ComPak Series with CommandPak Control System CPCS BACnet MS/TP BAS Interface User s Guide DOCUMENT #: SVW06-CPBACNETMSTP

Similar documents
CPCS SWHP BACnet MS/TP Interface User s Guide DOCUMENT #: SVW05-BACNET-MSTP

PoolPak SWHP with CommandPak Control System CPCS BACnet IP User s Guide DOCUMENT #: SVW05-BACNETIP

LYNX Quick User Guide

POOLPAK SWHP SERIES (SR, S, SE, SEP)

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products

CM3500 Controller - ClimateMaster DOAS Water-Source Heat Pumps - Rev.: 7 Oct, 2008B

Reference Guide for Microprocessor Controller

C-TRAC3 COMMUNICATION MANUAL FOR. BACnet NOVEMBER 2010 TO JANUARY 2014 USA HEAD OFFICE AND FACTORY

PoolPak MPK Series. PoolPak.com. Environmental Control Systems REDUCED FOOTPRINT & WEIGHT COMPARED TO EARLIER GENERATIONS

Reference Guide for Microprocessor Controller

Siemens RDY2000BN. Start Up Guide

Fan Coil Thermostat Controller Specification and Installation Instructions. Model TFHB24F3XYZ1 with External Humidity Sensor and BACnet Communication

Networkable Fan Coil Controller Specification and Installation Instructions

Introduction. What is the W2W Open controller?

Standard Instructions For MC-2000/3000/4000 Controllers

*IG1583EW* Aurora Touch UPC Kit Instruction Guide. Aurora Touch UPC Kit Instruction Guide

EOS INTERFACE GUIDE AND POINTS LIST For EOS BTCII Firmware Version J1239D-570 and newer

TEC2620 Series Non-Programmable Fan Coil Network Thermostat Controller and Remote I/O Relay Packs

Sequence of operation

Danfoss gas detection unit Type GD Heavy Duty

Multiview Monitor / Controller

MicroTech Self-Contained Air Conditioning System

Siemens Thermostats. RDY2000BN Thermostat

Contents. Appendix E: LonWorks Protocol Implementation Conformance Statement Document revision history... 47

Installation, Operation and Maintenance

TECHNOLOGY GUIDE. :: the dawn of a new era in commercial HVAC technology. The all-new Rheem Commercial Renaissance Line featuring:

VT8300 Series Installation Guide 24 Vac Low Voltage

Safety & Installation Instructions

Danfoss gas detection units

AD-1272 Advanced Thermal Dispersion Probe Airflow Measuring System

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

DAP III Zone Master User s Guide

I/O ZONE 560/583 USERS GUIDE

ARO Series. Description. Features. Modbus CO2 VOC. Networkable* ARO AROB24TGVH AROB24TGH. room controller. (AROB series only) or network

TECHNOLOGY GUIDE :: THE DAWN OF A NEW ERA IN COMMERCIAL HVAC TECHNOLOGY. The all-new Ruud Commercial Renaissance Line featuring:

Cultivator & Hybrid Cultivator

Reference Guide for Microprocessor Controller

BACnet Points for Single Compressor Water-to- Air Heat Pumps With Hot Gas Reheat Utilizing the FX10 Controller

Marvel J MICROPROCESSOR CONTROLLER

CONTROLS MANUAL. CARRIERrtc basic & medium electronic control 48/50 EN/EH 50 HB/HF/NZ/NF. Original document

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER

Installation Instructions / User s Manual TSTAT0406 and TSTAT0408

ICC INDUSTRIAL CONTROL COMMUNICATIONS, INC.

Operation manual. Rooftop Packaged Unit


SCIENTIFIC WARMING CABINET Installation, Operation and Maintenance Instructions

POOLPAK R-410A MPK SERIES

MicroTech Series-200 Flooded Screw Chiller

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

Introduction. What is the RTU Open controller?

