NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section CHLORINE GAS LEAK DETECTOR

Similar documents
Section K CHLORINATION EQUIPMENT

Model Gas Alarm Panel APPLICABILITY & EFFECTIVITY. This manual provides instructions for the following Sierra Monitor products:

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

SPECIFICATIONS - DETAILED PROVISIONS Section Magnetic Flowmeters C O N T E N T S

SPECIFICATION CHEMGARD INFRARED GAS MONITOR SERIES

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

Model 4001 Series Single Channel Controller

SETION EMERGENCY LIGHTING NATIONAL FIRE PROTECTION ASSOCIATION (NEPA) (2006) Life Safety Code, 2006 Edition

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

Self-contained and intrinsically safe wireless stand-alone multi-point gas detector.

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

GasSens. Self Checking Gas Sensors. Modular Gas Detector... Gas & Range Availability

Beacon 800 Gas Monitor Operator s Manual

Process Protection. MFA 4P Motion Failure Alarm

ACCURATE ELECTRONICS INC PO BOX SW HALL BLVD BEAVERTON OR USA FAX

GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL. Installation and Operation Manual

Across-the-Line SERIES MP300 Combined Manual and Automatic

NET BARRIER REDUCED RISK FINAL DENIAL VEHICLE BARRIER Model Va-Net-300

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION

SECTION AUTOMATIC TRANSFER SWITCHES

VA301C CONTROLLER WITH BACnet OPTION

elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems

Variable Frequency Drive SERIES MP800 VFD

SENTRY PRODUCTS, INC. 01/98 SCAN - STAND-ALONE - Sample Specification

Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts

APPLICATION DATA SHEET

Architectural and Engineering Specification for a Personal Alarm System System (PAS)

Architectural and Engineering Specification for a. Flash / Flare

Soft Start Series MP700 Solid State, Reduced Voltage

SPECIFICATION MODEL 5200 GAS MONITOR SYSTEM. User Instructions For The Model 5200 Gas Monitor System

Spectron LSN (Life Safety Network) Suggested Specifications

Oxygen (O2) Single-Point Gas Detection System

GAS MONITOR Model Model

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

Carbon Monoxide (CO) Detecting Ventilation Fan Controller Model 120VC Single Relay (100/25 PPM) (200/35 PPM)

SECTION GENERATOR PARALLELING CONTROLS

GASGUARDIAN Channel Controller OPERATING & INSTALLATION MANUAL

Section PERIMETER SECURITY SYSTEMS

SECTION AUTOMATIC TRANSFER SWITCHES

MODEL ZAC ZONE ANNUNCIATOR/CONTROLLER DESIGNED FOR ZONE ANNUNCIATION AND MONITORING

Universal Gas Detector

TD80 LEVEL GAUGING & OVERFILL PREVENTION SYSTEM PRODUCT MANUAL. TPM 001 Revision 0.1

Pioneer-R16 Gas Monitor Operator s Manual

RAM3 Remote Alarm Module

Two-Channel Gas Controller

Improve Performance and Reduce Maintenance Costs. Model Q45D. Dissolved Oxygen Monitor...

SECTION FIRE ALARM SYSTEMS

~500 V AC / DC. Wireless 500 VAC/VDC Voltage Meter. The Leader in Low-Cost, Remote Monitoring Solutions. Monnit Sensor Core Specifications

Models LBW-420-LEL (24 VDC powered) Ammonia Leak Detector

User Guide. for the Beacon ProActTM 200 System

UFGS (August 2004) UNIFIED FACILITIES GUIDE SPECIFICATIONS

Commercial and Light Industrial Fire Alarm Control Panel

SECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY

SECTION COMMERCIAL DOOR OPERATORS OVERHEAD RSX FIRE DOOR OPERATOR

ICS Regent. Fire Detector Input Modules PD-6032 (T3419)

SEC 2000 Millenium Infrared Gas Detector

F PC and AO OUTPUT BOARDS INSTRUCTION MANUAL. Blue-White. Industries, Ltd.

