MAC-120HE-03 Air-Cooled Chiller

Similar documents
MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC N-407 Air-Cooled Chiller

MACH N-407 Heat Pump Air-Cooled Chiller

MHNCCW (4-Pipe) Chilled/Hot Water Ceiling Concealed 208/230V 4-Pipe Heating & Cooling Fan Coil 12,000 BTUH

CFFWA4P-16-1-U Chilled/Hot Water Universal Mount Fan Coil (4-Pipe) 4-Pipe Heat / Cool Fan Coil 48,000 BTUH

CFFWA4P-12-1-U Chilled/Hot Water Universal Mount Fan Coil (4-Pipe) 4-Pipe Heat / Cool Fan Coil 36,000 BTUH

MHCCW Chilled Water Ceiling Concealed With 5kW Electric Heat 2-Pipe Heat / Cool Fan Coil 30,000 BTUH

CFFWA4P-08-1-U Chilled/Hot Water Universal Mount Fan Coil (4-Pipe) 4-Pipe Heat / Cool Fan Coil 24,000 BTUH

MHCCW Chilled Water Ceiling Concealed Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000 BTUH

MH1WC4W-06-1-B Chilled/Hot Water 1-Way Cassette Fan Coil

MHCFC4W Chilled/Hot Water Cassette Fan Coil

MHCFC4W Chilled/Hot Water Cassette Fan Coil

MHCFC4W Chilled/Hot Water Cassette Fan Coil

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

Table of Contents (Hydronic)

MHNCCX DX with Hot Water Heat Ceiling Concealed 4-Pipe Heat / Cool Fan Coil 12,000-36,000 BTUH

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

CWA4 Chilled & Hot Water Fan Coil

Commercial High-Efficiency Condensing Units

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

MAC120 Air-Cooled Chiller

MHWW-24-H-1 Chilled/Hot Water Hi-Wall Fan Coil 2-Pipe Heat / Cool Fan Coil 24,000 BTUH

MHWW-09-H-1 Chilled/Hot Water Hi-Wall Fan Coil 2-Pipe Heat / Cool Fan Coil 9,000 BTUH

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

CWA2 Chilled Water Fan Coil With or Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000-60,000 BTUH

Commercial High-Efficiency Condensing Units

FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 3 of 13

60 TON AIR-COOLED CHILLER. Call us today! (800) PA-ACCTR-60 GENERAL DIMENSIONS ELECTRICAL DATA 60 TON AIR-COOLED CHILLER FEATURES

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

TECHNICAL GUIDE MODELS: H5CE090, H3CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS EER DESCRIPTION

PACKAGE AIR CONDITIONER

Multiaqua Chiller Manual

Call us today! (800)

Call us today! (800)

Call us today! (800)

JOB NAME: LOCATION: PURCHASER: ENGINEER: SUBMITTED TO: FOR: REFERENCE [ ] APPROVAL [ ] CONSTRUCTION [ ] SUBMITTED BY: DATE:

Compact, Self-Contained unit that offer low installation cost plus dependable performance.

SKYPAK II, 3 Ton Series, gives you a

High Ambient / High Efficiency Series. R - 410a. 50Hz. Ducted Split Air Conditioners (5.0 kw kw)

Product Data. Features/Benefits. 50TJ S Side Discharge Single-Package Rooftop Units 50/60 Hz 15 to 30 Nominal Tons

Product Data. 50LJS/TJS Single- Package. Features / Benefits. Rooftop Units - 50 Hz 6 to 12 Nominal Tons

SKYPAK II, 3 Ton Series, gives you a

Air-Cooled Split System Condensing Unit for Rooftop Systems and Air Handlers

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C13-Series Engineering Guide

Catalog Air Cooled Split System Condensing Units for Rooftop Systems and Air Handlers

UP to 14.5 SEER, PACKAGE AIR CONDITIONER UNIT, 2 to 5 TONS 208/230 Volt, 1 phase, 60 Hz REFRIGERATION CIRCUIT

Air-Cooled Condensers

ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical

PAJ3. Product Specifications

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: INDOOR UNIT:

CHS. Product Specifications COMMERCIAL SPLIT SYSTEMS HEAT PUMP UNITS R 410A, 6 10 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

Product Data. Features/Benefits. 38AH Commercial Air-Cooled Condensing Units 50/60 Hz. 20 to 130 Nominal Tons (63 to 390 Nominal kw)

Air-Cooled Global Chiller

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw)

Table of Contents. Page 2 of 28

GTIP60 ISO GT Series, Inch Pounds - 60 Hz GT (iso) Spec Guide Drawings Spec Sheets Low Temp Heating P/T Charts

MIN. CCT. QTY RLA LRA HP FLA AMPACITY /1/ /3/

GUIDE SPECIFICATIONS AQUARIUS ii

TECHNICAL GUIDE LISTED. SPLIT-SYSTEM AIR CONDITIONERS 10 SEER R22 60Hz MODELS: AC036X10(3,4) THRU 060 (3 THRU 5 NOMINAL TONS, 3 PH) DESCRIPTION

VertiCool Aurora Engineering Guide

30GT FLOTRONIC AIR-COOLED CHILLERS

Product Chillers A P P L I C AT I O N S

Liebert CSU3000 Chiller

TECHNICAL GUIDE LISTED. SPLIT-SYSTEM AIR CONDITIONERS 10 SEER R22 60Hz MODELS: H*BA-(T,W)036 THRU 076 (3 THRU 6.3 NOMINAL TONS, 3 PH) DESCRIPTION

WJH4 Product Specifications

30GN FLOTRONIC II AIR-COOLED CHILLERS

PACKAGED AIR COOLED Product Data Catalog

RECORD SUBMITTAL COVER SHEET

SUBMITTAL AG015KSVAJH/AA Samsung DVM Heat Pump Chiller. Submitted to Reference Approval Construction Unit Designation Schedule #

SpaceKeeper Console (SKC)

Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

PAR5. Product Specifications

Product Data. Features/Benefits. OMNIZONE 50BV Remote Air-Cooled and Water-Cooled Indoor Self-Contained Systems and Water Source Heat Pumps

SUBMITTAL M4MCW1509A-SUB-1C. Specifications 15 SERIES. Single Zone Mini-Split Inverter System M4MCW1509A1N0A M4TCS1509A11NA TAG:

SUBMITTAL M4MCW1509A-SUB-1B. Specifications 15 SERIES. Single Zone Mini-Split Inverter System M4MCW1509A1N0A M4TCS1509A11NA TAG:

SPLIT-SYSTEM HEAT PUMPS 50 AND 60 HZ DESCRIPTION

Product Data. Features/Benefits. GEMINI 38AKS Commercial Air-Cooled Split Systems 50/60 Hz. 25 to 40 Nominal Tons (82.8 to 127.

Indoor Air Handlers with Compressors MVS and MVW

Advance Release September 2009

Product Data. Features/Benefits. OMNIZONE 50BRN,BZN Water-Cooled and Remote Air-Cooled Indoor Self-Contained Systems. 5 to 20 Nominal Tons

VariCool VAV Engineering Guide

Unit Data - RCA 051 RATED IN ACCORDANCE TO AHRI STANDARD

Guide Specifications PART 1 GENERAL 1.01 SUMMARY

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM

GUIDE SPECIFICATIONS. WW Series Water-to-Water Reverse Cycle Chillers & Low Temp Boilers. WW Reverse Cycle Chillers / Low Temperature Boilers

RetroAire Model Number: 9,000 to 36,000 Btuh (2.6 to 10.5 kw)

MODELS W1LC220, 260 AND 320 STYLE B

SECTION AIR COOLED WATER CHILLERS

DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data

VertiCool CLASSIC. Engineering Guide. Effective March Air-Cooled, Water-Cooled, Chilled Water and Water Source Heat Pump

TECHNICAL SPECIFICATIONS

60Hz. R134a HXWC SERIES. 205 to 560 Tons. Products That Perform...By People Who Care WATER-COOLED SEMI-HERMETIC SCREW COMPRESSOR WATER CHILLERS

Coil-In-Tank Design: Refrigeration System: Cabinet Construction:

