IDP-Zone-6 Six Zone Interface Module

Similar documents
MMF Six Zone Interface Module

CZ-6A Six Zone Interface Module

SC-6 Six Supervised Control Module

Multiple Input and Output Modules

ADEMCO 4208SNF V-Plex Universal Class A Module INSTALLATION AND SETUP GUIDE

XP6-C. Six Circuit Supervised Control Module and SYNC-1 Accessory Card

Booster Power Supply Manual

Addressable NAC Output Module D327A

D350PL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS

D350RPL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS

4100U City and Relay Cards Installation Instructions

DH200RPL Intelligent Air Duct Smoke Detector with Extended Air Speed Range

RMS/RPX Reader. User Manual

DH200PL Intelligent Air Duct Smoke Detector with Extended Air Speed Range

Model 17A00 Expansion Enclosure

DH200PL Intelligent Air Duct Smoke Detector with Extended Air Speed Range

180 Degree Ceiling Mounted Occupancy Sensors

F220-B6PS/M. Installation Guide. Addressable Detector Bases

Independent Zone Control (I.Z.C.)

Multiplex Eight Input Remote Modules

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep.

The Digital Door Viewer! User Manual. Motion Activated Sensor MAS 100

NetworX NX-548E Receiver Installation Instructions

LDM Series Lamp Driver Modules For Graphic Annunciation and Control

INSTALLATION GUIDE XTLN-WIFI PANEL

Installer Guide smart connect

Light Level Detector, Surface Mount 5754PE. Installation Instructions

Supplement to The PDRP-1001/PDRP-1001A/PDRP-1001E Deluge Preaction Control Panel Manual

GARAGE HEATER WITH REMOTE INSTRUCTION MANUAL MODEL: HA24-100E HA24-150E. Figure 1

1125 PIR Motion Detector

MANUAL RESET ALARM RELEASE

SIGA-CC1 Single Input Signal Module Installation Sheet

Table of Contents What to Expect with Your Installation. Top Housing. Ceiling Plate. Tools Needed.

Installation and ZONES: Operation Manual. Model: ON STI-34108

IFT-RC150 IntelliFire Touch Remote Control Installation Instructions

General Routing Interface

INSTALLATION GUIDE XR5FC AND XR5SL COMMERCIAL FIRE PANELS

FCPS-24F FIRE ALARM FIELD CHARGER/POWER SUPPLY FOR FIRE PROTECTION/SIGNALING SERVICE FCPS-24F/FCPS-24FE. Field Charger/Power Supply

NXSMP-LMI LOW MOUNT INDOOR SENSOR MODULE

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

Conventional Fire Alarm Control Panel

Installation and Operation Manual. Model: STI TRIGGERED OUTPUT PLUG 12VDC, 75mA, 3 SEC. EMBOSSED PROGRAMMING

Wireless ShatterPro Acoustic Sensor Installation Instructions

MS-2410BC. Conventional Fire Alarm Control Panel. Programming, Installation, Maintenance and Operating Instruction Manual

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

PRODUCT DIAGRAM PACKAGE CONTENTS

Public Safety DAS Annunciator Panel

The ACM-8R Annunciator Control Module

PRODUCT DIAGRAM PACKAGE CONTENTS

Remote NAC Power Supply D7038

RONDISH DoorWatcher EASY INSTALL STRIP DOOR MONITOR

RELEASE DEVICE CONTROLS

PSN-1000 & PSN 1000(E) Installation Manual

Clipsal is a registered trademark of Clipsal Australia Pty Ltd. Saturn is a trademark of Clipsal Australia Pty Ltd.