Model OEM-2 INSTRUCTIONS FOR USE

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10

IGD.CO.UK

Fort Rouge Leisure Centre Section HVAC Upgrades Phase 2 Page 1 of 5 Bid Opportunity No March 2013 FIRE ALARM SYSTEMS

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Danfoss gas detection units

TECHNICAL DATA SHEET CONVENTIONAL FIRE ALARM SYSTEMS Conventional Fire Alarm Control Panel

SECTION AUTOMATIC TRANSFER SWITCHES

GLD-30 Gas Leak Detector

ANNUNCIATOR INSTRUMENTS Model PD141AFO Instruction Manual

Ammonia Detection System Codes and Design Specifications

ABB Instrumentation. Specifications. COMMANDER 150 Universal Process Indicator. the 1 /8 DIN indicator to match all your display requirements

SIL 2. Ultima X Series Gas Monitors CERTIFIED

Carbon Monoxide (CO) Detecting Ventilation Fan Controller Model COSTAR 24VC-e Single Relay

Architectural and Engineering Specification for a Real-Time Locating System Flare

EG Controls. SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF E G

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Sentry LIQUID LEVEL GAUGE MODEL 200 or 200C OWNER MANUAL REV 1.7 SEPT08 PAGE 1 OF 12

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description.

DNC-PS700-A10 Differential Pressure Control Meter. Operation and Installation Manual

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description

TECHNICAL DATA OBSOLETE

SCAN200E USER S MANUAL

GASGUARD Cl 2. Chlorine Sensor OPERATING & INSTALLATION MANUAL

Specification/ Data Sheet

5New features & EXtreme design, now with HART Protocol and DuraSource Technology. Ultima X Series Gas Monitors

Hinesville First United Methodist Church SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

Remote Alarm Panels Features

Use this Specification Template to develop a specification to be used for requesting a quote or defining a job work description.

Digital Electronic Thermostat With RF

EATON DFDAP-M / FDAP-M Remote Alarm Panels

TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS

WATCHMAN Model LBW-WATCHMAN Ammonia Leak Detector

/8 DIN Level Indicator

Wireless DC Voltage Detector

SECTION LIGHTING CONTROLS

WARRANT Y AND LIMITS OF LIABILIT Y Vulcain Inc. warrants to the original purchaser that its product, and the component parts thereof, will be free fro

GASGUARD NH 3. Ammonia Sensor OPERATING & INSTALLATION MANUAL

1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1 ANSI/NFPA 20, Centrifugal Fire Pumps.

SECTION FIRE ALARM SYSTEMS

XRRS Specification Fire Ready Hood

Transcription:

Section 11263 PART 1 GENERAL 1.01 SUMMARY This Section includes the furnishing and installation of chlorine leak detectors as shown on Plans and specified herein. 1.02 MEASUREMENT AND PAYMENT No separate payment will be made for chlorine gas leak detectors under this Section. Include payment in price for Work of which this is a component part. 1.03 REFERENCES This specification references the following publications in their current editions. The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by basic designation only. A. American Petroleum Institute Pamphlet 1: Chlorine Basics B. The Chlorine Institute Pamphlet 073: Atmospheric Monitoring Equipment for Chlorine 1.04 SUBMITTALS A. Submit Shop Drawings and product data in accordance with Section 01330 Submittal Procedures. B. As a minimum, submit the following: 1. Catalog bulletins or comparable illustrations and data sheets for all components and accessories. 2. Manufacturer's installation instructions C. Submit Operations and Maintenance Manual in accordance with Section 01782 Operations and Maintenance Data. 1.05 RELATED REQUIREMENTS A. Section 01330 Submittal Procedures B. Section 01610 Basic Product Requirements C. Section 01782 Operations and Maintenance Data 11263-1

D. Section 16473 - "Water Receiving Facilities (WRF) Programmable Logic Controllers (PLC), SCADA Interface Panels and Panel Mounted Equipment" 1.06-1.07 (NOT USED) 1.08 DELIVERY, SOTRAGE, AND HANDLING Deliver equipment to site, store and protect in accordance with Section 01610 Basic Product Requirements. 1.09-1.12 (NOT USED) 1.13 WARRANTY The Manufacturer shall warrant the leak detector to be free of defects in material and workmanship for a period of two years from date of shipment, provided the detector is installed and used in accordance with all applicable instructions. PART 2 PRODUCTS 2.01 MANUFACTURER(S) A. Capital Controls Company Model Series 1610B Single Point Gas Detector or Series 1620B Multipoint Gas Detector B. Wallace & Tiernan Model ACUTEC 35 Gas Detection System C. Or Approved Equal 2.02 MATERIALS AND/OR EQUIPMENT A. Detectors shall sense and provide local indication of gas concentration and contacts for remote alarm at adjustable levels. B. Single point or multipoint gas detectors complete with sensor and cable (See "ATTACHMENT" for type of detector selected.) C. If multipoint gas detector is selected, it must be expandable in the field with sensing modules for each location. D. Sensor module shall consist of an electrochemical type sensor (requiring no chemical additions) E. Power Requirements: 120 or 240 Volts (ac); 50/60 Hz; Single phase F. Dual alarm output for remote warning and device control G. Number of locations to be monitored: 1 to 8 (See "ATTACHMENT" for number of locations) 11263-2