CATALOG. SKYPAK Self-Contained Heating/Cooling Units

PDF Created with deskpdf PDF Writer - Trial ::

SECTION ROTARY-SCREW WATER CHILLERS

Transcription:

MAC-120HE-03 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 380/415/460-3-50/60 1

HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-03 Part 1-General 1.01 System Description Multiaqua air-cooled liquid chillers are designed using scroll compressors and high volume condenser fans. 1.02 Quality Assurance A. Certified in accordance with U.L. Standard 1995, latest version (U.S.A.). B. Third Party Certified EER Ratings are at ANSI/AHRI Standard 550/590 with Addendum 3-2011 Conditions, unit running at 95 F ambient, 45 F leaving water temperature with sub-cooling 6.5 F, superheat 11.9 F and with (2) PSC condenser motors. C. Manufactured in a facility registered to ISO 9002, Manufacturing Quality Standard, ETL certified. D. Damage resistant packaging. 1.03 Delivery, Storage and Handling A. Packaged and readied for shipment from distribution center. B. Controls shall be capable of withstanding 150 F storage temperatures in the control compartment. C. Stored and handled per manufacturer s recommendations. Part 2-Product 2.01 Equipment A. General: 1. Unit shall be a factory assembled and tested air-cooled liquid chiller. 2. Shall be assembled on heavy gauge steel mounting/lifting rails. 3. Contained within the unit cabinet shall be all factory wiring, piping, controls, refrigerant charge (R407c), POE oil and special accessories required prior to start up. 4. Brass body strainer with 20 mesh screen and blow down shall be supplied in cabinet as a field installable accessory. B. Unit Cabinet: 1. Composed of heavy gauge galvanized steel casing with a baked polyester powder coating. 2. Capable of withstanding 500-hour salt spray test in accordance with the ASTM (U.S.A.) standard. C. Condenser Fans: 1. Four glass reinforced polypropylene (PPG) petals mounted on a cast aluminum hub construction and shall be dynamically balanced and corrosion resistant. 2. Discharge air is vertical. 3. Motors and blades shall be protected by coated steel wire safety guards. D. Fan Motors: 1. Standard condenser fan motors shall be single phase, single speed, direct drive PSC type motors. 2. Standard condenser fan motors shall be totally enclosed, use Class B insulation and permanently lubricated ball bearings and/or sleeve bearings. 3. Standard condenser fan motors shall be internally overload protected with automatic reset. 2

E. Compressors: 1. Unit shall contain two fully hermetic scroll compressors. 2. Direct-drive, 3500 rpm (50/60Hz). 3. Compressor motor shall be suction gas cooled. 4. Internal motor protection. 5. Externally protected by low and high pressure cutout devices. 6. Individual vibration isolators. F. Pump: 1. Unit shall not be capable of incorporating a field installed chilled liquid solution pump. (Space restricted) 2. Unit shall have chilled liquid solution piping to the exterior of the cabinet. G. Evaporator: 1. Evaporator shall have two independent refrigerant circuits and single liquid solution circuit. 2. Rated for a refrigerant side working pressure of 450 psig and a maximum water side working pressure of 150 psig. 3. Single pass, ANSI type 316 stainless steel, brazed plate construction with copper/nickel brazing material. 4. Externally insulated with closed cell, elastomeric foam. (ASTM518) H. Condenser: 1. Condenser coil shall be air-cooled with integral sub-cooler. 2. Independent condenser coil for each refrigerant circuit. 3. Constructed of rifled copper tubing mechanically bonded to aluminum fins. 4. Cleaned and dehydrated. 5. Factory leak tested to 450 psig. I. Refrigerant Circuits: 1. Each circuit shall contain a sight glass, liquid line strainer, thermal expansion valve, and a refrigerant charge of R407c and POE compressor oil. Part 3-Controls and Safeties 3.01 Controls A. Chiller shall be completely factory wired and tested. B. Temperature control shall be based on leaving chilled liquid solution temperature. C. Controls shall be capable of staging the two compressors. D. Controls shall include the following components: 1. 24vac transformer to serve all controllers relays and control components. 2. Microprocessor based liquid solution temperature controller. 3. Leaving water temperature thermistor. 4. Pump bypass timer. 5. Compressor recycle timer. 6. Optional fan cycling control for low ambient operation. 7. Chilled liquid solution flow switch. 3.02 Safeties A. Unit shall be equipped with all necessary components in conjunction with the control system to provide the following protection: 3