INSTRUCTION MANUAL Z-WAVE DIMMER 12387

Register the Gateway via PC. Package Content. Gateway Installation. 1 x Gateway 1 x Voice Siren 1 x IP Camera*

Operation and Installation Guide. Fire Alarm Control Panel

ANNUNCIATOR FIXED MODULE

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

1126 Series Ceiling Mount PIR Motion Detector

D296/D297. Installation Instructions Long-Range Beam Smoke Detectors

AGES. instruction manual DAISY BLOOM PROJECTION ALARM CLOCK

Fume Hood Operating Display Panel

E529 Smart Digital Thermostat Product Guide

Fire Safety. Installation Instructions Model SMB-2 Main Control Board OPERATION INSTALLATION

These instructions detail procedures to follow in order to avoid damage to equipment.

Long Range Radio Alarm Transmitter

Ultrasonic Wall Switch Occupancy Sensor Single Circuit

KT-100 Door Controller

Installation Instructions Model HZM

Home & Yard Alert Long Range System Home & Yard Alert Extended Long Range System

DS7465i. Installation Instructions. Input/Output Module

DT8050A DUAL TEC Motion Sensor with Anti-Mask - Installation Instructions

SILENT KNIGHT. Model SK-2/E & SK-4/E. Installation and Operations Manual. Fire Alarm Control Panel. Part Number Rev. A ECN /08/05

D326A/D334A/D339A. Installation Instructions. Point Contact Modules

Print Specification. Publication. Instructions. Specific requirements. General requirements

40 Built-in Electric Fireplace Operating and Installation Instructions

FTP-1000 Touchpad/Display Installation Manual

AL600ULX Series. Power Supply/Charger. Installation Guide

Table of Contents. What to Expect with. Mounting Options. Tools Needed

Installation Instructions

READ ME FIRST DIY WIRELESS ALERT. Add-on Alert Sensor. For Swann Wireless Alert systems. Instruction Manual

/5121/5122 TrueAlert Power Supply Installation Instructions

MAJIK ENGLISH 11/20/02 11:30 AM Page 1 M A J I K O W N E R S M A N U A L

1400 Direct Wire Ionization Smoke Detector

AL600ULADA. NAC Power Extender. Installation Guide

FMR Installation Instructions. Addressable Fire System Controller

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

The MS-4412B/MS-4424B(E) FIRE ALARM CONTROL PANELS

Sentrol. ShatterPoint Glassbreak Sensor. Installation Instructions DESCRIPTION. Models (3 Volt) (6 Volt) STEP 1 MOUNTING

Duct smoke housings, 4-wire D341/D341P and D342/D342P

TECHNICAL DATA OBSOLETE

DCP-FRCME - FAST RESPONSE CONTACT MODULE

Fire alarm system specification for multiple tenant retail buildings

SPEC SHEET. Simple Expansion Solutions ZONE EXPANSION MODULES: SINGLE AND MULTIPLE POINT

HP101U Conventional Fire Alarm Control Panel Installation And Operation Manual

Series DV-100 VoiceLink Operation and Installation Manual

MANUAL RESET ALARM RELEASE BOX

Duct smoke housing, 2-wire D340/D340P

Table of Contents. What s in the Box... 3 Power Requirements... 4 Quick Setup... 5 Lighting Guide With Ring, you re Always home.

Transcription:

INSTALLATION AND MAINTENANCE INSTRUCTIONS IDP-Zone-6 Six Zone Interface Module BEFORE INSTALLING If the modules will be installed in an existing operational system, inform the operator and local authority that the system will be temporarily out of service. Disconnect the power to the control panel before installing the modules. This system contains static sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. The module housing should also be grounded. NOTICE: This manual should be left with the owner/user of this equipment. GENERAL DESCRIPTION SPECIFICATIONS Normal Operating Voltage: Stand-By Current: Alarm Current: Temperature Range: Humidity: Dimensions: Accessories: Wire Gauge: Max. IDC Wiring Resistance: External Supply Voltage DC Voltage: Ripple Voltage: Current: 5- VDC ma 40 ma (assumes all six LEDs solid on) ºF to 0ºF ( 0ºC to 49ºC) 0 to 9% Non-condensing 6.8 H x 5.8 W x.0 D IDP-ACB Cabinet and chassis -8 AWG 5 ohms 8-8 volts power limited 0. volts RMS maximum 90mA per module The IDP-Zone-6 Six Zone Interface Module is intended for use in an intelligent alarm system. Each module pro- IDC: Supervised and power limited vides an interface between the intelligent alarm system and a conventional alarm system loop. A common input is used for all modules, and the initiating device loops share a common supervisory supply and ground. Otherwise, each monitor operates independently from the others. Each module has its own unique address. A pair of rotary code switches is used to set the address of the first module from 0 to 94. The remaining modules are automatically assigned to the next five higher addresses. Provisions are included for disabling a maximum of two unused modules to release the addresses to be used elsewhere. Each module also has panel controlled bicolor LED indicators. The panel can cause the LEDs to blink, latch on, or latch off. Compatible Two-wire System Sensor Smoke Detectors for use with IDP-Zone-6 DET. DETECTOR MODEL DET. ID MANUFACTURER BASE MODEL MAX DET. 5 A SYSTEM SENSOR B0LP, B40 45 A SYSTEM SENSOR B40, B40B 0 45DH A SYSTEM SENSOR DH400 0 5 A SYSTEM SENSOR B0LP, B40 45 A SYSTEM SENSOR DH400, B40B, B40 45TH A SYSTEM SENSOR B40, B40B 0 545 A SYSTEM SENSOR B40 00 A SYSTEM SENSOR N/A 0 400 A SYSTEM SENSOR N/A 0 ** 00AT A SYSTEM SENSOR N/A 0 00B A SYSTEM SENSOR N/A 0 00D A SYSTEM SENSOR N/A 0 00S A SYSTEM SENSOR N/A 0 00TB A SYSTEM SENSOR N/A 0 00TD A SYSTEM SENSOR N/A 0 00TS A SYSTEM SENSOR N/A 0 00B A SYSTEM SENSOR N/A 0 00TB A SYSTEM SENSOR N/A 0 400 A SYSTEM SENSOR N/A 0 400TH A SYSTEM SENSOR N/A 0 * W-B A SYSTEM SENSOR N/A 0 * W-TB A SYSTEM SENSOR N/A 0 DH00LP A SYSTEM SENSOR N/A 0 * Class B, Style B only ** No Accessory will be supported by 00AT K00-6-00 I56-7-00

67 8 5 4 5 4 ADDRESS DISABLE NONE ONE TWO THREE 67 8 5 4 5 4 4 56 7 8 9 ADDRESS DISABLE NONE ONE TWO THREE 4 56 7 8 9 Included: (5) x 4 Terminal Blocks () /4 Stand offs () Shunts INSTALLATION STEPS. Cabinet Mounting In a clean, dry area, mount the backbox using the four holes provided in the back surface of the cabinet (Figure ). (4) Machine Screws () Long Power Supply Jumper () Nuts Backbox Mounting Holes (6).9k Ohm End of Line Resistors Shipped on Board: () Shunts in Class A/B position (Shipped in Class B position, remove shunts for Class A) COMPATIBILITY REQUIREMENTS To ensure proper operation, this module shall be connected to a compatible Silent Knight system control panel (list available from Silent Knight). COMPONENTS The following is a description of the IDP-Zone-6 mounting framework: One or two IDP-Zone-6 modules can be installed in a IDP-ACB cabinet Figure : Typical mounting hole locations. Module Installation There are two methods for installing a module in the rear position of a chassis. Method one is for installation of a rear module only, when no module will be installed in front of it. Refer to Figure for instructions. Method two is for installation of a rear module when another module will be installed in the chassis position in front of it. Refer to Figures 4a and 4b for method two. All necessary screws and standoffs are supplied with the modules. C05-00 9 0 9 0 C07-00 Figure : Installation of rear module only, method one C04-04 Figure : IDP-ACB Cabinet The IDP-ACB cabinet has a built-in chassis that will accommodate one or two IDP-Zone-6 modules. For cabinet dimensions refer to the IDP-ACB instruction manual. The front IDP-Zone-6 module positions of each chassis are offset below the rear IDP-Zone-6 module positions so that all of the status indicators are visible. Step : Insert the bottom of the IDP-Zone-6 module down into a rear slot on the chassis. Step : Carefully swing the upper edge of the board back towards the back of the chassis until it touches the two standoffs. Step : Align two 4-40 screws with the two standoffs and tighten. Step 4: Address and wire the modules according to the instructions in this manual. K00-6-00 I56-7-00

