BOBINE ANTIDEFLAGANTI (ATEX) ISTRUZIONI EXPLOSION PROOF COILS (ATEX) - INSTRUCTIONS

Instructions. Explosion Proof Smoke Detector U Rev: 9/

Operating Instructions

SPECIFICATION SHEET. Installation, Operation, Maintenance Instructions for safety use Series EX SOCKET SWITCH

Airo Wireless Intrinsically Safe White Paper. Written By: David Schmitt

UL HAZARDOUS LOCATIONS SERVICES

Dräger Polytron 5700 IR Detection of flammable gases and vapours

CCA-03EX. - Easy installation - Low energy consumption - New COB LED technology - Zone 1, 2, 21, 22. Directional LED spotlights

User manual. Explosion-safe window air conditioning system Type series AR-054. II 3 G Ex ic nac h IIC T3 Gc

Circulation heaters for ATEX/IECEx hazardous areas or in non-atex version

SOLUZIONI PER ATMOSFERA ESPLOSIVA

IECEx Certificate of Conformity

Intrinsically Safe Solutions

IECEx Certificate of Conformity

Hazardous Area Zirconia Oxygen Systems

HAZARDOUS AREA CLASSIFICATION AND SELECTION OF EQUIPMENT FOR SAFE USE THEREIN FROM AN ELECTRICAL VIEWPOINT

USER MANUAL FOR EXPLOSION PROTECTED FLUORESCENT LIGHT FITTING type PSF 236

Certificate of Compliance

THE BELGIAN PIONEER IN GAS DETECTION

DB4 Range - SPEAKERS - Up to 25 Watts

IECEx Certificate of Conformity

PYROS. Código: FT-PY01-I Revisión: TECHNICAL DATA. Polycarbonate tube of 4 mm. thickness LIGHT FITTING. Laquered steel painted white

OPTIBAR DP 7060 Supplementary Instructions

A guide to the use of electrical equipment in potentially explosive atmospheres To view this document in PDF format click here.

GS100-ATEX. Hazardous Areas Infra-Red Beam PULSE MODULATED ACTIVE INFRA-RED BEAM FOR HAZARDOUS AREAS ZONE 1 OR ZONE 2 GENERAL

Survey of electrical equipment installed in hazardous areas on tankers

DB5 Intrinsically Safe Sounder Type DB-5

GS100-ATEX. Hazardous Areas Infra-Red Beam PULSE MODULATED ACTIVE INFRA-RED BEAM FOR HAZARDOUS AREAS ZONE 1 OR ZONE 2 GENERAL

USER GUIDE EXPLOSION-PROOF TELEPHONES ATEX GASES AND DUSTS TYPE 227A1 IM2 FOR GROUP I MINING II 2GD FOR GROUP IIC AND IIIC GASES AND DUSTS

Installation Guide. EXGP Oxygen Analyzer System (ATEX) Interface Electronics Unit

Equipment and Solutions

Instructions. Det-Tronics SmokeWatch Explosion Proof Smoke Detector U Rev: 3/

PILOT VALVE ENCLOSURES FOR HAZARDOUS LOCATIONS PENTAIR CLEAN AIR SYSTEMS

TXgard-Plus. Flameproof Toxic and Oxygen Gas Detector with Non-intrusive One-man Calibration. Installation, Operation and Maintenance Instructions

IECEx TEST REPORT IEC Explosive atmospheres Part 0: Equipment General requirements

Manual Power relay SR853

ARRAN LED LED FLOODLIGHT. Standard Specification. Features

Both enclosures provide an IP 66 degree of ingress protection and are suitable for both indoor and outdoor installation.

ARGENTA ATEX For potentially explosive atmospheres. ARGENTA ATEX Technical Specifications Wall-mounting cabinets. ARGENTA ATEX Certifications

Transcription:

Page 1 of 9 TECHNICL MNUL EXPLOSION PROOF STTUS LIGHT / LMP TEX Marking: Code: II 2GD EPL Gb, Db Ex d IIC T4/T5/T6 IP66 Ex tb IIIC TXXX C Marking details: Please note that every care has been taken to ensure the accuracy of our technical manual. We do not, however, accept responsibility for damage, loss or expense resulting from any error or omission. We reserve the right to make alterations in line with technical advances and industry standards.