1. Low refrigerant pressure. 2. High refrigerant pressure. 3. Low chilled liquid solution flow. 4. Internal motor thermal protection. 5. Anti-short cycling. Part 4-Operating Characteristics 4.01 Temperatures A. Unit shall be capable of starting and running at outdoor temperatures from 55 F to 120 F. B. Optional Low Ambient Kit shall allow starting and running at outdoor temperatures from 54 F to 0 F. A field supplied and field installed crank case heater must be used when operating at these temperatures. C. Unit shall be capable of initial starting up with a maximum 80 F entering fluid temperature and ambient not above 95 F. D. Maximum sustained entering fluid solution temperature to the evaporator shall not exceed 70 F. E. Minimum 10% glycol solution is required in all applications. For outdoor temperatures below 32 F, reference the propylene glycol manufacture s data table of field installed polypropylene glycol solution. 4.02 Electrical Requirements A. Primary electrical power supply shall enter the unit at a single location. Single phase units require phase matched dual line voltage supply. Three phase units require only singe line voltage supply. B. Electrical power supply shall be rated to withstand 90 C operating ambient temperature. C. Units shall be available in single or 3-phase power at the voltages shown in the equipment electrical data. Part 5- Definitions 5.01 Abbreviations A. CFM = Cubic Feet per Minute B. DB = Dry Bulb Temperature C. EWT = Entering Water Temperature D. LWT = Leaving Water Temperature E. EAT = Entering Air Temperature F. EAT/DB = Entering Air Temperature Dry Bulb G. EAT/WB = Entering Air Wet Bulb H. GPM = US Gallons Per Minute I. MBH = BTU X 1000 J. SC = Sensible Cooling K. TC = Total Cooling = Sensible + Latent L. WB = Wet Bulb Temperature M. WPD = Water Pressure Drop in feet of head N. db = Decibel Level 5.02 Measurements A. All measurements with regard to length, width, and height shall be in inches. B. All measurements with regard to pipe sizes shall be in outside diameter (OD) unless otherwise noted. 4

MAC-120HE-03 Product Specifications Model Number Height (in) Physical Data Condenser Coil Chiller Weight (lbs.) Copper Length (in) Tubing Coil Width Refrigerant Height (in) Length (in) Diameter Rows (in) R407c Net Shipping (in) MAC-120HE-03 44 48 3/8 2 57 66 36 224 oz. x 2 850 1100 Electrical Data Model Number Volts/ Phase/ Hertz Compressor (Qty 2) Condenser Fan Motor (Qty 2) SCCR Fuse or HACR Circuit Breaker (RLA) (LRA) (RLA) (RPM) Minimum Amps(MCA) MAC-120HE-03 380/415/460-3-50/60 14 x 2 63 x 2 1.4 x 2 1130 10kA 40 See note 1 Note: 1. The MAC-120HE-03 has one independent line voltage termination. Maximum Amps(MOCP) 50 See note 1 Compressor Refrigerant Heat Exchanger Max. Flow Rate Copeland Scroll R407c Brazed Plate 28.8 gpm Min. Flow Rate 18 gpm Supply Water Temp 44 Return Water Temp 54 Minimum System Solution Content 50 Gallons Expansion Tank Size 3% of Total System Water Connections 1 3/8" OD Supply & Return Internal Pressure Drop 18 ft. of head Multiaqua chillers are designed to operate exclusively with R407c refrigerant in a self-contained, pre-charged refrigerant system. Do not access the closed refrigerant circuit for any reason other than after-sale, after installation component replacement. Routine maintenance and service is to be performed by qualified personnel only. 5