Installation and Operation Manual for QS/QV and Aura Units

MicroTech Series 200 Centrifugal Chiller

PIR Ready VT76xx Series Programmable & Non-Programmable Thermostats For Commercial HVAC Applications. BACnet Integration Manual September 1, 2010

HAI Omni-Bus Network Installation. 5. Typical Application

NetworkAIR AFX. Operation and Maintenance AFX65 AFX18

RC-2000 Thermostat Installation Instructions

Wiser Air User Interface Guide. Thermostat


TECHNICAL MANUAL CVM 20 C 5005 CV/04-99 GB

Introduction. What is the W2W Open controller?

Table of Contents. WSHP Open v3

TEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers

Installation and Maintenance Manual IM

T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability

INSTALLATION INSTRUCTIONS

Master devices. Type X-AIR-ZMAS. Zone master module for up to 25 zone modules, with integral webserver and interfaces to higher-level systems

Bacnet Room Setpoint & Temp Display. Descriptions. Specifications

GeneSys Air-Cooled Screw Compressor Chiller

SA Series Start up Report

Dehumidification units CONTROL BROCHURE NA A Electronic control. CIATpool

ibox Modbus Server Gateway for the integration of Notifier ID3000 / ID3002 / ID60 / ID50 fire panels in Modbus enabled monitoring and control systems

Danfoss gas detection units

CONTENTS. Installation Guide. VT7200 Series

InfinityPro. Control System for Rapid Engineering, LLC Air Handlers. User, Operation & Troubleshooting Manual

Metasys Integrator Airflow Application

BACnet Integration Manual ITG-VH72xx-BAC-E00 ( _R0 Issue Date: October 21, 2008)

SCC Inc. Master Panel. Specifications. Document No. TS 2010 February 11, Product Description. Sample Specification

Sales and Engineering Data Sheet ED

NGC-40 Bridge. Modbus Overview. Raychem-AR-H58862-NGC40BridgeModbusOV-EN-1805 nvent.com 1

AQUATROL Zone Synchronizing Universal Injection/Mixing Boiler Reset Controls AQ252

Refrigerated Incubator Model and Operating Instructions

INSTALLATION & USER MANUAL

Emerson Inspire 1HDEZ Installation Instructions. Thermostat/Interface Equipment Control TROUBLESHOOTING

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom

Modular Standard HP Chiller 1/4 screw compressor with Carel driver

IMR 5000 IMR 400. CEMS Operating Manual IMR USA S/N: Sample IMR Sensors Inside IMR 400. Gas Dryer Inside. IMR Environmental Equipment Inc.

Setup Instructions. This manual is only valid for A36D/TPSD Chargers. equipped with a 341S control card with P341S0012 or P341S0013 software

TDU Series LCD Thermostat For EFCB and EVCB Controllers. Models. Features. Functions. Onboard Sensors. Model # Temp RH CO2 Color.

CONTROLS MANUAL For all Innovent and Valent air handling products

Manual Supplement. Model Number: 8680-N2. Communications Protocol. Contents of this manual supplement include:

Modbus RTU RS485 Manual

EXPERT TRI-STAR. Temperature controller. User s Manual

Water Source Heat Pump Module Technical Guide

BACnet MODBUS N2 LON Description Type Point Description Name # Object Type Register Type ID SNVT # Name SNVT Read Only

BAC-4000 Series AppStat

Daikin Loop Water Manager Protocol Information

ATC32U01 igate Communicating, Programmable Thermostat

CT224 Setup Tutorial

RC-112 Two Speed Heat Pump 3 Stage Heat / 2 Stage Cool With Energy Efficient Control

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas

Transcription:

ComPak Series with CommandPak Control System CPCS BACnet MS/TP BAS Interface User s Guide DOCUMENT #: SVW06-CPBACNETMSTP-20180529 UPDATED: MAY 2018