Page 2 of 9 1.0 INTRODUCTION BSL 125/ 150 series Explosion-proof status light / lamp is designed for use in Oil & Gas, Offshore Platform, Chemical, Petrochemical, Refinery and Marine Industries etc. Enclosure material is Stainless Steel (BSL 125) or GRP (BSL 150). Different flash or rotary rate can be adjusted from unique design. Three working statuses-flash type, rotary type and steady type are available (LED). There are 2 types of beacon (Xenon type and LED type) available for the customer. 2.0 EXPLOSION-PROOF LBELING ll products have a rating label, which carries the following important information: Product order no.: Input voltage: Code: TEX Marking: e.g. BSL125B3JR10DCRD (Refer to the datasheet for product order selection) up to 48V DC or 100-254V C Ex d IIC Tx Gb Ex tb IIIC Txxx Gas Group and Category: II 2G CE Mark: Warning: DO NOT OPEN WHEN N EXPLOSIVE GS TMOSPHERE IS PRESENT Finish product serial no. (Include date of construction) Note; exact information is given on the actual label, ref also example on page 1. 3.0 TYPE PPROVL STNDRD The BSL series products have been approved according the following standards: IEC/ EN 60079-0 IEC/ EN 60079-1 General Requirements Flameproof Enclosure d IEC/ EN 60079-31 Dust atmosphere t

Page 3 of 9 4.0 ZONES, GSGROUP, CTEGORY ND TEMPERTURE CLSSIFICTION The BSL series products have been certified Ex d IIC T4~T6. This means that the units can be installed in locations with the following conditions: rea Classification: Zone 1: Explosive gas air mixture likely to occur in normal operation. Zone 2: Explosive gas air mixture not likely to occur, and if it does, it will only exist for a short time. Gas Groupings: Group II Propane Group IIB Ethylene Group IIC Hydrogen and cetylene Equipment Category: 2GD EPL: Gb / Db Temperature Range: -40 C <Ta < 70 C 5.0 INSTLLTION General Requirement Selection, Installation, Maintenance and repair of electrical apparatus for use in potentially explosive atmosphere should be done in according to IEC/ EN 6079-14/ -17/ -19. Product installation must be carried out in accordance with any local codes that may apply and should only be carried out by a competent electrical engineer. Location The location of the unit should be made with due regard to the area over which the warning signal must be visible and the manual call point/junction box can be easily operated. The unit should only be fixed to services that can carry the weight of the unit. Mounting The BSL serious of products should be mounted on a vertical surface via a stainless steel mounting plate (See Fig 1/1B/1C/1D/1E). The fixing holes on the mounting plate are designed to fit M8 llen Screw only. The diameter is 9mm. Use of stainless steel fastener is recommended by BRTEC TECHNOR.

Page 4 of 9 Fig. 1 Fig. 1B Fig. 1C Fig. 1D The figures are related to BSL 150

Page 5 of 9 Fig. 1E 6.0 WIRING General Requirement BRTEC TECHNOR recommends that all cables and cores should be fully identified (suggest using cable from 2.0 to 2.5 mm²). Ensure that all nuts, bolts and screws are secured. Ensure that only the right and certified cable glands are used and earthed correctly. Ensure that only the right and certified stopping plugs are used to blank off unused gland entry points. In order to maintain the IP rating of the product, we recommend SS316L for this application. Cable Connection The cable connection is connected with the terminal blocks assembly located in the flameproof enclosure of the bottom unit which can be Beacon Component (See Fig 2) or Junction Box/Push Button. Cable connection should be carried out in accordance with relevant technical requirement. Remove End Cover (Beacon Component) Unscrew socket head screws (4 for BSL 125 and 5 for BSL 150) of the bottom Beacon Component (See Fig 2). This will release the cover from the base and allow cover to hang on the retaining wire strap. Before replacing the lid, check that the flameproof joints are clean and not damaged, and the gasket is retained in the groove CUTION: Before removing the cover, ensure the power to the product is isolated. Remove the four pieces of M5 socket screws to open the cover. Twist the cover gently clockwise and anti-clockwise, whilst pulling away from the base, until it comes off. Replace the cover in similar way, but operate in reverse manner as above.