H. Audible and visual alarms I. Remote Indicator: 1. Provide remote indicator to indicate and alarm when a preset gas level is exceeded 2. Capital Controls Model 1630 (Or Approved Equal) 3. Bar graph indicator shall provide level indication 4. Annunciator shall provide audible indication of an alarm condition. Audible alarm can be turned off but the visual ALARM indicator light will flash until the condition is cleared. J. The receiver shall contain the following components: 1. A power switch and LED indicators for power and ready 2. Set point alarm level, field set via push button on the front of the receiver and indicated by on the color bar graph by a flashing bar segment 3. LED alarm indicator and annunciators with corresponding contact 4. LED malfunction indicator with jumper-selectable manual or automatic reset relay contact 5. RESET button for clearing alarm and malfunction circuits 6. Timer for sensor stabilization 7. LED bar graph display in the range of 0-10 ppm for chlorine; 0-50 ppm and 0-100 ppm for ammonia. 8. A 4-20 ma DC output signal shall be provided to transmit scanned levels. K. Receiver shall process and display incoming signals from the sensor module and be housed in a corrosion-resistant NEMA 4X enclosure suitable for wall mounting. L. Alarm contacts: 1. Warning alarm set point, field adjustable from 0.5 to 1.0 ppm 2. Danger alarm set point, field adjustable from 1.0 to 5.0 ppm 3. Power loss alarm contacts 4. Alarm reset switch for alarm acknowledgement 11263-3

M. Alarm Light: 1. Provide a "Leak Detected" alarm light mounted outside the room where chlorine gas leak detector is located. 2. Weatherproof cast steel fixture, with red globe and guard mounted on top of control panel. 3. See "ATTACHMENT" for recommended manufacturer and model. N. Relay contacts rate: 5 amp at 240 VAC O. 8 character alpha/numeric display P. Leak detector shall have the capability to send the "Leak Detected Alarm" to the customer operated control panel or PLC and/or the Owner s Supervisory Control and Data Acquisition (SCADA) system. See Section 16473 - "Water Receiving facilities (WRF) Programmable Logic Controllers (PLC), SCADA Interface Panels and Panel Mounted Equipment" for more information on the interface between the leak detector and the Owner s SCADA system, if applicable. Q. Provide Radio Frequency/Electromagnetic Interference (RFI/EMI) protection R. Provide a minimum of two spare sensors per installed detector. Each spare sensor shall come sealed as a complete unit. S. Back-Up Power: 1. Capital Controls Company Model 1640 Power Back-Up (Or Approved Equal) 2. Automatically provide battery backup for continuous operation 3. No manual switching shall be required 4. Automatically and continuously recharge to supply maximum support to the gas detector and/or the remote indicator 5. 120 VAC / 18 Volt DC 2.03-2.04 (NOT USED) PART 3 EXECUTION 3.01-3.02 (NOT USED) 3.03 ERECTION / INSTALLATION AND CONSTRUCTION A. Install in accordance with Manufacturer s written instructions. 11263-4

B. Install two (2) feet above the floor near the chlorinators or the active 150 lb. cylinders and vacuum regulators. C. Testing and Placing in Service: Manufacturer s technical representative to assist Contractor in testing and calibration of all components. 3.04-3.10 (NOT USED) END OF SECTION 11263-5

ATTACHMENT [Design Engineer is to complete blanks per site requirements] Water District Name: A. EQUIPMENT 1. Leak Detector Manufacturer: 2. Leak Detector Model: 3. Remote Indicator Manufacturer: 4. Remote Indicator Model: 5. Power Back-Up Manufacturer: 6. Power Back-Up Model: 7. Number of Detectors: 8. Single or Multipoint: 9. Number of Locations: 10. "Leak Detected" Alarm Light: END OF SECTION 11263-6