MAC-120HE-03 Product Specifications Entering Air Temperature Entering Air Temperature Entering Air Temperature 70 F 80 F 95 F LWT ( F) BTU's TONS EER COP BTU's TONS EER COP BTU's TONS EER COP 35 111469 9.29 13.16 3.86 104646 8.72 11.33 3.32 93000 7.75 8.61 2.52 40 123192 10.27 14.23 4.17 115133 9.59 12.24 3.59 103320 8.61 9.41 2.76 42 126720 10.56 14.80 4.34 120120 10.01 12.66 3.71 110160 9.18 9.82 2.88 44 130800 10.90 15.11 4.43 123840 10.32 12.92 3.79 113400 9.44 10.37 3.04 45 134242 11.19 15.17 4.44 126463 10.54 13.16 3.86 115080 9.59 10.74 3.15 48 140876 11.74 15.70 4.60 133650 11.14 13.69 4.01 121440 10.12 10.83 3.17 50 143990 12.00 15.92 4.66 137925 11.49 14.01 4.10 125040 10.42 11.07 3.24 55 154279 12.86 16.68 4.89 150063 12.51 14.91 4.37 138480 11.54 12.00 3.52 60 162034 13.50 17.24 5.05 161061 13.42 15.66 4.59 150600 12.55 12.78 3.74 Entering Air Temperature Entering Air Temperature Entering Air Temperature 100 F 105 F 110 F LWT ( F) BTU's TONS EER COP BTU's TONS EER COP BTU's TONS EER COP 35 88920 7.41 7.99 2.34 85920 7.16 7.27 2.13 77280 6.44 6.26 1.83 40 98760 8.23 8.69 2.55 95160 7.93 7.91 2.32 89520 7.46 7.09 2.08 42 101880 8.49 8.91 2.61 99600 8.30 8.29 2.43 93240 7.77 7.35 2.15 44 106200 8.85 9.27 2.72 102840 8.57 8.47 2.48 97800 8.15 7.61 2.23 45 109680 9.14 9.46 2.77 104400 8.70 8.57 2.51 99840 8.32 7.75 2.27 48 116760 9.73 10.01 2.93 111120 9.26 8.96 2.63 106200 8.85 8.15 2.39 50 120240 10.02 10.20 2.99 114720 9.56 9.22 2.70 110160 9.18 8.39 2.46 55 131760 10.98 10.97 3.21 125280 10.44 9.85 2.89 120960 10.08 9.06 2.65 60 143160 11.93 11.63 3.41 136920 11.41 10.58 3.10 131520 10.96 9.63 2.82 Entering Air Temperature Entering Air Temperature Entering Air Temperature 115 F 118 F 120 F LWT ( F) BTU's TONS EER COP BTU's TONS EER COP BTU's TONS EER COP 35 73440 6.12 5.66 1.66 71760 5.98 5.36 1.57 71730 5.98 5.36 1.57 40 86760 7.23 6.53 1.91 85743 7.15 6.37 1.87 78240 6.52 5.65 1.66 42 90240 7.52 6.75 1.98 89880 7.49 6.63 1.94 81360 6.78 5.86 1.72 44 94920 7.91 7.06 2.07 93715 7.81 6.86 2.01 87000 7.25 6.24 1.83 45 96720 8.06 7.17 2.10 95634 7.97 6.99 2.05 88440 7.37 6.34 1.86 48 102480 8.54 7.50 2.20 100817 8.40 7.29 2.14 94440 7.87 6.67 1.95 50 105960 8.83 7.68 2.25 103496 8.62 7.45 2.18 96960 8.08 6.83 2.00 55 115920 9.66 8.26 2.42 112648 9.39 7.94 2.33 60 126000 10.50 8.83 2.59 122103 10.18 8.47 2.48 6

MAC-120HE-03 Product Specifications Entering Air Temperature 95 F Percent of Load % 100% 75% 50% 25% LWT ( F) 44 F 44 F 44 F 44 F Capacity Point Btu/hr. 113400 123960 134040 133800 Capacity Point Tons 9.45 10.33 11.17 11.15 EER 10.37 12.94 15.83 17.13 IPLV 13.80 7