The steps in Figures 4a and 4b describe and illustrate module installation when the rear chassis position and the position in front of it will be filled. Front position installation is possible only if the rear position is filled with a module. Figure 4a: Installation of IDP-Zone-6 module in a rear chassis position, method two Step : Insert the bottom edge of the IDP-Zone-6 module down into a rear slot of the chassis. Step : Carefully swing the upper edge of the board towards the back of the chassis until it touches the short standoff attached to the chassis. Step : Align the long standoff with the short standoff and tighten. Figure 4b: Installation of IDP-Zone-6 module in front chassis position Step : Insert the bottom edge of the IDP-Zone-6 module down into a front slot of the chassis. Step : Carefully swing the upper edge of the board towards the back of the chassis until it touches the /4 (.75mm) standoffs installed on the rear module. Step : Align two 4-40 screws with the two standoffs and tighten. Step 4: Address and wire the modules according to the instructions in this manual. WIRING NOTE: All wiring must conform to applicable local codes, ordinances, and regulations.. Install module wiring in accordance with the job drawings and appropriate wiring diagrams. C05-00 C06-00. All wiring to the IDP-Zone-6 is done via terminal blocks. In order to properly make electrical connections strip approximately /4 of insulation from the end of wire, sliding the bare end of the wire under the clamping plate screw.. Set the address on the modules per the job drawing. Use the rotary code switches to set the address of the first module (between 0 and 94). In Class B operation, the remaining modules are automatically assigned to the next five higher addresses. For example, if the base address switch is set to 8, the next five modules will be addressed to 9, 0,, and. The module is shipped in Class B position, remove shunts for Class A. When operating in Class A, alternate modules are paired together (0/, /, 4/5), resulting in a total of three modules. For example, if the base address switch is set to 8, then 0 and will be automatically assigned to the modules while 9, and are available to be used for other modules on the. For Class A and B operation, DO NOT set the lowest address above 94, as the other modules will be assigned to nonexistent addresses. NOTE: The IDP-Zone-6 must have power cycled for shunt changes to take effect. 4. A shunt is provided to disable a maximum of two unused modules in Class B operation and Class A operation. Modules are disabled from the highest address and work downward. If two modules are disabled, the lowest four addresses will be functional, while the highest two will be disabled. For example, in Class B operation, if the shunt for Address Disable is placed on two and the base switch is set to 8, the modules will be assigned to 8, 9, 0 and while disabling the highest two positions. NOTE: Place unused shunts on single pin to store on board for future use. WIRING NOTES Power-limited circuits must employ type FPL, FPLR, or FPLP cable as required by Article 760 of the NEC. All wiring must be in accordance with the NEC, NFPA 7 and all other applicable codes and standards. All external power supplies must be power limited with battery back-up. All external power supplies and detectors must be UL listed for fire protection signaling applications. PROGRAMMING The modules are programmed as devices in each system according to the programming instructions in the appropriate FACP manual. K00-6-00 I56-7-00