INTRODUCTION ComPak dehumidifiers equipped with the CommandPak Control System can be directly connected to a BACnet MS/ TP based Building Automation System (BAS). Based on Carel s pconet serial card, the interface allows connection to an RS-485 network. 25 control points, including all basic information and set points for the PoolComPak dehumidification system, are available through the interface BACNET CONFIGURATION PARAMETERS The BACnet configuration parameters for the controller are accessed in the BAS Interface menu. To access this menu: 1. Press the Prg button on the controller or RIU. 2. Use the arrow keys to scroll down to Service and then press Enter. 3. Enter the service password 0005. 4. Scroll down to the Unit Config menu and then press Enter. 5. Enter the factory password 9995. 6. Scroll down to the Installed Options menu. 7. Scroll down to the parameter LonWorks Board. Change this parameter to a value of NO. 8. Press Esc one time and then scroll down to the BAS Interface menu and then press Enter. 9. If the settings of these parameters differ from those shown below, change them with the Enter button and the arrow keys. 10. After changing any of these parameters, the controller should be rebooted by cycling power to the dehumidifier. Type Selects the type of BAS interface. It must be set to BACnet. The factory default setting is Modbus. Baud Rate Sets the baud rate for the onboard serial port. It must be set to 19200 for use with the BACnet interface. 19200 is the factory default setting for this parameter. BAS Addr Sets the address of the BACnet interface card in the serial slot of the controller. It must be set to 1 for proper operation of the BACnet interface. The factory default setting is 1. PHYSICAL NETWORK CONNECTION The 8P8C ( RJ-45 ) Ethernet socket is located on the pcoweb interface card. The pcoweb card occupies the serial card slot in the CM1 control module. This control module is located in the main control panel of the ComPak dehumidifier. The Ethernet connection to the interface card should comply with standard installation practices. Use care to route the cable away from sources of interference and keep the maximum cable length less than 300 feet. 2018 PoolPak LLC. All rights reserved. Page 2

CONTROL POINTS MAPPING 25 objects are accessible through the BACnet interface. Set points, sensor values, and enumerated variables are shared as analog-value objects. Status information points are shared as binary-value objects. The interface card is pre-configured at the factory with a device instance number of 77000. To change this value, follow the instructions shown in the Interface Card Field Setup and Configuration section of this document. The following table lists the available points along with their object types and instance numbers. OBJECT TYPE OBJECT INSTANCE OBJECT NAME DESCRIPTION UNITS AV 1 RtnAirTemp Return Air Temperature ºC AV 2 OutsAirTemp Outside Air Temperature ºC AV 3 SurfaceTemp Cold Surface Temperature ºC AV 4 RtnAirRH Return Air Relative Humidity % AV 5 PoolTemp Pool Temperature ºC AV 1001 ActvFault Active Fault Code N/A AV 1002 FaultCount Compressor Fault Count N/A AV 1003 RtnTempSetp_R Return Air Temp Set Point (Readable) ºF AV 1004 PoolTempSetp_R Pool Water Temp Set Point (Readable) ºF AV 1005 RtnRHSetp_R Return Air RH Set Point (Readable) % AV 1006 BASRtnTempSetp_W Return Air Temp Set Point (Writeable) ºF AV 1007 BASPoolTempSetp_W Pool Water Temp Set Point (Writeable) ºF AV 1008 BASRtnRHSetp_W Return Air RH Set Point (Writeable) % BV 1 PurgeMode Purge Mode Status On/Off BV 2 ACProof AC Proof Status On/Off BV 3 PoolHeatActv Pool Heating Status On/Off BV 4 AuxPoolHeatActv Aux Pool Heating Status On/Off BV 5 DehumidActv Dehumidification Status On/Off BV 6 AirHeatActv Air Heating Status On/Off BV 7 AirCoolActv Air Cooling Status On/Off BV 8 AuxAirHt1Actv Aux Air Heating Stage 1 Status On/Off BV 9 AuxAirHt2Actv Aux Air Heating Stage 2 Status On/Off BV 10 ForcePurge Force Purge Mode (Writeable) On/Off BV 11 ForceNoPurge Force No Purge Mode (Writeable) On/Off BV 12 ActvAlmPres Active Alarm Present On/Off 2018 PoolPak LLC. All rights reserved. Page 3