Page 6 of 9 Fig. 2 Power Supply Input voltage: up to 48V DC or 100-254V C. PCB Wiring Terminals (See Fig 3) pply power supply to 12V/24V/36V/48V DC 100-250V L & N (See Fig 3) Fig. 3

Page 7 of 9 7.0 STTUS CHOSEN ND FLSHING FREQUENCY DJUSTMENT LED Beacon The LED beacon provides flashing and rotary status to be selected Use Switch with 3 binary codes on the LED Beacon PCB to select flashing or rotary status (including steady status), the 3 rd binary code is for high and low frequency chosen. LED Status Selection Switch 1 st & 2 nd Switch: ON=1 OFF=0 3 rd Switch: HIGH=1 LOW=0 S1/S2: ON= Connect with 0/COM OFF= Disconnect with 0/COM Switch 1 st 2 nd S1/S2 3 rd S1=OFF S2=OFF larm Stage 1 S1=ON S2=OFF larm Stage 2 S1=OFF S2=ON larm Stage 3 S1=ON S2=ON larm Stage 4 1 1 0(1) OFF Flash 60 (75) Flash 75 (90) Steady 0 1 0(1) OFF Rotary 60 (75) Rotary 75 (90) Steady light 1 0 0(1) OFF Double Flash 60 (75) Double Flash 75 (90) Double Flash 100(120) 0 0 0(1) OFF Flash & Rotary 60 (75) Flash & Rotary 75 (90) Flash & Rotary 100(120)

Page 8 of 9 Xenon beacon The Xenon Beacon provides flashing status. Use Switch with 2 binary codes on the Xenon Beacon PCB (see fig. 3) for frequency adjustment. Xenon Beacon Flashing Frequency djustment Switch: ON = 1 OFF = 0 S1/S2: ON = Connect to COM OFF = Disconnect to COM Switch 1 st S1/S2 2 nd S1=OFF S2=OFF larm Stage 1 S1=ON S2=OFF larm Stage 2 S1=OFF S2=ON larm Stage 3 S1=ON S2=ON larm Stage 4 1 1 OFF OFF OFF OFF 0 1 OFF 60 80 120 Flash Once a time 1 0 OFF 100 120 150 Twice a time 0 0 OFF 120 150 180 Three Times a time 8.0 CBLE GLND The BSL series of product has cable gland entries. Only cable glands approved for Ex d applications can be used, which must be suitable for the type of cable being used and also meet the requirements of the Ex d flameproof installation standard IEC/EN 60079-14. SFETY WRNING: If the BSL products is used at high ambient temperatures, i.e. over +40ºC, then the cable entry temperature may exceed +70ºC and therefore suitable heat resisting cable glands must be used, with a rated service temperature of at least 95ºC. If a high IP (Ingress Protection) rating is required, a suitable sealing washer must be fitted under the cable gland. When only one cable entry is used, the other one must be closed with an Ex d flameproof blanking plug, which must be suitably approved for the installation requirements.

Page 9 of 9 9.0 END OF LINE MONITORING n end of line monitoring diode or an end of line monitoring resistor can be connected across the 24V+ and 0 terminals. If an end of line monitoring resistor is used, it must have a maximum resistance value of 3k ohms and a minimum wattage of 0.5 Watts; or a minimum resistance value of 1.2k ohms and a maximum wattage of 2 Watts. 10.0 MINTENNCE During working life of the product, little or no maintenance is required. Stainless Steel is resistant to most of the acids, alkalis and chemicals. If abnormal or unusual environmental conditions occur due to accident etc., visual inspection is recommended. To avoid electrostatic charge build-up, only exterior of the product can be cleaned with a damp cloth. If spare parts are required, these can be supplied by BRTEC TECHNOR Company. If any failure occurs but not caused by human factor, the product can be returned to BRTEC TECHNOR for free repair or replacement during warranty period 11.0 CONDITIONS FOR SFETY USE i. The apparatus is suitable to be used only in ambient temperature as stated at the label. ii. iii. Other than product manufacture, painting and surface finishing are not permitted by the third party. When used in dusty atmosphere, flameproof cable entry devices or stopping plugs have to be selected and installed