.9K EOL RESISTOR (INCLUDED) CONNECT MODULES TO LISTED COMPATIBLE SILENT KNIGHT CONTROL PANELS ONLY 4 5 CLASS B IDC (TYPICAL) 0 POWER TO THE NEXT INTERFACE MODULE MUST BE EXTERNALLY SWITCHED TO RESET THE DETECTORS. AN FRM- RELAY CONTROL MODULE CAN BE USED TO SWITCH POWER FROM A STANDARD POWER SUPPLY. SEE FIGUR 0. FROM PANEL OR PREVIOUS DEVICE TO NEXT DEVICE T6 T5 DISABLE STATUS INDICATORS SIGNAL LINE CIRCUIT () VDC MAX. SEE PANEL INSTRUCTION MANUAL FOR WIRE REQUIREMENTS. POWER-LIMITED AND SUPERVISED DETECTORS MUST BE UL LISTED COMPATIBLE WITH THE MODULE. INSTALL DETECTORS PER MANUFACTURER'S INSTALLATION INSTRUCTIONS. C08-0 Figure 5: Interface two-wire conventional detectors Class B, Style B.. To use a common power supply between multiple IDP- Zone-6 modules, connect a long power supply jumper from T5 or T6 to T5 or T6 on the adjacent IDP-Zone-6 module. CONNECT MODULES TO LISTED COMPATIBLE SILENT KNIGHT CONTROL PANELS ONLY IDC CLASS A IDC (TYPICAL) 4 5 IDC 0 POWER TO THE NEXT INTERFACE MODULE MUST BE EXTERNALLY SWITCHED TO RESET THE DETECTORS. AN FRM- RELAY CONTROL MODULE CAN BE USED TO SWITCH POWER FROM A STANDARD POWER SUPPLY. SEE FIGURE 0. FROM PANEL OR PREVIOUS DEVICE TO NEXT DEVICE T6 T5 DISABLE STATUS INDICATORS SIGNAL LINE CIRCUIT () VDC MAX. SEE PANEL INSTRUCTION MANUAL FOR WIRE REQUIREMENTS. POWER-LIMITED AND SUPERVISED DETECTORS MUST BE UL LISTED COMPATIBLE WITH THE MODULE. INSTALL DETECTORS PER MANUFACTURER'S INSTALLATION INSTRUCTIONS. C08-0 Figure 6: Interface two-wire conventional detectors Class A, Style D.. To select Class A, remove the two shunts from the A/B select positions.. To use a common power supply between multiple IDP- Zone-6 modules, connect a long power supply jumper from T5 or T6 to T5 or T6 on the adjacent IDP-Zone-6 module. K00-6-00 4 I56-7-00

SIGNAL LINE CIRCUIT () VDC MAX. TWISTED PAIR IS RECOMMENDED CONNECT MODULES TO LISTED COMPATIBLE CONTROL PANELS ONLY. TO NEXT DEVICE POWER LIMITED DC POWER SUPPLY, LISTED FOR FIRE PROTECTION WITH BATTERY BACKUP 9 8 7 6 RELAY CONTROL MODULE 0 5 4 FROM PANEL OR PREVIOUS DEVICE LOOP ADDRESS C048-0 Figure 7: Relay control module used to disconnect a power supply. EXTERNAL POWER SUPPLY VIEW A-A PCB PCB 0 4 5 0 4 5 T6 T5 T6 T5 DISABLE DISABLE C04-0 Figure 8: Example of multiple boards sharing same external supply. Refer to figures 8 and 9 for typical wiring. Make certain lip on long power supply jumper engages retaining tab on T5 or T6 as shown in View A-A. K00-6-00 5 I56-7-00

7550 Meridian Circle Maple Grove, MN 5569-497 76-49-6455; 800-8-00 Fax: 76-49-6475 http://www.silentknight.com 006 Silent Knight /06 FCC Statement This device complies with part 5 of the FCC Rules. Operation is subject to the following two conditions: () This device may not cause harmful interference, and () this device must accept any interference received, including interference that may cause undesired operation. NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 5 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: Reorient or relocate the receiving antenna. Increase the separation between the equipment and receiver. Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. Consult the dealer or an experienced radio/tv technician for help. K00-6-00 6 I56-7-00