UNIT ACTIVE FAULT CODE AV1001 is an enumerated value indicating the most significant active fault in the dehumidifier. The present value for this object can be decoded as follows: 0 No Active Fault All Systems Normal 1 System in OFF Mode (Aux Water Heating System still enabled) 2 System Startup Active 4 Fan Motor Overload is Tripped 5 Fire Trip is Active 7 Space Temperature is out of normal range (70ºF < Normal < 105ºF) 12 Defrost Mode Active 13 Low Refrigerant Pressure 14 High Compressor Motor Temperature 15 High Refrigerant Pressure 16 Space Temperature Sensor Failure 17 Space Relative Humidity Sensor Failure 18 Pool Water Temperature Sensor Failure 19 Outside Air Temperature Sensor Failure 20 Surface Temperature Sensor Failure 21 Controller Failed Self Diagnostic Test 22 Compressor Locked Out After 10 Faults CHANGING A SET POINT Two analog value objects are allocated for each set point, a readable value and a writeable value. To change a set point, set the present value of the writeable object to the new set point value. Verify that the controller accepted the change by reading the value of the corresponding readable object. The controller applies limits to the set point values. If the BAS tries to set an inappropriate value, the readable object will show the min or max allowed value instead of the requested value. The BAS can detect this event by verifying the change in the readable object s present value. The following limits are applied by the controller: Return Air Temperature: 70 F 95 F Return Air Humidity: 40% 65% Pool Water Temperature: 70 F 104 F Set points for temperature are represented by integer values in degrees Fahrenheit. CONTROLLING PURGE MODE The BAS can control the dehumidifier s Purge mode directly. This control overrides all internal schedules and controls except for the freeze protection algorithm. To force purge mode, set the ForcePurge object value to the On state and the ForceNoPurge object value to the Off state. To force non-purge mode, set the value of the ForcePurge object to Off and the ForceNoPurge object to On. 2018 PoolPak LLC. All rights reserved. Page 4

SYMPTOM POSSIBLE CAUSE SOLUTION The interface card is not properly connected to the network. Correct network wiring. The dehumidifier cannot be seen on the BACnet network. Power to the controller is off. The BAS is trying to access the interface with the wrong device instance number. If safe to do so, turn on the main disconnect and the control power switch (CPS) in the control compartment of the dehumidifier. Follow the instructions in this document to set the instance number to a value appropriate for the BAS. Incorrect setting of the BAS configuration parameters in the service menu. Correct the parameter values to match the settings shown in this document. The variable values sent by the controller are different than those shown on the RIU. The BAS Type parameter is not set to BACnet. Set the BAS Type parameter to BACnet. The LonWorks Board parameter is set to Yes. Set the LonWorks Board parameter to No. Set point changes are different than requested by the BAS. Requested set point change is outside of the acceptable range. Select set points based on the acceptable range. For questions about the interface that are not answered in this document, please contact the PoolPak Service department at 800-959-7725. BACnet is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE). This trademark is used in the text, but for the sake of readability, it is not individually marked. With more than 45 years of experience in indoor pool dehumidification equipment manufacturing, PoolPak LLC is the most well-known brand in the industry. Our people and products work daily to improve the quality and comfort of indoor pool environments. PoolPak dehumidification solutions include a variety of heating, ventilation, and air conditioning systems, in addition to an industry-leading PoolPak support network. For more information, please visit www.poolpak.com. 3491 Industrial Drive York, Pennsylvania 17402 USA 800-959-7725 Fax 717-757-5085 2018 PoolPak LLC. All rights reserved. SVW06-CPBACNETIP-20180529