MAC-120HE-03 Product Specifications Glycol Solution Concentration Data Propylene Glycol % Min. Ambient Temp 10% 26 F 20% 18 F 30% 8 F 40% -7 F 50% -29 F Estimated Propylene Glycol Adjustment Factors: Percent of Propylene Glycol Capacity adjustment Pressure Drop adjustment Multiply TONS by: Multiply PD by: 10% 0.995 1.02 15% 0.992 1.04 20% 0.986 1.08 25% 0.972 1.13 30% 0.96 1.21 35% 0.95 1.26 40% 0.928 1.47 50% 0.878 2.79 Important Required Use of 10% Minimum Propylene Glycol Multiaqua Inc. requires a minimum concentration of 10% propylene glycol in the chiller system solution. This requirement applies to all chiller product models for protection of the brazed plate heat exchanger (BPHE), regardless of outdoor ambient operating temperature. The Multiaqua chiller operating at a 44 leaving water temperature (LWT) will have an internal BPHE temperature of 32 F to 38 F. Without the required MINIMUM 10% concentration of propylene glycol, the unit is susceptible to areas of freezing within the BPHE which could result in failure of the BPHE. With any deviation from full flow through the BPHE, the BPHE would also be susceptible to areas of freezing within the BPHE. This could be caused by, but not limited to, contaminates being caught in the wye strainer, flow switch or pump failure. Each chiller is supplied from the factory with a Wye strainer that is to be installed on the inlet (suction) side of the pump on the MAC- 036HE, 048HE, 060HE, and MAC120HE chillers. Failure to follow this requirement will void the chiller warranty. Failure to comply may result in BPHE failure due to freezing followed by compressor failure, all of which are not covered by Multiaqua s warranty. 8

MAC-120HE-03 Altitude Adjustment Factors Altitude Tons 1000 ft..995 2000 ft..990 3000 ft..986 4000 ft..983 5000 ft..980 6000 ft..978 Important notes about Low Ambient Operation: If the outside temperature is expected to fall below freezing (32 F) in the area where the Multiaqua chiller is to be installed; the installer must take the following precautions. Failure to do so will void the warranty. To not engage in cold ambient mitigation will result in the failure of components such as the heat exchanger, piping, circulating pump, etc and or property damage. Keep the liquid solution at a minimum of 10% percent Propylene Glycol even in areas where there is no danger of freezing. The percentage amount of glycol recommended is dependent on the expected ambient temperatures and the solution makeup recommendation of the glycol manufacturer. For outdoor temperatures below 32 F, reference glycol manufacture s data table of field installed polypropylene glycol solution. Ensure the system circulating pump is in a constant energized mode to keep a continuous circulation of liquid solution. The Multiaqua chiller is a self-contained, air-cooled condenser, coupled with an insulated brazed plate heat exchanger (evaporator). The system utilizes a scroll compressor to circulate refrigerant between the condenser and heat exchanger. The refrigerant is metered into the heat exchanger with a thermal expansion valve. Protecting the system are both high and low pressure switches as well as a pump flow switch. Liquid solution (water and propylene glycol; minimum 10 % is required at any ambient) is circulated through the heat exchanger by an externally mounted pump. The liquid solution flows through the heat exchanger to the system supply piping and on to the air handlers. Factory installed low ambient kits are available for operating ambient temperatures down from 54 F to 0 F. A field supplied and field installed crank case heater must be used continuously when operating at temperatures below 54 F. Factory installed low ambient kits consist of an ICM 325 (+) Low Pressure switch set to open at 10PSI for chillers with standard condenser motors. Initial startup in ambient conditions less than 54 F requires the activation of the field supplied/field installed crank case heater and must be activated for not less than 4 hours prior to energizing of compressor contactor. 9

MAC-120HE-03 Sound Data MODEL # Fan Speed MAC120HE-03 db(a) @ 3 m H 68 10

MAC-120HE-03 Wiring Diagram 11

MAC-120HE-3 Dimensional Drawing MAC-120HE Minimum Clearances Coil Air Inlet Sides Service Panel Sides 36.00" 36.00" 12

306 Hagood Street Easley, SC 29640 Ph: 864-850-8990 Fax: 864-850-8995 www.multiaqua.com For Technical Assistance: 1-855-THNK-WTR (1-855-846-5987) 13